Trim Extrusion Installation
Log Placement
Door Installation
Mantle Clearances
Logo Placement
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
Pg 9 OPERATION / MAINTENANCE
Operating Instructions
Maintenance
10 REPLACEMENT BLOWER
11 ADJUSTMENTS
Pilot Burner Adjustment
Vent Restrictions
Venturi Adjustments
12-13 REPLACEMENTS
Ordering Replacement Parts
Replacement Parts
Terminal Kits
Accessories
14-15 TROUBLE SHOOTING GUIDE
16 SERVICE HISTORY
WARNING
• The fi replace insert is a vented gas-fi red heater. Do not burn wood or other materials in this fi replace in-
sert.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should
stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room as
the fi replace insert.
• Due to high temperatures, the fi replace insert should be located out of traffi c and away from furniture and
draperies.
• Clothing or other fl ammable material should not be placed on or near the fi replace insert.
• Any safety screen or guard removed for servicing must be replaced prior to operating the fi replace insert.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the
fi replace insert and venting system are kept clean. The fi replace insert and its venting system should be
inspected before use and at least annually by a qualifi ed service person. More frequent cleaning may be
required due to excessive lint from carpeting, bedding material, etc. The fi replace insert area must be kept
clear and free from combustible materials, gasoline and other fl ammable vapours and liquids.
• Under no circumstances should this fi replace insert be modifi ed.
• This fi replace insert must not be connected to a chimney fl ue pipe serving a separate solid fuel burning
appliance.
• Do not use this fi replace insert if any part has been under water. Immediately call a qualifi ed service tech-
nicianto inspect the fi replace insert and to replace any part of the control system and any gas control which
has been under water.
• Do not operate the fi replace insert with the glass door opened, cracked or broken. Replacement of the
glass should be done by a licensed or qualifi ed service person.
• Do not strike or slam shut the fi replace insert glass door.
• This fi replace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple
supplied by Wolf Steel Ltd.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
W415-0223 / E / 03.05.09
Page 3
NAPOLEON gas fi replaces are manufactured under the strict Standard of the world recognized
ISO 9001:2000 Quality Assurance Certifi cate.
NAPOLEON products are designed with superior components and materials, assembled by trained craftsmen
who take great pride in their work. The burner and valve assembly are leak and test-fi red at a quality test station.
The complete fi replace is thoroughly inspected by a qualifi ed technician before packaging to ensure that you, the
customer, receives the quality product that you expect from NAPOLEON.
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
The following materials and workmanship in your new NAPOLEON gas fi replace are warranted against
defects for as long as you own the fi replace. This covers: combustion chamber, heat exchanger, stainless steel
burner, phazer™ logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing,
porcelainized enamelled components and aluminum extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch,
switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and NAPOLEON will
provide replacement parts free of charge during the fi rst year of the limited warranty.
Labour related to warranty repair is covered free of charge during the fi rst year. Repair work, however,
requires the prior approval of an authorized company offi cial. Labour costs to the account of NAPOLEON are
based on a predetermined rate schedule and any repair work must be done through an authorized NAPOLEON
dealer.
3
CONDITIONS AND LIMITATIONS
NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on
the warranty registration card fi led with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions
and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas fi replace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included
with the product and all local and national building and fi re codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will
nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain
enamel parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fi replace.
NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the fi rst 10 years NAPOLEON will
replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.
In the fi rst year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been
operated in accordance with the operation instructions and under normal conditions.
After the fi rst year, with respect to this President's Limited Lifetime Warranty, NAPOLEON may, at its discretion, fully discharge all obligations with respect to this warranty by
refunding to the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the fi rst year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses
are not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty , NAPOLEON’S responsibility under this warranty is defi ned as above and it shall not in any
event extend to any incidental, consequential or indirect damages.
This warranty defi nes the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fi replace and any other warranties expressed or implied with respect to this
product, its components or accessories are excluded.
NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible
for: over-fi ring, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting
confi gurations, insuffi cient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fi replace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damag-
ing chemicals or cleaners will not be the responsibility of NAPOLEON.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration
card must be returned within fourteen days to register the warranty.
NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
THIS GAS FIREPLACE INSERT SHOULD BE INSTALLED
AND SERVICED BY A QUALIFIED INSTALLER to conform
with local codes. Installation practices vary from region to
region and it is important to know the specifi cs that apply
to your area,
for example: in Massachusetts State:
• The fi replace damper must be removed or welded in the open
position prior to installation of a fi replace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or
bathroom unless the unit is a direct vent sealed combustion
product.
• WARNING: This product must be installed by a licensed plumber
or gas fi tter when installed within the commonwealth of
Massachusetts.
In absence of local codes, install to the current CAN1B149 Installation Code in Canada or to the National Fuel
Gas Code, ANSI Z223.1, and NFPA 54 in the United
States. Mobile home installation must conform with local
codes. In the absence of local codes, install to the current
standard for gas equipped mobile housing CAN/CSA Z240
MH Series in Canada or the manufactured home construction and safety standard, Title 24 CFR, part 3280, or the
Fire Safety Criteria for manufactured home installations,
Sites and Community Standard ANSI/NFPA 501A in the
United States.
Purge all gas lines with the glass door of the fi replace insert
opened. Assure that a continuous gas fl ow is at the burner
before closing the door.
Under extreme vent confi gurations, allow several minutes
(5-15) for the fl ame to stabilize after ignition.
The fi replace insert and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess
of 1/2 psig (3.5 kPa). The fi replace insert must be isolated
from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).
A 1/8 inch NPT plug, accessible for test gauge connection,
must be installed immediately upstream of the gas supply
connection to the fi replace insert.
The fireplace insert must be electrically connected and
grounded in accordance with local codes. In the absence of
local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA 70-1990 NATIONAL ELECTRICAL CODE in the United States. The blower
power cord must be connected into a properly grounded
receptacle. The grounding prong must not be removed from
the cord plug.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE INSERT
HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION
AND QUALITY!
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 1 1 inches water column for propane.
Maximum inlet gas pressure is 7 inches water column for
natural gas and 13 inches water column for propane. Manifold
pressure under fl ow conditions is 3.5 inches water column for
natural gas and 10 inches water column for propane. When
the fi replace is installed at elevations above 4,500ft, and in the
absence of specifi c recommendations from the local authority
having jurisdiction, the certifi ed high altitude input rating shall
be reduced at the rate of 4% for each additional 1,000ft.
Expansion / contraction noises during heating up and cooling
down cycles are normal and to be expected.
Maximum input is 24,000 BTU/hr for natural gas and propane.
Maximum output for natural gas and propane is 20,400 BTU/
hr at an effi ciency of 85% with the fan on. Maximum A.F.U.E.
(annual fuel utilization effi ciency) rating is 79 % for natural gas
and propane. This fi replace insert is not approved for closet or
recessed installations. It is approved for bathroom, bedroom
and bed-sitting room installations and is suitable for mobile
homes. The natural gas model is suitable for installation in a
mobile home that is permanently positioned on its site and
fuelled with natural gas.
This insert must be recessed into a vented noncombustible
wood-burning fi replace (prefabricated or masonry) only. The
minimum fi replace opening size in which the heater is to be
installed is:
HEIGHT 14½ inches
WIDTH 25 inches
DEPTH 11 inches
The minimum allowable chimney fl ue size is 6" round.
The minimum distance, from the bottom of a combustible
mantle projecting 3" maximum from the wall to the top of the
aluminium trim, is 3".
65.5%
GDIZC
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean these parts. Buff lightly
with a clean dry cloth.
The glass is 3/16" ceramic glass available from your Napoleon
/ Wolf Steel Ltd. dealer. DO NOT SUBSTITUTE MA TERIALS.
Clean the glass after the fi rst 10 hours of operation with a
recommended gas fi replace glass cleaner. Thereafter clean as
required. DO NOT CLEAN GLASS WHEN HOT! If the glass
is not kept clean permanent discolouration and / or blemishes
may result.
