NATIONAL CONTROLS IST-200T User Manual

5-6
UNDER
OVER
L1
L2
COM
NO
min.
max.
max.
min.
POINT
TRIP
FAULT
CURRENT
CURRENT
MODE SELECT SWITCH
NON-
LATCH
LATCH
AC CURRENT SENSOR
TRIP
DELAY
MOTOR
ALARM
Motor
Supply
Voltage
120 or 240 VAC
Input Voltage
SETTINGS:
TRIP POINT: approx. 10 amps TRIP DELAY: approx. 4.5 sec.
MODE SELECT SWITCH:
Non-Latching Over-Current
CURRENT MONITORS
2-20 A Current Monitor
IST-200T Series
FEATURES
100% functionally tested
Low cost
Fault status LED
Adjustable trip delay timer
Adjustable trip point from 2 to 20 A
Selectable ouput modes: – Latching – Non-latching
Selectable sensing modes:
– Over-current – Under-current
120 VAC and 240 VAC models
50/60 Hz operation
SPDT 10 A relay output
Epoxy encapsulated
File #E59090
through the torroid transformer; two turns would change the range to 1 to 10 A, four turns would change it to 0.5 to 5 A.
TYPICAL APPLICATION
As long as the operating current of the motor is less than 10 A, the alarm will not sound. If the motor draws greater than 10 A for longer than 4.5 seconds, the FAULT LED will light and the alarm will sound. Because the NON-LATCH mode is set, the fault con dition will clear as soon as the current draw of the motor drops below 10 A. When the fault is cleared, the FAULT LED will turn off and the alarm will stop sounding. If, how
­ever, the LATCH mode was selected and an OVER-CURRENT fault is detected, the fault will not clear when the motor current
-
draw dropped below 10 A. In this case, the
Operating Logic: The Current Monitor senses AC load current passing through its torroid transformer. In the OVER-CURRENT mode, the on-board relay will initiate the
alarm would continue to sound until reset of the Current Sensor by either removing and reapplying power or by switching to NON­LATCH mode.
TRIP DELAY timer and illuminate the FAULT LED when the sensed current is greater than the TRIP POINT setting. If the sensed current is still greater than the TRIP POINT setting after the TRIP DELAY timer has elapsed, the on-board relay will energize. If the UNDER-CURRENT mode is select
­ed, the on-board relay will be un-energized as long as the sensed current is greater than the TRIP POINT setting. Once the sensed current drops below the TRIP POINT setting, the TRIP DELAY timer will start tim
­ing and the FAULT LED will illuminate. If the sensed current is still less than the TRIP POINT setting after the TRIP DELAY time has elapsed, the on-board relay will ener gize and its contacts will change state. The Current Monitor will automatically
-
reset itself when the sensed current returns to its non-fault value if the NON-LATCH mode is selected. However, if the LATCH mode is selected, the on-board relay will remain energized regardless of any sub sequent change in the sensed current. To reset the fault in this mode, either remove input power from unit and reapply it, or switch to NON-LATCH mode. The Current Monitor is designed to sense a range of 2 to 20 A with a single loop of the load wire passed through the torroid trans
-
­former. Greater sensitivity can be achieved by passing multiple loops of the load wire
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
SPECIFICATIONS
TERMINALS ARE
QUICK CONNECT (5
)
.25 X .032
MOUTING HOLES (2)
.188 DIA.
.375 DIA.
.50 [12.7]
1.94
.28
2.94
.28
1.375 MAX.
3.50
2.50
R
Corporation
National Controls
West Chicago, IL. 60185
UNDER
OVER
L1
L2
COM
NO
NC
min.
MADE IN THE U.S.A .
max.
max.
min.
POINT
TRIP
FAULT
CURRENT
CURRENT
MODE SELECT SWITCH
NON-
LATCH
LATCH
AC CURRENT SENSOR
CONTACT RATING: 10A, 250VAC
TRIP
DELAY
Model: IST-200T*-14* INPUT:***VAC Range: 2-20 AMPS, .*-** seconds
INPUT
Operating Voltage:
IST-200TA-141: 105 to 135 VAC, 50/60 Hz IST-200TA-145: 210 to 270 VAC, 50/60 Hz
Power Consumption: 3.5 VA max. Current Sense Input: 0 to 40 A steady-state
200 A inrush for 100 ms max.
OUTPUT
Type: Relay contacts SPST (1 form C) Rating: 10 A resistive, 1/2 hp at 250 VAC Life:
Mechanical: 1,000,000 operations Electrical: 100,000 operations at full load
CURRENT SENSE ADJUSTMENT
Range: 2 to 20 A with single load wire through
sensor, Trimpot adjustable
Power-up surge delay: 100 ms max. Response time: 100 ms max. over or under cur
rent mode
CURRENT TRIP DELAY ADJUSTMENT
Range: 0.1 to 10 sec., Trimpot adjustable
MECHANICAL
Termination: 5 - .25” x .032” male fast-on
terminals Mounting: 3.5” x 2.5” encapsulated enclosure
with 2 mounting holes suitable for #8 screw
ENVIRONMENTAL
Storage Temperature: -40°C to +85°C Operating Temperature: -40°C to +65°C
CURRENT MONITORS
5-7
-
ORDERING INFORMATION
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
INPUT VOLTAGE TRIP POINT TRIP DELAY PART NUMBER
120 VAC 2 to 20 A .1 to 10 sec. IST-200TA-141
240 VAC 2 to 20 A .1 to 10 sec. IST-200TA-145
Loading...