Napoleon Fireplaces B36DFN, B36DFP User Manual

1
W415-0484 / A / 07.26.06
W415-0484 / A / 07.23.06
WARNINGS & SAFETY PRECAUTIONS
WHAT TO DO IF YOU SMELL GAS
PG 2-5 INTRODUCTION
Warnings and Safety Precautions Warranty General Instructions General Information Care of Glass & Plated Parts
6 - 13 VENTING
Venting Lengths Air Terminal Locations Typical Vent Installations Special Vent Installations Venting Specifications
14
-
18INSTALLATION
Wall and Ceiling Protection Using Flexible Vent Components Fireplace Vent Connection Restricting Vertical Vents Gas Installation Mobile Home Installation Framing Nailing Tab Installation Mantle Installation
TABLE of CONTENTS
19-20 FINISHING
Door Removal & Installation Louvre Installation Log Placement / Glowing Embers Charcoal Embers Charcoal Lumps Logo Placement
21
OPTIONAL BLOWER INST ALLA TION
2 2 OPTIONAL FAN INST ALLA TION /
GD36 THERMOSTA TIC SENSOR CONTROL
23 OPERATION / MAINTENANCE
Operating Instructions Maintenance
24 ADJUSTMENTS
Pilot Burner Adjustment Venturi Adjustment
25-26 REPLACEMENTS
Ordering Replacement Parts Replacement Parts Vent Kits Terminal Kits Accessories
27-28 TROUBLE SHOOTING GUIDE
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
WARNING
• Do not burn wood or other materials in this fireplace.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Keep young children and animals away when the fireplace is hot.
• Clothing or other flammable material should not be placed on or near the fireplace.
• Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the
fireplace and venting system are kept clean. The fireplace and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The fireplace area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
• Under no circumstances should this fireplace be modified.
• This fireplace must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to
inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
• Do not operate the fireplace with the glass door removed, cracked or broken. Replacement of the glass should
be done by a licensed or qualified service person. Use only with a glass door certified with the fireplace.
• Do not strike or slam shut the fireplace glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple
supplied by Wolf Steel Ltd.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
4
NAPOLEON NAPOLEON
NAPOLEON
NAPOLEON NAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON trained craftsmen who take great pride in their work. The burner and valve assembly are leaktrained craftsmen who take great pride in their work. The burner and valve assembly are leak
trained craftsmen who take great pride in their work. The burner and valve assembly are leak
trained craftsmen who take great pride in their work. The burner and valve assembly are leaktrained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test station. Once assembled the complete fireplace is thoroughlyand test-fired at a quality test station. Once assembled the complete fireplace is thoroughly
and test-fired at a quality test station. Once assembled the complete fireplace is thoroughly
and test-fired at a quality test station. Once assembled the complete fireplace is thoroughlyand test-fired at a quality test station. Once assembled the complete fireplace is thoroughly inspected by a qualified technician before packaging to ensure that you, the customerinspected by a qualified technician before packaging to ensure that you, the customer
inspected by a qualified technician before packaging to ensure that you, the customer
inspected by a qualified technician before packaging to ensure that you, the customerinspected by a qualified technician before packaging to ensure that you, the customer quality product that you expect from quality product that you expect from
quality product that you expect from
quality product that you expect from quality product that you expect from
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTYNAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTYNAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
The following materials and workmanship in your new The following materials and workmanship in your new
The following materials and workmanship in your new
The following materials and workmanship in your new The following materials and workmanship in your new
long as you own the fireplace. This covers: combustion chamberlong as you own the fireplace. This covers: combustion chamber
long as you own the fireplace. This covers: combustion chamber
long as you own the fireplace. This covers: combustion chamberlong as you own the fireplace. This covers: combustion chamber embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled componentsembers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled components
embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled components
embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled componentsembers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled components and aluminum extrusion trims.and aluminum extrusion trims.
and aluminum extrusion trims.
