4-2
adjust
On
Of
f
Fan
Switch
Off
On
Load
Shaker
1.8 sec.- 3 min
fixed
2 minutes
New
cycle
DUST COLLECTOR CONTROLS
Intermittent Use Collectors
Model T2101
FEATURES
Simple 4 wire installation
●
Replaces electromechanical timers
●
Completely solid state timing and
●
switching logic
High quality locking bushing
●
potentiometers for timing adjustment
●
Very low power consumption
●
Conformally coated for protection
against vibration, humidity, and con
tamination
LED function lights on PC board
●
Function indicating lights on T2101-020
●
Mounts in standard NEMA 4/JIC
●
enclosures
●
LOGIC FUNCTION DIAGRAM
File #E65038
Operating Logic: The control is used on
intermittent type dust collectors to auto
matically activate the shaking mechanism 2
minutes after the fan motor is turned off.
Upon removing power from the fan, a 2
minute fixed delay is initiated. At the end
of the delay, the shaker output is activated
for an adjustable period of 1.8 seconds to
3 minutes. Resetting the control occurs by
turning the fan motor on again.
CAUTION: The control must be wired according to the schematic
provided.
-
-
SPECIFICATIONS
TIMING
Delay Time: 120 sec. ±10% fixed
Shake Time: Adjustable from 1.8 to 180 sec.
Repeatability: ±3% over temperature and volt-
age range
INPUT
Operating Voltage: 105 to 135 VAC
Power Consumption: 5.5 W plus shaker contac
tor coil power
Frequency: 50/60 Hz
OUTPUT
Type: Solid state switch, 1 A continuous at 1.5 V
below input voltage
TRANSIENT PROTECTION
Input: Transformer and large filter capacity
Output: Solid state switch rated for 10 A at 400V
protected by metal oxide varistor; 3 A fuse protects against external short circuit
ENVIRONMENTAL
Operating Temperature: -40°C to 65°C
Storage Temperature: -40°C to 70°C
-
ORDERING INFORMATION
DESCRIPTION PART NUMBER
Control on Chassis DNC-T2101-010
Control in Hinged NEMA 4 Box with Functional Lights
ACCESSORY DIMENSIONS PART NUMBER
NEMA 4 Box 6” x 8” x 4” BOX-A0606-CHNF
Pilot Lamp NEMA 4 Rated Red Light ASL-00RED-NEMA 4
On/Off Switch NEMA 4 Rated with Legend Plate MSW-0DPST-011
AMETEK NCC offers NEMA 4 type enclosures for mounting our controls. These enclosures are made of heavy gauge steel and have a continuous hinge cover. All seams are continuously welded. The finish is gray hammer-tone enamel inside and out, over phosphatized surfaces.
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
DNC-T2101-020
Caution:
1. Do not mount controls in high vibration areas with
out shock mounts.
2. Do not mount controls in areas of high dust or cor
rosive atmospheres without a protective enclosure.
3 Do not use a converter or inverter for the power
source.
4. Do not mount control in high transient voltage
areas without an isolation transformer
5. Do not leave control box open.
6. Do not allow a local repair shop to repair the con
trols, as we employ some very sophisticated compo
nents that could be further damaged. For service, call
us directly: 800-323-2593
-
-
-
-
Control Power On
Load On
4.0
6.
0
1.
0
6.0
6.75
7.5
4.875
.75
.312 DIA.
4 HOLES
(4250-1 10/92)
sec. 1801.8
4.625
5.125
.25
5.625
6.125
.2
5
4 HOLES
.25 DIA.
.625
2.125 Max.
Metal Chassis
T2101
1
2
3
4
On
Off
L2
L1
F
S
Fan
Contactor
Coil
Fan
Start/Stop
Switch
Terminal
Block
N.O.
Aux.
Shaker
Contactor
Coi
l
120
VAC
L1
L2
#6 screw typ.
Shake Time
Adjust
1
2
3
4
3A
L1 L2
Model DNC-2101-010
DUST COLLECTOR CONTROLS
4-3
Model DNC-2101-020
Field Wiring Diagram
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com