W415-0223 / E / 03.05.09
Page 5
36"
15
1
/2"
25"
10 9/16"
5 ½"
AIR INLET
EXHAUST
4 15/16"
15
1
/2"
11 5/8"
7 3/8"
3"Ø
44 7/8"
3 SIDED BACKER PLATE
ALUMINUM TRIM
44 7/8 "
36 1/2 "
4 SIDED BACKER PLATE
ALUMINUM TRIM
14"
15 1/
2
"
20 3/
4
"
INSTALLATION
Provide adequate ventilation air.
Provide adequate accessibility clearance for servicing
and operating the fi replace insert.
Never obstruct the front opening of the fi replace
insert.
Objects placed in front of the fi replace must be kept a
minimum of 48" away from the front face of the unit.
FIGURES 1a-c
3 SIDED BACKER PLATE - FRONT VIEW
Clean out ashes from the inside of the wood-burning fi replace.
Make sure that the chimney and wood-burning fi replace
are in a clean and sound condition and constructed of noncombustible materials. If necessary have any repair work done
by a qualifi ed person before installing the insert. Remove the
existing fi replace damper or lock into an open position.
Using screws, attach the fi replace warning tag (W385-0199)
to the inside of the fi rebox of the fi replace into which the insert
is being installed.
WARNING: THIS FIREPLACE HAS BEEN CONVERTED FOR USE WITH A GAS FIREPLACE
INSERT ONLY AND CANNOT BE USED FOR BURNING WOOD OR SOLID FUELS UNLESS
ALL ORIGINAL P AR TS HAVE BEEN REPLACED AND THE FIREPLACE IS RE-APPROVED BY
THE AUTHORITY HAVING JURISDICTION.
ATTENTION: CE FOYER A ETE CONVERTI AFIN D'ETRE UTILISE SEULEMENT COMME
FOYER ENCASTRE AU GAZ ET NE PEUT ETRE UTILSE POUR BRULER DU BOIS OU TOUT
AUTRE COMBUSTIBLE SOLIDE, SANS QUE TOUTES LES PIECES ORIGINALES AIENT ETE
REMPLACEES ET QUE LE FOYER SOIT APPROUVE DE NOUVEAU PAR
AYANT JURIDICTION.
LES AUTORITES
W385-0199
The sheet-metal parts of the fi replace, in which the gas fi re-
place insert is to be installed, must not be cut.
If the wood-burning factory-built fi replace has no gas access
hole(s) provided, an access hole of 1½ inch or less may be
drilled through the lower sides or bottom of the fi replace in
a proper workman like manner. This access hole must be
plugged with non-combustible insulation after the gas supply
line has been installed.
Ensure that existing chimney cleanouts fi t properly .
The refractory , glass doors, screen rails, screen mesh and log
grates may be removed from the fi replace before installing
the gas fi replace insert.
Smoke shelves, shields and baffl es may be removed if at-
tached by mechanical fasteners.
The ventilation openings in the fi replace may be obstructed
by the backer plates, aluminium trim etc. but these parts are
not to be applied so as to have an airtight seal.
5
3 & 4 SIDED BACKER PLATES - SIDE VIEWS
TOP VIEW
4 SIDED BACKER PLATE - FRONT VIEW
W415-0223 / E / 03.05.09
Page 6
6
2" OVERLAP
EXHAUST
SEALANT
HI-TEMP
INTAKE
VENT
CONNECTION
ASSEMBLY
R
INSERT VENT CONNECTION
Move the insert close to its fi nal position inside the wood-
burning fi replace. This unit is equipped with 6 levelling screws
located as follows: two are on either side of the circulation
blower on the rear panel; four are located front and back on
either side beneath the log support. Level using four of the levelling screws. See Figure 1a. Levelling the unit will eliminate
rocking or excessive noise when the fan is in operation. Once
the unit is level, move it partially into place within the fi replace
to allow for all connections to be made. It is not practical to
level the insert once the it has been installed. Determine the
required depth prior to installing the unit and adjust the four
levelling screws accordingly.