and aluminum extrusion trims.and aluminum extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch, switches,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch, switches,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch, switches,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch, switches,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch, switches,
wiring, remote controls, ignitorwiring, remote controls, ignitor
wiring, remote controls, ignitor
wiring, remote controls, ignitorwiring, remote controls, ignitor free of charge during the first year of the limited warfree of charge during the first year of the limited war
free of charge during the first year of the limited war
free of charge during the first year of the limited warfree of charge during the first year of the limited war
LL
abour related to warabour related to war
L
abour related to war
L
L
abour related to warabour related to war
approval of an authorized company official. Labour costs to the account of approval of an authorized company official. Labour costs to the account of
approval of an authorized company official. Labour costs to the account of
approval of an authorized company official. Labour costs to the account of approval of an authorized company official. Labour costs to the account of schedule and any repair work must be done through an authorized schedule and any repair work must be done through an authorized
schedule and any repair work must be done through an authorized
schedule and any repair work must be done through an authorized schedule and any repair work must be done through an authorized
gas fireplaces are manufactured under the strict Standard of the world recog-gas fireplaces are manufactured under the strict Standard of the world recog-
gas fireplaces are manufactured under the strict Standard of the world recog-
gas fireplaces are manufactured under the strict Standard of the world recog-gas fireplaces are manufactured under the strict Standard of the world recog-
nized nized
nized
nized nized
products are designed with superior components and materials, assembled by products are designed with superior components and materials, assembled by
products are designed with superior components and materials, assembled by
products are designed with superior components and materials, assembled by products are designed with superior components and materials, assembled by
ranty repair is covered free of charge during the first yearranty repair is covered free of charge during the first year
ranty repair is covered free of charge during the first year
ranty repair is covered free of charge during the first yearranty repair is covered free of charge during the first year
ISO 9001 : 2000 Quality Assurance Certificate.ISO 9001 : 2000 Quality Assurance Certificate.
ISO 9001 : 2000 Quality Assurance Certificate.
ISO 9001 : 2000 Quality Assurance Certificate.ISO 9001 : 2000 Quality Assurance Certificate.
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
, gask, gask
eting, and pilot assembly are covered and eting, and pilot assembly are covered and
, gask
eting, and pilot assembly are covered and
, gask, gask
eting, and pilot assembly are covered and eting, and pilot assembly are covered and
rantyranty
..
ranty
.
rantyranty
..
..
.
..
gas fireplace are warranted against defects for as gas fireplace are warranted against defects for as
gas fireplace are warranted against defects for as
gas fireplace are warranted against defects for as gas fireplace are warranted against defects for as
, heat e, heat e
xchangerxchanger
, heat e
xchanger
, heat e, heat e
xchangerxchanger
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
, stainless steel burner, stainless steel burner
, stainless steel burner
, stainless steel burner, stainless steel burner
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
. R. R
epair work, howeverepair work, however
. R
epair work, however
. R. R
epair work, howeverepair work, however
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
dealer dealer
dealer
dealer dealer
are based on a predetermined rate are based on a predetermined rate
are based on a predetermined rate
are based on a predetermined rate are based on a predetermined rate
..
.
..
, receives the, receives the
, receives the
, receives the, receives the
, phazer™ logs and, phazer™ logs and
, phazer™ logs and
, phazer™ logs and, phazer™ logs and
will provide replacement partswill provide replacement parts
will provide replacement parts
will provide replacement partswill provide replacement parts
, requires the prior, requires the prior
, requires the prior
, requires the prior, requires the prior
CONDITIONS AND LIMITA TIONS
NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with the product and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.
NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated in accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President's Limited Lifetime Warranty, NAPOLEON may, at its discretion, fully discharge all obligations with respect to this warranty by refunding to the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event extend to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product, its components or accessories are excluded.
NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
ALL SPECIFICA TIONS AND DESIGNS ARE SUBJECT T O CHANGE WITHOUT PRIOR NOTICE DUE T O ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL L TD. PA TENTS U.S. 5.303.693.801 - CAN. 2.073.41 1, 2.082.915. © WOLF STEEL L TD. W415-0484 / A / 07.26.06
5
GENERAL INSTRUCTIONS
THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERV­ICED BY A QUALIFIED INSTALLER to conform with local
codes. In absence of local codes, install the B36DF to the current National Fuel Gas Code, ANSI Z223.1, or the current CAN/CGA B149, Installation Codes.
Installation practices vary from region to region and it is important to know the specifics that apply to your area,
for example: in Massachusetts State:
• The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
• A carbon monoxide detector is required in all rooms containing gas fired appliances
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
• WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of
Massachusetts.
