CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE.
INSTALLATION AND
OPERATING INSTRUCTIONS
MODEL NPS45/NPI45 MEET THE 2015 U.S ENVIRONMENTAL PROTECTION AGENCY (E.P.A.) PELLET FUEL EMISSION LIMITS FOR PELLET APPLIANCES SOLD
AFTER MAY 15, 2015, 40 C.F. R. PART 60. THESE STOVES HAVE BEEN TESTED AND LISTED BY INTERTEK TESTING SERVICES TO STANDARDS: ASTM E 1509,
ULC/ORD C1482M-90, ULC S627 AND ULC S628.
NPS45
PELLET STOVE
NPI45
PELLET INSERT
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA
METHODS.
1
EN
FR
PG
57
SAFETY INFORMATION
!
WARNING
PLEASE READ ENTIRE MANUAL
BEFORE YOU INSTALL OR USE THIS
PELLET BURNING APPLIANCE.
If the appliance is not properly installed,
a house fi re may result causing personal
injury or loss of life.
- Authorities having jurisdiction (such as
municipal building department, fi re department, fi re
prevention bureau, etc.) should be consulted before
installation to determine the need to obtain a permit.
- Contact local building or fi re offi cials about
restrictions and installation inspection
requirements in your area.
- This appliance is hot while in operation. Keep
children, clothing and furniture away. Contact may
cause skin burns.
- Do not start a fi re with chemicals or fl uids such as
gasoline, engine oil, etc...
- Do not burn trash or garbage, lawn clippings /
waste, rubber, waste petroleum products, paints
or paint thinners / solvents, plastic, materials
containing asbestos, construction debris, railroad
ties, manure or animal remains, salt water driftwood
or salted materials, unseasoned wood, coloured
paper, cardboard, plywood or particleboard.
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
4.5.1 HORIZONTAL EXHAUST THROUGH WALL INSTALLATION 20
4.5.2 THROUGH THE WALL WITH VERTICAL RISE / HORIZONTAL TERMINATION 20
4.5.3 MINIMUM INSIDE VERTICAL CLEARANCES 21
4.5.4 CLASS A CHIMNEY RETROFIT 21
4.5.5 HEARTH MOUNT INSTALLATION 22
4.6 INSERT VENTING INSTALLATION EXAMPLES 23
4.6.1 TYPICAL EXISTING MASONRY INSTALLATION 23
4.6.2 FACTORY BUILT FIREPLACE 24
5.0 FRAMING (INSERT ONLY) 25
5.1 INSTALLATION INTO A COMBUSTIBLE ENCLOSURE 26
5.2 MINIMUM ENCLOSURE CLEARANCES 27
5.3 MINIMUM CLEARANCE TO COMBUSTIBLES 27
5.4 MINIMUM MANTEL CLEARANCES 28
5.5 REAR TO TOP VENT CONVERSION INSTRUCTIONS 29
6.0 FINISHING 29
6.1 INSTALLING VIEWING DOOR 29
6.2 FLASHING INSTALLATION 30
6.3 TRIVET INSTALLATION 30
7.0 WIRING DIAGRAM 31
8.0 OPERATING INSTRUCTIONS 32
8.1 PROPER PELLET LOADING 32
8.2 START UP CYCLE 32
8.3 LIGHTING APPLIANCE MANUALLY 32
8.4 LIGHTING INSTRUCTIONS 33
8.5 CONTROLS 33
8.6 CONTROL ADJUSTMENT 34
8.7 INSTALLING A THERMOSTAT OR REMOTE CONTROL 35
8.8 SHUTDOWN INSTRUCTIONS 35
9.0 NORMAL OPERATING SOUNDS 36
10.0 MAINTENANCE 37
10.1 DAILY MAINTENANCE 37
10.1.1 MAIN DOOR OPENING 37
10.1.2 ASH DISPOSAL 37
10.1.3 BURN POT INSPECTION 37
10.1.4 CARE OF PLATED PARTS 37
10.1.5 CARE OF GLASS 38
10.1.6 HEAT EXCHANGER TUBES CLEANING 38
10.1.7 PELLET PILE UP MAINTENANCE 38
10.1.8 BURN POT CLEANING 39
10.2 BI-WEEKLY MAINTENANCE (OR EVERY 10 BAGS OF PELLETS) 39
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1472 / A / 10.11.16
10.2.1 FIREBOX MAINTENANCE (VACUUM) 39
10.3 SEMI-ANNUALLY (OR EVERY TWO TONS OF PELLET) 40
10.3.1 VACUUM HOPPER 40
10.3.2 SOOT AND FLY ASH FORMATION 40
10.3.3 VERTICAL EXHAUST DUCT CLEANING 40
10.3.4 EXHAUST HOUSING CLEAN (INSERT ONLY) 41
10.3.5 EXHAUST BLOWER CLEANING 41
10.3.6 SEAL CHECKS 41
10.3.7 VENT CLEANING 42
10.4 IN THE EVENT OF A JAMMED AUGER 42
11.0 REPLACEMENTS 43
12.0 TROUBLESHOOTING 50
13.0 WARRANTY 53
14.0 SERVICE HISTORY 54
11.1 COMMON REPLACEMENT PARTS 46
11.2 NPS45 REPLACEMENT PARTS 47
11.3 NPI45 REPLACEMENT PARTS 48
11.4 COMMON ACCESSORY PARTS 49
11.5 NPI45 ACCESSORY PARTS 49
1.0 INSTALLATION OVERVIEW
1.1 STOVE
Venting, see “VENTING”
and “INSTALLATION
Rating Plate, see
“RATING PLATE
INFORMATION”
section.
PLANNING” sections.
3
EN
Door, see
“INSTALLING
VIEWING DOOR”
section.
Floor, see “INSTALLATION
PLANNING - FLOOR
PROTECTION REQUIREMENTS”
section.
See “OUTSIDE
AIR” section.
