NATIONAL CONTROLS K2K-00010-661, K2 User Manual

Single Shot
Timing
On Off
On Off
Input Voltage
Relay Coil
OpenSwitch
Start Closed
Single Shot Function
2.125 .25
Case 6
1.531
1.406
(By Cust.)
Start Switch
(3021-4)
Input
Voltage
Max.
.70
Polarity Shown is
for D.C. Models
3 6
9 BA
7
4
1
8
5
+
-
K2 Series
TIME DELAY RELAYS
1-17
FEATURES
100% functionally tested
Time delays to 10 seconds
Compact size
Spade type base
Wide operating temperature range
Fiberglass reinforced circuit board
Polycarbonate, 94V-2 housing material
Operating Logic: Voltage is applied to the timer at all times. Upon a momentary or maintained closure of a normally open iso lated start switch, the output relay coil is energized and the time delay starts. At the end of the preset time delay, the relay coil is de-energized and the timer is ready for a new cycle.
Note: 1) Do not apply voltage or ground to the Start switch;
2) Switch leads should be shielded when running close to other wires (Start switch supplied by customer)
LOGIC FUNCTION DIAGRAM
File #E59090
SPECIFICATIONS
TIME DELAY
Adjustment: Knob, factory fixed on special
order (min. order required)
Range: 100 ms to 10 sec. Repeatability: ±3% at constant temperature Accuracy:
Maximum time +10%/-0% Minimum time +0%/-50%
Reset Time: 200 ms max.
INPUT
Operating Voltage: 120 V AC ±10% Start Switch Closure Time: 50 ms min. Power Consumption: 3 VA max. Frequency: 50/60 Hz
-
OUTPUT
Type: Relay contacts, DPDT (2 form C) Rating: 10 A max. resistive at 240 VAC 100 mA at
5 VDC min. load current
Life:
Mechanical: 10,000,000 operations Full Load: 500,000 operations
PROTECTION
Transient Voltage: Timers are protected by a 5
joule metal oxide varistor Dielectric Breakdown: 1500 VAC RMS min. at
60 Hz between input and outputs and between outputs
MECHANICAL
Termination: Spade (.187” x .020” terminal) type
plug-in base Mounting: Socket mount, part number
MS0-00KUP-012
ENVIRONMENTAL
Storage Temperature: -23°C to 70°C Operating Temperature: -23°C to 55°C
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
ORDERING INFORMATION
TIME RANGE 120 VAC
.1 to 10 sec. K2K-00010-661
Consult factory for any special requirements not listed in catalog (minimum order requirement may apply).
Loading...