NATIONAL CONTROLS Q3F-00001-321, Q3F User Manual

Delay On Break (Retriggerable)
Timing
On Off
On Off
Input V
oltage
Load
Open
Closed
Delay On Break Function
Switch
Start
76
.88
1.25
Rt
5 4
2.00 SQ.
L
C
C
L
321
START
(3667-4)
.25 X .032 MALE FAST-ON
TERMINALS (7 PL.)
.170
DIA.
SWITCH
LOAD
INPUT
VOLTAGE
Polarity Shown is
for DC Models
Q3F Series
TIME DELAY RELAYS
1-21
FEATURES
100% functionally tested
Solid state digital timing
20:1 maximum to minimum timing ratio
Low cost
Compact size
Superior transient protection
Flame-retardant and solvent-resistant polyester thermoplastic housing
Operating Logic: Input voltage is applied to the timer at all times. Upon closure of a normally open isolated start switch, the load energizes and remains energized as long as the switch is closed. When the start switch opens, the timing cycle starts. At the end of the preset time delay, the load de-ener gizes and the timer is ready for a new timing cycle. (Start switch supplied by customer.)
Note: 1) Do not apply voltage or ground to start switch; 2) remote start switch leads should be shielded when running close to other wires; 3) If the start switch is re-closed during timing, the delay will reset and will not start timing until the start switch is opened; 4) Remote potentiometer leads should be shielded when running close to other wires; 5) The minimum time setting on external resistor-adjustable time delay relays is obtained by shorting together the external resistor terminals of the relay; 6) The maximum time setting within tolerance limits is obtained by using a 1 megohm resistor; 7) Timing values between the mini­mum and maximum limits are linear with resistance within 10%;
8) Recommend 1/4 W minimum resistor be used.
File #E65038
LOGIC FUNCTION DIAGRAM
SPECIFICATIONS
TIME DELAY
Adjustment: External resistor, factory fixed on
special order (min. order required)
Range: 50 ms to 10 hours in 9 ranges Repeatability: ±.5% +8 ms max. (0.25% typical)
at constant temperature Accuracy:
Maximum time ±2% at Rt = 1 megohm
-
Minimum time +0%-30% at Rt = 0 ohm
INPUT
Operating Voltage: 120, 240 VAC; 12 VDC; 24
VAC/DC ±10% (DC models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified)
Frequency: 50/60 Hz
OUTPUT
Type: Solid state normally open Rating: 1 A steady state Life: 100,000,000 cycles
MECHANICAL
Termination: .25” x .032” male fast-on
terminals Mounting: Surface mount with one #8
screw
ENVIRONMENTAL
Storage Temperature: -40°C to 85°C Operating Temperature: -40°C to 65°C
PROTECTION
Transient Voltage: 30 joule metal oxide varistor,
see ratings below Dielectric Breakdown: 3000 VAC, RMS, termi
nals to mounting
-
Isolation Resistance: 100 megohms min.
ORDERING INFORMATION
TIME RANGE 12 VDC +10% 24 VAC/DC +10% 120 VAC +10% 240 VAC +10%
.05 to 1 sec. Q3F-00001-326 Q3F-00001-327 Q3F-00001-321
.25 to 5 sec. Q3F-00005-326 Q3F-00005-321 Q3F-00005-325
.5 to 10 sec. Q3F-00010-326 Q3F-00010-327 Q3F-00010-321 Q3F-00010-325
3 to 60 sec. Q3F-00060-326 Q3F-00060-327
15 to 300 sec.
30 to 600 sec. Q3F-00600-327
180 to 3600 sec. Q3F-03600-326 Q3F-03600-327 Q3F-03600-321 Q3F-03600-325
Trigger time (start switch closure)
Reset time 200 ms 300 ms 200 ms 200 ms
Min. load 5 mA 5 mA 2 mA 2 mA
Max. leakage current 10 uA 10 uA 200 uA 300 uA
Voltage drop at 1 A 2.1 V max. 3.2 V max. 3.3 V max. 3.3 V max.
Power consumption 2.6 W 3.7 VA max. 4.3 VA max. 5.8 VA max.
Peak 1 cycle surge 4 A 4 A 20 A 20 A
Protection 8.8j. MOV 8.8j. MOV 30j. MOV 30j. MOV
Optional Potentiometer: Part Number ASY-0001M-450
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
.25 to 5 hrs. Q3F-18000-327 Q3F-18000-321
.5 to 10 hrs. Q3F-36000-326 Q3F-36000-321 Q3F-36000-325
Q3F-00300-327 Q3F-00300-321 Q3F-00300-325
20 ms 20 ms 20 ms 20 ms
between terminals and case
External Resistance/Time Delay Relationship
1 megohm external resistance is required to obtain the maximum time for all ranges. To determine the actual resistance needed to obtain the required time delay, use the following formula:
Trequired - Tminimum
Rt=
Tmaximum - Tminimum
Note: Due to component tolerances, the actual time obtained will normally be within 5% of desired time.
Consult factory for any special requirements not listed in catalog (minimum order requirement may apply).
x 1,000,000 ohms