1-32
On
Off
Closed
Open
Control
Input
Output
50 mSec.
max.
50 mSec.
max.
.250 X .032 MALE
SPADE TERMINAL
(4 PLACES)
West Chicago, IL.
ASY-INPUT-BUFR
1 3
60185
Model No.:
5 4
OUTPUT
(TO START SW)
CONTROL INPUT
12-240 VAC/DC
INPUT BUFFER
TO NCC
TIMER-TRIGGER
INPUTS
V
INPUT VOLTAGE SOURCE
1.25
.885
2.00 SQ.
Corporation
National Controls
.170
DIA.
(Typical Wiring Diagram)
TIME DELAY RELAYS
Universal Voltage Input Buffer
ASY-INPUT-BUFR
FEATURES
Universal control voltage range: 12 to
●
240 VAC/DC
Controls all NCC timers requiring start
●
switch input
No need for isolated start switch con
●
tacts
Easy interface to programmable logic
●
controllers
Completely solid state, no moving parts
●
to wear out
Circuitry completely encapsulated
●
●
Low cost
●
Compact size
●
Superior transient protection
●
Flame-retardant and solvent-resistant
polyester thermoplastic housing
●
File #E164906
The universal input buffer will take any voltage from 10.6 to 265 VAC/DC and actuate
any NCC timer requiring a start switch to
initiate a timing cycle.
Operating Logic: Upon application of input
voltage, the output becomes an effective
contact closure (within 50 ms). Upon remov
al of input voltage, the output becomes an
effective open circuit (within 50 ms).
-
SPECIFICATIONS
INPUT
AC: 10.6 to 265 VAC 50/60 Hz, 5 mA max.
DC: 10.6 to 265 VDC 5 mA max.
Input-Output Delay: 50 ms max.
OUTPUT
Effective contact closure for NCC timers:
Closure: VAC = 9 to 265, 50/60 Hz (6 mA max.)
Closure: VDC = 9 to 265, (6 mA max.)
Voltage drop across output: 2.2 VAC/VDC max.
at I=6 ma
Output leakage: At Vin= 0 VDC and Vout = 265
VDC, leakage is 25 uA DC max.
PROTECTION
Transient Voltage: 30 joule metal oxide varistor
Dielectric breakdown: 3000 Vrms terminal to
mounting; 1500 Vrms input to output
Insulation resistance: 100 megohms min.
between terminals and case
MECHANICAL
Termination: .25” x .032” male fast-on terminals
Mounting: Surface mount with one #8 screw
ENVIRONMENTAL
Storage temperature: -40°C to 85°C
Operating temperature: -40°C to 65°C
Humidity: 95% relative max.
-
LOGIC FUNCTION DIAGRAM
ORDERING INFORMATION
INPUT VOLTAGE RANGE PART NUMBER
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
12 to 240 VAC/DC ASY-INPUT-BUFR
Consult factory for any special requirements not
listed in catalog (minimum order requirement may
apply).