Narada 12REXC70, 12REXC200, 6REXC300 Operation Manual

Page 1
LEAD-CARBON BATTERY
OPERATION
MANUAL
VersionV1.0
NARADA POWER SOURCE CO., LTD
12REXC Series
Page 2
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
2
Content
Safety and Warning ......................................................................................................... 3
Chapter One Introduction of 12REXC series ............................................................... 4
1. Product Characters .............................................................................................. 4
2. Main applications ................................................................................................. 5
3. Configuration ....................................................................................................... 5
4. Types and Dimensions ......................................................................................... 6
5.Lead Carbon Working Principle ......................................................................... 6
Chapter Two Technical characteristic ............................................................................ 7
1. Discharge Curve and Discharge Data ................................................................ 7
2. Charge Curve ....................................................................................................... 8
3. Internal Resistance and Short-Circuit Current ................................................ 8
Chapter Three Operation and Maintenance ................................................................. 8
1. Parameters Setup ................................................................................................. 8
2. Capacity and Influence Factor ......................................................................... 10
3. Ambient Temperature vs. Battery .................................................................... 10
4. Requirement for Charge ................................................................................... 13
5. Storage ................................................................................................................. 16
6. Maintenance ....................................................................................................... 16
After-sales Service / Customer Service Hotline ........................................................... 17
Annex 1 ........................................................................................................................... 18
Page 3
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
3
Safety and Warning
Please read this manual! It provides very important direction for fix and operation, which can make best capability for the equipment, and elongate the using life. For your safety, please do not try to dismantle or open the equipment. The equipment does
not contain any spare parts for you. The maintain work can only be done by specially trained service persons.
As a result of the batteries’ latent endanger to health and environment, they should be only
changed in our authorization service center. If you need to change the battery or maintain the equipment, please call the nearest service center.
Batteries can be reclaimed, if it could not be carefully handled, it will do great harms to
environment and heath. Please check local laws and regulations to get the validity handle ways or send the equipment to authorized service center.
The replacement of battery can only be done by persons who know well about the danger
and the prevention. When changing the battery, please use the same model and type of sealed lead acid battery.
Warningdo not smoke or use fire near batteries
Warningdo not use organic solvent to wash batteries
Warningdot not put batteries into the fire, or it may bombed Warningdo not open batteries, it contains electrolyte, which can hurt the skin and eyes. WarningThere may happen shock or short circuit when replacing the batteries. Please
operate with tools with insulated handles.
Please take care of the following marks in using
Warning
Electricity
danger
Protecting
your eyes
Watch
Short-circuits
With adults
custody
Do not put batteries
into dustbin
Read the
manual
Fire
forbidden
Circle used
Page 4
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
4
Chapter One Introduction of 12REXC series
12REXC series battery is designed for renewable energy sources such as wind power and solar system, and developed for home energy system with long life, high energy efficiency, superb security and reliability characteristic, which can be applied to energy storage system, telecom and generator, etc.
1. Product Characters
Lead carbon battery add carbon material with high capacitance or highly
conductive into the negative electrode, combine the advantages of lead acid battery and super capacitors, lead carbon battery provide not only high energy density, but also high power, rapid charge and discharge, longer cycle life.
Combine the advantages of lead acid battery and super capacitors Ideal for PSOC cycle application Excellent recharge acceptance performance, super fast charge/large discharge
performance
Reduce sulfation of the negative plate, longer cycle life
1.1 Design life is above 20 years
Grid alloy with special patented formula Special patented negative paste formula 4BS paste technology Extra-thick plate design
1.2 Initial capacity above 100%, the remaining capacity above 90% when storage for 3 months (25ºC)
1.3 Remarkable high rate discharge performance.
Low internal resistance. Patented grid design. Large section copper structure
1.4 Innovation patented lead carbon technology
The innovation patented lead carbon technology can solve sulfation of the negative plate when used underfilling; compare with tradition VRLA battery, cycle life of the lead carbon battery can be extended 3-10 times
1.5 Ideal for PSOC cycle application
Cycle use at 80% SOC (part state of charge) can be longer PSOC cycle life, which especially designed for solar or wind energy storage system
1.6 Supply the unique flexible connectors made of rubber wrapped with copper wires and another option is copper bar connector.