W415-1472 / A / 10.11.16
4
1.2 INSERT
EN
See “MINIMUM MANTEL
CLEARANCES” section.
Drywall
(or other
combustible
material).
See “MINIMUM
CLEARANCES TO
COMBUSTIBLES”
section.
Door, see
“INSTALLING
VIEWING DOOR”
section.
See “ENCLOSURE
CLEARANCES”
section.
See “VENTING”
and “INSTALLATION PLANNING”
sections.
Side
Wall
Rating Plate, see
“RATING PLATE
INFORMATION”
section.
See “INSTALLATION
INTO A BUIL T -IN
ENCLOSURE” section.
W415-1472 / A / 10.11.16
2.0 INTRODUCTION
5
!
WARNING
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to
operating instructions could cause fi re or injury. Contact the local building or fi re authority and follow their guidelines. Notify
your insurance company of this appliance as well.
• Never try to repair or replace any part of the appliance unless instructions are given in this manual. All other work should be
done by a trained technician.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not operate without fully assembling all components.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or
clothing ignition. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is
recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable
safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces.
These screens and guards must be fastened to the fl oor.
• Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting
system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a
qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the
appliance and to replace any part of the control system and any gas control which has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a
licensed or qualifi ed service person. The viewing door and ashpan must be closed and latched during operation.
• Do not strike or slam shut the appliance glass door.
• Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags,
these are not toys and should be kept away from children and infants.
• If the appliance is not properly installed, a house fi re may result. Do not expose the appliance to the elements (ex. rain, etc.)
and keep the appliance dry at all times. Wet insulation will produce an odour when the appliance is used.
• The chimney must be sound and free of cracks. Clean your chimney a minimum of twice a year and as required.
• The heater is designed and approved for pelletized wood fuel only. Any other type of fuel burned in this heater will void the
warranty and safety listing. D
or paint thinners / solvents, plastic, materials containing asbestos, construction debris, railroad ties or treated wood, manure
or animal remains, salt water driftwood or salted materials, unseasoned wood, coloured paper, cardboard, plywood or
particleboard.
• Do not start a fi re with chemicals or fl uids such as gasoline, engine oil, etc.
• Ashes must be disposed in a metal container with a tight lid and placed on a non-combustible surface well away from the
home or structure.
• Your appliance requires periodic maintenance and cleaning. Failure to maintain your appliance may lead to smoke spillage in
your home.
• The exhaust system must be completely straight and properly installed. It is recommended that the pellet vent joints be sealed
with a minimum 500°F (260°C) silicone sealant. Install according to the vent manufacturer’s instructions.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated
temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V.
or other electronic components.
• During a power outage this appliance will not operate. If a power outage does occur, check the appliance for smoke spillage
and open a window if any smoke spills into the room.
• Keep foreign objects out of the hopper.
• Disconnect the power cord before performing any maintenance. NOTE: Turning the pellet feed to “OFF” does not
disconnect all power to the heater.
• Do not throw this manual away. This manual has important operating and maintenance instructions that you will need at a
later time. Always follow the instructions in this manual.
• At no point should you use fi rewood or fi relogs in this appliance. The use of which could cause a house fi re.
• This appliance must be connected to a standard 115 V, 50Hz grounded electrical outlet. Do not use an adapter plug or sever
the grounding prong. Do not route the electrical cord underneath, in front of, or over the appliance.
• When installed in a mobile home, the appliance must be bolted to the fl oor, have outside air, and NOT BE INSTALLED IN THE
BEDROOM (per H.U.D. requirements). Check with local building offi cials.
o not burn trash or garbage, lawn clippings / waste, rubber, waste petroleum products, paints
3.8C
EN
W415-1472 / A / 10.11.16
6
p
2.1 DIMENSIONS
2.1.1 STOVE
EN
30 1/2"
774mm
22 1/2"
571mm
26 5/8"
676mm
1 1/8”
9 7/8"
251mm
17 3/8"
441mm
11 3/4"
298mm
568mm
22 3/8"
2.1.2 NPI45 COMPLETE WITH NI800 FLASHING
975mm
38 3/8"
29 5/16"
642mm
21 1/2"
546mm
20 3/8"
8"
Center line
of exhaust
11 3/16"
284mm
203mm
Center line of
insert
22 3/8"
518mm
4 1/4"
108mm
568mm
12 1/2"
318mm
673mm
26 1/2"
2 1/4"
57mm
Center line of
air intake
15"
12 3/4"
324mm
381mm
Center line of
Stand-o’s
7 5/8"
194mm
Center line
of exhaust
2 3/4"
70mm
air intake
20 5/8"
524mm
W415-1472 / A / 10.11.16
523mm
20 5/8"
829mm
*32 5/8"
12 1/2"
572mm
22 1/2"
975mm
38 3/8"
*In order to install ashing ush to a nished wall and centered within the opening, the front
ening of the replace or enclosure must be this wide.
o
1 1/4"
32mm
318mm
2.1.3 NPI45 COMPLETE WITH AK8 ADAPTER AND GICSK FLASHING
1180mm
46 7/16"
292mm
10 5/16"
29 3/16"
741mm
15 5/8"
7
EN
397mm
Stand-o’s
20 5/8"
524mm
7 5/8"
194mm
26 1/2"
518mm
20 3/8"
8"
Center line
of exhaust
10 1/2"
267mm
*In order to install ashing ush to a nished wall and centered within the opening, the front
203mm
46 7/16"
opening of the replace or enclosure must be this wide.