Mobile home installation must conform with local codes or in the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA ZA240 MH Series in Canada or the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the Fire Safety Criteria for Manufac­tured Home Installations, Sites and Communities St andard ANSI/ NFPA 501A in the United S tates.
The fireplace and its individual shutoff valve must be discon­nected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the fireplace is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the fireplace shall be installed on a metal or wood panel extend­ing the full width and depth.
If the optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA 70 NA TIONAL ELECTRICAL CODE in the United States.
Minimum inlet gas supply pressure is 4.5 inches water col­umn for natural gas and 11 inches water column for propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for propane. Mani­fold pressure under flow conditions is 3.5 inches water col­umn for natural gas and 10 inches water column for propane.
This fireplace is approved for bathroom, bedroom and bed­sitting room installations and is suitable for mobile home installation.
No external electricity (1 10 volts or 24 volts) is required for the gas system operation.
Expansion / contraction noises during heating up and cool­ing down cycles are normal and are to be expected.
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean plated parts. Buff lightly with a clean dry cloth. The B36DF is factory equipped with tempered glass. The glass thickness is 3/16". Use only re­placement glass available from your Napoleon dealer. DO NOT SUBSTITUTE MA TERIALS. Clean the glass after the first 10 hours of operation with a recommended gas fireplace glass cleaner. Thereafter clean as required. DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent
discolouration and / or blemishes may result.
Use only accessories designed for and listed with
your specific fireplace.
Provide adequate ventilation air. Provide adequate ac­cessibility clearance for servicing and operating the fireplace. Never obstruct the front opening of the fire­place.
For safe and proper operation of the fireplace follow the venting instruction exactly.
In order to avoid the possibility of exposed insulation or vapour barrier coming in contact with the fireplace body, it is recommended that the walls of the fireplace enclo­sure be 'finished', (i.e. drywall/sheetrock) as would any other outside wall of the home. This will ensure that clearance to combustibles is maintained within the cav­ity.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
Maximum input is 23,000 BTU/hr for natural gas and propane. When the fireplace is installed at elevations above 4,500ft, and in the absence of specific recommendations from the local au­thority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.
Maximum output for natural gas and propane is 15,200 BTU/ hr at an efficiency of 66% with the fan on. The maximum A.F.U.E. (annual fuel utilization efficiency) rating is 62% for natural gas and propane.
W415-0484 / A / 07.23.06
6
FIGURE 1
VENTING
For safe and proper operation of the fireplace follow the venting instruction exactly.
Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning.
Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed.
Vent lengths that p ass through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation wrapped in a protective sleeve to minimize condensation.
VENTING LENGTHS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or American Metal Amerivent venting components.
For Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent, follow the installation procedure provided with the venting components.
All outer pipe joints of these venting systems must be sealed using Red RTV Hight Temperature Sealant.
Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent venting systems must not be combined.
A starter adaptor must be used and may be purchased from the corresponding supplier:
PART 5"/8" SUPPLIER
Duravent W175-0170 Wolf Steel Amerivent 5DSC-N American Metal Direct T emp 5DT-AAN Selkirk
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant maybe used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the fireplace flue collar which must be sealed using the black high tempera­ture sealant Mill Pac. When using Wolf Steel venting components, use only ap­proved Wolf Steel rigid / flexible components with the fol­lowing termination kits: WALL TERMINAL KIT GD422, or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT GD410, 8/12 TO 12/12 ROOF TERMINAL KIT GD411, FLAT ROOF TERMI- NAL KIT GD412 or PERISCOPE KIT GD401 (for wall pen- etration below grade). With flexible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD420 or the 10 foot vent kit GD430.
W415-0484 / A / 07.26.06
These vent kits allow for either horizontal or vertical venting of the fireplace. FIGURES 3 & 5. The maximum allowable horizontal run is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of 5" vent connections is two horizontally or three vertically (exclud­ing the fireplace and the air terminal connections) when using aluminum flexible venting.
For optimum flame appearance and fireplace performance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.
Purge all gas lines with the glass door of the fireplace removed. Assure that a continuous gas flow is at the burner before re-installing the door.
