NATIONAL CONTROLS DNC-T2003 User Manual

4-4
L1 L2 1 2 3 4 5 6 7 8 9 10
C
Pressure switch
voltage
Input
120V
Last
Solenoid
S
S
Solenoid
Last
TIMER #2
C
10987654321L2
L1
Pressure switch
3867-1
11
4
8
13
9
COM
coil
Reset
12
coil
Set
N.C.
COM
1
N.C.
N.O.
N.O.
5
10
14
Alternate action
dual coil latching
relay. Contacts
shown with reset
coil energized last.
DUST COLLECTOR CONTROLS
AC Input, Pulse Cleaning of Bag House Dust Collectors
Models DNC-T2003 through DNC-T2032
FEATURES
Digital Timing Circuitry: allows for sta-
ble timing from -40°C to 65°C tempera ture range
Pulse Time: line synchronized to elimi
nate 8 millisecond triac turn off variation 10 A-400/600V Output Triacs: for maxi
mum protection against output shorts. 200 VA load rating
Conformally coated for protection
against vibration, humidity, and con tamination
2 Modes of Operation: can be operated
Continuously or On Demand via external pressure switch
Field Selectable: for numbers of outputs required
LED Indicators: for compartment being cleaned indication
Rugged Timing Adjustments: large sta ble potentiometers are used for ON and OFF time adjustments
Metal Chassis Provided: for mounting
directly into NEMA 4 box
Timer Functionally Tested for 24 Hours: to eliminate field failures
Input Protection: 30 joule metal oxide
varistor One Year Warranty: warranted to be free
from defects in materials or workmanship for one year from date of manufacture
File #E65038
Program wire allows the user to select the maximum number of outputs to be acti vated.
-
Note: Controls are shipped with jumper across pressure switch terminals
-
-
SPECIFICATIONS
-
TIME DELAY
ON-Time: Adjustable from 50 to 500 ms OFF-Time:
-
Range A: adjustable from 1.5 to 30 seconds Range B: adjustable from 8.5 to 180 seconds
Note: Range S designates customer specified time range. Consult factory for parameters
Repeatability: ±3% over temperature and volt­age ranges
INPUT
Operating Voltage: 120 ±10%, 220 ±10% VAC Frequency: 50/60 Hz Power Consumption: 2 VA max.
OUTPUT
-
Type: Solid state switch (triac) Switch Rating: 200 VA maximum per output
PROTECTION
Transient Voltage: 30 joule metal oxide varistor Short Circuit Protection: 3 A fuse
ENVIRONMENTAL
Operating Temperature: -40°C to 65°C Storage Temperature: -40°C to 70°C
Operating Logic: The control can function
in 2 modes. In Continuous Mode, the pressure switch terminals are shorted. Upon application of input voltage, the control activates output #1 after the preset off time. It will continue to activate outputs sequentially until input voltage is removed. In On Demand Mode, the pressure switch terminals are connected to an isolated set of contacts of a differential pressure switch. The control will activate the outputs sequen tially whenever the pressure switch contacts are closed. When the pressure switch con tacts open, the output sequencing stops. Re-closing of the contacts will cause the control to resume activating the outputs.
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
-
-
C
A
D
B
.25
.31
.25 Dia. Hole
(4 Pl.)
L1
L2
AC Voltage Input
C 1 2
Solenoid Valve
OFF & ON Time Adjustments
Program Wire-
Determines number
of outputs to be activated
(4250-2 10/92)
.625
2.0 Max.
.050 Aluminum
Chassis
OFF
ON
3 AMP
# 6 screw typ.
NOTE: Not all components
a
re shown. Component
l
ocations can vary from
m
odel to model.
Pressure Switch Input­For on demand cleaning. (Controls are shipped with inputs shorted out)
ORDERING INFORMATION
DUST COLLECTOR CONTROLS
4-5
OUTPUTS
DNC-T2003 THROUGH DNC-T2032 120 VAC INPUT VOLTAGE
DNC-T2006 THROUGH DNC-T2032 220 VAC INPUT VOLTAGE
Note: Special time ranges are available with the following maximum to minimum time ratio restrictions: ON Time–10:1; OFF Time–20:1
Enclosure for DNC-T2003 8” x 6” x 3.5” BOX-A0806-CHNF
Enclosure for DNC-T2006 10” x 8” x 4”
Enclosure for DNC-T2010 10” x 8” x 4”
Enclosure for DNC-T2020 12” x 10” x 5” BOX-A1210-CHNF
Enclosure for DNC-T2032 14” x 12” x 6”
Pilot Lamp NEMA 4 Rated Red Light ASL-00RED-NEMA-4
On/Off Switch NEMA 4 Rated with Legend Plate MSW-0DPST-001
Alternate Action Dual Coil Latch Relay
Socket For Latch Relay
AMETEK NCC offers NEMA 4 type enclosures for mounting our controls. These enclosures are made of heavy gauge steel and have a con­tinuous hinge cover. All seams are continuously welded. The finish is gray hammer-tone enamel inside and out, over phosphatized surfaces.
MAX.
NO. OF
DIMENSIONS
A B C D
SIZE OF
NEMA 4 ENCLS.
REQUIRED
PROGRAM­MABLE NO.
OF OUTPUTS
3 6.75 4.875 6.25 4.25 8” x 6” x 3.5” 1-3
6 8.75 6.875 8.25 6.25 10” x 8” x 4” 2-6
10 8.75 6.875 8.25 6.25 10” x 8” x 4” 3-10
20
10.75 8.875 10.25 8.25
12” x 10” x 5”
32 12.75 10.875 12.25 10.25 14” x 12” x 6” 17-32
6 8.75 6.875 8.25 6.25 10” x 8” x 4” 2-6
10 8.75 6.875 8.25 6.25 10” x 8” x 4” 3-10
20
10.75 8.875 10.25 8.25
12” x 10” x 5”
32 12.75 10.875 12.25 10.25 14” x 12” x 6” 17-32
ACCESSORY DIMENSIONS PART NUMBER
ACCESSORY DIMENSIONS PART NUMBER
KDD-LATCH-120AC
MSO-0D11P-012
11-20
11-20
OFF TIME PART NUMBER
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
1.5 to 30 sec.
8.5 to 180 sec.
BOX-A1008-CHNF
DNC-T2003-A10
DNC-T2003-B10
DNC-T2006-A10
DNC-T2006-B10
DNC-T2010-A10
DNC-T2010-B10
DNC-T2020-A10
DNC-T2020-B10
DNC-T2032-A10
DNC-T2032-B10
DNC-T2006-A220
DNC-T2006-B220
DNC-T2010-A220
DNC-T2010-B220
DNC-T2020-A220
DNC-T2020-B220
DNC-T2032-A220
DNC-T2032-B220
BOX-A1008-CHNF
BOX-A1412-CHNF
Caution:
1. Do not mount controls in high vibration areas with out shock mounts.
2. Do not mount controls in areas of high dust or cor rosive atmospheres without a protective enclosure.
3 Do not use a converter or inverter for the power source.
4. Do not mount control in high transient voltage areas without an isolation transformer.
5. Do not leave control box open.
6. Do not allow a local repair shop to repair the con trols, as we employ some very sophisticated compo nents that could be further damaged. For service, call us directly: 800-323-2593.
-
-
-
-
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com