Assure the good connections of post and connectors and low connection resistance;
Page 5
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
5
Combination of suppleness and rigidity for more flexible connections;
1.7 Flexible and convenient installation, slinky outside looking
Shockproof blocking assembling
Satisfy customer’s individual requirements and provide up to 8-class shockproof
Streamline and dime-light battery outside-looking design.
2. Main applications
Home energy storage system Hybrid energy system such as solar and wind energy Distributed energy storage system Smart power grids and microgrids system Generator and battery hybrid energy system Solar power generation grid/off-grid energy storage system Emergency lighting system Other standby, cycling system
3. Configuration
Fig. 1-1 Configuration
Lid
Pole
Container
Page 6
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
6
4. Types and Dimensions
Table 1-1 type specifications
Battery Type
Rated Voltage per cell (V)
Rated Capacity (Ah)
Dimensions (mm)
Weight
(Kg)
C10
C
100
Length
Width
Height
Overall
Height
End-volta ge
1.80V
End-volt
age
1.85V
12REXC70
2
60
70
280
180
230
244
30
12REXC200
2
165
200
438
227
281
294
79.5
6REXC300
2
250
300
338
227
281
294
61
5.Lead Carbon Working Principle
Fig.1-2 Lead carbon battery working principle sketch map It forms a new active center in negative electrode by adding active carbon, that can reduce lead deposition overpotential, the lead sulfate will be translated into lead more easily. Growing up of lead sulfate can be suppressed efficiently through this technology.
Fig.1-3 Lead carbon negative electrode surface current distribution sketch map
The chemical reaction taking place in lead carbon battery is as follows: positive electrode:
Page 7
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
7
negative electrode:
Because of the reaction is based on double layer capacitance which caused from carbon electrode/electrolyte interface, thereby the lead carbon battery has part characteristic of super capacitors. Thus the lead carbon battery can possess large current and long cycle life performances. 12REXC battery adopts a design of barren-liquor and utilizes AGM (micro porous glass fiber) separator. Thus there is a path existing between the positive and the negative. Also special alloy grid is chosen to increase vent hydrogen over-potential gassing on the negative plate, which prevents generation of hydrogen. Otherwise, the oxygen generated from positive diffuses through separator to the negative and the
oxygen gas reacts quickly and is recombined into water. The reactions are as follows: 2Pb +O2 2PbO ;
PbO+ H2SO
4
PbSO4 +H2O;
So it is possible to build 12REXC battery in sealed structure.
Chapter Two Technical characteristic
1. Discharge Curve and Discharge Data
Fig. 2-1 12REXC Battery Discharge Performance Curves at Different Discharge Rates
25
Discharge curve at different rate 25 ℃)
1
C120C10
C3
C1
Discharge voltage V( )
HoursMin
13.20
12.00
10.80
9.60
8.40
O(l)2H(s)PbSO
arg
arg
2(aq)3H(aq)HSO(s)PbO
24
-
-
42
ech
edisch
e
-
2-x
2)-(x
6x
x 6
2e (aq)2H(aq))(HnC
arg
arg
(aq))(HnC
--
ech
edisch
Page 8
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
8
Fig.2-1 Discharge characteristic curve
2. Charge Curve
Fig.2-2 Recharge characteristics of 12REXC battery with current of 0.1C10A and limit voltage of 2.30V/cell (25). The 100% DOD battery can be recharged 105% of capacity after charging for 24 hours. Imaginary line is the recharge curve of 50%DOD.
