NATIONAL CONTROLS NS129 User Manual

2-6
NS129, NS132
2.12
3.00
To probes
and tank
3.62
4.00
(4) .14 Dia Mounting Holes
Isolated Relay Output
Input Voltage
1.75
Sens. Adjust
Increase
N.C. N.O. COM.
L1 L2
L H C
(3673-1)
.19
.44
(3673-2)
1.75
Increase
Adjust
Sens.
2.62
3.00
Mounting holes
(4) .14 Dia
NS139
N.C. N.O. COM.
Output
Isolated Relay
N.C. N.O. COM.
Voltage
Input
Output
Isolated Relay
and tank
To probes
L
H
C
4.62
5.00
L1 L2
.19
.19
L
To conductive tank
High Probe
.
Low Probe
Typical Probe Connectio
n
To Level Contro
l
C
H
LIQUID LEVEL CONTROL SERIES
Resistance Sensors (Dual Probe)
Models NS129, NS132 and NS139
FEATURES
100% functionally tested
Solid state sensing circuitry
Isolated UL Class ll sensing voltage
#6 screw terminal connections
Conformal coating to protect circuit from harsh environments
File #E61377
Operating Logic: In Models NS129 and NS139 (Pump Down) the output relay is de­energized until the liquid reaches the high probe. When liquid touches the high probe, the output relay is activated until the level drops below the low probe. In Models NS132 (Pump Up) the output relay is energized until the liquid reaches the high probe. When the liquid touches the high probe, the output relay is deactivated until the level drops below the low probe. If the tank is non-conductive, a third (common) probe must be installed at a level where it will always be submerged.
SPECIFICATIONS
CONTROL TYPE
On/Off Resistance Sensing:
NS129 and NS139: Probe resistance below set point activates relay NS132: Probe resistance above set point acti­vates relay
Sensing Voltage: 15 VAC, max. RMS Sensing Current: 2.0 mA, max. RMS Sensitivity Adjustment: Adjustable by a Trimpot
from .1-100 K ohms +10%, -0%
INPUT
Operating Voltage: 120, 240 VAC, ±10% Power Consumption: 11 VA max. for 120 VAC
units
Frequency: 50/60 Hz
OUTPUT
Type:
NS129 and NS132: Relay contacts SPDT (1 Form C) NS139: Relay contacts DPDT (2 Form C)
Rating: 10 A resistive at 120 VAC; 5 A resistive at 240 VAC; 100 mA at 5 VDC min. load current
Life: Mechanical: 10,000,000 cycles Electrical: 100,000 min. at full load
PROTECTION
Isolation: 1500 VAC between probe and other
terminals
MECHANICAL
Terminations: Terminal blocks with #6 screw
connections
Mounting: 4-.141” dia. mounting holes
ENVIRONMENTAL
Operating Temperature: -20°C to 55°C
ORDERING INFORMATION
Pump Down 120 VAC LNC-NS129-120
Pump Down 240 VAC
Pump Down 120 VAC
Pump Up 120 VAC
Pump Up 240 VAC
Probe Holder with Ground LLH-11383-010
Probe, 6” Long, 1/4” Dia., S.S.
Probe, 12” Long, 1/4” Dia., S.S.
Probe, 24” Long, 1/4” Dia., S.S.
Probe Assembly, Plastic Body LLP-001/2-011
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
LOGIC TYPE INPUT VOLTAGE PART NUMBER
ACCESSORY PART NUMBER
LLP-06.00-OSS
LLP-12.00-OSS
LLP-24.00-OSS
LNC-NS129-240
LNC-NS139-120
LNC-NS132-120
LNC-NS132-240