Napoleon Manhattan GE38NT-M, Manhattan GE38PT-M Installation And Operation Instructions Manual

INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS AND CSA 22.2 NO. 46 FOR ELECTRIC AIR HEATER.
DIRECT VENT MILLIVOLT SYSTEM
INSTALLATION AND OPERATION INSTRUCTIONS FOR
COMBINATION ELECTRIC AND DIRECT VENT GAS FIREPLACE
1
NATURAL GAS MODEL
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS
GE38NT-M
GE38PT-M
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency
or the gas supplier.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.napoleonfireplaces.com • ask@napoleon.on.ca
W415-0429 / C / 11.04.05
2
PG 2-4 INTRODUCTION
Warranty General Instructions General Information Care of Glass & Plated Parts
5 - 11 VENTING
Venting Lengths Air Terminal Locations Typical Vent Installations Special Vent Installations Venting Application Flow Chart Venting Specifications
12
-
16 INSTALLATION
Wall and Ceiling Protection Using Flexible Vent Components Fireplace Vent Connection Using Rigid Vent Components Gas Installation Mobile Home Installation Framing Nailing Tabs Mantle Clearances & Enclosures
17-18 FINISHING
Door Removal & Installation Louvre Installation
TABLE of CONTENTS
Log Placement Charcoal Embers Glowing Embers Glowing Crystal Embers Logo Placement
19
20 20-21 OPERATION / MAINTENANCE
22 ELECTRICAL CONNECTION 23 ADJUSTMENTS
24-25 REPLACEMENTS
26-28 TROUBLE SHOOTING GUIDE
BLOWER REPLACEMENT FLAME EFFECT BULB REPLACEMENT EMBER BED BULB REPLACEMENT
Fireplace Operation Hand Held Remote Operation Operating Instructions Maintenance
Pilot Burner Adjustment Venturi Adjustment
Ordering Replacement Parts Replacement Parts Vent Kits Terminal Kits Accessories
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
WARNING
Do not burn wood or other materials in this fireplace.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room as the fireplace.
• Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
• Clothing or other flammable material should not be placed on or near the fireplace.
• Any safety screen or guard removed for servicing must be replaced prior to operating the fire­place.
• It is imperative that the control compartments, burners and circulating blower and its passage­way in the fireplace and venting system are kept clean. The fireplace and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The fire­place area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
• Under no circumstances should this fireplace be modified.
• This fireplace must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
• Do not operate the fireplace with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person. Use only with a glass door certified with the fireplace.
• Do not strike or slam shut the fireplace glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
W415-0429 / C / 11.04.05
NAPOLEON products are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certificate. NAPOLEON products are designed with superior components and materials, assembled by trained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test station. Once assembled the complete fireplace is thoroughly inspected by a qualified technician before packaging to ensure that you, the customer, receives the quality product that you expect from NAPOLEON.
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
3
The following materials and workmanship in your new The following materials and workmanship in your new
The following materials and workmanship in your new
The following materials and workmanship in your new The following materials and workmanship in your new
ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber,
ranted against defects for as long as you own the fireplace. This covers: combustion chamber,
ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-
heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-
heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break­age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-
age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-
age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi­num extrusion trims.num extrusion trims.
num extrusion trims.
num extrusion trims.num extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are
thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are
thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and covered and
covered and
covered and covered and the limited warranty. Light bulbs are not covered by this warranty.the limited warranty. Light bulbs are not covered by this warranty.
the limited warranty. Light bulbs are not covered by this warranty.
the limited warranty. Light bulbs are not covered by this warranty.the limited warranty. Light bulbs are not covered by this warranty.
Labour related to warranty repair is covered free of charge during the first year. RepairLabour related to warranty repair is covered free of charge during the first year. Repair
Labour related to warranty repair is covered free of charge during the first year. Repair
Labour related to warranty repair is covered free of charge during the first year. RepairLabour related to warranty repair is covered free of charge during the first year. Repair
work, however, requires the prior approval of an authorized company official. Labour costs towork, however, requires the prior approval of an authorized company official. Labour costs to
work, however, requires the prior approval of an authorized company official. Labour costs to
work, however, requires the prior approval of an authorized company official. Labour costs towork, however, requires the prior approval of an authorized company official. Labour costs to the account of the account of
the account of
the account of the account of must be done through an authorized must be done through an authorized
must be done through an authorized
must be done through an authorized must be done through an authorized
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
will provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year of
will provide replacement parts free of charge during the first year of
will provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year of
are based on a predetermined rate schedule and any repair work are based on a predetermined rate schedule and any repair work
are based on a predetermined rate schedule and any repair work
are based on a predetermined rate schedule and any repair work are based on a predetermined rate schedule and any repair work
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
dealer. dealer.
dealer.
dealer. dealer.