Charge curve 25 ( ℃ )
14.1
13.5
12.9
12.3
100% disc harge
50% discharge
0 244 1612 208
C harge capacity(%)
C harge current(C A)
C harge voltage(V )
Charge current
Charge capacity
Charge voltage
Time ( h )
Fig.2-2 Charge characteristic curve
3. Internal Resistance and Short-Circuit Current
The internal resistance of the battery is a dynamic nonlinear parameter that is continuously changed along with the temperature and discharge state. The internal resistance is the lowest when battery is fully charged. The table 2-3 shows the internal resistance and short circuit current of 12REXC battery in fully charged state according to the IEC60896 standard. Pay attention to the battery to short-circuit causes the battery voltage to reduce to 0V, and will cause the battery internal component damaged.
Table 2-3 Referenced Internal Resistance and Short Current
Battery Type
Internal Resistance
()
Short Current (A)
12REXC70
9.79
1291
12REXC200
3.83
3274
6REXC300
1.35
4619
Chapter Three Operation and Maintenance
1. Parameters Setup
Page 9
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
9
Table3-1 Home energy storage system parameter setup table (48V system)
Parameter name
Unit
Grid
Off-grid
Floating Voltage per cell
V/cell
2.30
2.30
Equalization Voltage per cell
V/cell
2.25
2.25
Charging Current
A/cell
0.1C10
0.2C10
Discharge under-voltage protection
per cell
V
Please refer to table 3-2
Condition To Change Equalization
Charge To Float Charge
mA/Ah
5
5
Condition to Change Float Charge To
Equalization Charge
mA/Ah
50
50
Pack equalization voltage
V
55.2
55.2
Pack floating voltage
V
54.0
54.0
Pack charging current
A
0.1C10
0.2C10
Pack discharge under-voltage
protection
V
Please refer to table 3-2
Temperature Compensate Ratio With
Floating Voltage
mV/ /
cell
-3
-3
Temperature Compensate Ratio With
Equalization Voltage
mV/ /
cell
-5
-5
High Temperature Warning
35
35
Short circuit protection current
A
Please refer to table 3-2
1. The voltage in above table is at 25. Please adjust the data according to table 3-3 at other temperature.
2. Energy storage system can be off-grid power supply and grid power supply according to real situation. The off-grid defined as tough power supply, to protect the battery better, please set refer to above table or contact to manufacture.
3. Above are standard setup parameters in table 3-1. We suggest you to set up end voltage (LVBD) based on different load current to make the battery life longer. Please refer to table 3-2.
Table 3-2 Voltage setup parameter of LVBD and LVLD
Load currentA
End voltageV/cell
LVBD for 48V system
V
I0.025C10
1.97
47.3
0.025C10≤I<0.05C10
1.92
46.1
Page 10
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
10
0.05C10≤I<0.1C10
1.87
44.9
0.1C10≤I<0.2C10
1.83
43.92
0.2C10≤I<0.5C10
1.75
42.0
If the battery is not recharged in time after discharge, or the power is off again during recharge, the insufficient-charged batteries will be frequently discharge, thus the batteries will lose part of capacity in short period. And it may cause capacity loss at initial stage and the batteries will be rejected if the situation is serious.
2. Capacity and Influence Factor
The capacity of battery is the capacity that battery can be discharged in the established conditions, expressed as signal C. The usual unit of capacity is ampere-hour, shortened as AH. The rated time is marked in the right and low corner of C, i.e. C10 is the capacity at 10 hours rate; C3 is the capacity at 3 hours rate. The capacity can be expressed in Rated Capacity or Actual Capacity. For Rated Capacity of 12REXC, please see Table 1-1. The Actual Capacity is the actual output capacity in certain discharge conditions, which is equal to product of the discharge current and the discharge time, the unit is AH. The actual capacity is effected by discharge rate, discharge mode, end voltage and temperature.
3. Ambient Temperature vs. Battery
The recommendation temperature for 12REXC is 15 ~ 25 . Used at high or low temperature, battery performance will be affected. Table 3-3 is the working temperature range for battery.
