Napoleon Installation And Operating Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE.
INSTALLATION AND
EN
OPERATING INSTRUCTIONS
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: ANSI Z21.50 ● CSA 2.22 FOR VENTED GAS APPLIANCES.
CONFORMS TO AMERICAN NATIONAL STANDARDS: ANSI Z21.50, CERTIFIED TO CANADIAN CSA 2.22 FOR VENTED GAS FIREPLACES.
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
!
WARNING
If the information in these instructions are
not followed exactly, a fi re or explosion
may result causing property damage,
personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
Decorative Product: Not for use as a heating appliance.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this appliance
and shall be installed for the protection of children
and other at-risk individuals.
LV50N / LV50N2
NATURAL GAS
LV50P / LV50P2
PROPANE
SAFETY BARRIER
SEE-THRU ILLUSTRATED
!
DANGER
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
FR
PG
69
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
NOTE: The camera icon indicates video tutorials are available as additional reference, visit
http://www.napoleonfi replaces.com/category/product-support/support-centre/
3.1 VENTING LENGTHS AND COMPONENTS FOR DIRECT VENT INSTALLATIONS 9
3.2 TYPICAL VENT INSTALLATIONS 10
3.3 SPECIAL VENT INSTALLATION 11
3.3.1 PERISCOPE TERMINATION 11
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES 12
3.5 VENT APPLICATION FLOW CHART 13
3.6 DEFINITIONS 13
3.7 ELBOW VENT LENGTH VALUES 13
3.8 HORIZONTAL TERMINATION 14
3.9 VERTICAL TERMINATION 16
4.1 WALL AND CEILING PROTECTION 18
4.1.1 HORIZONTAL INSTALLATION 19
4.1.2 VERTICAL INSTALLATION 19
4.2 USING FLEXIBLE VENT COMPONENTS 20
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 20
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 21
4.2.3 APPLIANCE VENT CONNECTION 22
4.3 MOBILE HOME INSTALLATION 22
4.4 GAS INSTALLATION 23
5.1 TWO SIDED APPLIANCE 26
5.2 ONE SIDE APPLIANCE 28
5.3 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 30
5.4 VENTILATION OPENINGS AND ENCLOSURE CLEARANCES 32
5.5 INSTALLING NON-COMBUSTIBLE BOARD 33
5.6 RECESSED INSTALLATION 35
5.7 MINIMUM COMBUSTIBLE MANTEL CLEARANCES 36
6.1 SAFETY SCREEN INSTALLATION / REMOVAL 38
6.2 DOOR INSTALLATION / REMOVAL 39
6.3 GLASS MEDIA INSTALLATION 40
6.4 OPTIONAL ROCK / DRIFTWOOD PLACEMENT 41
6.5 LOGO PLACEMENT 41
7.1 HARD WIRING CONNECTION 42
7.2 RECEPTACLE WIRING DIAGRAM 43
7.3 REMOTE RECEIVER INSTALLATION 43
7.4 SCHEMATIC 44
8.1 GENERAL TRANSMITTER LAYOUT 45
8.4 INITIALIZING THE TRANSMITTER/BATTERY HOLDER FOR THE FIRST TIME 46
8.2 TEMPERATURE DISPLAY 46
8.3 FLAME HEIGHT 46
8.5 LED ON/OFF LIGHT CONTROL 47
8.6 CONTINUOUS PILOT / INTERMITTENT PILOT (CPI / IPI) SELECTION 48
8.7 CHILD PROOF FUNCTION 48
8.8 LOW BATTERY / MANUAL BYPASS 48
8.9 IN THE EVENT OF A POWER FAILURE 48
8.10 TIMED BLOWER 49
10.1 RESTRICTING VERTICAL VENTS 50
10.2 PILOT BURNER ADJUSTMENT 50
10.3 VENTURI ADJUSTMENT 51
10.4 FLAME CHARACTERISTICS 51
11.1 ANNUAL MAINTENANCE 53
11.2 CONTROL ACCESS 53
11.3 VALVE REMOVAL 54
11.4 BURNER REMOVAL 55
11.5 CONTROL MODULE REMOVAL 55
11.6 LED REPLACEMENT 56
11.7 GLASS / DOOR REPLACEMENT 57
11.8 CARE OF GLASS 57
11.9 CARE OF PLATED PARTS 57
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
TABLE OF CONTENTS
1.0 INSTALLATION OVERVIEW
3
See the section
“FRAMING MINIMUM
MANTEL
CLEARANCES”
See the section
“FRAMING MINIMUM CLEARANCE TO
COMBUSTIBLE
ENCLOSURES” for
drywall (or other
combustible
material)”
See the section
“FRAMING”
See the section
“RATING PLATE / LIGHTING
INSTRUCTION LOCATION”
Side
Wall
See the section
“ANTI CONDENSATION
CONTROL SWITCH”
EN
See the section
“VENTING - VENTING
LENGTHS AND AIR TERMINAL
LOCATIONS”
SAFETY BARRIER
See the section
“FRAMING MINIMUM
CLEARANCE
TO COMBUSTIBLE
ENSLOSURES”
for noncombustible
materials such
as tile, marble,
granite, etc.
Important: Extra
support may be
required
See the section
“CONTROL ACCESS”
for the control box.
See the section
“REMOTE
RECEIVER
INSTALLATION”.
NOTE: A ventilated
enclosure is required.
See “VENTILATION
OPENINGS” section
W415-1439 / A / 07.10.15
4
2.0 INTRODUCTION
EN
EN
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES OR ALTERATIONS TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND IS
PROHIBITED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance
according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may
be sharp.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier
is recommended if there are at risk individuals in the house. To restrict access to an appliance, install an
adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and
away from hot surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and
draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot
surfaces. These screens and guards must be fastened to the fl oor.
• Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating
the appliance.
• The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance
• It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance
and venting system are kept clean. The appliance and its venting system should be inspected before use and at
least annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials,
gasoline and other fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect
the appliance and to replace any part of the control system and any gas control which has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be
done by a licensed or qualifi ed service person.
• Do not strike or slam shut the appliance glass door.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent
exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping
through these openings can also cause the surrounding combustible materials to overheat and catch fi re.
• Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic
bags, these are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well
as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon
Monoxide.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance.
Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage of
decorations, a T.V. or other electronic components.
• A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and
shall be installed.
• If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
• Installation and repair should be done by a qualifi ed service person. The appliance should be inspected
before use and at least annually by a professional service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments,
burners and circulating air passageways of the appliance be kept clean.
!
WARNING
3.2C
W415-1439 / A / 07.10.15
2.1 DIMENSIONS
5
FRONT VIEW
SAFETY BARRIER
TOP VIEW
66 13/16"
1698mm
SIDE VIEW
EN
52 5/16"
1329mm
17 1/4"
438mm
1270mm
50"
SEE-THRU
FRONT VIEW
SAFETY BARRIER
TOP VIEW
52 5/16"
1329mm
SIDE VIEW
50"
1270mm
22 13/16"
579mm
66 13/16"
1698mm
SINGLE SIDED
W415-1439 / A / 07.10.15
6
A
A
2.2 GENERAL INSTRUCTIONS
EN
EN
!
WARNING
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUA TE VENTILA TION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” (1219mm) FROM
THE FRONT FACE OF THE APPLIANCE.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35 mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth
of Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of an appliance
insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches (914mm).
• A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed in
accordance with the current standard CAN/CSA Z240MH
Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location
for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1B
W415-1439 / A / 07.10.15
2.3 GENERAL INFORMATION
FOR YOUR SA TISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERA TION AND
QUALITY!
LV50N LV50N2
Altitude (FT)0-4,5000-45000-4,5000-4500
Max. Input (BTU/HR)40,00040,00040,00040,000
Min. Input (BTU/HR)26,00032,00026,00032,000
P449%49%54%54%
7
EN
NGLPNGLP
Min. Inlet Gas Supply
Pressure
Max. Inlet Gas Supply
Pressure
Manifold Pressure (Under
Flow Conditions)
When the appliance is installed at elevations above 4,500ft (1372m), and in the absence of specifi c recommendations
from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for
each additional 1,000ft (305m). Expansion / contraction noises during heating up and cooling down cycles are
normal and are to be expected. Change in fl ame appearance from “HI” to “LO” is more evident in natural gas
than in propane.
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is certifi ed for mobile
home installation.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certifi ed kit is used.
There are two switches that control the function of the appliance. One on the receiver that must be placed
in the middle position. The other is on the control module that must be in the “I” position, which denotes
on. If these switches aren’t in these locations the appliance will not work, see “REMOTE RECEIVER
INSTALLATION” and “CONTROL MODULE” section.
NOTE: The protective wrap on plated parts is best removed when the assembly is at room temperature
but this can be improved if the assembly is warmed, using a hair dryer or similar heat source.
This appliance is equipped with a remote control system, which requires batteries to be installed. The
transmitter takes 3 “AAA” batteries and in the case of a power failure the receiver takes 4 “AA” batteries.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the
appliance and must be installed.
W415-1439 / A / 07.10.15
8
40MH SERIES GAS EQUIPPED MOBILE HOMES,0MH SERIES GAS EQUIPPED MOBILE HOMES
PART 3280. WHEN THIS US STANDARD IS NOTART 3280. WHEN THIS US STANDARD IS NOT
INSTALLATION CODES.ON CODES.
FOR USE WITH BARRIER W565-01USE WITH BARRIER W565
FOYFO
9700
40
LV50N LV50N
CLV
0-4500FT (00-4500F
404
0" RECESSED0" RECESSED
0" RECESSE
5 INCHES W.C. (NG)
COLO
)COLONNE D'EA
4.5" W.C.(NG) 4.5" W
4.5" D'UNE4
COLONNE D'EAU (GN)COLONNE D'EAU (GN)
AX. SUPPLY PRESSURE:
X. SUPPLY PRESSURE:
) 7" W.C. (NG)
7" D'UNE
COLO
)COLONNE D'EAU (GN)
W
RACKED
EMENT OF
D BE DONE
A
L
ver
lisé uniquemen
qués sur la plaque
allé dans une
uée (É.-U. seulement) ou
le permettent.
V
oir la notice de
eur pour plusde renseignements. Une
appareil.»
VOT
AS ENTREPOSER NI UTILISER
ENCE NI D’AUTRES
V
APEURS
QUIDES INFLAMMABLES
E VOISINAGE DE CET
OU DETAU
AREIL.
TISSE
ILISER
ANNEAU FRO
AS EN
2.4 RATING PLATE / LIGHTING INSTRUCTION LOCATION
EN
EN
!
WARNING
ALLOW THE APPLIANCE TO COOL BEFORE PERFORMING ANY MAINTENANCE OR CLEANING.
Both the rating plate and lighting instructions are attached to a key chain located on the left side of the control
area near the valve. Remove the front to gain access to the control area, refer to the “SAFETY SCREEN
INSTALLATION / REMOVAL” section for detailed removal instructions.
To replace, slide the instructions back into the control area and reinstall the safety screen assembly.
KEEP BURNER AND CONTROL
COMPARTMENT CLEAN. SEE
INSTALLATION AND OPERA TING
INSTRUCTIONS MANUAL.
