LIQUID LEVEL CONTROL SERIES
L2 L1
LOW
HEAT FILL
C
To Probes
and Tank
3.50
4.00
2.25
1.25
4.50
5.00
.25
.25
NS210
Input
Voltage
1.75 max.
LIGHT
(5) .14 Dia
Low
Light
Heat
L H
Mounting Holes
Fill
(3672-1)
(3672-2)
PROBES
FILL
HEAT
HEAT
FILL
Input
Voltage
To Probes
and Tank
3.50
4.00
2.50
3.00
1.75
Max.
L H
To conductive
tank
High Probe
Low Probe
Heating
Element
To Level Control
L H
C
L1 L2
(4) .14 Dia
C
Mounting Holes
NS211
.25
.25
Resistance Sensors (Pump Up Logic with Heater Burn Out Protection)
Models NS210 and NS211
2-5
FEATURES
100% functionally tested
●
Solid state sensing circuitry
●
Isolated UL Class ll sensing voltage
●
1/4” male fast-ons for circuit connection
●
Conformal coating to protect circuit
●
from harsh environments
File #E61377
●
Operating Logic: Assuming an empty tank,
upon application of voltage to the system,
the fill output is turned on and the heat
er output is off. As the liquid fills the tank,
and when it reaches the low probe (above
heater), the heater output is turned on. The
level will rise until it reaches the high probe
causing the fill output to turn off. As liquid
is removed from the tank, 2 to 4 seconds
after it breaks contact with the high probe,
the fill output is turned on and stays on until
the liquid reaches the high probe. This time
delay eliminates fill output chatter if the liq
uid is splashing.
If the tank is non-conductive, a third
(common) probe must be installed at a level
where it will always be submerged.
SPECIFICATIONS
CONTROL TYPE
On/Off Resistance Sensing:
On low probe: probe resistance below set
point activates heater output
On high probe: probe resistance above set
point activates fill output after a 2 to 4 sec.
delay
Sensing Voltage: 15 VAC, max. RMS
Sensing Current: 2 mA, max. RMS
Sensitivity Adjustment: Factory set at
50 K ohms ±10%
-
INPUT
Operating Voltage: 24, 120, 240 VAC, ±10%
Power Consumption: 3.0 VA max.
Frequency: 50/60 Hz
OUTPUT
Type: Relay contacts, switch loads to L1
Rating: 5 A resistive at 240 VAC
Life:
Mechanical: 5,000,000 cycles
Electrical: 100,000 min. at full load
PROTECTION
-
Isolation: 1500 VAC between probe and other
terminals
MECHANICAL
Terminations: 1/4” x .032” male fast-ons
Mounting: 4 - .141” dia. mounting holes
ENVIRONMENTAL
Operating Temperature: 0°C to 55°C
ORDERING INFORMATION
Pump Up 24 VAC LNC-NS210-024
Pump Up 120 VAC
Pump Up 240 VAC LNC-NS210-240
Pump Up 120 VAC
Probe Holder with Ground LLH-11383-010
Probe, 6” Long, 1/4” Dia., S.S.
Probe, 12” Long, 1/4” Dia., S.S.
Probe, 24” Long, 1/4” Dia., S.S.
Probe Assembly, Plastic Body LLP-001/2-011
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
LNC-NS210-120
LLP-06.00-OSS
LLP-12.00-OSS
LLP-24.00-OSS
LNC-NS211-120
LOGIC TYPE INPUT VOLTAGE PART NUMBER
ACCESSORY PART NUMBER