Table 3-3 Working temperature range for battery
Working condition
Temperature range
Recommended temperature
Discharge
-4050
1525
Charge
-2050
1525
Storage
-2040
1525
Temperature affects capacity of the battery. Fig. 3-1 is the available capacity (10h rated, end voltage 1.80Vpc) curve vs. ambient temperature. When the temperature is low, the capacity will decrease, for example, the capacity will decrease 10% if temperature decreases from 25 to 0; And too low temperature will cause battery long term insufficient charged, also will make negative plates sulfate and make battery unable to discharge. The capacity will increase at some range when temperature rises. For example the
Page 11
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
11
capacity will increase 5% if temperature raises from 25 to 35. But when the temperature go up further, the capacity will increase slowly, and at last stop increasing.
However, high temperature will quicken up plates’ corrosion and cause water loss, thus
shortens battery’s life.
Fig.3-1 Available Capacity Curve VS. Ambient Temperature
3.1 Temperature and Floating Voltage, Equalization Voltage
The purpose to select certain floating voltage is make the battery operate in best conditions. If the floating voltage is higher, the floating current is also higher; it will accelerate the corruption of grids and shorten the life of the battery. If the floating
voltage is lower, the battery can’t be kept in fully charged state, this will crystallize
PbSO4, decrease the capacity, and also shorten the life of the battery. At 25, the floating voltage is 2.25V, at other temperature, please adjust according to Table 3-4. The temperature compensation coefficient for float charge is -3mV//cell. Valve regulated sealed lead acid battery need to be equalized charge regularly, in order to guarantees the battery normal operation. 12REXC battery’s equalization voltage is
2.30V/cell.
Capacity %
Ambient Temperature(℃)
Page 12
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
12
Fig. 32 The Voltage Setting Curve Vs. Ambient Temperature
If the voltage lower than 2.225 or higher than 2.35 after temperature correction, the suggesting adopted can be charging by 2.25V or 2.35V directly without using temperature compensation.
Table 3-4 Relationship of ambient temperature and voltage
Ambient Temperature()
Equalization Voltage(V/cell)
Float Voltage(V/cell)
≤15
2.350
2.275
20
2.325
2.260
25
2.300
2.245
30
2.275
2.230
35
2.250
2.215
≥40
2.225
2.200
3.2 Ambient temperature vs. Battery Life The high temperature will damage the battery, reduce the battery life. When temperature exceeds 25, the battery life will decrease half per 10 temperature raise. For example, the design life of battery is 20 years at 25, if the battery is operate at 35 for long term, the life will be 10 years. Below is the formula:
L25=LT×2
(T-25)
/10
NotesT is the actual ambient temperature;
Floating and equalization setting voltage at different temperature
Voltage (V)
Temperature ()
Page 13
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
13
LT is designed life at T ambient temperature
L25 is designed life at 25 ambient temperature Ambient temperature elevating, also will accelerate the battery grids corrosion and the battery water loss, thus will greatly reduce the battery life. So it is important to control the ambient temperature. When heat is accumulated to a certain degree, it will damage the battery, seriously will lead to thermal run away. If indoor temperature reaches too high, please improve the ambient temperature by making room ventilated, etc. The battery spacing cannot to be less than 10mm, at the same time regulating cell floating and equalization voltage value according to handbook’s request.
3.3 Conductance, Resistance vs. Capacity There is a certain corresponding relationship between conductance & resistance and battery capacity. We suggest to test battery conductance and resistance data at different stage with same type instruments from same factory. Conductance and resistance data is only a reference to judge whether battery is good. These data cannot replace loading test to judge whether battery is good. Narada recommend to test these data on the surface or side of battery post. If there are several pairs of post, please test on nearest pair of post.
