
INSTALLATION AND
OPERATING INSTRUCTIONS
If the information in these instructions are
not followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
- Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier from
a neighbour’s phone. Follow the gas
supplier’s instructions.
If you cannot reach your gas supplier,
call the fire department.
- Installation and service must be
performed by a qualified installer, service
agency or the supplier.
SAFETY INFORMATION
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
!
WARNING
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
APPLY SERIAL NUMBER LABEL FROM CARTON
Serial No.
MODEL NO.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 4Y8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone (705)721-1212 • Fax (705)722-6031 • www.napoleonfireplaces.com • ask@napoleon.on.ca
1
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: ANSI Z21.88, CSA 2.33 FOR VENTED GAS FIREPLACE HEATERS.
GDS25N
NATURAL GAS
GDS25P
PROPANE
$10.00
W415-0547 / D / 11.14.08
W415-0547 / D / 11.14.08

2
TABLE OF CONTENTS
1.0 INTRODUCTION 3
1.1 WARRANTY 4
1.2 DIMENSIONS 5
1.3 GENERAL INSTRUCTIONS 5
1.4 GENERAL INFORMATION 6
1.5 CARE OF GLASS AND PLATED PARTS 6
2.0 VENTING 7
2.1 VENTING LENGTHS AND COMPONENTS 7
2.2 SPECIAL VENT INSTALLATIONS 9
2.2.1 PERISCOPE TERMINATION 9
2.2.2 CORNER TERMINATION 9
2.3 MINIMUM AIR TERMINAL LOCATION CLEARANCES 10
2.4 DEFINITIONS 11
2.5 ELBOW VENT LENGTHS 11
2.6 HORIZONTAL TERMINATION 11
2.7 VERTICAL TERMINATION 13
2.8 VERTICAL THROUGH EXISTING CHIMNEY 15
3.0 VENT INSTALLATION 16
3.1 WALL AND CEILING PROTECTION 16
3.1.1 HORIZONTAL INSTALLATION 16
3.1.2 VERTICAL INSTALLATION 17
3.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 18
3.2.2 EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INSTALLATION 18
3.2.3 VERTICAL AIR TERMINAL INSTALLATION 19
3.3 STOVE VENT CONNECTION 20
3.4 MOBILE HOME 20
3.5 GAS INSTALLATION 21
4.0 MINIMUM CLEARANCE TO COMBUSTIBLES 22
4.3 MINIMUM MANTEL OR SHELF CLEARANCES 23
5.0 FINISHING 24
5.1 CAST FRONT INSTALLATION AND REMOVAL 24
5.2 GLASS DOOR INSTALLATION AND REMOVAL 24
5.3 SWITCH FUNCTIONS 25
5.4 LOGO PLACEMENT 25
5.5 LOG PLACEMENT 26
6.0 OPTIONAL BLOWER INSTALLATION 27
7.0 NIGHT LIGHT REPLACEMENT 28
8.0 WIRING DIAGRAM 29
9.0 OPERATION 30
10.0 MAINTENANCE 31
11.0 ADJUSTMENT 31
11.1 VENTURI ADJUSTMENT 31
11.2 FLAME ADJUSTMENT 31
11.3 FLAME CHARACTERISTICS 32
11.4 PILOT INJECTOR AND ORIFICE REPLACEMENT 32
11.5 RESTRICTING VERTICAL VENTS 32
12.0 REPLACEMENT PARTS 33
13.0 TROUBLESHOOTING 37
14.0 SERVICE HISTORY 39
15.0 NOTES 40
W415-0547 / D / 11.14.08

