4-20
L1
L2
FAILURE TO COMPLY WILL VOID ANY
WARRANTY
DO NOT USE SLOW-BLOW OR LARGER SIZE
Model DNC-T2310-010
SOL
COM
L1
L2
3AMP
1
2
3 4
OUTPUTS
5 6
7 8
10
9
HI SIDE
CONNECTIONS:
PRESSURE
LOW SIDE
1725 Western Dr.
S/N:
INTELLIGENT DUST CONTROL
West Chicago, IL. 60185
INPUT VOLTAGE:120 VAC, 10VA
MODEL NO.: DNC-T2310-010
Date Code:
BYPASS
INPUT
ALARM
OUTPUT
ALARM
INPUT
INCHES OF WATER
DIFFERENTIAL PRESSURE ( P)
National Controls
Corporation
D
OUTPUT
STEP
CANCEL
ALARM
CONNECTOR
RS232
ITEM VALUE
National Controls
Corporation
RS-232 Null Modem Cable
T2310 & I/O Board Wiring Diagram
DNC-T2310-010
DNC-T2300-I/O
Network Connection
to DSP-T2300-010
DUST COLLECTOR CONTROLS
Intelligent Dust Collector Controller
Remote Input/Output Module
Model DNC-T2300-I/O
FEATURES
Enhances T2310 and T2320 timer oper-
●
ation
Monitors three 4-20 mA analog inputs
●
Monitors three switched inputs
●
Monitors one type J thermocouple
●
Operating temperature range from
●
-40°C to 65°C
Communicates via RS232 port to intel
●
ligent controller
Communicates via 2 wire network to
●
remote sites
Interconnectable for overall system
●
management
Large storage capacity for historical
●
trending of system data
Aids in system diagnostics
●
●
Increases overall system efficiency
●
Conformally coated for protection
against vibration, humidity, and con
tamination
Metal chassis provided: for mounting
●
directly into
Timer functionally tested to eliminate
●
field failures
One Year Warranty:
●
free from defects in materials or work
manship for one year from date of
manufacture
●
NEMA 4 box
warranted to be
File #E65038
non-volatile memory for the storage of
up to one year of input trending data. The
I/O board requires either a T2310 or T2320
Timer to program and operate the board
and a T2300 Display Panel to access data
trending reports.
The I/O board offers significant versatil
controller’s 8 character display and
output via the two wire Enhanced
Timer Network to the DNC-T2300-
-
DSP remote display panel.
ity to the Intelligent Dust Collector Controller
system. It can monitor, display, alert, and
store dust collector system parameters from
-
pressure sensors, emission monitors, ple
num air flow sensors, broken bag detectors,
fan motor current sensors and any other
device which has a 4-20 mA current output
or contact closure output. The unit works
in conjunction with the T2310 and T2320
Timers and also with the DNC-T2300-DSP
Display Panel.
Inputs: There are three gener-
al purpose 4-20mA current loop
-
inputs which are configured by the
Timer. Depending on how the par
ticular 4-20 mA inputs are config
ured, the messages that appear
on the Timer’s display would either
show a generic range of 0-100%
based on the 4-20 mA input or
data units specific to three pre-pro
-
-
-
grammed sensing devices would
Operating Logic: Upon application of
power to the unit, communication will be
-
established with the T2310 or T2320 Timer
via the RS232 port. The I/O board can then
be configured for the inputs provided to it
by using the keypad on the controller. Alarm
setpoints and 4-20 mA scaling can be pro
grammed for different types of inputs to be
displayed in a meaningful fashion on the
be displayed.
There are two general purpose
switched inputs which will moni
tor and report up to two contact
closures as alarm conditions to
the Timer, and one contact clo
-
sure input which allows the user to
place the Enhanced Timer system
in standby mode.
-
-
-
The Model DNC-T2300-I/O module provides
several functions. It communicates with a
T2310 or T2320 Dust Collector Timer via the
RS232 port to form an Enhanced Timer sys
tem, and it communicates pertinent system
data to remote control/display devices via
the 2 wire Enhanced Timer Network. It also
incorporates three 4-20 mA current loop
inputs, three contact closure type inputs,
and one type J thermocouple input. In addi
tion, the I/O board provides 16K bytes of
ORDERING INFORMATION
INPUT VOLTAGE PART NUMBER
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
105 to 135 VAC DNC-T2310-A10
210 to 270 VAC
ACCESSORY DIMENSIONS PART NUMBER
Enclosure 10” x 8” x 4” BOX-A1008-CHNF
DNC-T2310-A220
-
-
DUST COLLECTOR CONTROLS
.06 THICK ALUMINUM
MOUNTING PLATE
2 POS. SCREW
TERMINAL
(8 PL.)
2.50 MAX.
RS-232 9 CIRCUIT
MALE CONNECTOR
TO
NETWORK
CONNECTION
.25 DIA. MOUNTIN
G
HOLE
(4 PL.)