4 1/4"
108mm
Center line of
insert
523mm
20 5/8"
781mm
*30 3/4"
572mm
22 1/2"
1180mm
2 1/4"
57mm
Center line of
air intake
13 3/8"
340mm
10 5/16"
262mm
673mm
2 3/16"
56mm
Center line
of exhaust
2 3/4"
70mm
Center line of
air intake
W415-1472 / A / 10.11.16
EN
8
2.1.4 NPI45 COMPLETE WITH AK9 ADAPTER AND CISK FLASHING
270mm
10 5/8"
16 1/2"
419mm
31"
787mm
1180mm
46 7/16"
Center line
of exhaust
11 3/16"
284mm
20 3/8"
8"
203mm
Center line of
insert
20 5/8"
*32 5/8"
28 1/8"
714mm
518mm
4 1/4"
108mm
523mm
829mm
2 1/4”
Center line of
air intake
26 1/2"
14 1/4"
362mm
10 5/8"
270mm
673mm
1 5/8"
42mm
Stand-o’s
20 5/8"
524mm
7 5/8"
194mm
Center line
of exhaust
2 3/4"
70mm
Center line of
air intake
572mm
22 1/2"
46 7/16”
*In order to install ashing ush to a nished wall and centered within the opening, the front
opening of the replace or enclosure must be this wide.
NPI45 Hopper Capacity45 Pounds (20kg)
Minimum Appliance Opening SizeFront: 32 5/8" (829mm)* W x 20 5/8" (532mm) H x 14 1/4" (362mm)
* In order to install, fl ashing fl ush to fi nished wall and centered within the opening the front opening of the appliance or
enclosure must be 32 5/8" (829mm) wide.
2.2.1 HEATING SPECIFICATIONS
Approximate Maximum Heating Capacity (in square feet)* 800 to 2000 Sq. Feet (243-610 Sq. Meters)
Burn Rate (Pounds per Hour)**1.0 to 5.0
BTU/hr**8500 to 42500
Maximum Burn Time on Low Burn**55 Hours (NPS45), 45 Hours (NPI45)
* Heating capacity will vary depending on the home's fl oor plan, degree of insulation, and the outside temperature. It is
also affected by the fuel size, quality, and moisture level.
** Small pellets will increase or decrease the stated burn rates and burn times. Differences of plus or minus 20%
depending on fuel quality may occur.
9
EN
D Back: 20 3/8" (518mm) W
2.3 GENERAL INSTRUCTIONS
ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE
WITH LOCAL CODES. IN THE ABSENCE OF LOCAL CODES, USE THE CURRENT CSA C22.1
CANADIAN ELECTRIC CODE (IN CANADA) OR THE ANSI/NFPA NO. 70 NATIONAL ELECTRIC CODE
DO NOT CONNECT THIS APPLIANCE TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE. DO
NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” (1219.2mm)
FROM THE FRONT FACE OF THE APPLIANCE.
!
WARNING
IN THE UNITED STATES.
PROVIDE ADEQUA TE VENTILA TION.
W415-1472 / A / 10.11.16
10
Thank you for purchasing a Wolf Steel Ltd. Pellet Appliance. This appliance is designed for use with Pelletized
Wood Only.
EN
Please read this entire manual before installation and use of this pellet fuel-burning room appliance. Failure to
follow these instructions could result in property damage, bodily injury or even death.
Keep this manual handy for future reference.
This Pellet Appliance, when installed, must be electrically grounded in accordance with the local codes, or in
the absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI/NFPA
70 National Electrical Code in the United States.
This appliance will not operate using natural draft or without a power source for the blower systems and fuel
feed system.
These appliances are equipped with levelling screws that penetrate the front corners of the fi rebox. If these
screws are missing it will have a negative infl uence on the performance of this appliance. Ensure that the
levelling screws are tightened into position.
The protective wrap on plated parts is best removed when the assembly is at room temperature but this can be
improved if the assembly is warmed, using a hair dryer or similar heat source.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a non-combustible hearth pad extending the full width and depth.
2.4 GENERAL INFORMATION
2.4.1 PELLET SPECIFICATIONS
4.5B
!
WARNING
IT IS IMPORTANT TO SELECT AND USE ONLY PELLETS THAT ARE DRY AND FREE OF DIRT
OR ANY IMPURITIES SUCH AS HIGH SALT CONTENT. DIRTY FUEL WILL ADVERSELY AFFECT
THE OPERATION AND PERFORMANCE OF THE APPLIANCE AND WILL VOID THE WARRANTY.
THE PELLET FUEL INSTITUTE (P.F.I.) HAS ESTABLISHED STANDARDS FOR WOOD PELLET
MANUFACTURERS. WE RECOMMEND THE USE OF PELLETS THAT MEET OR EXCEED THESE
STANDARDS. ASK YOUR DEALER FOR A RECOMMENDED PELLET TYPE.
Pellet quality is important, please read the following:
Your Wolf Steel Ltd. Pellet Appliance has been designed to burn premium hard or soft wood pellets only. Do
not use any other type of fuel such as fi re logs or fi re starting pellets, as this will void the warranties stated in
this manual.
The performance and heat output of the pellet appliance is directly related to the quality and moisture of the
pellets. Store pellets in a cool dry area to prevent moisture absorption.
64.1
W415-1472 / A / 10.11.16
P.F.I. PELLET STANDARDS:
11
Inorganic Fines (fi ne
particles)
Bulk Density38 pound per cubic foot minimum
Size1/4" (6.4mm) to 5/16" (8mm) diameter, 1/2" - 1 1/2" (13mm
Ash ContentNo more than 2%
Moisture Content8% maximum
Chlorides300 parts per million by weight
Trace MetalsLess than 100mg/kg
Heat ContentApproximately 8200 BTU per pound minimum
Construction WasteNot to contain any waste materials
1% maximum through a 1/8" (3.2mm) screen
- 38mm) long maximum
If the fuel does not comply to
this standard, the appliance
may not operate as designed.
We recommend the use of
premium grade (1% ash
content) for longer appliance
life and less frequent cleaning.
2.4.2 SAFETY FEATURES
HIGH LIMIT SWITCH: Your appliance is equipped with a high limit switch. In the event that the temperature
of the appliance approaches an unsafe operating temperature, this switch will shut down the pellet feed,
which will eventually shut down the appliance. If this happens, it is important to fi nd out why the appliance
overheated. Contact your local dealer.