• Do not operate heater before reading and understanding operating instructions. Failure to operate heater according to
operating instructions could cause fire or injury.
• Risk of fire or asphyxiation do not operate heater with fixed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The heater should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal
edges may be sharp.
• Do not burn wood or other materials in this heater.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to
avoid burns or clothing ignition. Supervise young children when they are in the same room as the heater.
• Clothing or other flammable material should not be placed on or near the heater.
• Due to high temperatures, the heater should be located out of traffic and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the heater is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot
surfaces. These screens and guards must be fastened to the floor.
• Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the heater and
venting system are kept clean. The heater and its venting system should be inspected before use and at least annually
by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding
material, etc. The heater area must be kept clear and free from combustible materials, gasoline and other flammable
vapors and liquids.
• Under no circumstances should this heater be modified.
• This heater must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the
heater and to replace any part of the control system and any gas control which has been under water.
• Do not operate the heater with the glass door removed, cracked or broken. Replacement of the glass should be done
by a licensed or qualified service person.
• Do not strike or slam shut the heater glass door.
• Pressure relief doors must be kept closed while the heater is operating to prevent exhaust fumes containing carbon
monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause
the surrounding combustible materials to overheat and catch fire.
• Only doors / optional fronts certified with the unit are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic
bags, these are not toys and should be kept away from children and infants.
!
WARNING
1.0 INTRODUCTION
3
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
TP - DV_NV_KEN WARNING_NO THERM
W415-0547 / D / 11.14.08

4
®
The following materials and workmanship in your new NAPOLEON® gas heater are warranted against
defects for as long as you own the heater. This covers: combustion chamber, heat exchanger, stainless
steel burner, phazer™ logs and embers, rocks, ceramic glass (thermal breakage only), gold plated parts
against tarnishing, porcelainized enameled components and aluminum extrusion trims.*
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch,
switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and NAPOLEON® will
provide replacement parts free of charge during the first year of the limited warranty.*
Labour related to warranty repair is covered free of charge during the first year. Repair work, however,
requires the prior approval of an authorized company official. Labour costs to the account of NAPOLEON®
are based on a predetermined rate schedule and any repair work must be done through an authorized
NAPOLEON® dealer.
* Construction of models vary. Warranty applies only to items available with your specific heater.
NAPOLEON® products are manufactured under the strict Standard of the world recognized ISO 9001 : 2000
Quality Assurance Certificate.
NAPOLEON® products are designed with superior components and materials assembled by trained crafts-
men who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test
station. The complete heater is again thoroughly inspected by a qualified technician before packaging to
ensure that you, the customer, receives the quality product that you expect from NAPOLEON®.
NAPOLEON® warrants its products against manufacturing defects to the original purchaser only. Registering your warranty is not necessary. Simply provide
your proof of purchase along with the model and serial number to make a warranty claim. NAPOLEON® reserves the right to have its representative inspect
any product or part thereof prior to honouring any warranty claim. Provided that the purchase was made through an authorized NAPOLEON® dealer your
heater is subject to the following conditions and limitations:
This factory warranty is non-transferable and may not be extended whatsoever by any of our representatives.
The gas heater must be installed by a licensed, authorized service technician or contractor. Installation must be done in accordance with the installation
instructions included with the product and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other
manufacturers will nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discoloring caused by excessive heat, abrasive and chemical cleaners nor
chipping on porcelain enamel parts, mechanical breakage of PHAZER™ logs and embers.
NAPOLEON® warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first
10 years NAPOLEON® will replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON® will provide replacement
burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the
product has been operated in accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President’s Lifetime Limited Warranty, NAPOLEON® may, at its discretion, fully discharge all obligations with respect
to this warranty by refunding to the original warranted purchaser the wholesale price of any warranted but defective part(s).
NAPOLEON® will not be responsible for installation, labour or any other expenses related to the reinstallation of a warranted part and such expenses are
not covered by this warranty.
Notwithstanding any provisions contained in the President's Lifetime Limited Warranty, NAPOLEON’S responsibility under this warranty is defined as above
and it shall not in any event extend to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of NAPOLEON® with respect to the NAPEOLON® gas heater and any other warranties expressed or
implied with respect to this product, its components or accessories are excluded.
NAPOLEON® neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product.
NAPOLEON® will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees,
hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not
be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to heater, combustion chamber, heat exchanger, brass trim or other components due to water, weather damage, long periods of dampness,
condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON®.
1.1 WARRANTY
TP - NAPOLEON - GAS WARRANTY
W415-0547 / D / 11.14.08