4-20mA
Inputs
"J" THERMOCOUPLE
Input
CURRENT LOOP SINK
OR SOURCE SWITCH
(SWITCH SHOWN IN
SINK POSITION)
Input Voltage
50/60Hz
4.250
5.000
Switched
Inputs
6.75
6.25
GROUND
RECEIVE DATA
TRANSMIT DATA
6197 8
32 4 5
GROUND
61978
32 4 5
61978
32 4 5
RS-232 Null Modem Cable
Wiring Diagram
RS232 CONNECTORS (TOP VIEW)
9-PIN RS232 D-SUB (PLUG) CONNECTOR
MOUNTED ON CONTROLLER
MATES WITH 9 PIN (RECEPTACLE)
CONNECTOR AMP #747150-1 OR EQUIV.
The I/O board also has the capacity to
monitor the temperature of a type J thermo
couple in °F, with a range of 40°F to 700°F.
History Trending: The I/O board has the
capability to store data generated by the
Timer connected to its RS232 port as well
as data generated by the various sensing
devices connected to its inputs. Data histo
ry is subdivided into three categories: Short
Term History, Long Term History, and Alarm
History.
Short Term History is a time and date
stamped recording of the hourly averages of
the 4-20mA inputs, the Differential Pressure
from the Timer, the highest temperature
recorded, and the number of outputs that
were pulsed in that hour. This Short Term
History period is two weeks, after which
time the oldest 24 hours of recorded data
is averaged along with the highest recorded
temperature and the number of outputs that
were pulsed for that period and is stored in
Long term history.
The Long Term History period is one
year, after which time the oldest recorded
data is discarded to make room for new
data.
Alarm History is event driven, if any
alarm conditions occur, a time and date
stamped “snapshot” of all the system
parameters is recorded in a First-In-FirstOut circular data buffer. This FIFO buffer
can store up to 212 alarm events and is not
time dependent.
In order to generate the Data History
Reports, a DNC-T2300-DSP Remote
Display Panel and a terminal device capable
of communicating standard ASCII via an
RS232 connection are required.
SPECIFICATIONS
INPUTS
Voltages: 105-135 VAC, 50/60 Hz; 210-270 VAC,
50/60 Hz
4-20 mA Current Loops:
Input Impedance: 401.5 ohms +20 ohms
Accuracy: +1% of applied signal.
#1: Emissions/Aux1 (Sink Capability Only)
User Selectable Functions:
Emissions: Output is percent of full scale input
Generic: Output is percent of full scale input
#2: Air Flow/Aux2 (Sink Capability Only)
User Selectable Functions:
Air Flow: Pitot Tube sensing device required,
output range 0 to 6.5 mega SCFM
Generic: Output is percent of full scale input
#3: Manifold/Aux3 (Source or Sink Capability)
Source Voltage: +24v
User Selectable Functions:
Manifold pressure: Output range: 0 to 999 psi
Generic: Output is Percent of full scale input.
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
+2v
-
-
Switched Inputs:
Alarm Input Open Circuit Voltage: 40 VDC
Alarm Input Short Circuit Current: 4.5 mA
#1: Airlock Fault/Aux4 Alarm: Input will be
labled and recorded as either Air Flow or Aux4
depending on user selection.
#2: High Hopper/Aux5 Alarm: Input will be
labled and recorded as either High Hopper or
Aux5 depending on user selection.
#3: Standby Function: Dedicated as a Remote
Standby Switch Input.
Thermocouple Input:
Thermocouple: Type J
Temp. Measurement Range: -40°F to 700°F
Temp. Measurement Accuracy: +4°F
SERIAL COMMUNICATIONS
Null modem type connection required between
controller and I/O board.
Type: RS232
Mode: 4800 baud, 8-data bits 1-start bit 1-stop
bit, X ON - X OFF, no parity
Function: Dedicated for communication with a
T2300 Series Dust Collector Controller.
Connector: 9-pin male IBM-compatible D-SUB
connector. Null modem type connection required
between controller and I/O board.
Network Connection:
Type: 2 wire twisted pair
Termination: 52.3 ohm, 1%, 1/8 W resistor
Network Connection Device: FTT-10A Transceiver
ENVIRONMENTAL
Operating Temperature Range: -40° to 65°C
Humidity: 90% non-condensing
Environmental Protection: RTV conformal coat
ing for humidity and vibration
Contact factory for additional information
Caution:
1. Do not mount controls in high vibration areas with
out shock mounts.
2. Do not mount controls in areas of high dust or cor
rosive atmospheres without a protective enclosure.
3 Do not use a converter or inverter for the power
source.
4. Do not mount control in high transient voltage
areas without an isolation transformer.
-
5. Do not leave control box open.
6. Do not allow a local repair shop to repair the con
trols, as we employ some very sophisticated compo
nents that could be further damaged. For service, call
us directly: 800-323-2593.
4-21
-
-
-
-