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
gas fireplace are war- gas fireplace are war-
gas fireplace are war-
gas fireplace are war- gas fireplace are war-
CONDITIONS AND LIMITATIONS
NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the
warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with
the product and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify
this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel
parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.
NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will
replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated
in accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President's Limited Lifetime Warranty, NAPOLEON may, at its discretion, fully discharge all obligations with respect to this warranty by refunding
to the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are
not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event
extend to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product,
its components or accessories are excluded.
NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD.
W415-0429 / C / 11.04.05
4
GENERAL INSTRUCTIONS
THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERV­ICED BY A QUALIFIED INSTALLER to conform with local codes.
Installation practices vary from region to region and it is important to know the specifics that apply to your area,
for example: in Massachusetts State:
• The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
• WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of
Massachusetts.
In absence of local codes, install the GE38 to the current National Fuel Gas Code, ANSI Z223.1, or the current CAN/ CGA B149, Installation Codes. Mobile home installation must conform with local codes. In the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA Z240 MH Series in Canada or the manufactured home construction and safety standard, Title 24 CFR, part 3280, or the Fire Safety Criteria for manu­factured home installations, Sites and Community Stand­ard ANSI/NFPA 501A in the United States.
The fireplace and its individual shutoff valve must be dis­connected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the fireplace is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth.
The junction box must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELEC­TRICAL CODE in Canada or the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the United States.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUAL­ITY! Maximum input is 26,000 BTU/hr for natural gas and
propane. When the fireplace is installed at elevations above 4,500ft, and in the absence of specific recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.
Maximum output for natural gas is 22,360 BTU/hr at an efficiency of 86% with the fan on, and 22,880 BTU/hr for propane at an efficiency of 88% with the fan on. The maxi­mum A.F.U.E. (annual fuel utilization efficiency) rating is 64% for natural gas and 65% for propane.
W415-0429 / C / 11.04.05
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 11 inches water column for propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for propane. Manifold pressure under flow conditions is 3.5 inches water column for natural gas and 10 inches water column for propane.
This fireplace is approved for bathroom, bedroom and bed­sitting room installations and is suitable for mobile home installation. The natural gas model can only be installed in a mobile home that is permanently positioned on its site and fueled with natural gas.
No external electricity (110 volts or 24 volts) is re­quired for the gas system operation.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean plated parts. Buff lightly with a clean dry cloth. The GE38 is factory equipped with ceramic glass for both the firebox front and back panels. The glass thickness is 3/16". Use only replacement glass available from your Napoleon dealer. DO NOT SUBSTITUTE MATERIALS. Clean the glass after the first 10 hours of opera­tion with a recommended gas fireplace glass cleaner. There­after clean as required. DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent discolouration and /
or blemishes may result.
Use only accessories designed for and listed with
your specific fireplace.
Provide adequate ventilation air. Provide adequate accessibility clearance for servicing and operating the fireplace. Never obstruct the front opening of the fireplace.
For safe and proper operation of the fireplace follow the venting instruction exactly.
Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning.
Provide a means for visually checking the vent con­nection to the fireplace after the fireplace is installed.
Vent lengths that pass through unheated spaces (at­tics, garages, crawl spaces) should be insulated with the insulation wrapped in a protective sleeve to minimize condensation.
Objects placed in front of the fireplace must be kept a minimum of 48" away from the front face of the unit.
VENTING
5
FIGURE 1
VENTING LENGTHS
Use only Wolf Steel or Simpson Dura-Vent Model DV-GS venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air termi­nal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, follow the installation procedure provided with the venting com­ponents.
When using Wolf Steel venting components, use only ap­proved Wolf Steel rigid / flexible components with the fol­lowing termination kits: WALL TERMINAL KIT GD222, or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT GD210, 8/12 TO 12/12 ROOF TERMINAL KIT GD211, FLAT ROOF TERMI- NAL KIT GD212 or PERISCOPE KIT GD201 (for wall pen- etration below grade). With flexible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD220 or the 10 foot vent kit GD230.
Wolf Steel rigid and flexible venting systems must not be combined.
Wolf Steel and Simpson Dura-Vent venting systems
must not be combined.
