NATIONAL CONTROLS Q1F, Q1F-00001-3A5 User Manual

1-10
Timing
On Off
On Off
Input V
oltage
Audio Alarm
Delay On Make Function
.88
1.25
L
C
C
L
.25 X .032 MALE FAST-ON
TERMINALS (5 PL.)
.170
DIA.
2.00 SQ.
Input
Voltage
Rt
TIME DELAY RELAYS
Delay On Make (Alarm Output)
Q1F Alarm Series
FEATURES
100% functionally tested
Time delays to 10 hours standard
Loud audio alarm for use in noisy envi
ronments Solid state digital timing
20:1 maximum to minimum timing ratio
Low cost
Compact size
Superior transient protection
Flame-retardant and solvent-resistant polyester thermoplastic housing
The Q1F Delay to Alarm Cube Timer is intended for use as a Delay On Make audi ble alarm.
Operating Logic: Upon application of the input voltage, the time delay starts. At the end of the preset time delay the audible alarm is activated. Reset is accomplished by removing input voltage.
Note: 1) Remote potentiometer leads should be shielded when running close to other wires; 2) The minimum time setting on external resistor-adjustable time delay relays is obtained by short ing together the external resistor terminals of the relay; 3) The maximum time setting within tolerance limits is obtained by using a 1 megohm resistor; 4) Timing values between the minimum and maximum limits are linear with resistance within 10%; 5) Recommend 1/4 W minimum resistor be used.
LOGIC FUNCTION DIAGRAM
File #E165149
SPECIFICATIONS
TIME DELAY
Adjustment: External resistor, factory fixed on
special order (min. order requirement)
Range: 50 ms to 10 hours in 9 ranges Repeatability: ±.5% +8 ms max. (0.25% typical)
at constant temperature
Accuracy: Max. +0%, -30% at Rt = 0 ohm Reset Time:
During Timing: 300 ms After Timeout: 150 ms
INPUT
Operating Voltage: 120 or 240 VAC ±10% Frequency: 50/60 Hz
OUTPUT
Type: Solid state Piezo Audio Alarm Alarm Frequency: 3.15 kHz ±0.5 kHz
Sound Pressure Level: 76 dB at 1 meter Life: 10,000,000 operations
PROTECTION
Transient Voltage: Metal oxide varistor Dielectric Breakdown: 3000 VAC, RMS, termi
nals to mounting Insulation Resistance: 100 megohms min.
between terminals and case
MECHANICAL
Termination: .25” x .032” male fast-on terminals
-
Mounting: Surface mount with one #8 screw
ENVIRONMENTAL
Storage Temperature: -40°C to 75°C Operating Temperature: 0°C to 65°C Humidity: 95% relative
-
ORDERING INFORMATION
TIME RANGE 120 VAC 50/60 Hz 240 VAC 50/60 Hz
Optional Potentiometer: Part Number ASY-0001M-450
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
.05 to 1 sec. Q1F-00001-3A5
.25 to 5 sec.
.5 to 10 sec.
3 to 60 sec.
15 to 300 sec.
30 to 600 sec. Q1F-00600-3A5
180 to 3600 sec.
.25 to 5 hrs.
.5 to 10 hrs.
Q1F-00005-3A5
Q1F-00010-3A5
Q1F-00060-3A1 Q1F-00060-3A5
Q1F-00300-3A5
Q1F-03600-3A1 Q1F-03600-3A5
Q1F-18000-3A1 Q1F-18000-3A5
Q1F-36000-3A1 Q1F-36000-3A5
External Resistance/Time Delay Relationship
1 megohm external resistance is required to obtain the maximum time for all ranges. To determine the actual resistance needed to obtain the required time delay, use the following formula:
Trequired - Tminimum
Rt=
Tmaximum - Tminimum
Note: Due to component tolerances, the actual time obtained will normally be within 5% of desired time.
Consult factory for any special requirements not listed in catalog (minimum order requirement may apply).
x 1,000,000 ohms
Loading...