4-10
DUST COLLECTOR CONTROLS
DUSTRONIX™ Core-10/Expander-10
Dust Collector Controls
Models DNC-T2610-010/020
FEATURES
Communicates via 2 wire CANbus net-
●
work
Universal input voltage 100-240 VAC,
●
50/60 Hz
10 outputs on-board, expands to 990
●
outputs (with expansion boards)
Solenoid current sense:
●
– allows automatic system setup
– senses 3 solenoids per output
– monitor up to 2970 solenoids
Diagnostic/program LEDs for “at-a-
●
glance” system status indication
Settable to read 0-10, 0-15, and 0-25
●
inches of differential pressure
●
Finger-safe terminations
CORE-10 UNIQUE FEATURES
Simple one knob programming
●
Non-volatile memory for program and
●
status storage
On-Demand operation:
●
– with external pressure switch (not
included)
– with external pressure sensor (not
included)
– source/sink 4 to 20 mA sensor input
3-digit, 7-segment alpha-numeric
●
display
Settable alarm output relay normally
●
open or normally closed
The Core-10 is the main control module in the
DUSTRONIX line. The Core-10 is capable of
operating as a standalone module controlling
1 to 10 solenoids, or in combination with the
Expander-10 for up to 98 expansion modules for
a total of 990 outputs. The Expander-10 is the
expansion output board in the DUSTRONIX family. The Expander-10 operates in combination with
the Core-10 Control Module.
ORDERING INFORMATION
INPUT VOLTAGE PART NUMBER
100 to 240 VAC DNC-T2610-010
100 to 240 VAC
DNC-T2610-020
The Expander-10 communicates with the Core10 on a twisted pair of wires using CANbus architecture which provides robust noise immunity.
Two rotary switches on the Expander-10 are used
to set and provide visual indication of the address
assigned.
The Core-10 can operate in On-Demand mode
with input from an external pressure sensor (4 to
20 mA) or a pressure switch (not included), or it
can operate in the Continuous mode by use of a
jumper across the pressure switch input. A switch
can also be connected to the pressure switch
input to act as a bypass switch. Input for a cycle
down switch is also provided to allow for end-ofoperation cleaning.
A unique feature of the Core-10 is its simple
one-button programming. This single push-but
ton/encoder is used to select operating parameters. LEDs indicate program function. The
push-button is also used to view alarm conditions
and cancel the alarm output. Operating and programming information is displayed on a 3-digit
7-segment display. The compact size of the
Core-10 and the Expander-10 allows mounting in
enclosures as small as 8” x 6”.
Programmable Parameters:
Solenoid ON-Time/OFF-Time
●
Number of cycle down cycles
●
Cycle down time delay
●
Run/Standby: enable/disable outputs
●
●
Differential pressure high setpoint/low
setpoint
Differential pressure high alarm setpoint/
●
low alarm setpoint
Alarm contact (normally open or normally
●
closed)
Differential Pressure Sensor Select:
●
10, 15, 25 in. w.c.
Output: 1 to 990 manual or auto-config
●
ured
Status LEDs: when illuminated
Differential Pressure: Display indicates
●
P
-
-
Output: Display indicates cur-
●
rent output
Alarm (System Status): P or
●
Solenoid Fault
Output Pulsing: Display indi-
●
cates output being pulsed
Cycle Down: Unit in cycle down
●
mode
Output Status: Unit pulsing
●
solenoids
CANbus Status: CANbus trans
●
mission activity
DUSTRONIX “Kit” Configurations
DNC-T2610-N4A: Includes
1.
Core-10, PS700, 3-position
switch, NEMA 4 10”x8”x6” metal
enclosure with cutouts, bulk
head fittings, mounting chassis,
mounting
DNC-T2610-N4XA: Same as
2.
above but mounted in fiberglass
enclosure
DNC-T2610-N4B: Same as Kit
3.
1 but also includes Expander-10
module
DNC-T2610-N4XB: Same as
4.
Kit 3 but mounted in fiberglass
enclosure
-
-
ACCESSORY DIMENSIONS PART NUMBER
Enclosure for DNC-T2610-010 10” x 8” x 6”
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
BOX-A1008-CHSC
BOX-A1008-CHNF
DUST COLLECTOR CONTROLS
Nat io n al C on t ro ls Cor p..
E65038
.25 DIA. HOLE (4 PL.)
L2 TERMINALS ARE INTERNALLY CONNECTED TO L2 SUPPLY
GND
TO EXPANSION UNITS (IF USED)
TWISTED PAIR COMMUNICATIONS CABLE
N.C.N.O.