LOW LIMIT SWITCH: This switch will automatically shut down the appliance if the fi re goes out or fails to
light within 15 minutes.
EN
HOPPER DOOR INTERLOCK: Your appliance is equipped with a micro switch in the hopper assembly that
shuts off the auger when the hopper door is opened. Closing the door switches the auger back on, allowing
pellets to feed again.
VACUUM SWITCH: This switch will sense lack of air fl ow through the appliance and shut down the pellet
feed. This lack of fl ow could be caused by a blocked vent.
POWER FAILURE: In the event of a power failure, the appliance will shut down. Once power is restored, the
appliance will restart, unless the convection air temperature has gone above the high limit switch setting. If
this happens, contact your local dealer.
2.4.3 EPA COMPLIANCE
We suggest that our woodburning hearth products
be installed and serviced by professionals who are
certified in the U.S. by the National Fireplace
Institute® (NFI) as NFI Woodburning Specialists or
who are certified in Canada by
Wood Energy Technical
Training (WETT).
- INSTALL AND USE ONLY IN ACCORDANCE WITH THE
MANUFACTURER’S INSTRUCTIONS AND LOCAL
BUILDING CODES. MINIMUM CEILING HEIGHT: 7FT
(2.13M) HEARTH EXTENSION / COMBUSTIBLE FLOOR
PROTECTION: IF INSTALLED ON A COMBUSTIBLE
FLOOR, UNIT MUST BE PLACED ON A
NON-COMBUSTIBLE FLOOR PROTECTOR EXTENDING
6” IN FRONT.
- DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
- REPLACE GLASS WITH ONLY CERAMIC GLASS.
DANGER: RISK OF ELECTRICAL SHOCK. DISCONNECT
POWER BEFORE SERVICING UNIT.
- KEEP VIEWING DOOR TIGHTLY CLOSED DURING
OPERATION.
- CONTACT LOCAL BUILDING AND FIRE OFFICIALS
ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR LOCAL AREA.
- SUITABLE FOR USE IN MOBILE HOMES WHEN USED
WITH OUTSIDE AIR INSTALLATION KIT.
- REFER TO INSTALLATION INSTRUCTIONS OR LOCAL
BUILDING CODES WHEN PASSING EXHAUST SYSTEM
THROUGH COMBUSTIBLE WALL OR CEILING.
CAUTION: HOT WHILE IN OPERATION. DO NOT TOUCH.
KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.
CONTACT MAY CAUSE SKIN BURNS.
THIS WOOD APPLIANCE NEEDS PERIOD INSPECTION
AND REPAIR FOR PROPER OPERATION. CONSULT
THE OWNER’S MANUAL FOR FURTHER INFORMA-
TION. IT IS AGAINST UNITED STATES FEDERAL
REGULATIONS TO OPERATE THIS WOOD APPLIANCE
IN A MANNER INCONSISTENT WITH THE OPERATING
INSTRUCTIONS IN THE OWNER’S MANUAL.
WOLF STEEL LTD.
24 NAPOLEON ROAD.
BARRIE, ONTARIO L4M 0G8 CANADA
LISTED PELLET FUEL BURNING ROOM HEATER TESTED TO: ASTM E 1509, UL1482, ULC S628 MODEL NPI45
U.S. ENVIRONMENTAL PROTECTION AGENCY
emissions standards. Not approved for sale after May 15, 2020.
MASONRY FIREPLACE INSTALLATION
MANTEL
B
A
INSERT
C
HEARTH EXTENSION
BUILT-IN FIREPLACE INSTALLATION
WOOD MANTEL
WOOD MANTE
B
(FRONT VIEW)
FRONT VIEW
D
ENCLOSURE
INSERT
E
MANUFACTURE DATE: / DATE DE FABRICATION:
YEAR:
MONTH:
2016
243658710912111
Certified to comply with 2015 particulate
E
20172018
40 CFR Part 60, Subpart AAA.
BUILT-IN FIREPLACE INSTALLATION
MANTEL
MINIMUM CLEARANCES TO COMBUSTIBLE
Sidewall A 8”
Mantel B 8”
Floor Protector C 6”
Recess Width D 31 1/2”
Recess Height E 26 1/2”
Recess Depth F 16”
Mantel Depth G 10”
INPUT RATING
MIN 1 LB/HR
MAX 5 LB/HR
ELECTRICAL RATING
120V 3.6A 60HZ
C
(SIDE VIEW)
B
G
ENCLOSURE
F
20192020
NPI45
2.4g/hr
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
W415-1472 / A / 10.11.16
3.0 INSTALLATION PLANNING
13
!
WARNING
READ ENTIRE MANUAL BEFORE YOU INSTALL OR USE THIS APPLIANCE. FAILURE TO FOLLOW THE
INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY OR EVEN DEATH.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH
THIS APPLIANCE. USING NON-LISTED ACCESSORIES AND REPLACEMENT PARTS (BLOWERS,
DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENT COMPONENTS, ETC.) COULD RESULT IN A
SAFETY HAZARD AND WILL VOID THE LIMITED LIFETIME WARRANTY.
Check with local building offi cials for any permits required for installation of this pellet appliance and notify your
insurance company before proceeding with installation.
Before installing we recommend placing the appliance outside and load 5 lbs (2.3k) of pellets inside the hopper. Plug the appliance in and let it run on HIGH until the pellets run out. This will cure the paint and burn off
most of the oils on the steel, thereby minimizing any smell inside the home.
68.1A
3.1 APPLIANCE PLACEMENT
Have an authorized dealer install the appliance. If you install the appliance yourself, have your dealer review
your installation plans and/or installation.
Draw out a detailed plan of the installation including dimensions and verify the dimensions with the
requirements listed in this manual.
You may wish to adjust the appliance position slightly to ensure the vent does not intersect with a framing
member. Appliance must be positioned so that no combustibles are within, or can swing within (e.g. drapes,
doors), 4 feet (1.2m) of the front of the appliance.
