NATIONAL CONTROLS Q1T, Q1T-00001-311 User Manual

1-8
Timing
On Off
On Off
Input V
oltage
Load
Delay On Make Function
.25 X .032 MALE FAST-ON
1.25
.88
.170
2.00 SQ.
3
1
C
L
L
C
TERMINALS (4 PL.)
DIA.
(3667-2)
VOLTAGE
INPUT
LOAD
TIME DELAY A
DJUSTMENT
A
CCESS
TIME DELAY RELAYS
Delay On Make (Series Load)
Q1T Series
FEATURES
100% functionally tested
Solid state digital timing
20:1 maximum to minimum timing ratio
Low cost
Superior transient protection
Epoxy encapsulated
Flame-retardant and solvent-resistant polyester thermoplastic housing
Trimpot on-board with sealed cermet element
Operating Logic: Upon application of input voltage, the time delay starts. At the end of the time delay, the load is energized. Reset is accomplished by removing input voltage.
Note: The load may be located on either side of the line
LOGIC FUNCTION DIAGRAM
File #E65038
SPECIFICATIONS
TIME DELAY
Adjustment: On-board Trimpot Range: 50 ms to 10 hours in 9 ranges Repeatability: ±.5% +8 ms max. (0.25% typical)
at constant temperature Accuracy: Maximum time -0%, +10%;
Minimum time -30%, +0%
INPUT
Operating Voltage: 12, 24, 120, 240 VAC/DC
±10% (on DC models, unfiltered supply voltage must be full-wave rectified)
Frequency: 50/60 Hz
OUTPUT
Type: Solid state normally open series load Rating: Maximum current -1 A AC/DC (resistive
or inductive)
Life: 100,000,000 operations
PROTECTION
Transient Voltage: Metal oxide varistor (see rat-
ings below) Dielectric Breakdown: 3000 VAC, RMS, termi
nals to mounting Isolation Resistance: 100 megohms min.
between terminals and case
MECHANICAL
Termination: .25” x .032” male fast-on terminals Mounting: Surface mount with one #8 screw
ENVIRONMENTAL
Storage Temperature: -40°C to 85°C Operating Temperature: -40°C to 65°C Humidity: 95% relative
-
ORDERING INFORMATION
Reset time, during timing 125 ms 125 ms 125 ms 125 ms
Reset time, after timeout 10 ms 10 ms 10 ms 10 ms
Min. load 10mA DC, 60 mA AC 10mA DC, 40 mA AC 10 mA 10 mA
Max. leakage current 2 mA 4 mA 2 mA 2 mA
Voltage drop at 1 A 3.3 V max. 3.3 V max. 3.3 V max. 3.3 V max.
Power consumption 0.25 VA max. 0.25 VA max. 0.5 VA max. 0.5 VA max.
Peak 1 cycle surge 4 A 4 A 20 A 20 A
Protection 8.8j. MOV 8.8j. MOV 30j. MOV 30j. MOV
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
TIME RANGE 12 VAC/DC +10% 24 VAC/DC +10% 120 VAC/DC +10% 240 VAC/DC +10%
.05 to 1 sec. Q1T-00001-316 Q1T-00001-317 Q1T-00001-311 Q1T-00001-315
.25 to 5 sec. Q1T-00005-316 Q1T-00005-317 Q1T-00005-311 Q1T-00005-315
.5 to 10 sec. Q1T-00010-316 Q1T-00010-317 Q1T-00010-311 Q1T-00010-315
3 to 60 sec. Q1T-00060-316 Q1T-00060-317 Q1T-00060-311 Q1T-00060-315
15 to 300 sec. Q1T-00300-316 Q1T-00300-317 Q1T-00300-311 Q1T-00300-315
30 to 600 sec. Q1T-00600-316 Q1T-00600-317 Q1T-00600-311 Q1T-00600-315
180 to 3600 sec. Q1T-03600-316 Q1T-03600-317
.5 to 10 hrs. Q1T-36000-316
TIME RANGE 24 to 240 VAC/DC +10%
24 to 480 sec. Q1T-00480-31M
Consult factory for any special requirements not listed in catalog (minimum order requirement may apply).