1.2 DIMENSIONS
7" DIA.
23 1/2"
12
3
/4"
23
5
/8"
25
5
/8"
17 1/2"
4" DIA.
THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local
codes. Installation practices vary from region to region and it is important to know the specifics that apply to your area, for
example in Massachusetts State:
• The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• A Carbon Monoxide detector is required in all rooms containing gas fired appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed
combustion product.
The installation must conform with local codes or, in absence of
local codes, the National Gas and Propane Installation Code
CSA B149.1 in Canada, or the National Fuel Gas Code,
ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile
home installation if installed in accordance with the current
standard CAN/CSA Z240MH Series, for gas equipped mobile
homes, in Canada or ANSI Z223.1 and NFPA 54 in the United
States.
The fireplace and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated from the
gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psig (3.5 kPa).
Provide adequate accessibility clearance for servicing and operating the fireplace.
Provide adequate ventilation.
Never obstruct the front opening of the fireplace.
Objects placed in front of the fireplace must be kept a minimum of 48” from the front face of the unit.
This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth
of Massachusetts.
!
WARNING
FIGURE 1.2a-c
1.3 GENERAL INSTRUCTIONS
5
The heater, when installed with a blower, must be electrically connected and grounded in accordance with
local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in
Canada or the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the United States.
TP - DV_NV_KEN GENERAL INSTRUCTIONS
W415-0547 / D / 11.14.08

6
DO NOT CLEAN GLASS WHEN HOT! DO NOT USE ABRASIVE
CLEANERS TO CLEAN GLASS OR PLATED PARTS.
Buff lightly with a clean dry soft cloth. Clean the glass after the first 10
hours of operation with a recommended fireplace glass cleaner.
Thereafter clean as required. If the glass is not kept clean permanent
discoloration and / or blemishes may result.
Refer to “REPLACEMENT PARTS” to find out what this product is
equipped with. Use only replacement glass available from your
Authorized dealer.
DO NOT SUBSTITUTE MATERIALS.
1.4 GENERAL INFORMATION
The blower power cord must be connected into a properly grounded receptacle. The grounding prong must not
be removed from the cord plug.
FOR YOUR SATISFACTION, THIS STOVE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 11 inches water column for
propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for
propane. When the valve is set to “HI”, the manifold pressure under ow conditions is 3.5 inches water column
for natural gas and 10 inches water column for propane. When the replace is installed at elevations above
4,500ft, and in the absence of specic recommendations from the local authority having jurisdiction, the certied high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convert-
ible for use with other gases, unless a certied kit is used.
Maximum input is 24,500 BTU/hr for natural gas. Maximum output for natural gas is 19,600 BTU/hr at an ef-
ciency of 80%. Maximum input is 23,000 BTU/hr for propane. Maximum output for propane gas is 18,400 BTU/
hr at an efciency of 80%.
This stove is approved for closet or recessed installations, as well as for bathroom, bedroom and bed-sitting
room installations and is suitable for mobile home installations. The natural gas model can be installed in a
mobile home that is permanently positioned on its site and fueled with natural gas.
1.5 CARE OF GLASS AND PLATED PARTS
TP - CARE OF GLASS AND PLATED PARTS
W415-0547 / D / 11.14.08