67.1B
EN
3.2 INSTALLATION OPTIONS
NPS45:
To install in a Residential or Mobile Home, see "MOBILE HOME INSTALLATION" section. For alcove installations, see "ALCOVE INSTALLATION REQUIREMENTS" section. For horizontal vent or vertical vent, see
"VENTING" section. For outside air, see "OUTSIDE AIR" section.
NPI45:
To install as an insert into an existing masonry appliance or factory built appliance, see "VENTING" section.
To install into a combustible enclosure, see "INSTALLATION INTO A COMBUSTIBLE ENCLOSURE" section.
W415-1472 / A / 10.11.16
14
3.3 STOVE MINIMUM CLEARANCE TO COMBUSTIBLES
!
EN
DO NOT INSTALL INTO ANY AREA HAVING LESS THAN 48" (1219mm) (CEILING TO APPLIANCE
BOTTOM, EXCLUDING HEARTH HEIGHT).
3.3.1 STRAIGHT INSTALLATION
WARNING
Through the Wall Installations complete
with outside air
3.3.2 CORNER INSTALLATION
Through the Wall Vents complete with outside airInterior Vertical Vents
Interior Vertical Vents
2”
2”
45°
6”
2”
6”
Floor Protection
6”
NOTE: If interior vertical pellet vent is used, the clearance to the back wall is determined by the
upward-turning elbow or "Tee". It will vary in depth depending on the brand of pellet vent used (it is
approximately 5" (127mm). Before placing the appliance, connect the elbow or "Tee" and allow for the
minimum 3" (76mm) clearance to the combustible wall.
W415-1472 / A / 10.11.16
3.3.3 ALCOVE INSTALLATION REQUIREMENTS (MINIMUM)
35”
30”
48”
STOVE
15
EN
Minimum Alcove Dimensions
W415-1472 / A / 10.11.16
16
3.4 FLOOR PROTECTION REQUIREMENTS INSTALLATION
EN
THERMAL PROTECTOR:
This appliance must be installed on a non-combustible thermal protector that extends to the front, sides
and back of the appliance as per the minimum requirements below.
NOTE: Floor protection is required for spark and ash shielding, and for limiting fl oor
temperatures from the radiant heat of the appliance.
L
J
R = Thickness / K-Value
K = Thickness / R-Value
With K values, the lower value is a better insulator. With R values, the higher number is better.
J
The thermal protector must have an overall R-Value of 1.0. For multiple layers, add
R-Values for each layer to determine the overall R-Value.
I
CONVERTING MATERIAL SPECIFICATIONS TO R OR K VALUES
COMMON K and R VALUES CHART
MATERIALK-VALUER-VALUE
Per inch Per inch
Micore 3000.432.33
Wonderboard (cement board)1.920.52
Common Brick5.000.20
Cement Mortar5.000.20
Ceramic Tile12.500.08
Marble11.000.09
Air Space (ventilated)0.701.43
Sand and Gravel1.700.59
Drywall (gypsum)1.001.00
Rockwool or Fiberglass Batts0.303.33
MINIMUM FLOOR PROTECTION
FRONT (I)SIDES (J) VENT (L)
6” (152mm)6” (152mm)2” (51mm)
K-Value Example:
A wood stove may call for thermal protection which has a K factor of 1 or less. A product
such as Micore 300 Board from USG has a K-Value of approximately .43 per inch.
Therefore, a 1/2” (12.7mm) thickness of this board would have a K-Value of .86, which meets the requirement of our example stove.
R-Value Example:
W415-1472 / A / 10.11.16
This fi replace calls for thermal protection with an R-Value of 0.59. This same board
above is rated as having an R-Value of 2.33 for a 1” (25.4mm) thickness. Therefore,
1/2” (12.7mm) of the Micore 300 Board would have a R-value of 1.165, which meets
the specifi cations for this fi replace.
99.2C
3.5 OUTSIDE AIR
17
Available from your Authorized Dealer (114KT)
Outside air must not be drawn from an enclosed space (garage, unventilated crawl space).
NOTE: Wolf Steel Ltd. strongly suggests using outside air for all residential installations, especially
for those that are energy effi cient, air-tight homes.
Outside air supply must not be over 15' (4.5m) long.
Outside air vents must be made with 1 3/4" (44mm) diameter or larger metal or aluminum duct with a metal
screen attached to the end to keep out rodents (P.V.C. or other materials may not be used).
The outside air inlet must not be above or within 12" (305mm) of the chimney termination, must have a rain
cap or down-turned elbow to prevent the water from entering and be located so that it will not become
plugged by snow or other material.
Outside air is required for all combustible built-in enclosure installations.
3.6 MOBILE HOME
!
WARNING
DO NOT INSTALL IN A SLEEPING ROOM.
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND CEILING ROOF
MUST BE MAINTAINED.
EN
Installation into a manufactured home or mobile home should be installed in
accordance with the Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard,
CAN/CSA Z240 MH Series, in Canada.
The appliance must be grounded to the steel chassis of the mobile home
(Some states do not require this; check with your local building department).
STOVE
ILLUSTRATED
29.4A
W415-1472 / A / 10.11.16
18
4.0 VENTING
4.1 TYPE OF VENT
EN
Must be an approved 3" (76mm) or 4" (102mm) diameter Type "L" or "PL" vent, vented to the outside or connect
the vent to a factory built type lined "A" chimney using an adaptor; and/or stainless steel chimney liner for
masonry appliance installations. Use 4" (102mm) diameter vent if vent or liner height is over 15' (4.5m) or if
installation is over 4,000' (1219m) above sea level.
4.2 INSTALLING THE PELLET VENT
PELLET VENT MUST MAINT AIN A MINIMUM 3" (76.2mm) CLEARANCE TO ANY COMBUSTIBLE (INST ALL
DO NOT CONNECT THE PELLET VENT TO A VENT OR CHIMNEY SERVING ANY OTHER APPLIANCE OR
The vent must have a support bracket every 5’ (1.5m)when on
the exterior wall. To achieve optimum performance, keep vent
runs as short as possible, especially on horizontal installations.