Under extreme vent configurations, allow several minutes (5-
15) for the flame to stabilize after ignition. Eight (8") inches is the minimum bend radius allowed for
the 8" diameter flexible liner. For optimum performance it is recommended that all hori-
zontal runs have a 1 inch rise per foot when using Napoleon flexible vent components.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regu­lations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" air gap all around between the inner liner and outer liner is required for safe operation. Use a firestop when penetrating interior walls, floor or ceiling.
Objects placed in front of the fireplace must be kept a minimum of 48" away from the front face of the unit.
Minimum clearance to combustible con­struction from fireplace and vent sur­faces:
sides, back and bottom 0" (to stand off) top (framing) 8" finishing 0" recessed depth 21" sides and bottom of the vent pipe 1" top of vent 2"
Horizontal runs may have a 0 inch rise per foot in all cases using SIMPSON DURA-VENT or NAPOLEON RIGID OR FLEXIBLE venting components when venting as illustrated in Figures 3, and 4.
AIR TERMINAL LOCATIONS
FIGURE 2
INSTALLATIONS
CANADIAN U.S . A.
A
12 INCHES
12 INCHES
Clearance above grade, veranda porch, deck or balcony.
7
B
C
12 INCHES
12 INCHES*
9 INCHES
12 INCHES*
Clearance to windows or doors that open.
Clearance to permanently closed windows.
Vertical clearance to ventilated soffit located above the terminal within
D
18 INCHES**
12 INCHES**
E
F
0 INCHES
0 INCHES***
G
2 INCHES***
H
I
J
K
L
M
N
O
**
* Recommended to prevent condensation on windows and thermal breakage
** ****
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.
**** ******
*** The periscope GD-201 requires a minimum 18 inches clearance from an inside corner.
****** ********
**** This is a recommended distance. For additional requirements check local codes.
******** ††
Three feet above if within 10 feet horizontally.
†† ‡‡
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family
‡‡
††††
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
†††† †*†*
†* Recommenced to prevent recirculation of exhaust products. For additional requirements check local codes.
†*†*
3 FEET
3 FEET
12 INCHES
6 FEET
7 FEET‡
12 INCHES††
16 INCHES
2 FEET†*
dwellings and serves both dwellings.
18 INCHES**
12 INCHES**
0 INCHES
0 INCHES***
2 INCHES***
3 FEET****
3 FEET****
9 INCHES
3 FEET†
7 FEET****
12 INCHES****
16 INCHES
2 FEET†*
a horizontal distance of 2 feet from the centerline of the terminal.
Clearance to unventilated soffit.
Clearance to an outside corner wall.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to an inside combustible corner wall or protruding com­bustible obstructions ( vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum vertical distance of 15ft.
Clearance to a service regulator vent outlet.
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
Clearance to a mechanical air supply inlet.
Clearance above a paved sidewalk or paved driveway located on public property unless fitted with a heat shield kit GD-301.
Clearance under a veranda, porch, deck or balcony.
Clearance above the roof.
Clearance from an adjacent wall including neighbouring buildings.
W415-0484 / A / 07.23.06
8
TYPICAL VENT INST ALLATIONS
NOTE: When terminating vertically, the restrictor
plate W500-0205 must be installed. Refer to Restricting V ertical Vents.
FIGURES 3 a-c
* When installing with no vertical rise,
ensure that the vent pipe does not slope
downward.
SPECIAL VENT INST ALLATIONS
PERISCOPE TERMINA TION
Use the GD401 periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum of 12 inches above grade. The maximum allow­able vent length depends on the fireplace, as illustrated.
FIGURE 4
W415-0484 / A / 07.26.06
VENTING APPLICATION FLOW CHART
9
HORIZONTAL
TERMINATION
Vertical rise is equal to or greater than the horizontal run
Horizontal run + verti­cal rise to maximum of 40 feet
Vertical rise is less than horizontal run
Horizontal run + verti­cal rise to maximum of 24.75 feet
4.2 times the vertical rise equal to or greater than the horizon­tal run
VERTICAL
TERMINATION
Vertical rise is equal to or greater than the horizontal run
Horizontal run + verti­cal rise to maximum of 40 feet
Vertical rise is less than horizontal run
Horizontal run + verti­cal rise to maximum of 40 feet
3 times the vertical rise equal to or greater than the horizontal run
W415-0484 / A / 07.23.06
Loading...
+ 21 hidden pages