CHIMNEY CONNECTION
Chimney installation must conform to both national and local
code requirements. The chimney must be lined with one 2"
or 3" diameter liner for intake and one 3" diameter liner for
exhaust. The minimum and maximum vent lengths are 10 and
35 feet respectively . Recommended Napoleon kits come in 3
lengths: While the liners must be continuous from the fi replace
to the terminal, to achieve the needed length, they may be
coupled, using an aluminium coupler, provided installation is
sealed & secured.
1-2" & 1-3" DOUBLE PLY ALUMINUM LINER-INLET AND EXHAUST
&
2-3" TO 2" REDUCER:
GDI-320KT VENT KIT 20FT
GDI-325KT VENT KIT 25 FT
GDI-335KT VENT KIT 35 FT
We recommend that exhaust vents that pass through unheated spaces, such as a garage or attic, be wrapped in a
protective sleeve to minimize condensation and reverse fl ow
symptoms. See Trouble Shooting for details.
This unit is approved for use with a 2" liner for air intake and
a 3" liner for exhaust. For best performance, however, it is
recommended to use two 3" liners.
If a 2" liner is used for the intake, it is necessary to adjust the
primary air shutter. See "Air Shutter Settings" on page 11.
1.OUTSIDE: Slip one
end of a liner a minimum of
2" over one of the collars of
TERMINAL
GDI-223
the terminal. Secure using
3 screws. Then seal the
joint and screw heads with
high temperature sealant. Repeat with the other
liner.
EXHAUST
COLLAR LABELED
INTAKE
NOTE: We recommend that the other end of the exhaust liner
be marked to eliminate the exhaust liner being connected to
the intake collar at the unit.
FIGURE 2
FLASHING
PLATE
2"
OVERLAP
SEALANT
HI-TEMP
2. Gently stretch the liners to the required lengths and insert into the chimney. Place the terminal onto the top of the
chimney cap and fi t the fl ashing plate to suit. Make weather
tight by sealing with caulking (not supplied) and fasten to the
chimney with screws and plugs (not supplied)
3. INSIDE: Attach and secure the fl ex liners to the vent
connection assembly using the same procedure as before,
ensuring that the marked exhaust liner is attached to the
exhaust collar.
FIGURE 3
FIGURE 4
4. Detach the two screws from the back of the fi rebox and
remove the panel, as illustrated.
STUDS
VENT
CONNECTOR
EXTENSION
RESTRICTO
PLATE
FIGURE5a-b
5. Reaching in through the insert, manoeuvre the vent connection assembly through the openings in the fi rebox top,
taking care not to damage the gasket. In case of a low ceiling
fi replace, the extension should be removed and reinstalled
after the vent connection is secured to the fi rebox. Attach the
restrictor plate to the centre stud and secure the assembly
using the three studs and ¼-20 hex nuts.
W415-0223 / E / 03.05.09
Page 7
7
WALL SWITCH / THERMOSTATGAS INSTALLATION
For ease of accessibility , an optional remote wall switch
or millivolt thermostat may be installed in a convenient
location. Route 2-strand solid core millivolt wire from
the gas fi replace insert to the wall switch / millivolt
thermostat. The recommended maximum lead length
depends on the wire size:
WIRE SIZE MAX. LENGTH
14gauge 100 feet
16gauge 60 feet
18gauge 40 feet
Do not connect either the wall switch, thermostat
or gas valve to electricity (110 VOLTS).
Install suitable supply piping connection to the
nector supplied (as per local gas codes).
FIGURE 6
The insert may now be
pushed into its fi nal position
inside the wood-burning
fi replace. Secure the insert
to the fi replace using per-
forated strapping attached
to the two securing holes
on either side of the unit as
shown. We recommend that
the trim be installed before
the unit is placed into its fi nal
position.
FINISHING
SECURING
HOLES
FIGURE 7
3
/8" fl ex con-
In order to close off the fi replace opening or if the opening is
larger than the 3- or 4-sided aluminium extrusion trim kits, it is
recommended to reduce the opening using a noncombustible
material such as ceramic tile, marble, etc or the GIZBP6-3 or
GIZBP6-4 backer plate kits. The outside edge of the backer
plate is fi nished off with gold trim included in each kit. A
deluxe fl ashing kit complete with marquis trim may also be
used to complete the installation. These fl ashing and trim
combinations are available in 6 and 9 inch widths as well as
many fi nishes to accent any room decor. Mounting brackets, GIZBRKT, are required to install the deluxe fl ashing. Detailed
installation instructions are included with each kit.