MAXIMUM VENTING: Maximum venting height is 33’ (10.1m)
Maximum horizontal without vertical rise is 5’ (1.5m) straight
off the back of the appliance. Use no more than 180° of
elbows (two 90° elbows, or two 45° elbows and one 90°
elbow, etc), excluding the tee and the termination.
VENT INST ALLATION: Termination must exhaust above
the air inlet elevation, and parallel or above the exhaust
output of the pellet appliance. It is recommended that at
least 3’ (0.9m) of vertical pipe be installed to create some
natural draft. This is to help prevent the possibility of smoke
or odour entering the home during the appliance shut down
or in the event of a power outage. Horizontal sections must
have a 1/4” (6.4mm) rise every 12” (304.8mm) of travel if
longer than 3’ (0.9m).
The pellet vent connections must be sealed with HI-Temp
RTV Silicone and screwed together with at least 3 3/8”
(85.7mm) long stainless steel screws. Seal each vent
section by injecting a liberal amount of 500°F (260°C) RTV
silicone sealant into the gap. We recommend sealing the
outside of the vent connections to permit easier access
when servicing.
!
WARNING
VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER, CHIMNEY LINER EXCLUDED).
HEATER.
DO NOT INST ALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
33’ (10.1m)
30’ (9.1m)
Use 4”
(101.6mm)
diameter “L”
vent if venting
in this shaded
region.
25’ (7.6m)
20’ (6.1m)
15’ (4.6m)
Use 3” (76.2mm)
or 4” (101.6mm)
diameter “L”
vent if venting
in this shaded
region.
10’ (3.1m)
5’ (1.5m)
0
0
5’
(1.5m)
10’
(3.1m)
4.3 VENTING THE PELLET APPLIANCE
Use an approved wall thimble when passing the vent through walls and a ceiling support / fi restop spacer when
passing the vent through ceilings (maintain a 3" (76mm) clearance to any combustibles).
W415-1472 / A / 10.11.16
7.5D
4.4 PELLET VENT TERMINATION
19
The vent termination must have an approved cap (to prevent water from entering) or a 45° downturn.
If the termination is located on a windy side of the house, a shield is recommended to prevent soot from
building up on the side of the house.
Horizontal terminations must protrude 12" (305mm) from the wall, vertical terminations require a minimum 24"
(610mm) above the highest point that it penetrates through the roof.
Depending on pellet quality, vent confi guration and air settings, black soot may occur on the terminal wall.
4.5 VENT TERMINAL CLEARANCES
D
A
NOTE: Illustration dimensions are to the center of
the exhaust exit point of the vent.
EN
E
C
K
J
G
I
F
H
B
B
L
E
CLEARANCES
A12” (304.8mm)Clearance above grade, veranda porch, deck or balcony. (Including vegetation and mulch)
9” (228.6mm)*Clearance beside or below any windows or doors that open.
B
12” (304.8mm)*Clearance above any window or door that opens.
C
D0” (0mm)Clearance to an outside corner wall.
E3” (0.9m)Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.)
F9” (228.6mm)Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
G3’ (0.9m)Clearance to a mechanical air supply inlet.
H7’ (2.1m) **Clearance above a paved sidewalk or paved driveway located on public property.
I12” (304.8mm)**Clearance under a veranda, porch, deck or balcony.
J24” (609.6mm)Clearance above the roof.
K2’ (0.6m)Clearance from an adjacent wall including neighbouring buildings.
L
*Recommended to prevent condensation on windows and thermal breakage
**This is a recommended distance. For additional requirements check local codes.
18”
(457.2mm)
3’ (0.9m) within a
height of 15 feet
(13.7m) above the
meter / regulator
assembly
Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet
(0.6m) from the center line of the terminal.
Clearance to each side of center line extended above natural gas or propane meter / regulator assembly or
mechanical vent.
12.7C
W415-1472 / A / 10.11.16
20
4.5.1 HORIZONTAL EXHAUST THROUGH WALL INSTALLATION
EN
3” Minimum
6”
Minimum
Floor
Protection
4.5.2 THROUGH THE WALL WITH VERTICAL RISE / HORIZONTAL TERMINATION
11 5/8”
17”
12” Minimum
Wall
Thimble
5’ Maximum
Outside Air
(Recommended)
6”
Minimum
Floor
Protection
11 5/8”
17”
2”
3”
Wall Thimble
Outside Air
(Recommended)
W415-1472 / A / 10.11.16
4.5.3 MINIMUM INSIDE VERTICAL CLEARANCES
Vertical Cap
Storm Collar
21
EN
Roof Flashing
Floor Protection
4.5.4 CLASS A CHIMNEY RETROFIT
Ceiling Support
Vertical Cap
Storm Collar
Vent must maintain 3”
clearance to combus-
tibles.
3”
2”
Outside air (Recommended)
(Installation showing inlet of out-
side air in ventilated crawl space)
Roof Flashing
Class A Chimney
Ceiling Support
Floor Protection
Vent must maintain
3” clearance to
combustibles.
3”
2”
Outside air
(Recommended)
(Installation showing inlet of outside
air in ventilated
crawl space)
W415-1472 / A / 10.11.16
22
oootec
t
Co
4.5.5 HEARTH MOUNT INSTALLATION
EN
Chimney Cap
Pellet
Liner
Clean-out
ut
tee
Vertical Cap
Storm Collar
Pellet
Vent
torm
Flue Cover
6”
MIN
Floor Protection
Bring outside air to the heater
Outside Air (Recommended)
For installation instructions, see "TYPICAL EXISTING MASONRY" section.
W415-1472 / A / 10.11.16
4.6 INSERT VENTING INSTALLATION EXAMPLES
l
e
r
o
Cap
Ver
23
4.6.1 TYPICAL EXISTING MASONRY INSTALLATION
!
WARNING
DO NOT REMOVE BRICKS OR MORTAR FROM THE FIREPLACE.