These vent kits allow for either horizontal or vertical venting of the fireplace. FIGURES 3a, & 5a. The maximum allow- able horizontal run is 20 feet. The maximum allowable ver­tical vent length is 40 feet. The maximum number of 4" vent connections is two horizontally or three vertically (exclud­ing the fireplace and the air terminal connections) when using aluminum flexible venting.
For optimum flame appearance and fireplace perform­ance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.
Purge all gas lines with the glass door of the fireplace open. Assure that a continuous gas flow is at the burner before closing the door.
Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition.
6" inches is the minimum bend radius allowed for the 7" diameter flexible liner.
For optimum performance it is recommended that all horizontal runs have a 1 inch rise per foot when using Napoleon flexible vent components.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two sin­gle family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" air gap all around between the inner liner and outer liner is required for safe operation. Use a firestop when pen­etrating interior walls, floor or ceiling.
Minimum clearance to combustible con­struction from fireplace and vent sur­faces:
fireplace framing - 0" to stand-offs (top, rear and sides) fireplace finishing - 0" to sides, 3" to top of unit vent pipe - 1 inch recessed depth - 17½" inches
Horizontal runs may have a 0 inch rise per foot in all cases using SIMPSON DURA-VENT or NAPOLEON RIGID OR FLEXIBLE venting components when vent­ing as illustrated in Figures 3, and 4.
Only a clearance to combustibles of 1" all around the vent pipe is required.
W415-0429 / C / 11.04.05
6
i
AIR TERMINAL INSTALLATIONS
FIGURE 2
INSTALLATIONS
CANADIAN U.S.A.
A
12 INCHES
12 INCHES
Clearance above grade, veranda porch, deck or balcony.
B
C
12 INCHES
12 INCHES*
9 INCHES
12 INCHES*
Clearance to windows or doors that open.
Clearance to permanently closed windows.
Vertical clearance to ventilated soffit located above the terminal within
D
18 INCHES**
12 INCHES**
E
F
0 INCHES
0 INCHES***
G
2 INCHES***
H
I
J
K
L
M
N
O
**
* Reco mme nded to preven t condensa tio n on windows and the rma l break age
** ****
** It is recommended t
**** ** *** *
** * The perisco pe G
** *** * ** * *** * *
** * * This is a reco
** * *** * * ††
Three feet above if wi thin 10 fe
†† ‡‡
A vent shall not terminate directl y above a sidewalk or paved driveway that is l
‡‡
† †† †
† † Permitted onl y if the veranda, porch, or deck is fully
† †† † † *† *
† * Recomm enc ed to prev ent recirculatio n of ex
† *† *
W415-0429 / C / 11.04.05
3 FEET
3 FEET
12 INCH
ES
6 FEET
7 FEET‡
12 INCHES††
16 INCHES
2 FEET†*
mmended distanc e. For additi onal require ments check local codes.
dwe llings and serves both dwellings.
18 INCHES**
12 INCHES**
0 INCHES
0 INCHES***
2 INCHES***
3 FEET***
3 FEET****
9 INCHES
3 FEET†
a horizontal distance of 2 feet from the centerline of the terminal.
Clearance to unventilated soffit.
Clearance to an outside corner wall.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to an inside combustible corner wall or protruding com­bustible obstructions ( vent chase, etc.).
Clearance to each side of the centerline extended above the meter
*
/ regulator assembly to a maximum vertical distance of 15ft.
Clearance to a service regulator vent outlet.
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
Clearance to a mechanical air supply inlet.
Clearance above a paved sidewalk or paved driveway located on
7 FEET****
12 INCHES****
16 INCHES
2 FEET†*
o use a heat shield and to maximize the distance to vinyl clad sof fits.
D-20 1 requ ires a mini mum 18 inches clearan ce from an ins ide cor ner.
et horizonta lly.
public property unless fitted with a heat shield kit GD-301.
Clearance under a veranda, porch, deck or balcony.
Clearance above the roof.
Clearance from an adjacent wall including neighbouring buildings.
open on a minimum of two sides beneath the floor.
haus t prod uct s. For addit ional req uirem ents check local cod es.
ocated between two single fam
TYPICAL VENT INSTALLATIONS
7"
For optimum performance, it is recommended that all horizontal runs have a 1 inch rise per foot.
When terminating vertically, the vertical rise is a minimum 36 inches and a maximum 40 feet from the centre of the fireplace flue outlet.
SPECIAL VENT INSTALLATIONS
PERISCOPE TERMINATION
7
FIGURES 3
40 FT MAX
3 FT MIN
Use the GD201 periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum of 12 inches above grade. The maximum allow­able vent length depends on the fireplace, as illustrated.