2 1
L1
100-240 VAC
L2
OUTPUTS TO 120 OR 240V AC AIR SOLENOIDS
SENSOR
P
SENSOR
P
+
–
SHOWS "SINK"
SHOWS "SOURCE"
(6.35)
Alarm
Output Pulsing
Cycle Down
Standby
Run
Pressure
Output
Solenoid Output
Solenoid On Time
Solenoid Off Time
Cycle Down Delay Time
Cycle Down Cycles
Pressure High Set Point
Alarm
Pressure Low Set Point
Pressure High Alarm Point
Pressure Low Alarm Point
3.15A
ALARM
ALARM
POWER
4.25 (107.95)
4.75 (120.65)
.25 (6.35)
.313 (7.95)
6.25 (158.75)
6.875 (174.63)
6.250 (158.75)
6.875 (174.63)
1.50
(38.1)
.50
(12.7)
L2 TERMINALS ARE INTERNALLY CONNECTED TO L2 SUPPLY
OUTPUTS TO 120 OR 240V AC AIR SOLENOIDS
.25 DIA. HOLE (4 PL.)
(6.35)
.25 (6.3)
3.225 (82.0)
3.725 (94.6)
GND
L1
L2
100-240 VAC
.313 (7.95)
2 1
TWISTED PAIR COMMUNICATIONS CABLE
TO MAIN CONTROLLER AND OTHER
EXPANSION UNITS (IF USED)
CORE-10
EXPANDER-10
SPECIFICATIONS
CORE-10
INPUTS
Supply: 100-240 VAC, 50/60Hz, 4 VA max. at
240VAC without loads
Fuse: 3A fast, 5x20 mm
Pressure Sensor Input: 4 to 20 mA, sink/
source, programmable 10.0”, 15.0”, 25.0” w.c.
Pressure Switch Input: Dry contact, 4 mA at
13 VDC max.
Cycle Down Switch Input: Dry contact, 4 mA at
13 VDC max.
OUTPUTS
Solenoid Outputs: 10
Output Type: Triac
Output Rating: 150 VA (at max. ON, min. OFF, 1
output selected)
Timing Accuracy: -2mS, +10 mS or
ever is greater), ON-time synchronized to AC line
Alarm Relay: Form-A contact, 3A at 250
VAC/30 VDC, programmable normally open or
normally closed
DISPLAY INDICATORS
3-digit 7-segment LED display, 0.56 in. red
Program Parameters/Display Status/CANbus
Status: 17 green LEDs
Alarm: 1 red/yellow LED
Output Status: 1 red/green LED
PARAMETER RANGES
ON-Time: 0.050-600 sec.
OFF-Time: 1-999 sec.
Timing Accuracy: -2 ms, +10 ms or
ever is greater), ON-time synchronized to AC line
Cycle Down Cycles: 1-20, none
Cycle Down Delay: 60-600 sec.
P High Setpoint: 0-10/15/25” w.c., none
P Low Setpoint: 0-10/15/25” w.c., none
P High Alarm: 0-10/15/25” w.c., none
P Low Alarm: 0-10/15/25” w.c., none
COMMUNICATIONS
Type: CANbus architecture
Terminations: Screw terminals, #12 to #28 AWG,
ENVIRONMENTAL
finger safe
Operating Temperature: -40°F to +150°F (-40°C
to +65°C)
Environmental Protection: Conformal coating
for humidity and vibration
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
+1% (which-
+1% (which-
EXPANDER-10 SPECIFICATIONS
INDICATORS
Solenoid Pulse Indication: 10 green LEDs
CANbus Status: 1 green LED
Output Status1: 1 red/green LED
OUTPUTS
Solenoids: 10 per Expansion Module
Output Type: Triac
Output Rating: 150 VA (at max. ON, min. OFF, 1
output selected)
Timing Accuracy: -2 ms, +10 ms or
ever is greater), ON-time synchronized to AC line
+1% (which-
Caution:
1. Do not mount controls in high vibration areas with
out shock mounts.
2. Do not mount controls in areas of high dust or cor
rosive atmospheres without a protective enclosure.
3 Do not use a converter or inverter for the power
source.
4. Do not mount control in high transient voltage
areas without an isolation transformer.
5. Do not leave control box open.
6. Do not allow a local repair shop to repair the con
trols, as we employ some very sophisticated compo
nents that could be further damaged. For service, call
us directly: 800-323-2593.
4-11
-
-
-
-