NATIONAL CONTROLS 240T6 User Manual

5-4
1
2
3
4
5
6
7
8
1.770 (45.0)
2.400
(61.0)
120/240VAC
CONTACTS: 10AMP,1/3HP,345VA,
1 8
2
3
7
6
4
5
C B
AFFF
PIN CONFIGURATION
WEST CHICAGO, IL. 60185
MODEL: PLC-240T6-44T INPUT VOLTAGE: 160-240 VAC
R R
3 , 60 HZ
3 PHASE VOLTAGE MONITOR
N C
ATIONAL CONTROL
S
ORPORATION
F
.522
2.935
3.650 MAX
(74.5)
(93.0)
(13.26)
FaultNormal
Fault Delay
Yellow
VOLTAGE
LO
Green
LINE
HI
Red
TRICOLOR LED
VOLTAGE MONITORS
3-Phase Voltage Monitor
Model 240T6
FEATURES
100% functionally tested
Low cost
3 second fault delay timer
Line voltage setpoint adjustment range:
160 VAC to 240 VAC 50/60 Hz operation
SPDT 10 A relay output
Convenient plug in package
File #E59090
SPECIFICATIONS
SETPOINT
Adjustment: Single turn potentiometer for adjust-
ing nominal voltage Range:
160-240 VAC 60 Hz LO to HI 180-240 VAC 50 Hz LO to HI
Accuracy:
Min. Setting (Max. CCW): Must operate (green light) at 160 VAC, 60 Hz (180 VAC, 50 Hz) line to line Max. Setting (Max. CW): Must drop out (red light) at 240 VAC 50/60 Hz line to line
Hysteresis: 2% typical
Operating Logic: This control continuously
monitors 3-phase power lines for abnormal conditions. When properly adjusted, the control will detect:
Phase loss on a loaded motor, regard
less of regenerated voltage Low voltage on all phases Very low voltage or loss of any single
phase Phase reversal
If none of the above conditions are present, the control will energize the internal relay and the indicator light will be green. When any of the above faults are detected, the indicator light will turn yellow for approxi mately 3 seconds warning that the relay is about to de-energize. After the delay time the relay will de-energize and the indicator light will turn red. When the fault is correct ed, the monitor will automatically reset by energizing the relay and the indicator lamp will be green. Should the fault be corrected during the delay time, the monitor will not de-activate the relay and the indicator will again be green.
-
Fault Delay Time: 2 to 4 sec.
INPUT
3 Phase Operating Voltage: Three wire connec-
tion, no neutral required 160-240 VAC, 277 VAC max. line to line 60 Hz
-
180-240 VAC, 277 VAC max. line to line 50 Hz Power Consumption: 3 W max. at 277 VAC line
to line exclusive of load
Frequency: 50/60 Hz
OUTPUT
Contact Type: Relay SPDT (1 form C) Rating: 10 A max. resistive, 1/3 hp, 345 VA,
120/240 VAC Life:
Mechanical: 10,000,000 operations Full Load: 500,000 operations
Display: 1 tricolor LED
Green indicates status OK Yellow indicates fault condition imminent Red indicates fault condition
-
PROTECTION
Transient Voltage: protected by three 30 joule
metal oxide varistors Dielectric Breakdown: 1500 V RMS minimum at
60 Hz between input and outputs and between outputs
MECHANICAL
Termination: 8-pin plug
Adjustment: Apply 3-phase power with-
in operating range to the monitor (phase sequence must be observed). Turn adjust ment to maximum clockwise position. Indicator lamp will be illuminated red after the delay time. Slowly turn counterclock
-
Mounting: Socket mount, part number MSO-0008P-012
-
ENVIRONMENTAL
Storage Temperature: -23°C to 70°C Operating Temperature: -23°C to 55°C
wise until indicator changes to green (relay will activate). If voltage is nominal, setting should be correct.
Note: If phase sequence is incorrect, the monitor will not activate. Reverse any two input leads and readjust as described above.
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
ORDERING INFORMATION
VOLTAGE RANGE PART NUMBER
160 to 240 VAC PLC-240T6-44T
ACCESSORY PART NUMBER
8-pin circular socket, DIN rail mountable
MSO-0008P-012