THIS HEATER USES A 4" EXHAUST / 7" AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the heater follow the venting instruction exactly. Deviation from the minimum
vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent configurations,
allow several minutes (5-15) for the flame to stabilize after ignition. Vent lengths that pass through unheated
spaces (attics, garages, crawl spaces) should be insulated with the insulation wrapped in a protective sleeve to
minimize condensation. Provide a means for visually checking the vent connection to the heater after the heater
is installed. Use a firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or
ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided
for the initial installation.
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for
either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American
Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
PART 4"/7" SUPPLIER WEBSITE
Duravent GDS924N Wolf Steel www.duravent.com
Amerivent 4DSCB-N1 American Metal www.americanmetalproducts.com
Direct Temp 4DT-AAN Selkirk www.selkirkcorp.com
SuperSeal 4DNA Metal-Fab www.mtlfab.com
* For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red
high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe
joints of all other approved vent systems except for the exhaust vent pipe connection to the heater flue collar which must be
sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / flexible components with the following
termination kits: wall terminal kit GD175 (7-1/2” of venting included), or wall terminal kit GD176 (24” of venting included), or
1/12 to 7/12 pitch roof terminal kit GD110, 8/12 to 12/12 roof terminal kit GD111, flat roof terminal kit GD112 or periscope kit
GD180 (for wall penetration below grade) in conjunction with the appropriate venting components.
For optimum flame appearance and heater performance, keep the vent length and number of elbows to a
minimum. It is recommended that all horizontal runs have a minimum 1/4“ rise per foot.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it
is unobstructed and undamaged.
Different venting manufacturer components must not be combined.
These vent kits allow for either horizontal or vertical venting of the heater. The maximum number of 4” flexible connections
is 3 horizontally or three vertically (excluding the heater and the air terminal connections). When terminating vertically,
the minimum vertical rise is 3 feet above the heater and the maximum vertical rise is 40 feet. Deviation from the minimum
vertical vent length can create difficulty in burner start-up and/or carboning. Use an adjustable pipe as the final length of
rigid piping to the heater for ease of installation.
!
WARNING
Risk of fire, maintain specified air space clearances to vent pipe and appliance.
2.0 VENTING
2.1 VENTING LENGTHS AND COMPONENTS
7
TP - 4/7 GAS VENTING_GAS STOVE
W415-0547 / D / 11.14.08

8
16”
FIGURE 2.1a
24” MINIMUM
REGARDLESS
OF HORIZONTAL
VENT LENGTH
25 5/8”
FIGURE 2.1c
FIGURE 2.1b
24” MAXIMUM
25 5/8”
The maximum horizontal run with a 57” vertical rise immediately above the stove is 20 feet.
40FT
MAX
3FT
MIN
W415-0547 / D / 11.14.08

Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when
final grading is completed, the bottom air slot is located a minimum of 12" above grade. The maximum allowable vent lengths depends on the heater, as illustrated.
2.2 SPECIAL VENT INSTALLATIONS
2.2.1 PERISCOPE TERMINATION
24” MIN
REGARDLESS
OF HORIZONTAL
VENT LENGTH
9
20FT MAX
12” MIN TO
GRADE
12” MIN TO
GRADE
57”
MINIMUM
25 5/8”
FIGURE 2.2.1a
BELOW GRADE INSTALLATION
MAXIMUM 10FT VENT LENGTH
USE GD201 PERISCOPE KIT
HORIZONTAL RUN NOT TO EXCEED
VERTICAL RISE
25 5/8”
FIGURE 2.2.1b
MAXIMUM HORIZONTAL RUN
2.2.2 CORNER TERMINATION
FIGURE 2.2.2
W415-0547 / D / 11.14.08

10
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
2.3 MINIMUM AIR TERMINAL LOCATION CLEARANCES
FIGURE 2.3
TP - MINIMUM AIR TERMINAL LOCATION CLEARANCES
W415-0547 / D / 11.14.08

For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
HR - combined horizontal vent lengths in feet
HO - offset factor: .03 (total degrees of offset - 135°*) in feet
VT - combined vertical vent lengths in feet
FEET INCHES
1° 0.03 0.5
15° 0.45 6.0
30° 0.9 11.0
45° 1.35 16.0
90°* 2.7 32.0
* The first 45° and 90°offset has a zero value and is shown in the formula as -45° and - 90° respectively or
-135° when combined.
2.4 DEFINITIONS
(HT) < (VT)
Simple venting configuration (only one 45° and 90° elbow)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
0
2.5 5 7.5 10 12.5 15
40
10
20
30
17.5 20
39
REQUIRED
VERTICAL
RISE IN
FEET V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
For vent configurations requiring more than one 45° and 90° elbow, the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: HT + V
T
< 40 feet
Example 1:
V
1
= 8 FT
V
T
= V
1
= 8FT
H
1
= 2.5 FT
H
2
= 2 FT
H
R
= H
1
+ H
2
= 2.5 + 2 = 4.5 FT
H
O
= .03 (one 45° elbow + two 90° elbows - 135°) = .03 (225° - 135°) = 2.7 FT
H
T
= H
R
+ H
O
= 4.5 + 5.4 = 9.9 FT
H
T
+ V
T
= 4.5 + 2.7 = 7.2 FT
Formula 1: H
T
< V
T
7.2 < 8
Formula 2: HT + V
T
< 40 FT
15.2 < 40
Since both formulas are met, this vent configuration is acceptable.
The shaded area within the lines represents acceptable
values for H
T
and VT
90°
45°
90°
90°
V
1
H
1
H
2
45°
2.5 ELBOW VENT LENGTHS
2.6 HORIZONTAL TERMINATION
11
FIGURE 2.6a
FIGURE 2.6b
TP - ELBOW VENT LENGTHS_45
TP - HORIZONTAL TERMINATION_45
TP - DEFINITIONS_45
W415-0547 / D / 11.14.08

