2-8
240V120VCOM
LNC-NS141-*10
240 V COM120 V
LOAD
HI
LO
COM
3.50
4.00
1.40
2.80
.187 X .020 MALE
FAST-ON (3 PL)
.250 X .032 MALE
FAST-ON (6 PL)
.10
.312
MAX
1.70
.250
R
R
E61377
A B
IDLE
(RED LED)
LOAD
120 V
COM 240V120V
240 V
COM
COM HI
LO
075
120 VAC
240 VAC
INPUT VOLTAGE
LOAD
NOTE: MUST USE COM TO 120 V
OUTPUT WHEN 120V INPUT IS USED
MUST USE COM TO 240 V OUTPU
T
WHEN 240 V INPUT IS USED
4
8
12
16
0
68 (20) 104 (40) 140 (60) 176 (80)
AMBIENT TEMPERATURE F ( C)
MAXIMUM LOAD VS. AMBIENT
LOAD CURRENT (AMPS RMS)
075
075
075
075
075
075
075
075
12" X 12" HEATSINK
10" X 10" HEATSINK
6" X 6" HEATSINK
NO HEATSINK
4608/12/94
LIQUID LEVEL CONTROL SERIES
Resistance Sensors (Dual Probe, Dual Voltage) 1hp Solid State Output
Model NS141
FEATURES
100% functionally tested
●
16 A 1 hp solid state output rating
●
120/240, 100/200 VAC operation
●
voltages
Solid state sensing circuitry
●
Isolated UL Class ll sensing voltage
●
Adjustable sensitivity by Trimpot
●
●
1/4” male fast-ons for circuit connection
●
Conformal coating to protect circuit
from harsh environments
●
Operating Logic: In Model NS141-A10
(Pump Down) the load is de-energized until
the liquid reaches the high probe. When liq
uid touches the high probe, the load is acti
vated until the level drops below the low
probe.
Model NS141-B10 (Pump Up): The load
is energized until the liquid reaches the high
probe. When liquid touches the high probe,
the load is deactivated until the level drops
below the low probe.
On both models a red light is activated
when the load is off. If the tank is non-con
ductive, a third (common) probe must be
installed at a level where it will always be
submerged.
SPECIFICATIONS
CONTROL TYPE
On/Off Resistance Sensing:
NS141-A10/A100: Probe resistance below set
point activates relay
NS141-B10/B100: Probe resistance above set
point activates relay
Sensing Voltage: 30 VAC, max. RMS
Sensing Current: 1 mA, max. RMS
Sensitivity Adjustment: Factory set at
50 K ohms, ±20%
ORDERING INFORMATION
Pump Down 120/240 VAC LNC-NS141-A10
Pump Up 120/240 VAC
Pump Down 100/200 VAC
Pump Up 100/200 VAC LNC-NS141-B100
Probe Holder with Ground LLH-11383-010
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
File #E61377
LOGIC TYPE INPUT VOLTAGE PART NUMBER
ACCESSORY PART NUMBER
OUTPUT
Type: Single-pole solid state switch
Rating: 16 A 1 hp at 120, 240 VAC
Life:
Electrical: 1,000,000 min. at full load
INPUT
Operating Voltage:
NS141-A10: 120 VAC, ±10%, between COM
and 120 terminals
NS141-B10: 240 VAC, ±10%, between COM
and 240 terminals
NS141-A100: 100 VAC, ±10%, between COM
and 120 terminals
NS141-B100: 200 VAC, ±10%, between COM
and 240 terminals
Power Consumption:
NS141-A10/B10: 3.0 VA max.
NS141-A100/B100: 4.0 VA max.
Frequency: 50/60 Hz
-
-
PROTECTION
Isolation: 1500 VAC between probe and other
terminals
Transient Voltage: Protected by a 30 joule metal
oxide varistor
MECHANICAL
Terminations: 1/4” x .032” male fast-ons for
input voltage and load, .187” x .020” fast-ons for
probes
Mounting: 2 - 3/16” slots on 3.5” center in alumi-
-
num chassis
ENVIRONMENTAL
Operating Temperature: 0°C to 65°C
LNC-NS141-B10
LNC-NS141-A100