NATIONAL CONTROLS ASY-INPUT-BUFR User Manual

1-32
On Off
Closed Open
Control Input
Output
50 mSec. max.
50 mSec. max.
.250 X .032 MALE SPADE TERMINAL (4 PLACES)
West Chicago, IL.
ASY-INPUT-BUFR
1 3
60185
Model No.:
5 4
OUTPUT
(TO START SW)
CONTROL INPUT
12-240 VAC/DC
INPUT BUFFER
TO NCC
TIMER-TRIGGER
INPUTS
V
INPUT VOLTAGE SOURCE
1.25
.885
2.00 SQ.
Corporation
National Controls
.170
DIA.
(Typical Wiring Diagram)
TIME DELAY RELAYS
Universal Voltage Input Buffer
ASY-INPUT-BUFR
FEATURES
Universal control voltage range: 12 to
240 VAC/DC Controls all NCC timers requiring start
switch input No need for isolated start switch con
tacts Easy interface to programmable logic
controllers Completely solid state, no moving parts
to wear out Circuitry completely encapsulated
Low cost
Compact size
Superior transient protection
Flame-retardant and solvent-resistant polyester thermoplastic housing
File #E164906
The universal input buffer will take any volt­age from 10.6 to 265 VAC/DC and actuate any NCC timer requiring a start switch to initiate a timing cycle.
Operating Logic: Upon application of input voltage, the output becomes an effective contact closure (within 50 ms). Upon remov al of input voltage, the output becomes an effective open circuit (within 50 ms).
-
SPECIFICATIONS
INPUT
AC: 10.6 to 265 VAC 50/60 Hz, 5 mA max. DC: 10.6 to 265 VDC 5 mA max. Input-Output Delay: 50 ms max.
OUTPUT
Effective contact closure for NCC timers:
Closure: VAC = 9 to 265, 50/60 Hz (6 mA max.) Closure: VDC = 9 to 265, (6 mA max.)
Voltage drop across output: 2.2 VAC/VDC max. at I=6 ma
Output leakage: At Vin= 0 VDC and Vout = 265 VDC, leakage is 25 uA DC max.
PROTECTION
Transient Voltage: 30 joule metal oxide varistor Dielectric breakdown: 3000 Vrms terminal to
mounting; 1500 Vrms input to output Insulation resistance: 100 megohms min.
between terminals and case
MECHANICAL
Termination: .25” x .032” male fast-on terminals Mounting: Surface mount with one #8 screw
ENVIRONMENTAL
Storage temperature: -40°C to 85°C Operating temperature: -40°C to 65°C Humidity: 95% relative max.
-
LOGIC FUNCTION DIAGRAM
ORDERING INFORMATION
INPUT VOLTAGE RANGE PART NUMBER
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
12 to 240 VAC/DC ASY-INPUT-BUFR
Consult factory for any special requirements not listed in catalog (minimum order requirement may apply).