12
(HT) > (VT)
Simple venting configuration (only one 45° and 90° elbow)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
REQUIRED
VERTICAL
RISE IN
INCHES V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
For vent configurations requiring more than one 45° and 90° elbow, the following formulas apply:
Formula 1: H
T
< 4.2 V
T
Formula 2: HT + V
T
< 24.75 feet
Example 2:
V
1
= 4 FT
V
2
= 1.5 FT
V
T
= V
1
+ V2 = 4FT + 1.5FT = 5.5FT
H
1
= 2 FT
H
2
= 1 FT
H
3
= 1 FT
H
4
= 1.5 FT
H
R
= H
1
+ H2 + H3 + H4 = 2 + 1 + 1 + 1.5 = 5.5 FT
H
O
= .03 (one 45° elbow + three 90° elbows - 135°)
= .03 (315 - 135) = 5.4 FT
H
T
= H
R
+ H
O
= 5.5 + 5.4 = 10.9 FT
H
T
+ V
T
= 10.9 + 5.5 = 16.4 FT
Formula 1: H
T
< 4.2 V
T
4.2 VT = 4.2 x 5.5 = 23.1 FT
Formula 2: H
T
+ V
T
< 24.75 FT
16.4 < 24.75
Since both formulas are met, this vent configuration is acceptable.
0
5 15
20
100
50
150
12.5’
19 1/2”
57”
147”
2’
The shaded area within the lines represents acceptable
values for H
T
and VT
10
90°
45°
45°
45°
90°
90°
90°
V
1
V
2
H
1
H
2
H
3
H
4
FIGURE 2.6c
TP - TOP EXIT HORIZONTAL TERMINATION_45_2
W415-0547 / D / 11.14.08
FIGURE 2.6d

(HT) < (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
For vent configurations requiring more than one 45° and one 90° elbows the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: HT + V
T
< 40 feet
Example 6:
V
1
= 5 FT
V
2
= 10 FT
V
T
= V
1
+ V2 = 5 + 10 = 15 FT
H
1
= 3 FT
H
2
= 2.5 FT
H
R
= H
1
+ H
2
= 3 + 2.5 = 5.5 FT
H
O
= .03 (one 45° elbow + three 90° elbows - 135°)
= .03 (45 + 90 + 90 + 90 - 135) = 5.4 FT
H
T
= H
R
+ H
O
= 5.5 + 5.4 = 10.9 FT
H
T
+ V
T
= 10.9 + 15 = 25.9 FT
Formula 1: H
T
< 3.5 V
T
10.9 < 15
Formula 2: HT + V
T
< 40 FT
25.9 < 40
Since both formulas are met, this vent configuration is acceptable.
The shaded area within the lines represents acceptable
values for H
T
and VT
45°
V
1
V
2
H
1
H
2
90°
90°
90°
45°
20
10
0 5 10 15
90
100
120
110
30
40
50
60
70
80
130
140
150
20
2.7 VERTICAL TERMINATION
FIGURE 2.7a
13
FIGURE 2.7b
TP - TOP EXIT VERTICAL TERMINATION_45
W415-0547 / D / 11.14.08