APPLIANCE NEEDS FRESH
AIR FOR SAFE OPERATION
AND MUST BE INSTALLED
WITH ADEQUATE PROVISIONS
FOR COMBUSTION
AND VENTILATION AIR.
GARDEZ LE BRULEUR ET LE
COMPARTIMENT DES
CONTROLES PROPRES.
CONSULTEZ LE MANUEL
D’INFORMATION ET
D’INSTALLATION. PAR
MESURE DE SECURITE.
CET APPAREIL DOIT
ETRE ALIMENTE EN AIR
FRAIS ET AVEC SUFFISANT
D’AIR COMBURANTET
DE VENTILATION.
WARNING:
IMPROPER INSTALLATION,
ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE
CAN CAUSE PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF
LIFE. REFER TO OWNER’S
MANUAL. INSTALLATION AND
SERVICE MUST BE PERFORMED
BY A QUALIFIED INSTALLER,
SERVICE AGENCY OR THE
GAS SUPPLIER.
ATTENTION:
UN INSTALLATION OU UNE
MODIFICATION INAPPROPRIEE
DU REGLAGE, DU SERVICE ET DE
L’ENTRETIEN POURRAIENT ETRE
LA CAUSE DE DOMMAGES A LA
PROPRIETE DE BLESSURES
CORPORELLES OU MEME LA
MORT. CONSULTER LE MANUEL
D’INFORMATION, L’INSTALLATION
ET LE SERVICE DOIVENT
ETRE EXECUTES PAR UN
INSTALLATEUR QUALIFIE POUR
LE AZ, UNE ENTREPRISE DE
SERVICE OU LE FOURNISSEUR
DE GAZ SEULEMENT.
CAUTION:
HOT WHILE OPERATING. DO NOT TOUCH.
KEEP CHILDREN, CLOTHING, FURNITURE,
GASOLINE OR OTHER FLAMMABLE VAPORS
AWAY.
AVERTISSEMENT:
L’APPAREIL EST CHAUD PENDANT SON
FONCTIONNEMENT. LES ENFANTS, LES
VETEMENTS, LES MEUBLES, L’ESSENCE ET
AUTRES LIQUIDES QUI EMETTENT DES GAZ
VOLATILS INFLAMMABLES DOIVENT
ETRE TENUS ELOIGNES DE L’APPAREIL.
“This appliance is only for use with the type(s)
of gas indicated on the rating plate and may
be installed in an aftermarket, permanently
located, manufactured home (USA only) or
mobile home, where not prohibited by local
codes. See owner’s manual for details. This
appliance is supplied with a conversion kit.”
«Cet appareil doit être utilisé uniquement
avec les types de gaz indiqués sur la plaque
signalétique et peut être installé dans une
maison préfabriquée (É.-U. seulement) ou
mobile installée à demeure si les règlements
locaux le permettent. Voir la notice de
l’utilisateur pour plus de renseignements. Une
trousse de conversion est fournie avec cet
appareil.»
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE
OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN VICINITY OF THIS
OR ANY OTHER APPLIANCE.
CAUTION: DO NOT OPERATE
THE FIREPLACE WITH THE GLASS
REMOVED, CRACKED OR BROKEN.
REPLACEMENT OF THE GLASS
SHOULD BE DONE BYALICENSED
OR QUALIFIED PERSON.
POUR VOTRE
SECURITE:
NE PAS ENTREPOSER NI UTILISER
D’ESSENCE NI D’AUTRES VAPEURS
OU LIQUIDES INFLAMMABLES
ANS LE VOISINAGE DE CET
APPAREIL OU DE TOUT AUTRE
APPAREIL.
AVERTISSEMENT: NE PAS
UTILISER L’APPAREIL SI LE
PANNEAU FRONTAL EN VERRE
N’EST PAS EN PLACE, EST CRAQUÉ
OU BRISÉ. CONFIEZ LE
REMPLACEMENT DU
PANNEAU À UN
TECHNICIEN
AGRÉÉ.
ATION IF INSTALLED IN ACCORDANCE WITH THE
IO. APPROPRIÉ POUR INSTALLATION DANS UNE
UN COMBUSTIBLE SOLIDE NE
S, SITES AND COMMUNITIES, ANSI / NFPA 501A.
N VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA
LES COMMUNAUTÉS, ANSI/NFPA 501A.
- 2008 VENTED GAS FIREPLACE HEATER / APPAREIL DE CHAUFFAGE ALIMENTÉ
b
MODEL PROPANE
- 2008, ANSI Z21.88
b
GAZ NATURAL
MODEL NATURAL GAS /
VENTED GAS FIREPLACE HEATER. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALL
CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR,
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.33
PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATION
AU GAZ ET VENTILÉ
FOYER DE CHAUFFAGE AU GAZ AVEC ÉVACUATION. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE SALLE DE BAIN ET UN STUD
MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE MAISONS MOBILES ÉQUIPÉES AU GAZ, E
NORME DE SECURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE APPLIQUÉE, SE RÉFÉRER A LA NORME
RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES SITES ET
W/N 16131
REFERENCE #
NOT FOR USE WITH
SOLID FUEL. FOR USE
DOIT PAS ÊTRÉ UTILISÉ AVEC
LHD50PT
WITH GLASS DOORS
CET APPAREIL. UTILISER AVEC
LES PORTES VITRÉES
HOMOLOGUÉES SEULEMENT
AVEC CETTE UNITÉ.