If this unit is being installed into an existing wood burning,
zero clearance fi replace, then be aware of this precaution:
Any circulation air opening may be covered (with noncombustible material) but not sealed!
The insert can be equipped
ALUMINIUM EXTRUSION TRIM KIT
INSTALLATION
with either a 3- or 4-sided
trim kit to fi nish off the fi re-
place opening. Slide the trim
assembly over the keyholes
(2 per side) and drop into
place. If installing the optional
3- or 4-sided backer plate
(GIZBP6-3 or GIZBP6-4), it
must be hung prior to the trim
kit installation using the same
keyholes.
FIGURE 9
FIRE VIEWING DOOR
VALVE
CONTROL
DOOR
FIGURE 8
FIGURE 10
To adjust the trim: If the mitre is out of alignment, open each
side and loosen the two screws at either side trim hinge. Slide
the trim up or down to adjust and re-tighten screws. There is
also a very slight in/out adjustment that can be made.
Note: Since the side panels open and close, to access the
controls, a gap is necessary at the mitre joint.
The top trim piece has an adjustable securing bracket which
enables the trim to be secured to the fi rebox shell.
SLIDE TO
ADJUST
LOOSEN
SCREWS
FIGURE 11
W415-0223 / E / 03.05.09
Page 8
8
0
347
8
9
11
13
1256
7
10
12
H
E
I
G
H
T
M
A
N
T
L
E
MANTLE WIDTH
LOG PLACEMENTDOOR INSTALLATION
Positioning the logs improperly will cause fl ame impingement
and carboning.
PHAZER
Fireplaces, glow when exposed to direct fl ame and provide
a unique and realistic glowing effect that is different in every
installation. Take the time to carefully position the glowing
embers for a maximum glowing effect. Use only certifi ed
PHAZERTM logs available from your Napoleon / Wolf Steel
Ltd. dealer.
1. Place the rear log (#1) onto the two log supports and against
the air intake pipe.
FIGURE 12
TM
logs and glowing embers, exclusive to Napoleon
#1
Place the door into the two lower door brackets, and secure
at the top of the unit with two #10-24 machine screws.
FIGURE 16
LOWER DOOR BRACKET
2. Position logs #2 and #3 against the grate posts and line up
the studs located on the burner with the holes on the bottom
of the logs. Keep slightly back of the front row of ports.
FIGURE 13
#2
#3
3. Fit the centre log (#4) into place behind log #3 and into the
pocket provided on the back log.
FIGURE 14
#4
FIGURE 15
GLOWING EMBERS
MANTLE CLEARANCE
This can vary according to the mantle depth. Use the graph
to help evaluate the clearance needed.
FIGURE 17
6” MANTEL
6”
5”
5”
4”
3”
4”
3”
LOGO PLACEMENT
Remove the backing of the logo supplied and place on the
glass viewing door, as indicated.
4. Tear the glowing embers into pieces and place along the
front row of ports covering all of the burner area in front of the
logs. Care should be taken to shred the embers into thin, small
irregular pieces as only the exposed edges of the fi bre hairs
will glow. The ember material will only glow when exposed to
direct fl ame; however, care should be taken to not block the
burner ports. Blocked burner ports can cause an incorrect
fl ame pattern, carbon deposits and delayed ignition.
Log colours may vary. During the initial use of the fi replace,
the colours will become more uniform as colour pigments burn
in during the heat activated curing process.
W415-0223 / E / 03.05.09
FIGURE 18
½”
LOGO
½”
Page 9
OPERATION / MAINTENANCE
OPERATING INSTRUCTIONS
The on-off switch is located behind the left side control
door.
Purge all gas lines with the glass door open. Assure that a
continuous gas fl ow is at the burner before closing the door.
Allow several minutes (5-15) for the fl ame to stabilize after
ignition.
Do not operate the main burner of the insert
with the door removed.