Prior to installation:
When installing the insert into a masonry fi replace, do not
remove any bricks or masonry. Do not weaken the structure,
or reduce the protection for combustible materials to less then
that required by the National Building Code. Bolted or screwed
together pieces (smoke shelf / defl ectors) may be removed,
but must be able to be re-installed if the appliance is removed.
External trim pieces, which do not affect the operation of the
fi replace, may be removed provided they are available to be reinstalled in event the appliance is removed.
A warning label must be attached to the back wall of the fi replace
stating that “This fi replace has been altered to accommodate a fi replace insert and must be re-inspected by a qualifi ed person
prior to re-use as a fi replace”.
Non-combustible fl oor protection must cover the fl ooring
underneath, as well as extend a minimum of 6” (152.4mm) in
front and to both sides of the appliance.
Cover Plate
Vertical Cap
Storm Collar
rm Colla
t
Pellet
Liner
Cover
Flue
EN
Clean all ashes out of the inside of the fi replace. Make sure
that the chimney and fi replace are free of cracks, loose mortar,
creosote deposits, blockage or other signs of deterioration.
If necessary, have any repair work done by a qualifi ed
professional before installing the appliance.
A. Remove the fi replace damper or fasten it permanently open.
B. Measure the throat of the fi replace and mark this shape on a piece of 24 (0.511mm) gauge sheet meta
(fl ue cover). Cut a hole sized for the pellet liner to lie directly below the fi replace fl ue opening. Allow 2”
(50.8mm) of material for a fl ange on all sides and cut to these measurements. Bend down the fl anges.
If you have never done this before, it might be a good idea to make a cardboard pattern and test it fi rst.
Fasten this fl ue cover in position as high as possible with two masonry screws per side through the fl anges into the fi replace.
C. If you plan on connecting outside air it is recommended to do so at this time.
D. Install fl oor protection if necessary.
E. Connect the pellet vent with a clean out tee to the back of the insert. Refer to manufacturer’s
installation instructions to see “REAR TO TOP VENT CONVERSION INSTRUCTIONS” section and th
“GENERAL VENTING” section.
F.Run a liner down the chimney and connect to tee.
Outside Air
(Recommended)
G. Position the insert in it’s fi nal location.
H. Pull the excess length of liner out through the top of the chimney. Trim the excess liner, install the cap
and cap the chimney.
62.3B
W415-1472 / A / 10.11.16
24
l
e
4.6.2 FACTORY BUILT FIREPLACE
EN
Prior to installation:
Do not weaken the structure or reduce the protection for
combustible materials to less then that required by the National
Building Code. Bolted or screwed together pieces (smoke shelf /
defl ectors) may be removed, but must be able to be re-installed
if the appliance is removed.
External trim pieces, which do not affect the operation of the
fi replace, may be removed provided they are available to be reinstalled in event the appliance is removed.
A warning label must be attached to the back wall of the
fi replace stating that “This heater has been altered to
accommodate a fi replace insert and must be re-inspected by a
qualifi ed person prior to re-use as a factory built fi replace”.
Non-combustible fl oor protection must cover the fl ooring
underneath, as well as extend a minimum of 6” (152.4mm) in
front and to both sides of the appliance.
Clean all ashes out of the inside of the fi replace. Make sure
that the chimney and fi replace are free of cracks, loose mortar,
creosote deposits, blockage or other signs of deterioration.
If necessary, have any repair work done by a qualifi ed
professional before installing the appliance.
A. Remove the fi replace damper or fasten it permanently
open.
Vertical
Cap
Storm
Collar
The smoke
shelf, damper
and baffles may
be removed
Floor Protection
Do not remove any part that would
alter the integrity in any way.
Roof
Flashing
B.Measure the throat of the fi replace and mark this shape on a piece of 24 (0.511mm) gauge sheet meta
(fl ue cover). Cut a hole sized for the pellet liner to lie directly below the fi replace fl ue opening. Allow 2”
(50.8mm) of material for a fl ange on all sides and cut to these measurements. Bend down the fl anges.
If you have never done this before, it might be a good idea to make a cardboard pattern and test it fi rst.
Fasten this fl ue cover in position as high as possible with two masonry screws per side through the fl anges into the appliance.
C. If you plan on connecting outside air it is recommended to do so at this time.
D. Install fl oor protection if necessary.
E. Connect the pellet vent with a clean out tee to the back of the insert. Refer to manufacturer’s
installation instructions to see “REAR TO TOP VENT CONVERSION INSTRUCTIONS” section and th
“GENERAL VENTING” section.
F. Run a liner down the chimney and connect to tee.
G. Position the insert in it’s fi nal location.
H. Pull the excess length of liner out through the top of the chimney. Trim the excess liner, install the cap
and cap the chimney.
80.1A
W415-1472 / A / 10.11.16
5.0 FRAMING (INSERT ONLY)
25
!
WARNING
RISK OF FIRE!
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE
APPLIANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH
ANY OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN
AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH
SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK
OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO
MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS
LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS
CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS,
OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING
ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE
FURNACE AT 1382°F (750°C) AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, OR SPECIFIED IN THE
IF SPECIFIED IN THE INSTALLATION INSTRUCTION FINISHING MUST BE DONE USING A NON-
COMBUSTIBLE MATERIAL SUCH AS NON-COMBUSTIBLE BOARD, CERAMIC TILE, MARBLE, ETC.
DO NOT USE WOOD OR DRYWALL. ANY FIRE RATED DRYWALL IS NOT ACCEPTABLE
COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY.
INSULATION AND OTHER MATERIALS ARE SECURED.
MATERIALS.
COULD RESULT.
BASE.
INSTALLATION INSTRUCTIONS, THEY MUST BE INSTALLED.
71.1C
EN
W415-1472 / A / 10.11.16
26
5.1 INSTALLATION INTO A COMBUSTIBLE ENCLOSURE
EN
!