0-4500FT (0-1370M)
30,000 BTU/H
ALTITUDE /ÉLÉVATION
INPUT / ALIMENTATION
REDUCED INPUT / ALIMENTATION RÉDUITE
30,000 BTU/H
23,000 BTU/H
0-4500FT (0-1370M)
LHD50NT
DO NOT ADD ANY MATERIAL
:
CERTIFIED WITH THIS
UNIT ONLY.
WARNING
TO THE APPLIANCE, WHICH WILL COME
AVERTISSEMENT:
23,000 BTU/H#53
ORIFICE / INJECTEUR
#38
3.5" WATER COLUMN/D'UNE COLONNE D'EAU
IN CONTACT WITH THE FLAMES, OTHER
THAN THAT SUPPLIED BY THE
N'AJOUTEZ PAS A
CET APPAREIL AUCUN MATÉRIAU DEVANT
ENTRER EN CONTACT AVEC LES FLAMMES
10" WATER COLUMN/D'UNE COLONNE D'EAU
MANIFOLD PRESSURE /
PRESSION AU COLLECTEUR
4.5" WATER COLUMN/D'UNE COLONNE D'EAU
MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO
AUTRE QUE CELUI QUI EST FOURNI AVEC
CET APPAREIL PAR LE FABRICANT.
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE
MAXIMUM SUPPLY PRESSURE /
PRESSION D'ALIMENTATION MAXIMALE
7.0" WATER COLUMN/D'UNE COLONNE D'EAU
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE
FLOOR 0”
RECESSED DEPTH ONE SIDED 23"
RECESSED DEPTH SEE THRU 13.5”
FRAMING (NOT INCLUDING
DIRECT VENT, VENTED GAS FIREPLACES. APPROVED FOR BEDROOM, BA THROOM AND BED-SITTING
ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE
WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES,
IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND
SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME
INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. THIS APPLIANCE MUST BE
INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THE CURRENT
ANSI Z223.1, OR CSA B149, INSTALLATION CODES. FOR USE WITH BARRIER W565-0198.
FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG)
W385-2007
PLANCHER 0”
ÉVENT 2"
CÔTES 0”
MANTEAU 15" *
ARRIÉRE 0”
CLASSIFICATION: 115V 0.82AMP, 60HZ
D'ÉVACUATION PROPRE A NAPOLEON. RÉFÉRER AU MANUEL
D'INSTALLATION DE PROPRIÉTAIRE POUR L'ÉVACUATION
PRÉCISE. IL EST IMPORTANT DE BIEN RÉINSTALLER ET
RESCELLER L'ÉVENT APRÈS AVOIR ASSURÉ LE MAINTIEN DU
SYSTÉME DE PRISE D'AIR.
DESSUS, COTÉS & ARRIÈRE: SELON LES ESPACEURS DE DÉGAGEMENT POUR LES MATÉRIAUX D'OSSATURE
SELON LE MANUELDE PROPRIÉTAIRE POUR LES MATÉRIAUX DE FINITION.
* L'EXTENSION HORIZONTALE MAXIMALE: 2". RÉFÉRER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS
PLUS GRANDES. RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE.
LV50
INTAKE SYSTEM.
SERIAL NUMBER/NO. DE SÉRIE:
FOR VENTING SPECIFICS. PROPER REINSTALLATIONAND
NAPOLEON VENT KITS. SEE OWNERS INSTALLATION MANUAL
RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR
FACE MATERIAL)
ELECTRICAL RATING: 115V 0.82AMP, 60HZ
SIDES 0”
MADE IN CANADA / FABRIQUÉ AU CANADA
VENT 2"
BACK 0”
MANTLE 15" *
TOP, SIDES & BACK: PER STAND OFF SPACERS FOR FRAMING MATERIALS. FOR FINISHING MATERIALS
SEE OWNERS MANUAL
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION
HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS.
WOLF STEEL LTD. BARRIE, ONTARIO, CANADA
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
PRESSION AU COLLECTEUR: 3.5" D'UNE
PRESSION D'ALIMENTATION MIN: 4.5" D'UNE
PRESSION D'ALIMENTATION MAX: 7" D'UNE
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS
DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES,
OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS / DÉGAGEMENTS MINIMAUX DES MATÉRIAUX COMBUSTIBLES:
TOP/ DESSUS 0" RECESSED DEPTH ONE SIDED/ PROFONDEUR D'ENCASTRE UNE FACE 22.5"
FLOOR / PLANCHER 0" RECESSED DEPTH SEE THRU/ PROFONDEUR D'ENCASTRE TRAVERS 17.25"
FRAMING (NOT INCLUDING FACE MATERIAL) / OSSATURE (MATÉRIAU DE FAÇON NON COMPRIS)
SIDES / CÔTÉS 0" BACK / ARRIÈRE 0"
VENT TOP / DESSUS DU CONDUIT D’ÉVENT 3"
VENT SIDES & BOTTOM / CÔTÉS ET DESSOUS DU CONDUIT D'ÉVENT 2"
VERTICAL VENT / CONDUIT D’ÉVENT VERTICAL 1"
MANTLE / TABLETTE 18" *
TOP, SIDES & BACK: PER STAND OFF SPACERS FOR FRAMING MATERIALS. FOR FINISHING MATERIALS
SEE OWNERS MANUAL
DESSUS, COTÉS & ARRIÈRE: SELON LES ESPACEURS DE DÉGAGEMENT POUR LES MATÉRIAUX D'OSSATURE SELON LA
MANUEL DE PROPRIÉTAIRE POUR LESMATÉRIAUX DE FINITION.