9
When lit for the fi rst time, the fi replace will emit a slight odour
for a few hours. This is a normal temporary condition caused
by the "burn-in" of paints and lubricants used in the manufacturing process and will not occur again. Simply open a window
to suffi ciently ventilate the room. After extended periods of
non-operation such as following a vacation or a warm weather
season, the fi replace may emit a slight odour for a few hours.
This is caused by dust particles in the heat exchanger burning
off. Open a window to suffi ciently ventilate the room.
PURGE THE GAS LINE WITH THE GLASS DOOR OPEN.
FOR YOUR SAFETY READ BEFORE LIGHTING:
A. This fi replace is equipped with a pilot which must be lit by
hand. While following these instructions exactly.
B. Before operating smell all around the fi replace area for gas
and next to the fl oor because some gas is heavier than air
and will settle on the fl oor.
C. Use only your hand to turn the gas control knob. Never use
tools. If the knob will not turn by hand, do not try to repair
it. Call a qualifi ed service technician. Force or attempted
repair may result in a fi re or explosion.
D. Do not use this fi replace if any part has been under water .
Immediately call a qualifi ed service technician to inspect
the fi replace and replace any part of the control system
and any gas control which has been under water.
LIGHTING INSTRUCTIONS
When lighting and re-lighting, the gas knob cannot be turned
from pilot to off unless the knob is depressed slightly.
1. Stop! Read the above safety information on this label.
2. Turn off all electric power to the fi replace.
3. Turn the gas knob clockwise to off.
4. Wait fi ve (5) minutes to clear out any gas. If you smell gas
including near the fl oor . Stop! Follow "B" in the above safety in-
formation on this label. If you don't smell gas go the next step.
5. Iffi replace is equipped with fl ame adjustment valve turn
clockwise to off.
6. Find pilot located in front of back log.
TO TURN OFF GAS
1. Turn off all electrical power to the unit if service is to be
performed.
WHAT TO DO IF YOU SMELL GAS:
• Turn off all gas to the fi replace.
• Open windows.
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in
your building.
• Immediately call your gas supplier from a neighbour's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fi re depart-
ment.
FIGURE 19
7. Turn gas knob counter-clockwise
8. Depress slightly and hold gas knob while lighting the
pilot with the push button ignitor. Keep knob depressed for
one minute, then release. If pilot does not continue to burn,
repeat steps 3 through 7.
9. With pilot lit, depress and turn gas knob counter-clockwise
to on.
10. If equipped with fl ame adjustment valve, push and turn
knob to high.
11. If equipped with remote on-off switch/thermostat, main
burner may not come on when you turn valve to on. Remote
switch must be in the on position to ignite burner.
12. Turn on all electric power to the fi replace.
2. Push in gas control knob slightly and turn clockwise
to off. Do not force.
FLAME ADJUSTMENT
KNOB
ON/OFF KNOB
FIGURE 20
to pilot.
MAINTENANCE
TURN OFF THE GAS AND UNPLUG ELECTRICAL
POWER BEFORE SERVICING THE FIREPLACE INSERT!
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing. This insert
and its venting system should be inspected before use and
at least annually by a qualifi ed service person. The fi replace
area must be kept clear and free of combustible materials,
gasoline or other fl ammable vapours and liquids. The fl ow of
combustion and ventilation air must not be obstructed.
1. In order to properly clean the burner and pilot assembly,
remove the logs exposing both assemblies.
2. Keep the control compartment, logs, burner, air shutter
opening and the area surrounding the logs clean by vacuuming or brushing, at least once a year.
3. Check to see that all burner ports are burning. Clean out
any of the ports which may not be burning or are not burning properly.
4. Check to see that the pilot fl ame is large enough to engulf
the thermocouple on one leg and reaches toward the burner
on the other leg.
5. Replace the cleaned logs.
6. Check to see that the main burner ignites completely on
all openings when the gas knob for the burner is turned on.
A 5-10 second total light-up period is satisfactory. If ignition
takes longer, consult your Napoleon dealer/distributor.
7. Check that the door gasketing is not broken or missing.
Replace if necessary.