Figure 3-3 Test location for conductance and resistance
4. Requirement for Charge
4.1 Periodically Equalization Charge
The battery needs an equalization charge after floating operation over three months, or
the voltage of at least two batteries are lower than 2.17V. The method of equalization
charge is constant current and limited voltage, as follows: charge with constant current
of 0.1C10A~0.15C10A till the average voltage reaches equalization charge voltage of
2.30Vpc (25), then keep charging with equalization charge voltage, meanwhile, the current is reduced, till the charge finished. The charging time is 24 hours.
Test location for
conductance and
resistance
Page 14
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
14
4.2 Charge after discharge
After discharge, the batteries should be charged in time. The charge method is constant current limit voltage as follows: charge with constant current of
0.1C10A0.20C10A till the average voltage reaches a certain voltage, then keep charging with this voltage, meanwhile, the current is reduced, till the charge
finished. The certain voltage could be equalization voltage or float voltage. When the depth of discharge is larger (normally larger than 10%), equalization voltage is recommended so as to give fully charge to the battery. We can also determine charge voltage according to initial current. When the current is larger than
0.05C10A (reference current to change to equalization charge), equalization voltage is recommended. The charge time is 24 hours. We can also setup the charge voltage according to different DOD, different charge current shown in figure 3-4, or we can judge according to charge current value.
Normally, the batteries are fully charged when the value of charge current is not changed for continuous three hours at the stage of constant voltage charge,
Sometimes, we need to charge a battery in a short time, we can raise charge current, but not higher than 0.25C10A.
Fig .3-4 The relationship between DOD and charge time
4.3 Battery recharging method This method is used for battery charging for the first time after installing or battery
recharging after long time storage. Recharging parameter
We use equalizing charge to recharge the batteries, the parameter is as below: 1 Charging mode: equalizing charge; 2 Charging voltage: (2.30±0.002)V/cell;
Charge
time(h)
Depth of discharge (DOD %)
Page 15
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
15
3 Charging current limited: 0.05C10A; 4 Cut-off condition: the charging current is less than 0.005C10 with another
extended 3 hours or charging time reached 24 hours (alternative);
Recharging procedure
1 Connect the batteries in series with cables or copper bars, and make sure that all the screws tightened with each joint, then connect the anode of battery group to the anode of charging equipment (charger), and the cathode of battery group to the cathode of charger. Pay attention: A breaker or fuse should be connected in the circuit in order to protect the batteries and charger, the capacity of breaker or fuse should be 1.5 times of circuit maximum current. 2 Turn on the charger, set the charging voltage and current according to 4.1 recharging parameter.
3 Turn the breaker or fuse, and then turn on the charger to recharging batteries. 4 Stop charging when reaching the cut-off condition. At the last one hour before
finishing, test the battery voltage one by one, the battery which voltage is below
2.16V/cell should be dealt with the method in chapter 3.3, if that battery can not accord with the requirement, it should be rejected.
Cycle procedure
We can use the method as below to recharge the batteries after long time storage (for example: more than 1 year): First connect the batteries in series to the charger, discharge batteries with constant current 0.25C
10
(A) for about 3 hours. Then use the method above to charge the batteries. Stop charging when reach the cut-off condition. If the capacity still can not be renewed by this method, this means the batteries fail because of long time storage or other reasons.
4.4 Maintenance of wind/solar generating energy storage system It is necessary to recharge one time every two months for maintenance because of the under-filling state of the batteries used in home energy storage system and wind/solar generating energy storage system. The battery maintenance method can operate as below: In the case of mains supply, the maintenance and battery recharge methods be the same as clause 4.1.
Page 16
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
16
In case of without mains supply, should cut off the load, then the solar and wind generating can charge the battery, but maximum limited voltage 2.30V/cell, maximum current 0.20 C
10
A. The battery fully charged on condition that the charging current is
less than 0.005C10 or the charging voltage stay constant for four hours.