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
3.5" D'UNE
9700539 (WSL) 4001657 (NGZ)
COLONNE D'EAU(GN)
NNE D'EAU(GN
4001658 (NAC) 4001659 (WUSA)
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
LV50N CLV50N MODEL CLV50P LV50P
40,000 BTU/h INPUT / ALIMENTATION 40,000 BTU/h
MAX. SUPPLY PRESSURE: 7" W.C. (NG)
COLONNE D'EAU (GN)
7" W.C. (NG
7" D'UNE
NNE D'EAU (GN
COLONNE D'EAU (GN)
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION MANUAL
FOR GREATER EXTENSIONS. RÉFÉRER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES.
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR LES LONGUEURS D'EVACUATION MINIMALE
ET MAXIMALE.
FOYER À GAZ VENTILÉ. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE
SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI
SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE
MAISONS MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA
NORME DE SECURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24
CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE
APPLIQUÉE, SE RÉFÉRER A LA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ
CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES
SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A. CODES. INSTALLER L’APPAREIL SELON LES
CODES OU RÈGLEMENTS LOCAUX, OU EN L’ABSENCE DE TELS RÈGLEMENTS, SELON LES
CODES D’INSTALLATION ANSI Z223.1 OU CSA-B149 EN VIGUER.
W565-0198
. SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE
BARRIÈRE
32,000 BTU/h
P4
UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ
AVEC CET APPAREIL. UTILISER AVEC LES PORTES
VITRÉES HOMOLOGUÉES SEULEMENT AVEC CETTE UNITÉ.
AVERTISSEMENT:N’AJOUTEZ PAS A CET APPAREIL AUCUN MATÉRIAU DEVANT ENTRER EN CONTACT
AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE NAPOLEON VENT KITS. SEE OWNERS INSTALLATION
MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS NECESSARY AFTER SERVICING THE
VENT-AIR INTAKE SYSTEM. /
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'ÉVACUATION PROPRE A NAPOLEON. RÉFÉRER AU
MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR L'ÉVACUATION PRÉCISE. IL EST IMPORTANT DE BIEN RÉINSTALLER
ET RESCELLER L'ÉVENT APRES AVOIR ASSURÉ LE MAINTIEN DU SYSTÉME DE PRISE D'AIR.
ELECTRICAL RATING: 115V, 60HZ. LESS THAN 12 AMPERES
SPÉCIFICATIONS ÉLECTRIQUES: 115V, 60HZ. MOINS DE 12 AMPÈRE
DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE
PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPAREIL DE CHAUFFAGE
49%49%
SERIAL NUMBER/NO. DE SÉRIE: LV50
POUR UNE UTILISER AVEC
MANUEL D'INSTALLATION.
MANIFOLD PRESSURE: 10 INCHES W.C.(LP)
PRESSION AU COLLECTEUR: 10" D'UNE
COLONNE D'EAU (P)
MIN SUPPLY PRESSURE: 11" W.C. (LP)
PRESSION D'ALIMENTATION MIN: 11" D'UNE
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to
the model, venting and gas type of the appliance.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate
information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
W415-1439 / A / 07.10.15
3.0 VENTING
9
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0067 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5” (127mm) EXHAUST / 8” (203.2mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.2C
EN
3.1 VENTING LENGTHS AND COMPONENTS FOR DIRECT VENT INSTALLATIONS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab
venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations,
and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson
Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure
provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the
corresponding supplier:
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a
red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent
pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar
which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following
-
W415-1439 / A / 07.10.15
EN
p
EN
10
kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With fl exible venting,
in conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD420 or the 10 foot (3.1m) vent kit
GD430.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a
minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must
not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent
connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when
using fl exible venting.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is recommended
that all horizontal runs have a minimum 1/4” (6.4mm) rise per foot/meter using fl exible venting. For safe and proper
operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family
dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼”
(31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
8.3_1A
3.2 TYPICAL VENT INSTALLATIONS
40" (1016MM)
MAXIMUM
32 1/4" (819MM)
MINIMUM
16" (406MM)
MINIMUM
40 FT (12M)
MAXIMUM
3 FT (1M)
MINIMUM
33"
(838MM)
* See “VENTING” section.
W415-1439 / A / 07.10.15
65 1/4"
(1657MM)
MINIMUM
PLUS
RISE*
33"
(838MM)
3.3 SPECIAL VENT INSTALLATION
11
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum 12” (305m) above grade. The maximum allowable vent length is 10’ (3m)
for a fi replace and 8’ (2m) for a stove.
EN
12"
(305MM)
MIN TO
GRADE
32 1/4" (819MM)
MINIMUM
33"
(838MM)
9.1B
W415-1439 / A / 07.10.15
EN
12
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES
EN
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
Q
= 3 feet
MIN
(0.9m)
R
= 2 x
MAX
Q
ACTUAL
INSTALLATIONS
CANADAU.S.A.
A12” (305mm)12” (305mm)Clearance above grade, veranda porch, deck or balcony.
B12” (305mm)
Δ
9”
(229mm)
Clearance to windows or doors that open.
Δ
C12” (305mm)* 12” (305mm) * Clearance to permanently closed windows.
D
18”
(457mm)**
18” (457mm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
E12” (305mm)** 12” (305mm)** Clearance to unventilated soffi t.
F0” (0mm)0” (0mm)Clearance to an outside corner wall.
0” (0mm)***
G
2” (51mm)***
0”
(0mm)***
2”
(51mm)***
H3’(0.9m)3’ (0.9m)****
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney,
etc.).
Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase,
etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a
maximum vertical distance of 15’ (4.6m).
I3’ (0.9m)3’ (0.9m)****Clearance to a service regulator vent outlet.
J12” (305mm)9” (229mm)
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other
appliance.
K6’ (1.8m)3’ (0.9m) †Clearance to a mechanical air supply inlet.
L7’ (2.1m) ‡7’ (2.1m) ****Clearance above a paved sidewalk or paved driveway located on public property.
M
12”
(305mm)††
12”
(305mm)****
Clearance under a veranda, porch or deck.
N16” (406mm)16” (406mm)Clearance above the roof.
O2’ (0.6m)†*2’ (0.6m) †*Clearance from an adjacent wall including neighbouring buildings.
P8’ (2.4m)8’(2.4m)Roof must be non-combustible without openings.
Q3’ (0.9m)3’ (0.9m)See chart for wider wall dimensions.
R6’ (1.8m)6’ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
S12” (305mm)12” (305mm)Clearance under a covered balcony
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18 inches clearance from an inside corner.
****This is a recommended distance. For additional requirements check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††*Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
12.1D
R
MAX
IHHW
(4.6m)
W415-1439 / A / 07.10.15
3.5 VENT APPLICATION FLOW CHART
13
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
HR - combined horizontal vent lengths in feet
HO - offset factor: .03 (total degrees of offset - 90°*) in feet
VT - combined vertical vent lengths in feet
Formula 1: HT < 3V
3VT = 3FT (0.9m) x 4.5FT (1.4m) = 13.5FT (4.1m)
T
16.1FT (4.9m) > 13.5FT (4.1m)Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + VT < 40 feet (12.2m)
20.6FT (6.3m) < 40 (12.2m)
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration will
need to be established to satisfy both formulas.
18.1_2B
T
EN
30
W415-1439 / A / 07.10.15
EN
18
4.0 INSTALLATION
EN
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
!
WARNING
THE GAS AND ELECTRICAL SUPPLY.
EXACTLY.
WHICH MUST BE SEALED USING MILL PAC.
ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2B
4.1 WALL AND CEILING PROTECTION
!
WARNING
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
70.1
For optimum performance it is recommended that all horizontal runs have a minimum of 1/4" (6mm) rise per
foot using fl exible venting. For safe and proper operation of the appliance, follow the venting instructions
exactly.
W415-1439 / A / 07.10.15
4.1.1 HORIZONTAL INSTALLATION
19
!
WARNING
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall.
Having determined the correct height for the air terminal
location, cut and frame a hole in the exterior wall as
illustrated to accommodate the fi restop assembly.
Dry fi t the fi restop assembly before proceeding to
ensure the brackets on the rear surface fi t to the
inside surface of the horizontal framing.
The length of the vent shield may be cut shorter
for combustible walls that are less than 8 1/2”
(215.9mm) thick but the vent shield must extend
the full depth of the combustible wall.
A. Apply a bead of caulking (not supplied) around the corner edge of
the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your
manual baggie).
B. Once the vent pipe is installed in its fi nal position, apply high temperature sealant W573-0007 (not supplied) between the pipe and the fi restop.
CAULKING
FIRESTOP
SPACER
VENT
SHIELD
DETERMINE
THE
CORRECT
HEIGHT
FINISHING
MATERIAL
20.2A
EN
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor.
See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1" (25mm)
clearance between the vent pipe and any combustible material. Try to
center the vent pipe location midway between two joists to prevent
having to cut them. Use a plumb bob to line up the center of the
openings. A vent pipe shield will prevent any materials such as
insulation, from fi lling up the 1" (25mm) air space around the pipe.
Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf Steel
vent pipe shield plate or equivalent (in the case of a fi nished ceiling), and secure
over the opening in the ceiling. A fi restop must be placed on the bottom of each
framed opening in a roof or ceiling that the venting system passes through.
Apply a bead of caulking all around and place a fi restop spacer over the vent
shield to restrict cold air from being drawn into the room or around the fi replace. Ensure
that both spacer and shield maintain the required clearance to combustibles. Once the
vent pipe is installed in its fi nal position, apply sealant between the pipe and the fi restop
assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1" (25mm)
air space around the pipe.
10 3/4"
(273mm)
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
SHIELD
21.1A
W415-1439 / A / 07.10.15
10 3/4"
(273mm)
CAULKING
VENT
PIPE
COLLAR
VENT
PIPE
EN
20
4.2 USING FLEXIBLE VENT COMPONENTS
EN
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
For safe and proper operation of the appliance, follow the venting
instructions exactly.
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high
ELBOW
SPACERS
temperature sealant W573-0002 (not supplied) or the high temperature
sealant W573-0007 Mill Pac (not supplied). However, the high temperature
sealant W573-0007 Mill Pac (not supplied) must be used on the joint
connecting the inner fl ex pipe and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
!
WARNING
“Wolf Steel Approved Venting” as identifi ed
by the stamp only on the outer fl ex pipe.
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION
A.Stretch the inner fl ex pipe to the required
length needed for the fi nished wall surface.
Apply a heavy bead of high temperature
sealant W573-0007 Mill Pac (not supplied) to
the inner sleeve of the air terminal. Slip the
vent pipe a minimum of 2” (50.8mm) over the
inner sleeve of the air terminal and secure
with 3 #8 screws.
B.Using the outer fl ex pipe, slide over the outer
combustion air sleeve of the air terminal
and secure with 3 #8 screws. Seal using
high temperature sealant W573-0002 (not
supplied).
C.Insert the vent pipes through the fi restop
maintaining the required clearance to
combustibles. Holding the air terminal (lettering
in an upright, readable position), secure to the
exterior wall and make weather tight by sealing
with caulking (not supplied).
#10x2"
SCREWS
HI-TEMP
SEALANT
22.1
OUTER FLEX
PIPE
CAULKING
INNER FLEX
PIPE
2" (50.8mm) OVERLAP
HI-TEMP
SEALANT
#8 X 1/2” SELF DRILLING
SCREWS
INNER COUPLER
OUTER COUPLER
D.If more vent pipe needs to be used to
reach the fi replace, couple them together
as illustrated. The vent system must be
supported approximately every 3 feet (0.9mm)
for both vertical and horizontal runs. Use
noncombustible strapping to maintain the
minimum 1” (25.4mm) clearance to combustibles.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth
of its return fl ange.
W415-1439 / A / 07.10.15
OUTER
FLEX PIPE
OUTER
FLEX PIPE
INNER
FLEX PIPE
23.3B
4.2.2 VERTICAL AIR TERMINAL INSTALLATION
21
!
WARNING
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
A.Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately
supported using either an alternate method suitable to the authority
having jurisdiction or the optional roof support.
B.Stretch the inner fl ex pipe to the required length. Slip the
inner fl ex pipe a minimum of 2” (51mm) over the inner pipe
of the air terminal connector and secure with 3 #8 screws.
Seal using a heavy bead of high temperature sealant
W573-0007 (not supplied).
C.Repeat using the outer fl ex pipe, using a heavy bead of
high temperature sealant W573-0002 (not supplied).
D.Thread the air terminal connector / vent pipe assembly down through
the roof. The air terminal must be positioned vertically and plumb.
Attach the air terminal connector to the roof support, ensuring that the
top of the air terminal is 16” (406mm) above the highest point that it
penetrates the roof.
E.Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” (19mm) of the air terminal connector showing
above the top of the fl ashing. Slide the fl ashing underneath the
sides and upper edge of the shingles. Ensure that the air terminal
connector is properly centred within the fl ashing, giving a 3/4”
(19mm) margin all around. Fasten to the roof. Do not nail through
the lower portion of the fl ashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and top edges of the
fl ashing with roofi ng material.
F.Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure
the vent pipe goes into the hole in the terminal. Secure with
the three screws provided.
G.Apply a heavy bead of weatherproof caulking 2” (51mm) above
the fl ashing. Install the storm collar around the air terminal and
slide down to the caulking. Tighten to ensure that a weathertight seal between the air terminal and the collar is achieved.
ROOF SUPPORT
AIR
TERMINAL
CONNECTOR
2” (51mm)
INNER PIPE
HIGH
TEMPERATURE
SEALANT
INNER FLEX PIPE
OUTER FLEX PIPE
AIR I NL ET
BASE
CAULKING
STORM COLLAR
WEA THER
SEALANT
FLASHING
EN
H.If more vent pipe needs to be used to reach the appliance see “HORIZONTAL
AIR TERMINAL INSTALLATION” section.
24.1A
W415-1439 / A / 07.10.15
22
A
4.2.3 APPLIANCE VENT CONNECTION
EN
A. Install the inner exhaust fl ue collar to the appliance. Secure
EN
B. Install the outer fl ex pipe to the appliance. Attach and seal the
with 3 screws. Seal the joint and screw holes using the high
temperature sealant Mill-Pac W573-0007 (not supplied).
joints using a high temperature sealant.
4.3 MOBILE HOME INSTALLATION
This appliance is also certifi ed to be installed as an OEM (Original Equipment Manufacturer) installation
in a manufactured home (U.S. only) or mobile home and must be installed in accordance with the
manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR,
Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This
appliance is only for use with the type(s) of gas indicated on the rating plate.
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit. Built
in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the
base. Use #10 hex head screws, inserted through the holes in the base to secure. For free standing products
contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the
appliance must be fastened in place. It is recommended that the appliance be secured in all installations. Always
turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the mobile home
and prior to lighting the appliance, ensure that the logs are positioned correctly.
#8 X 1/2”
SELF
DRILLING
SCREWS
2” (50.8mm)
OVERLAP
HIGH TEMP
SEALANT
28.1C
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certifi ed kit is used.
conversion kit is supplied with the mobile home appliance.
Conversion Kits
This appliance is fi eld convertible between Natural Gas (NG) and Propane (LP).
To convert from one gas to another consult your Authorized dealer/distributor.
29.1A
W415-1439 / A / 07.10.15
4.4 GAS INSTALLATION
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Installation and servicing to be done by a qualifi ed installer. Do not use open fl ame.
• Move the appliance into position and secure.
• If equipped with a fl ex connector the appliance is designed to accept a 1/2” (13mm) gas supply.
Without the connector it is designed to accept a 3/8” (9.5mm) gas supply. The appliance is equipped
with a manual shut off valve to turn off the gas supply to the appliance.
• Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
• When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
• Check for gas leaks by brushing on a soap and water solution.
!
WARNING
SPARKS OR OPEN FLAMES.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
23
EN
30.1A
2" (51mm)
NOTE: Connect the gas supply to the 1/2" (13mm) shut off and fl ex connector (supplied). Ensure gas
supply is secured.
14" (356mm)
W415-1439 / A / 07.10.15
24
5.0 FRAMING
EN
EN
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE
APPLIANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN
AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH
SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK
OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO
MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS
LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS
CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS,
OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING
ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE
FURNACE AT 750°C/1382°F AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
!
WARNING
RISK OF FIRE!
ANY OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO
COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY.
INSULATION AND OTHER MATERIALS ARE SECURED.
COULD RESULT.
BASE.
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, THEY MUST BE
INSTALLED.
71.1
The LV50 is installed into a rectangular opening. It is best to frame your appliance after it is positioned and the
vent system is installed. Use the steel stud frame provided.
Maintain these minimum clearances to combustibles from appliance and vent surfaces:
Appliance framing:
Use steel stud framing provided.
Non- Combustible Appliance fi nishing:
Front - 7" (177.8mm) to sides of appliance opening
- 26 1/2" (673.1mm) above appliance opening
Combustible Appliance fi nishing:
- 52" (1320.8mm) from bottom of appliance to enclosure top
- 3" (76mm) to top of vent pipe*
- 2" (51mm) to sides and bottom of vent pipe*
Non-combustible fi nishing material (ie. cement board, brick, stone, tile) must be used to fi nish the front of the
appliance.
*HORIZONTAL VENT SECTIONS: A minimum clearance of 3" (76mm) to the top and 2" (51mm) to the sides
and bottom of the vent pipe on all horizontal runs to combustibles is required when passing through a wall. Use
fi restop spacer W010-2107 (supplied).
Horizontal vent sections within enclosures require a minimum clearance of 6" (152mm) at the top of the vent
pipe, see “MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES” section and 1" (25mm) to the sides of
the vent pipe.
*VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required when passing through a ceiling. Use fi restop spacer W500-0028 (not supplied).
W415-1439 / A / 07.10.15
25 5/8"
574.7mm
25 5/8"
574.7mm
25
EN
1"
25.4mm
65 3/8"
1660.5mm
73"
1854.2mm
65 3/8"
1660.5mm
65 3/8"
1660.5mm
110"
2794mm
W415-1439 / A / 07.10.15
26
5.1 TWO SIDED APPLIANCE
EN
EN
!
WARNING
EDGES ARE SHARP, ALWAYS WEAR GLOVES WHEN WORKING WITH SHEET METAL.
A. The steel frame is pre-assembled but must be secured to the appliance in 3 places for both sides, as
shown.
B. The steel frame supplied must be installed as shown.
NOTE: For heavier fi nishing materials such as marble, we recommend adding extra support to the
frame. Screw the metal studs in place. Ensure there is adequate fl oor support for the appliance and fi nishing material.
METAL STUD
W415-1439 / A / 07.10.15
!
WARNING
METAL STUDS REQUIRED TO ENSURE CLEARANCE TO COMBUSTIBLES.
IMPORTANT: Before fi nishing in the appliance test the operation using the remote control, cycling it
through all of its different modes, see “OPERATION” section. Should trouble shooting be required,
access to the controls can be made through the pre-fi nishing access panel.
75 1/4"
1911mm
MINIMUM
50"
1270mm
MINIMUM
METAL STUDS (NOT MANDATORY)
27
EN
65 3/8"
1661mm
NOTE: Power vent system available with reduced
vent pipe clearances. Contact your authorized
dealer / distributor for more information.
16 1/4"
413mm
W415-1439 / A / 07.10.15
28
5.2 ONE SIDE APPLIANCE
EN
EN
!
WARNING
EDGES ARE SHARP, ALWAYS WEAR GLOVES WHEN WORKING WITH SHEET METAL.
A. The steel frame is pre-assembled but must be secured to the appliance in 3 places for both sides, as
shown.
B. The steel frame supplied must be installed as shown.
NOTE: For heavier fi nishing materials such as marble, we recommend adding extra support to the
frame. Screw the metal studs in place. Ensure there is adequate fl oor support for the appliance and fi nishing material.
METAL STUD
W415-1439 / A / 07.10.15
* When constructing the enclosure allow for fi nishing material thickness to maintain clearances.
IMPORTANT: Before fi nishing in the appliance test the operation using the remote control, cycling it
through all of its different modes, see “OPERATION” section. Should trouble shooting be required,
access to the controls can be made through the pre-fi nishing access panel.
75 1/4"
1911mm
MINIMUM
50"
1270mm
MINIMUM
29
EN
65 3/8"
1661mm
STAND OFF
2"
51mm
22 5/8"
574.7mm *
W415-1439 / A / 07.10.15
30
5.3 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
!
EN
EN
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THESE MATERIALS NEVER OVERHANG
INTO THE APPLIANCE OPENING.
IMPORTANT: The LV50 requires a minimum inside enclosure height of 75 1/4" (1911.4mm), measured
from the bottom of the appliance. For temperature requirements, this area must be left unobstructed. It is
recommended that the enclosure be ventilated at the top and bottom to circulate the hot air.
Before fi nishing in the appliance test the operation using the remote control, cycling it through all of its different
modes, see “OPERATION” section. Check pressure readings, see “PILOT BURNER ADJUSTMENT” section.
Once fi nished in, access to the control components can only be done through the inside of the appliance.
NOTE: JOINT COMPOUNDS AND TAPES THAT ARE RESILIENT
TO HEAT AND CRACKING SHOULD BE USED WHEN TAPING
AND MUDDING SEAMS.
STEEL STUD
FRAME
HEAT SHIELD
WARNING
TOP OF ENCLOSURE
152mm *
COMBUSTIBLE
6"
NON-COMBUSTIBLE
0” IF NON-COMBUSTIBLE
FINISHING IS USED SUCH
AS BRICK AND STONE.
3"
76mm
75 1/4"
1911mm
MINIMUM
ENCLOSURE
HEIGHT
26 1/2"
673mm
MINIMUM
TOP OF
APPLIANCE
OPENING
651mm
MINIMUM
25 5/8"
NON-COMBUSTIBLE
COMBUSTIBLE
MATERIAL
178mm
7"
TO SIDEWALL
2"
51mm
65 1/4"
1657mm
MINIMUM
PLUS RISE**
* Within the appliance enclosure a 6" (152mm) clearance between the top of the vent pipe and combustible
materials is required. All other clearances within the enclosure, including where the vent pipe exits the
enclosure are subject to 2" (51mm) to the sides and bottom and 3" (76mm) to the top for horizontal and 1"
(25mm) for vertical.
** See venting section.
W415-1439 / A / 07.10.15
Loading...
+ 106 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.