W415-0223 / E / 03.05.09
Page 10
10
OPTIONAL BLOWER INSTALLATION
THERMODISC
BRACKET
ASSEMBLY
BLOWER
WIRES
FIGURE 21
1. Turn off the electrical power and the gas supply to the
fi replace insert.
2. Remove the fi re viewing door. Remove the logs.
FIGURE 22
3. Detach the two screws from the back of the fi rebox and
remove the panel, as illustrated.
BLOWER ACCESS DOOR
FIGURE 23
4. Remove the blower access door held on with the remaining 8 screws. Replace the blower access door gasket when
changing the blower.
FIGURE 24
4. Disconnect the two blower wires. Remove the blower
bracket secured with one wing nut and lock washer.
For thermodisc replacement: Remove the "Z" shaped mounting bracket secured to the fi rebox wall to the left of the blower.
Remove the thermodisc from the bracket and replace.
B
C
A
FIGURE 25
5. Replace the blower using the existing bracket. Slide the
vibration reducing pad (A) into the clip (C) and up against the
threaded stud (B) at the other end. The blower must be able
to be positioned entirely onto the pad.
Slide the blower into the clip (C). Secure to the threaded stud
using the existing lock washer and wing nut. Ensure that the
blower does not touch the fi replace base or the fi rebox.
6. Reconnect the two wires. Holding the replacement gasket
in place, reattach the blower access door and panel. Replace
the logs. Re-install the fi re viewing door.
7. Turn the gas supply and electricity back on.
Because the blower is thermally activated, when turned
on, it will automatically start approximately 5-15 minutes after lighting the fi replace insert and will run for
approximately 30-45 minutes after the fi replace insert
has been turned off. Use of the fan increases the output
of heat.
Drywall dust will penetrate into the blower bearings
causing irreparable damage and must be prevented
from coming into contact with the blower or its compartment. Any damage resulting from this condition is not
covered by the warranty policy.
FIGURE 26
W415-0223 / E / 03.05.09
Page 11
FLAME MUST
ENVELOPE
UPPER 3/8" TO 1/2" OF
THERMOCOUPLE &
THERMOPILE
PILOT
BURNER
THERMOCOUPLE
THERMOPILE
ADJUSTMENTS
11
PILOT BURNER ADJUSTMENT
Remove the pilot screw cap. Adjust the pilot screw to provide
properly sized fl ame. Turn in a clockwise direction to reduce
the gas fl ow. Replace the pilot screw cap.
FIGURE 27
PILOT
SCREW
VENTURI ADJUSTMENT
This unit is approved for use with a 2" liner for air intake and
a 3" liner for exhaust. For best performance, however, it is
recommended to use two 3" liners.
Air shutter settings will differ depending on the liner system
used. Use the charts below to determine the correct air shutter setting:
NG 1/16"
LP 3/16"
AIR SHUTTER SETTING
NG 1/8"
LP 5/16"
AIR SHUTTER SETTING
Closing the air shutter will cause a more yellow fl ame, but can
lead to carboning. Opening the air shutter will cause a more
blue fl ame, but can cause fl ame lifting from the burner ports.
The fl ame may not appear yellow immediately; allow 15 to 30
minutes for the fi nal fl ame colour to be established.
HELPFUL HINT:
3"/ 3" LINER SYSTEM
2"/ 3" LINER SYSTEM
FIGURE 28
VENT RESTRICTION
Some vent confi gurations may display a very active fl ame.
If this appearance is not desirable, the vent exit may be restricted using the restrictor plate shown in FIGURE 6b. Bend
the fl ap up as shown to reduce the velocity of the exhaust
gases, slowing down the fl ame pattern and creating a more
traditional appearance.
FIGURE 29
Air shutter adjustment
must only be done by a
qualifi ed gas installer!
FIGURE 30
A mirror will let you see the opening
of the air shutter without removing the
burner. Scribe a line along the venturi
tube and air shutter cap. Open or close
according to the original opening by using the scribed line as your datum.
W415-0223 / E / 03.05.09
Page 12
12
REPLACEMENTS
Contact your dealer for questions concerning prices and availability of replacement parts. Normally all parts can be ordered
through your Napoleon dealer or distributor.