VENTING APPLICATION FLOW CHART
HORIZONTAL TERMINATION VERTICAL TERMINATION
vertical rise is equal to or greater than the horizontal run
vertical rise is less than horizontal run
vertical rise is equal to or greater than the horizontal run
FIGURE 4
vertical rise is less than horizontal run
horizontal run + ver­tical rise to maxi­mum of 40 feet
horizontal run + ver­tical rise to maxi­mum of 24.75 feet
4.2 times the verti­cal rise equal to or greater than the horizontal run
horizontal run + ver­tical rise to maxi­mum of 40 feet
horizontal run + ver­tical rise to maxi­mum of 40 feet
3 times the vertical rise equal to or greater than the horizontal run
W415-0429 / C / 11.04.05
8
DEFINITIONS
for the following symbols used in the venting calcula­tions and examples are:
> - greater than > - equal to or greater than < - less than < - equal to or less than HT- total of both horizontal vent lengths (HR) and offsets
) in feet
(H
H HO- offset factor: .03(total degrees of offset - 90°*) in
VT- combined vertical vent lengths in feet
O
- combined horizontal vent lengths in feet
R
feet
TOP EXIT / HORIZONTAL TERMINATION
when (HT) < (VT)
Simple venting configuration (only one 90° elbow)
FIGURE 5
ELBOW VENT LENGTH VALUES
feet inches
0.03 0.5 15° 0.45 6.0 30° 0.9 11.0 45° 1.35 16.0 90°* 2.7 32.0
* the first 90° offset has a zero value and is shown in the formula as -90°
For vent configurations requiring more than one 90° el­bow, the following formulas apply:
Formula 1: HT < V Formula 2: HT + VT < 40 feet
Example 1:
T
90°
H
2
See graph to determine the required vertical rise VT for the required horizontal run HT.
VERTICAL RISE IN FEET
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable values for HT and V
W415-0429 / C / 11.04.05
.
T
V
FIGURE 6
2
H
90°
V
1
V1=3 ft V2=8 ft VT= H1= 2.5 ft H2=2 ft HR= H1 + H2 = 2.5 + 2 = 4.5 ft HO=. HT= HR + HO = 4.5 + 5.4 = 9.9 ft
T
HT + VT = 9.9 + 11 = 20.9 ft
Formula 1: HT < V
Formula 2: HT + VT < 40 feet
Since both formulas are met, this vent configuration is ac­ceptable.
V1 +
V2 =
3 + 8 = 11 ft
03(three 90° elbows - 90°) = .03(270° - 90°) = 5.4 ft
9.9 < 11
20.9 < 40
T
90°
1
TOP EXIT / HORIZONTAL TERMINATION
when (Ht) > (Vt)
Simple venting configuration (only one 90° elbow)
See graph to determine the required ver­tical rise VT for the required horizontal run HT.
FIGURE 7
Example 3:
V
9
90°
V
H
H
4
2
3
H
1
H
90°
1
2
FIGURE 9
REQUIRED VERTICAL RISE IN INCHES
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
The shaded area within the lines represents acceptable values for HT and V
.
T
For vent configurations requiring more than one 90° elbow the following formulas apply:
Formula 1: HT < 4.2 V
T
Formula 2: HT + VT < 24.75 feet
H
Example 2:
V
1
1
90°
FIGURE 8
H
2
V
1
V
2
V
T
H
1
H
2
H
3
H
4
H
R
H
O
H
T
=4 ft = 1.5 ft = V1 + V2 = 4 + 1.5 = 5.5 ft =2 ft =1 ft =1 ft = 1.5 ft = H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1. 5 = 5.5 ft = .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft = HR + HO = 5.5 + 8.1 = 13.6 ft
HT + VT= 13.6 + 5.5 = 19.1 ft
Formula 1:HT < 4.2 V
T
4.2 VT = 4.2 x 5.5 = 23.1 ft
13.6 < 23.1
Formula 2:HT + VT < 24.75 feet
19.1 < 24.75
Since both formulas are met, this vent configuration is ac­ceptable.
V H H H H H
HT + VT=
Formula 1: HT < 4.2 V
= VT = 6 ft
1
=3 ft
1
=5 ft
2
= H1 + H2 = 3 + 5 = 8 ft
R
= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft
O
= HR + HO = 8 + 2.7 = 10.7 ft
T
10.7 + 6 =16.7
T
4.2 VT = 4.2 x 6 = 25.2 ft
10.7 < 25.2
Formula 2: HT + VT < 24.75 feet
16.7 < 24.75
Since both formulas are met, this vent configuration is ac­ceptable.
W415-0429 / C / 11.04.05