NATIONAL CONTROLS Z3T-00300-061, Z3 User Manual

Delay On Break (Retriggerable)
Timing
On Off
On Off
Input V
oltage
Relay Coil
Open
Closed
Delay On Break Function
Switch
Start
.187
SWITCH
SWITCH
START
START
.313
±.032
INC
CLEARANCE FOR #6 SCREW
.250 X .032 MALE 'FAST-ON'
(10 PL.)
R12
.775
(4 PL.)
3.625
.±032
N.0.
Z3T-*****-061
N.0.
COM
L1
COM
L2
VAC
VOLTAGE
INPUT
120
3.000
N.C.
R
1.500
N.C.
K1
2.125
±.032
.313
±.032
R
6360
+
-
TIME ADJUST
Polarity shown for DC models
.27
1.875
Z3 Series
TIME DELAY RELAYS
1-23
FEATURES
100% functionally tested
No false contact transfer when reset
Time delays to 5 minutes
±1% repeatability
Superior transient protection
Fast-on terminals for quick installation
Low cost, open board construction
Fiberglass reinforced circuit board
Trimpot on-board with sealed cermet element
Operating Logic: Voltage is applied to the timer at all times. Upon a closure of a nor mally open isolated start switch, the output relay is activated and remains so as long as the switch is kept closed. When the start switch is opened, timing starts. At the end of the preset time delay, the output relay is deactivated and the timer is ready for a new cycle.
Note: 1) Do not apply voltage or ground to the start switch; 2) Switch leads should be shielded when running close to other wires; 3) If the start switch is re-closed during timing, the timer will reset and will not start timing until start switch is opened (Start switch supplied by customer).
LOGIC FUNCTION DIAGRAM
File #E59090
SPECIFICATIONS
TIME DELAY
Adjustment: Trimpot, factory fixed on spe-
cial order (min. order required)
Range: 3 to 300 sec. Repeatability: ±1% at constant temperature Accuracy:
Maximum time -0%, +10% Minimum time +0%, -50%
Reset Time: 300 ms max. Start Switch Closure Time: 20 ms to initiate tim
ing; 50 ms to reset delay during timing
INPUT
Operating Voltage: 120 VAC ±10% Power Consumption: 3 VA max. Frequency: 50/60 Hz
OUTPUT
Type: Relay contacts, DPDT (2 form C)
-
Rating: 10 A max. resistive at 240 VAC - 100 mA at 5 VDC min. load current
Life: Mechanical: 10,000,000 operations Full Load: 500,000 operations
PROTECTION
Transient Voltage: Timers are protected by a 30
joule metal oxide varistor Dielectric Breakdown: 1500 VAC, RMS min. at
60 Hz between input and outputs and between outputs
MECHANICAL
Termination: .25” x .032” male fast-on terminals Mounting: .25” standoffs, #6 screw
ENVIRONMENTAL
Storage Temperature: -23°C to 70°C Operating Temperature: -23°C to 55°C
-
Consult factory for any special requirements not listed in catalog (minimum order requirement may apply).
ORDERING INFORMATION
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
TIME RANGE 120 VAC
3 to 300 sec. Z3T-00300-061