WARNING
OUTSIDE AIR IS MANDATORY FOR A COMBUSTIBLE BUILT-IN ENCLOSURE INSTALL.
When installing the insert as a "Built-in" appliance, it is important to maintain the clearances to combustibles,
see "MINIMUM CLEARANCE TO COMBUSTIBLES" section.
A non-combustible hearth must cover the fl ooring underneath, as well as, a minimum of six inches in front
and to both sides of the appliance.
A. Install fl oor protection.
B. Frame structure maintaining minimum clearances. Locate and frame openings for both the exhaust
and outside air. Outside air is mandatory for enclosure installations. See "OUTSIDE AIR" section.
C.Refer to vent manufacturer's installation instructions and to "VENTING" section. Connect the vent.
Install fl ashing, see "FLASHING INSTALLATION" section.
D.Consideration must be taken during installation that removal of the insert is necessary for inspection
and annual maintenance. Install the vent cap.
3 1/2” MAX
40”
MINIMUM
ENCLOSURE
HEIGHT
3 1/2”
MAX
17”
Non
combustible
floor protection.
This protection must
offer an R value of 0.4 (two
layers of 1/2” thick cement board, total 1” with each layer rated with an
R value of 0.2).
For temperature requirements, the enclosure space around and
above the heater must be left unobstructed.
33”
27”
Centerline of
heater opening
7 1/8”
4 7/8”
1 7/8”
2”
W415-1472 / A / 10.11.16
5.2 MINIMUM ENCLOSURE CLEARANCES
!
The stand-offs located on the back of the insert must not be removed when installing the insert into a
built-in combustible enclosure.
6 3/8” Minimum
40”
27”
WARNING
2 1/4”
27
EN
3” all around (Refer to vent
manufacturer’s instructions)
Stand-offs
6”
Non-combustible
floor protection
5.3 MINIMUM CLEARANCE TO COMBUSTIBLES
Side wall to appliance 8" (203mm)
Mantel to top of appliance 8" (203mm)
Top facing to appliance 6 3/8" (162mm)
Side facing to appliance 6" (152mm)
Floor protection* 6"* (152mm)
* Floor Protection: Minimum 6" (152mm)
in front of door and to either side.
10”
Side Wall
7 5/8”
2 3/4”
10” Mantel
8” MIN
8”
MIN
6”
6”
W415-1472 / A / 10.11.16
28
5.4 MINIMUM MANTEL CLEARANCES
EN
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
16” MANTEL
14”
12”
!
WARNING
CLEARLY MAINTAINED.
14”
12”
10”
10”
8”
73.1
W415-1472 / A / 10.11.16
5.5 REAR TO TOP VENT CONVERSION INSTRUCTIONS
NOTE: The insert is factory shipped in a rear vent confi guration. Be careful not to damage the gasket.
If installing 4" (102mm) diameter vent vertically, it will be necessary to start with a 12" (305mm) section of 3"
(76mm) diameter vent to clear the hopper, then increase to 4"(102mm)
diameter vent.
A.To vent exit vertically, remove the two screws holding the
exhaust cover.
B. Remove the two screws holding the exhaust tube.
C. Attach the exhaust tube and gasket in the vertical position.
D. Attach the exhaust cover and gasket over the horizontal exit.
6.0 FINISHING
6.1 INSTALLING VIEWING DOOR
29
EN
!
WARNING
GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED.
THE DOOR LATCHES ARE PART OF A SAFETY SYSTEM AND MUST BE PROPERLY ENGAGED. DO
NOT OPERATE THE APPLIANCE WITH LATCHES DISENGAGED.
BEFORE DOOR IS REMOVED TURN THE APPLIANCE OFF AND WAIT UNTIL APPLIANCE IS COOL TO
THE TOUCH. DOORS ARE HEAVY AND FRAGILE SO HANDLE WITH CARE.
75.2
The main viewing door has been boxed separate from the appliance, but MUST be installed before burning
the appliance.
A.Open both side panels, exposing the bushing on the left and the latches
on the right.
B.Align the pins on the door to the bushing on the left side of the
appliance. Lower into place until both bushings touch.
C.Engage the latch hooks into the door frame. Snap the rear handle hook
to lock the latch closed.
INSERT ILLUSTRATED
W415-1472 / A / 10.11.16
30
6.2 FLASHING INSTALLATION
EN
A.Secure the right fl ashing to the
right side of the appliance using
two of the #8 x 1/2" screws.
B.Remove the two control panel
securing screws, discard the
screws and shipping bracket.
C.Secure the control panel to the
right fl ashing using the two #8
x 3/8" screws. Secure the left
fl ashing with the remaining #8 x
1/2" screws.
D.Align the holes in the top of the
right and left fl ashing with those
on the bottom lip of the Top
Flashing and secure from the
rear using the four #8-32 x 3/8"
screws, washers and nuts.
E.The three pieces of trim are
assembled in the same manner
as a picture frame. Place the
corner brackets (with screw
loosened) into the trim sections.
Tighten the screw spreading
the two pieces apart. Attach the
adjoining section. Repeat with
the opposite side. Tighten all
screws fi rmly.
F.Slide the assembled trim down
over the fl ashing.
G. Affi x the logo to the bottom left
hand corner of the left fl ashing.
TRIM
UNDERSIDE
L
O
W
1
2
3
4
H
5
I
G
H
RIGHT
FLASHING
CONTROL
PANEL
CORNER
BRACKET
SHIPPING
BRACKET
SECURING
SCREWS
PUSH TO START / POUSSEE POUR COMMENCER
OPTIMUM
3
2
3
3
2
2
4
1
4
1
4
1
5
5
5
W385-0355
CONTROL
PANEL
SECURING
SCREWS
TOP
FLASHING
TRIM
ASSEMBLY
6.3 TRIVET INSTALLATION
The trivet for the insert is attached by
two set screws on the inside of the
hopper lid
W415-1472 / A / 10.11.16
SET
SCREW
SET SCREW
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.