LIQUID LEVEL CONTROL SERIES
To Conductive
Tank
Probe
Typical Probe Connection
3.50
1.22 1.12
2.75
.37
WATER
SOLENOID
Input
Mounting Bracke
t
by Customer
To Probe
NS156
.25
P
1.40
L2
L1
Load
.22 Dia.
2 places
Probe
Terminal
Probe
Com
Com
P
(3673-3)
To Level Control
Voltage
Mounting
Holes
Common
Probe
Common
2-9
Resistance Sensors (Single Probe, Pump Up Logic with Time Delayed Output)
Models NS156 and NS159
FEATURES
100% functionally tested
●
Solid state sensing circuitry
●
Isolated UL Class ll sensing voltage
●
1/4” male fast-ons for circuit connection
●
Conformal coating to protect circuit
●
from harsh environments
●
Operating Logic: As liquid is removed from
a tank and contact with a probe is interrupted, a fixed time delay is started. At the end
of the time delay, the output is activated
until the level rises and contacts the probe.
On Model NS159, when the output is
turned on, a fault timer is started. If the out
put is still on at the end of the fault time, the
fault timer will shut the output off until volt
age is removed and re-applied to the con
trol system. The purpose of the fault timer is
to eliminate overflow due to an open probe.
If the tank is non-conductive, a second
(common) probe must be installed at a level
where it will always be submerged.
File #E61377
SPECIFICATIONS
CONTROL TYPE
On/Off Resistance Sensing: Probe resistance
above set point activates fill output after a
fixed time delay
Sensing Voltage: 15 VAC, max. RMS
Sensing Current: 2 mA, max. RMS
Sensitivity Adjustment:
NS156: Factory set at 100 K ohms ±10%
NS159: Factory set at 500 K ohms ±10%
Activate Time Delay:
NS156: 5 sec. ±1 sec.
NS159: 1 sec. ±.5 sec.
Fault Timer Delay, NS159: 300 sec. ±15%
Contact factory for other sensitivity and time delay requirements.
INPUT
Operating Voltage: 120, 240 VAC, ±10%
-
Power Consumption: 3.0 VA max.
Frequency: 50/60 Hz
-
OUTPUT
-
Type:
NS156: Solid state switch, .75 A at 25°C, .34 A
at 77°C
NS159: Relay contact, 2 A at 120 VAC
Life:
NS156: 1,000,000 cycles min. at full load
NS159: 300,000 cycles min. at full load
PROTECTION
Isolation: 1500 VAC between probe and other
terminals
Transient Voltage: Protected by 30 joule metal
oxide varistor
Coating: Conformally coated with RTV to protect
against moisture
MECHANICAL
Terminations: 1/4” x .032” fast-ons
Mounting: 2 -.218” dia. holes
ORDERING INFORMATION
Pump Up 120 VAC LNC-NS156-120
Pump Up 240 VAC
Pump Up/Fault Timer 120 VAC
Probe Holder with Ground LLH-11383-010
Probe, 6” Long, 1/4” Dia., S.S.
Probe, 12” Long, 1/4” Dia., S.S.
Probe, 24” Long, 1/4” Dia., S.S.
Probe Assembly, Plastic Body LLP-001/2-011
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
LOGIC TYPE INPUT VOLTAGE PART NUMBER
ACCESSORY PART NUMBER
ENVIRONMENTAL
Operating Temperature:
NS156: +5°C to 77°C
NS159: +5°C to 65°C
LNC-NS156-240
LNC-NS159-120
LLP-06.00-OSS
LLP-12.00-OSS
LLP-24.00-OSS