When ordering replacement parts always give the following
information:
System is not correctly purged.
Out of propane gas
Pilot fl ame is not large enough
Pilot fl ame is not engulfi ng the
thermocouple.
Thermocouple shorting.
Faultly thermocouple.
Faulty valve.
- check if pilot can be lit by a match
- check that the wire is connected to the push button ignitor.
- check if the push button ignitor needs tightening.
- replace the push button ignitor.
- spark gap should be 0.150" to 0.175" (5/32" to 1 1/64" approx.)
from the electrode tip and the pilot burner.
- check that the manual valve is turned on.
- check the pilot orifi ce for blockage.
- replace the valve.
- call the gas distributor.
- fi ll the tank.
- purge the gas line with the glass door open.
- fi ll the tank.
- turn up the pilot fl ame.
- turn up pilot fl ame.
- replace pilot assembly.
- loosen and tighten thermocouple.
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- replace.
- replace.
Pilot burning; no gas to
main burner; gas knob
is on 'HI'; wall switch /
thermostat is on.
Pilot goes out while
standing; Main burner
is in 'OFF' position.
Main burner goes out;
pilot stays on.
Faulty valve.
Remote wall switch wire is too
long, too much resistance in the
system
Main burner orifi ce is plugged.
Faulty thermopile.
Faulty themostat or switch.
Gas piping is undersized.
Pilot fl ame is not large enough or
not engulfi ng the thermopile.
Thermopile shorting
Faulty thermostat or switch
- remove stoppage in orifi ce.
- replace.
- connect a jumper wire across the wall switch terminals; if main
burner lights, replace thermostat.
- disconnect the switch wires & connect a jumper wire across terminals 1 & 3; if the main burner lights, check the wires for defects
and / or replace wires.
- replace.
- turn on all gas appliances and see if pilot fl ame fl utters, di-
minishes or extinguishes, especially when main burner ignites.
Monitor supply pressure.
- check if supply piping size is to code. Correct all undersized
piping.
- turn up pilot fl ame.
- replace pilot assembly.
- clean thermopile and thermopile connection to valve.
- shorten wire to correct length or wire gauge.
- replace
W415-0223 / E / 03.05.09
Page 15
SYMPTOMPROBLEMTEST SOLUTION
15
Main burner goes out;
pilot goes out.
Exhaust fumes smelled
in room, headaches.
Carbon is being deposited on glass, logs
or combustion chamber surfaces.
REFER TO "MAIN BURNER GOES OUT; PILOT STAYS ON"
Vent re-circulating
Thermocouple shorting or
faulty.
Vent is reversing
Fireplace is spilling.
Air shutter has become
blocked
Flame is impinging on the logs
or combustion chamber.
- check joint seals and installation.
- loosen and tighten thermocouple
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- check all venting and insert seals.
- check that door is properly sealed. If the insert is allowed to burn
with the door off when purging the unit, exhaust products may
escape through the air intake pipe and reverse the venting action.
Let the unit cool down to correct the reversed venting action.
- check all seals.
- ensure air shutter opening is free of lint or other obstructions.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifi ce
size as specifi ed by the rating plate values.
- check that the door gasketing is not broken or missing and that
the seal is tight.
- check that both vent liners are free of holes and well sealed at
all joints.
Main burner fl ame is a
blue, lazy , transparent
fl ame.
White / grey film
forms.
Blockage in vent.- remove blockage. In really cold conditions, ice buildup may
occur on the terminal and should be removed as required.
Incorrect installation.
Sulphur from fuel is being deposited on glass, logs or combustion chamber surfaces.
- vent liners are reversed. Refer to Figure 2.
- check all venting and insert seals.
- clean the glass with a recommended gas fi replace glass
cleaner. DO NOT CLEAN GLASS WHEN HOT.
If deposits are not cleaned off regularly , the glass may become
permanently marked.
W415-0223 / E / 03.05.09
Page 16
16
Service PerformedSpecial ConcernsDealer Name
Name
Appliance Service History
This heater must be serviced annually depending on usage.
DateService Technician
W415-0223 / E / 03.05.09
43.1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.