5. Storage
The storage area of 12REXC series batteries must be clean, ventilated, dry and without direct sunshine. All lead acid batteries lose capacity when standing on open circuit because of self-discharge. The result is that the voltage of open circuit is decreased, and the capacity also decreased. The self-discharge rate is related with ambient temperature. The self-discharge degree is smaller when the ambient temperature is lower, otherwise is larger. Batteries should be supplementary charged if they have been stored for six months or the open circuit voltage is lower than 2.10V/cell. The equalization charge method should be adopted. All batteries, which are ready to store,
should be fully charged before storage. It’s suggested to record storage time in periodic
maintenance record and record the time when another necessary supplementary charge should be made. The quality certificates of 12REXC series batteries record the latest charge time of the batteries, next charge time can be calculated according to this charge time.
6. Maintenance
In order to assure service life, the batteries should be correctly inspected and maintained. The maintenance methods of 12REXC batteries are recommended as follows:
6.1 Monthly Maintenance
Keep the battery-room clean. Measure and record the ambient temperature of the battery-room. — Check each battery’s cleanness; check damage and overheating trace of the
terminal, container and lid.
Measure and record the total voltage and floating current of the battery system.
6.2 Quarterly Maintenance
Repeat monthly inspection. Measure and record floating voltage of every on-line battery. If more than two
cells’ voltage is less than 2.18Vpc after temperature compensation, the
batteries need to be equalization charged.
6.3 Yearly Maintenance
Repeat quarterly maintenance and inspection. Check whether connectors are loose or not every year and tight them Make a discharge test to check with exact load every year, discharging 30-40%
of rated capacity. Make an 80%DOD capacity test every year after three years’ operation.
6.4 Operation and Maintenance Precautions Insufficient Charge
If the floating voltage is not set correctly (too low or not compensate according to
Page 17
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
17
temperature), the battery system will in an insufficient charge state for a long period of time. When the electricity is out, the battery may not be able to work because the acid is satirized and the capacity is decreased.
Over Charge
If we neglect the performance of rectifier to transfer floating charge to equalization charge. If the rectifier cannot transfer charge modes because of its wrong performance or no adjustment, the battery system is always in an equalization charge state. Thus may cause serious problems for battery, such as water loss, life decrease, thermal runaway, deformation, etc.
Too low or too high temperature
We have mentioned that too low temperature will affect the capacity of battery. While too high temperature will also cause problems, such as water loss, life decrease, thermal runaway, deformation, etc.
Too low end voltage
The end voltage is also an important parameter for battery. The battery shall stop discharge when reach a certain voltage (The normal end voltage is 1.8Vpc for 10 hours rated). If the end voltage is too low, it will be difficult to recharge the battery and decrease the charge efficiency, thus reduce the life of battery.
Long time storage after discharge
If the battery is put aside without charge for a long time after discharge, it will affect the capacity and life of the battery, because some large size PbSO4 will be created in the negative, which are difficult to transfer to active Pb. Thus it will affect battery life and capacity
After-sales Service / Customer Service Hotline
P.R. China: Asia Pacific:
Narada Power Source Co., Ltd.
9F, Building A, No. 50 Zijinghua Road, Hangzhou, China Tel: +86-571-28827013 Fax: +86-571-28828290 E-mail: intl@narada.biz Website: www.naradabattery.com
NARADA ASIA PACIFIC PTE.LTD.
65 Ubi Crescent #07-05 Hola centre, Singapore Tel: +65-6848 1191 Fax: +65-6749 3498 E-mail: sales@narada.com.sg
12REXC series operation manual
(V1.0
N- EN August 2014)
Subject to revisio
n without prior
notice E.&O.E.
Page 18
Narada Power Source Co., Ltd. 12REXC operation manual V1.0
18
Annex 1
VRLA Battery Regular Maintenance Record
Type Place
Status
Number of battery
Total VoltageV
Current (A)
Temperature
No. VoltageV
No. VoltageV
1 13
2 14 3 15
4 16
5 17
6 18 7 19 8 20 9 21 10 22 11 23 12 24 Check by sight
Result:
Tester:
Date: