Napoleon HDX40NT-1, HDX40PT-1 Installation And Operating Instructions Manual

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE.
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22, ANSI Z21.50 FOR VENTED GAS FIREPLACES.
HDX40NT-1
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
NATURAL GAS
HDX40PT-1
!
WARNING
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
PROPANE
1
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
Phone (705)721-1212 • Fax (705)722-6031 • www.napoleonfi replaces.com • ask@napoleonproducts.com
$10.00
CERTIFIED
103 Miller Drive, Crittenden, Kentucky, USA, 41030
1.36A
W415-1089 / 08.08.12
2
TABLE OF CONTENTS
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 5
2.3 GENERAL INFORMATION 6
2.4 RATING PLATE INFORMATION 7
3.0 VENTING 8
3.1 VENTING LENGTHS AND COMPONENTS 8
3.2 TYPICAL VENT INSTALLATIONS 9
3.3 SPECIAL VENT INSTALLATIONS 10
3.3.1 PERISCOPE TERMINATION 10
3.3.2 CORNER TERMINATION 10
3.4 VENT TERMINAL CLEARANCES 11
3.5 VENT APPLICATION FLOW CHART 12
3.6 DEFINITIONS 12
3.7 ELBOW VENT LENGTH VALUES 12
3.8 HORIZONTAL TERMINATION 13
3.9 VERTICAL TERMINATION 15
4.0 INSTALLATION 17
4.1 WALL AND CEILING PROTECTION 17
4.1.1 HORIZONTAL INSTALLATION 18
4.1.2 VERTICAL INSTALLATION 18
4.2 USING FLEXIBLE VENT COMPONENTS 19
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 19
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 20
4.3 MOBILE HOME 21
4.4 ACCESS PANEL FOR GAS LINE CONNECTION 21
4.5 GAS INSTALLATION 22
5.0 FRAMING 22
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES 24
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 25
5.3 ALCOVE INSTALLATION 27
5.4 MINIMUM MANTEL CLEARANCES 28
6.0 FINISHING 29
6.1 DOOR REMOVAL / INSTALLATION 29
6.2 LOG PLACEMENT 30
6.3 GLOWING EMBER PLACEMENT 31
6.4 LAVA ROCK 31
6.5 OPTIONAL ROCK PLACEMENT 32
6.6 LOGO PLACEMENT 33
7.0 OPTIONAL BLOWER INSTALLATION 33
7.1 ACCESSING THE BLOWER 33
7.2 INSTALLING THE BLOWER 34
8.0 WIRING DIAGRAM / ELECTRICAL INFORMATION 35
8.1 WIRING REQUIREMENTS 35
8.2 JUNCTION BOX INSTALLATION 35
8.3 WIRING DIAGRAM (IFC MODULE) 36
9.0 OPERATION 37
9.1 GENERAL TRANSMITTER LAYOUT 38
9.2 INITIALIZING THE TRANSMITTER FOR THE FIRST TIME 38
9.3 TEMPERATURE DISPLAY 39
9.4 FLAME HEIGHT 39
9.5 BLOWER SPEED 39
9.6 NIGHT LIGHT DIMMER CONTROL 40
9.7 CONTINUOUS PILOT / INTERMITTENT PILOT (CPI / IPI) SELECTION 40
9.8 KEY LOCK 40
9.9 LOW BATTERY / MANUAL BYPASS 41
10.0 ADJUSTMENT 41
10.1 RESTRICTING VERTICAL VENTS 41
10.2 PRESSURE ADJUSTMENT 41
10.3 VENTURI ADJUSTMENT 42
10.4 FLAME CHARACTERISTICS 42
11.0 MAINTENANCE 43
11.1 LAMP REPLACEMENT 43
11.2 DOOR GLASS REPLACEMENT 44
11.3 CARE OF GLASS 44
11.4 CARE OF PLATED PARTS 44
12.0 REPLACEMENT PARTS 45
13.0 TROUBLESHOOTING 48
14.0 WARRANTY 51
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1089 / 08.08.12
1.0 INSTALLATION OVERVIEW
3
Mantel, see “MINI­MUM MANTEL CLEARANCES” section.
Enclosures, see the section “MINIMUM CLEARANCES TO COMBUSTIBLE ENCLOSURES” section for drywall (or other combustible material).
Framing, see “FRAMING” section.
Side Wall
Venting, see “VENTING” section.
Enclosures, see the section “MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES” section for non-combustible materials such as tile, marble, granite, etc.
Rating plate, see “RATING PLATE INFORMATION” section.
W415-1089 / 08.08.12
4
2.0 INTRODUCTION
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES OR ALTERATIONS TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers,
young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance
It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch re.
Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage of decorations, a T.V. or other electronic components.
!
WARNING
W415-1089 / 08.08.12
3.2B
2.1 DIMENSIONS
5
3”
41”
33 ¾”
2.2 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” FROM THE
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
3”
39 ¼”
38”
2"
!
WARNING
PROVIDE ADEQUA TE VENTILA TION.
FRONT FACE OF THE APPLIANCE.
FIRE RISK. EXPLOSION HAZARD.
28”
1"
10 ³/16”
20”
5"
8"
40 ¼”
2"
20 ½”
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas log.
The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
W415-1089 / 08.08.12
6
A
A
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
This appliance is equipped with a power back up control system. Four 1.5 volt “AA” batteries (not supplied) are required for the battery pack included in the system. Use Alkaline batteries only.
2.3 GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
www.ncertied.org
We suggest that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1A
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home installations.
This appliance is equipped with ceramic glass. Replacement glass must be obtained from your authorized dealer / distributor and is identifi ed in the replacement parts list. Do not substitute materials.
This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected. Changes in fl ame appearance from “HI” to “LO” is more evident in natural gas than in propane. Use only accessories designed for and listed with your specifi c appliance.
High Elevations
Input ratings are shown in Btu per hour and are certifi ed without de-rating up to 4,500 feet above sea level. For Installations at the elevations above 4,500 feet and in the absence of specifi c recommendations from the local authority having jurisdiction, the high altitude input rating shall be reduced at the rate of 4% for each additional 1,000 feet.
Model Fuel Gas
HDX40NT-1 Nat IPI Hi/Lo 40,000 26,000 HDX40PT-1 Prop* IPI Hi/Lo 36,000 26,000
IPI - Intermittent Pilot Ignition System * Using conversion kit ** Maximum Values Conversions must be made by a qualifi ed service technician using Wolf Steel specifi ed and approved parts.
GAS SPECIFICATIONS
Control
BTU/h
Max.
Input
Min.
Input
BTU/h
Minimum Inlet 4.5” w.c. 11.0” w.c. Maximum Inlet 7.0” w.c. 13.0” w.c. Manifold Pressure 3.5” w.c. 10.0” w.c.
GAS INLET AND MANIFOLD
PRESSURES
Natural Propane
EFFICIENCY RATINGS
Model Steady
State(%)
HDX40NT-1 61.5% 59.5% HDX40PT-1 61.5% 59.5%
AFUE%**
W415-1089 / 08.08.12
2.4 RATING PLATE INFORMATION
S
SERIALL NUMBER/NO. DE S NUMBER/NO. DE S
S.S.
LONGULONGUEEURUR
SS
D'EAUD'EAU
MNMN
UNE COLONNE D'EAUUNE COLONNE D'EAU
COLUMNCOLUMN
13" D'UNE COLONNE D'EAU13" D'UNE COLONNE D'EAU
: :
JOUTEZN'A JOUPASACE
T
APP
AREI
LL
UCUNAUCUN
MMTTAA
VEVECCLL
SES
F
LAM
U
TRE
Q
UEEC
E
I
QQ
UU
I
F
ABRICANBRICAN
TT
..
MU
S
TBEVENNTETEDD
UU
SISINNGG
TTHHEE
A
R
O
RRIIAA
TETE
WOLF ST WOLF ST
N
MMAA
UNU
A
LL
OFO
RVE
NNTITINN
GG
SPESPE
CC
IFI
CC
S.S
RR
OPEOPE
RR
RREIEINNSSRR
YY
A
SEAFTER SERRVICINGVIC
HE VENTT-AIR IN-AIR IN
TT
AKE SYSTEMAKE SYSTE
UU
ITI
LL
ISA
NNTTLL
'E'E
NN
SESE
MMBBLED'ÉVVAA
CUCUAATIOTIO
NNPP
RR
O
OPRE
ÀÀTTALLALL
AA
TIONTION
DUDUPRO
ÉPROPRIÉ
TT
AIRE
POUU
R LES SPÉCIFICAR LES SPÉCIFICA
TET
SES
LLLÉVETAPP
OIS AVOI
RAA
NE DOIT PAS ÊTRE UTILISÉ A
AVAV
OGUÉES AVEC CETTE UNITÉ SEUOGUÉES AVEC CETTE UNITÉ SE
VICE OR MAINTENANCE
N CAUSE PROPERTY
MAGE, PERSONAL
RY OR LOSS OF
E. REFER TO
R’S MANUAL
ERVICE
FOR
ND MU
WITH
ISIONS
7
CERTIFIED UNDER / HOMOLOGUÉ SELON LES NORMES: CSA 2.22b-2009, ANSI Z21.50b-2009 VENTED GAS FIREPLACE / APPAREIL À GAZ V E N T I L É S.
DIRECT VENT GAS FIREPLACE HEATER. SUITABLE FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. WHEN INSTALLED WITH SCREEN KIT GD-565KT, THE FIREPLACE COMPLIES WITH CGA CERTIFICATION REQUIREMENT CR95-006.
HDX40NT
THIS VENTED G AS F IR EP LA CE HE AT ER IS N OT FO R U SE WITH AIR FILTERS AND NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY
WARNING:
CONTACT WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS / DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES:
TOP/ DESSUS 6½" RECESSED DEPTH / PROFONDEUR D'ENCASTRE 20½" FLOOR / PLANCHER 0 VENT SIDES / COTES DE L'EVENT 2" SIDES / COTES 2” BACK / ARRIERE 1” MANTLE / MANTEAU 13"
*
MAXIMUM HORIZONTAL EXTENSION / EXTENSION HORIZONTALE MAXIMALE: 2".
SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS. SE RÉFÉRER AU
D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES.
MANUEL
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
SE RÉFÉRER AU MANUEL D'INSTALLATION DU PROPRIÉTAIRE POUR LES LONGUEURS D'EVACUATION MINIMALE ET MAXIMALE.
KEEP BURNER AND
CONTROL COMPARTMENT
CLEAN. SEE INSTALLATION
AND OPERATING
INSTRUCTIONS
MANUAL. APPLIANCE
NEEDS FRESH AIR FOR
SAFE OPERATION AND MUST
BE INSTALLED WITH
ADEQUATE PROVISIONS
FOR COMBUSTION
AND VENTILATION AIR.
GARDEZ LE BRULEUR ET LE
COMPARTIMENT DES
CONTROLES PROPRES.
CONSULTEZ LE MANUEL
D’INFORMATION ET
D’INSTALLATION. PAR
MESURE DE SECURITE.
CET APPAREIL DOIT
ETRE ALIMENTE EN AIR
FRAIS ET AVEC SUFFISANT
D’AIR COMBURANTET
DE VENTILATION.
Natural Gas/Gaz Naturel
PRESSION D'ALIMENTATIONMINIMALE: 4.5" D'UNE COLONNE D'EAU
PRESSION D'ALIMENTATIONMAXIMALE: 7.0" D'UNE COLONNE D'EAU
DO NOT ADD ANY MA TERIAL T O THE APPLIANCE, WHICH WILL COME IN
VENT TOP / DESSUS DE L’ÉVENT 2" VENT BOTTOM / DESSOUS DE L’ÉVENT 1"
*
CHDX40NT
0-4500 FT (0-1370m)
40,000 BTU/h 26,000 BTU/h
MANIFOLD PRESSURE: 3.5" WATER COLUMN
PRESSION AU COLLECTEUR: 3.5" D'UNE COLONNE D'EAU
MINIMUM SUPPLY PRESSURE: 4.5" WATER COLUMN
MAXIMUM SUPPLY PRESSURE: 7.0" WATER COLUMN
WARNING:
IMPROPER INSTALLATION, ADJUSTMENT, AL TERATION, SERVICE OR MAINTENANCE
CAN CAUSE PROPERTY
DAMAGE, PERSONAL
INJURY OR LOSS OF
LIFE. REFER TO OWNER’S MANUAL. INSTALLATION AND
SERVICE MUST BE PERFORMED BY A
QUALIFIED INSTALLER,
SERVICE AGENCY OR
THE GAS SUPPLIER.
ATTENTION:
UN INSTALLATION OU
UNE MODIFICATION
INAPPROPRIEE
DU REGLAGE, DU SERVICE
ET DE L’ENTRETIEN
POURRAIENT ETRE LA CAUSE
DE DOMMAGES A LA PROPRIETE
DE BLESSURES CORPORELLES
OU MEME LA MORT. CONSULTER
LE MANUEL D’INFORMATION,
L’INSTALLATION ET LE SERVICE
DOIVENT ETRE EXECUTES PAR
UN INSTALLATEUR QUALIFIE
POUR LE AZ, UNE ENTERPRISE
DE SERVICE OU LE
FOURNISSEUR
DE GAZ SEULEMENT.
CERTIFIED
TIFIED FOR
R
CE
TIFIEE POUR
R
CE
REFERENCE # 161746
ALTITUDE / ELEVATION INPUT / ALIMENTATION
REDUCED INPUT / ALIMENTATION REDUITE
TOUCH. KEEP CHILDREN, CLOTHING,
FURNITURE, GASOLINE OR OTHER
L’APPAREIL EST CHAUD PENDANT
MEUBLES, L’ESSENCE ET AUTRES
LIQUIDES QUI EMETTENT DES GAZ
VOLATILS INFLAMMABLES DOIVENT
ETRE TENUS ELOIGNES DE L’APPAREIL.
“This appliance is only for use with the
type(s) of gas indicated on the rating plate
and maybe installed in an aftermarket,
permanentlylocated, manufactured home
(USA only) ormobile home, where not prohibited by localcodes. See owner’s
manual for details. Thisappliance is
«Cet appareil doit être utilisé uniquemen-
tavec les types de gaz indiqués sur la
plaquesignalétique et peut être installé
dans unemaison préfabriquée (É.-U.
seulement) oumobile installée à demeure
si les règlementslocaux le permettent. Voir
la notice del’utilisateur pour plus de
conversion est fournie avec cetappareil.»
APPAREIL DE CHAUFFAGE À ÉVACUATION DIRECTE. HOMOLOGUÉ POUR INSTALLATION
DANS UNE CHAMBRE À COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIÉ
POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION EST
CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE MAISONS
MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA, OU AUX ÉTATS-UNIS, SELON
LA NORME DE SÉCURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES,
TITRE 24 CFR, SECTION 3280. DANS LE CAS OÙ CETTE NORME DES ÉTATS-UNIS NE
PEUT ÊTRE APPLIQUÉE, SE RÉFÉRER À LA NORME RELATIVE AU CRITÈRE DE
CANADA USA
MODEL
SERIAL NUMBER/NO. DE SERIE: HDX40
ERIA
HOT WHILE OPERATING. DO NOT
FLAMMABLE VAPORS AWAY.
SON FONCTIONNEMENT. LES
ENFANTS, LES VETEMENTS, LES
supplied with a conversion kit.”
renseignements. Unetrousse de
MESURES DE SÉCURITÉ CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES
MAISONS MANUFACTURÉES, LES SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A.
LORSQU'IL EST INSTALLÉ AVEC LE PARE-ÉTINCELLES GD-565KT , LE FOYER EST
CONFORME À LA NORME DE CERTIFICATION DE L'ACG CR95-006.
Propane
HDX40PT
0-4500FT (0-1370m)
36,000 BTU/h
MANIFOLD PRESSURE: 10" WATER COLUMN PRESSION AU COLLECTEUR: 10" D'UNE COLONNE D'EAU MINIMUM SUPPLY PRESSURE: 11" WATER COLUMN PRESSION D'ALIMENTATIONMINIMALE: 11" D'UNE COLONNE D'EAU MAXIMUM SUPPLY PRESSURE: 13" WATER COLUMN PRESSION D'ALIMENTATIONMAXIMALE: 13" D'UNE COLONNE D'EAU
CE FOYER À GAZ VENTILÉS NE DOIT PAS ÊTRE UTILISÉ AVEC DES FILTRES À AIR ET NE DOIT PAS ÊTRE UTILISÉ AVEC UN COMBUSTIBLE SOLIDE. UTILISER AVEC LES PORTES VITRÉES HOMOLOGUÉES AVEC CETTE UNITÉ SEULEMENT.
AVERTISSEMENT:
ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI A VEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINST ALLA TION AND RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.
GAZ EN UTILISANT L'ENSEMBLE D'ÉVACUATION PROPRE À
D'INSTALLATION DU PROPRIÉTAIRE POUR LES SPÉCIFICATIONS DE L'ÉVACUATION. IL EST IMPORTANT DE BIEN RÉINSTALLER ET RESCELLER L'ÉVENT APRÈS AVOIR EFFECTUÉ LE SERVICE DU SYSTÊME DE PRISE D'AIR. ELECTRICAL RATING / CLASSIFICATION: 115V, 60HZ, LESS THAN 12 AMPS. SPÉCIFICATIONS ÉLECTRIQUES : 115 V, 60 HZ, MOINS DE 12 A. OPTIONAL FAN KIT / SOUFFLERIE OPTIONNELLE : GZ550-KT, GD65
26,000 BTU/h
N'A JOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT
N'A
E
F
MESA
L
THE VEN
APP
IFI
N
A
F
FTER
T
ISA
PRI
TA
LLE
E
24 NAPOLEON ROAD, BARRIE. ONTARIO L4M 4Y8 CANADA
CAUTION:
OR OTHER FLAMMABLE VAPORS
AVERTISSEMENT:
GLASS REMOVED, CRACKED OR
LE VOISINAGE DE CET APPAREIL
CRAQUÉ OU BRISÉ. CONFIEZ LE
CHDX40PT
A
LUUI
I
P
P
L'APPAREIL DOIT ÉVACUER SES
WOLF
STEEL. SE RÉFÉRER
PRE
AV
AU MANUEL
WOLF STEEL LTD.
W385-0496 / A
FOR YOUR SAFETY: DO
NOT STORE OR USE GASOLINE
AND LIQUIDS IN VICINITY OF
THIS OR ANY OTHER
APPLIANCE.
CAUTION: DO NOT OPERATE
THE FIREPLACE WITH THE
BROKEN. REPLACEMENT OF
THE GLASS SHOULD BE DONE
BY A LICENSED OR QUALIFIED
PERSON.
POUR VOTRE SECURITE:
NE PAS ENTREPOSER NI
UTILISER D’ESSENCE NI D’AUTRES VAPEURS OU
LIQUIDES INFLAMMABLES ANS OU DE TOUT AUTRE APPAREIL.
AVERTISSEMENT: NE PAS
UTILISER L’APPAREIL SI LE
PANNEAU FRONTAL EN VERRE
N’EST PAS EN PLACE, EST
REMPLACEMENT DU PANNEAU
À UN TECHNICIEN AGRÉÉ.
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
W415-1089 / 08.08.12
8
3.0 VENTING
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5” EXHAUST / 8” AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
3.1 VENTING LENGTHS AND COMPONENTS
7.2B
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura­Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
PART 5”/8” SUPPLIER WEBSITE
Duravent W175-0170 Wolf Steel www.duravent.com
Amerivent 5DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 5DT-AA Selkirk www.selkirkcorp.com
SuperSeal 5DDA Metal-Fab www.mtlfab.com
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following termination kits: wall terminal kit GD422-1, GD422R-1, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12 roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD420 or the 10 foot vent kit GD430.
W415-1089 / 08.08.12
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” rise per foot however for optimum performance it is recommended that all horizontal runs have a minimum 1/4” rise per foot using fl exible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” air gap all around between the inner liner and outer liner is required for safe operation.
3.2 TYPICAL VENT INSTALLATIONS
9
8.3
24” MIN
38”
24” MAX
16” MIN
40FT MAX
3FT MIN
62”
MIN PLUS RISE*
* See “VENTING” section.
38”
W415-1089 / 08.08.12
10
3.3 SPECIAL VENT INSTALLATIONS
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when fi nal grading is completed, the bottom air slot is located a minimum 12” above grade. The maximum allowable vent length is 10’ for a replace and 8’ for a stove.
12” MIN TO
GRADE
30” MIN
38”
9.1A
3.3.2 CORNER TERMINATION
The maximum vent length for a corner installation is 24” of horizontal run with a minimum 24” rise.
24”
MAX
W415-1089 / 08.08.12
3.4 VENT TERMINAL CLEARANCES
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
11
INSTALLATIONS
CANADA U.S.A.
Q
R
R
MIN
MAX
MAX
= 3 feet
= 2 x
Q
 feet
ACTUAL
A 12” 12” Clearance above grade, veranda porch, deck or balcony. B 12”
Δ
9”
Δ
Clearance to windows or doors that open.
C 12” * 12” * Clearance to permanently closed windows.
D 18” ** 18” **
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ from the center line of the terminal.
E 12” ** 12” ** Clearance to unventilated sof t. F 0” 0” Clearance to an outside corner wall.
0” *** 0” *** Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
G
2” *** 2” *** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
H 3’ 3’ ****
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15’.
I 3’ 3’ **** Clearance to a service regulator vent outlet. J 12” 9” Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance. K 6’ 3’ † Clearance to a mechanical air supply inlet. L 7’ ‡ 7’ **** Clearance above a paved sidewalk or paved driveway located on public property.
M 12” †† 12” **** Clearance under a veranda, porch or deck. N 16” 16” Clearance above the roof. O 2’ †* 2’ †* Clearance from an adjacent wall including neighbouring buildings.
P 8’ 8’ Roof must be non-combustible without openings.
Q 3’ 3’ See chart for wider wall dimensions. R 6’ 6’
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an open­ing between the terminal and the open side of the structure.
S 12” 12” Clearance under a covered balcony
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
12.1C
W415-1089 / 08.08.12
12
3.5 VENT APPLICATION FLOW CHART
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are: > - greater than > - equal to or greater than < - less than < - equal to or less than HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet HR - combined horizontal vent lengths in feet HO - offset factor: .03 (total degrees of offset - 90°*) in feet VT - combined vertical vent lengths in feet
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet
4.2 times the
vertical rise equal to
or greater than the
horizontal run
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3 times the vertical
rise equal to or
greater than the
horizontal run
13.1
14.1
3.7 ELBOW VENT LENGTH VALUES
FEET INCHES 1° 0.03 0.5 15° 0.45 6.0 30° 0.9 11.0 45° 1.35 16.0 90°* 2.7 32.0
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
15.1
W415-1089 / 08.08.12
3.8 HORIZONTAL TERMINATION
13
(HT) < (VT)
Simple venting confi guration (only one 90° elbow)
See graph to determine the required vertical
rise VT for the required horizontal run HT.
40
39
30
REQUIRED
VERTICAL
20
RISE IN
FEET VT
10
0
2.5 5 7.5 10 12.5 15
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET H
T
The shaded area within the lines represents
acceptable values for HT and V
For vent confi gurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet
Example 1: V1 = 3 FT
90°
V2 = 8 FT VT = V1 + V2= 3 FT + 8 FT = 11 FT
V
H1 = 2.5 FT
2
H2 = 2 FT HR = H1 + H2 = 2.5 + 2 = 4.5 FT HO = .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT HT = HR + HO = 4.5 + 5.4 = 9.9 FT HT + VT = 9.9 + 11 = 20.9 FT
90°
90°
H
1
17.5 20
T
H
2
Formula 1: HT < V
T
9.9 < 11 Formula 2: HT + VT < 40 FT
20.9 < 40 Since both formulas are met, this vent confi guration is acceptable.
V
1
16.12
W415-1089 / 08.08.12
14
V
V V V
(HT) > (VT)
Simple venting configuration (only one 90° elbow)
REQUIRED
See graph to determine the required vertical rise VT for the
required horizontal run H
150
147”
100
.
T
VERTICAL
RISE IN
INCHES V
T
57”
50
24”
0
515
2’
10
12.5’
19.5’
20
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring more than one 90° elbow, the following formulas apply:
< 4.2 V
Formula 1: Formula 2: HT + V
H
T
T
< 24.75 feet
T
90°
H
1
H
2
Example 2:
= VT = 6 FT
1
H
= 3 FT
1
H
= 5 FT
2
H
= H
+ H
R
H
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7 FT
O
H
= H
T
H
+ V
T
= 3 + 5 = 8 FT
1
2
+ H
= 8 + 2.7 = 10.7 FT
R
O
= 10.7 + 6 = 16.7 FT
T
V
1
90°
Formula 1: HT < 4.2 V
4.2 VT = 4.2 x 6 = 25.2 FT
10.7 < 25.2
Formula 2: HT + V
16.7 < 24.75
Since both formulas are met, this vent configuration is acceptable.
Example 3:
= 4 FT
1
= 1.5 FT
2
= V
+ V
T
H
= 2 FT
1
H
= 1 FT
2
H
= 1 FT
3
H
= 1.5 FT
4
H
= H
R
H
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT
O
H
= H
T
H
+ V
T
= 4 + 1.5 = 5.5 FT
1
2
+ H2 + H
1
+ H
R
= 13.6 + 5.5 = 19.1 FT
T
+ H4 = 2 + 1 + 1 + 1.5 = 5.5 FT
3
= 5.5 + 8.1 = 13.6 FT
O
Formula 1: HT < 4.2 V
4.2 VT = 4.2 x 5.5 = 23.1 FT
T
< 24.75 FT
T
T
90°
90°
90°
H
1
90°
V
1
V
H
H
2
3
H
4
2
13.6 < 23.1 Formula 2: HT + V
19.1 < 24.75
< 24.75 FT
T
Since both formulas are met, this vent configuration is acceptable.
16.13
W415-1089 / 08.08.12
3.9 VERTICAL TERMINATION
15
(HT) < (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run HT.
40
30
REQUIRED
VERTICAL
20
RISE IN
FEET V
T
10
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring one or more 90° elbows the following formulas apply: Formula 1: H
Formula 2: HT + V
< V
T
T
< 40 feet
T
for the
T
T
Example: V
= 5 FT
1
V
= 6 FT
2
V
= 10 FT
3
V
= V
+ V2 + V3 = 5 + 6 + 10 = 21 FT
T
1
H
= 8 FT
1
H
= 2.5 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
T
H
+ V
T
Formula 1: HT < V
18.6 < 21 Formula 2: HT + V
39.6 < 40
= 8 + 2.5 = 10.5 FT
1
2
+ H
= 10.5 + 8.1 = 18.6 FT
R
O
= 18.6 + 21 = 39.6 FT
T
T
< 40 FT
T
Since both formulas are met, this vent configuration is acceptable.
V
90°
1
90°
V
3
H
2
V
H
1
2
90°
90°
18.1
W415-1089 / 08.08.12
16
(HT) > (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run H
20
19
REQUIRED
VERTICAL
RISE IN
FEET V
10
T
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring more than two 90° elbows the following formulas apply: Formula 1: H
Formula 2: HT + V
< 3V
T
T
< 40 feet
T
Example: V
= 2 FT
1
V
= 1 FT
2
V
= 1.5 FT
3
V
= V
+ V2 + V3 = 2 + 1 + 1.5 = 4.5 FT
T
1
H
= 6 FT
1
H
= 2 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
T
H
+ V
T
= 6 + 2 = 8 FT
1
2
+ H
= 8 + 8.1 = 16.1 FT
R
O
= 16.1 + 4.5 = 20.6 FT
T
90°
H
V
1
1
90°
for the
.
T
H
V
2
T
25 30
V
2
T
3
90°
90°
Formula 1: HT < 3V 3VT = 3 x 4.5 = 13.5 FT
T
16.1 > 13.5 Since this formula is not met, this vent configuration is unacceptable. Formula 2: HT + VT < 40 feet
20.6 < 40
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration will need to be established to satisfy both formulas.
18.1_2A
W415-1089 / 08.08.12
4.0 INSTALLATION
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
!
WARNING
EXACTLY.
WHICH MUST BE SEALED USING MILL PAC.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
17
68.2A
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For optimum performance it is recommended that all horizontal runs have a minimum of 1/4” rise per foot using exible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
WARNING
70.1
W415-1089 / 08.08.12
18
A
4.1.1 HORIZONTAL INSTALLATION
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall as illustrated to accommodate the fi restop assembly. Dry fi t the fi restop assembly before proceeding to ensure the brackets on the rear surface fi t to the inside surface of the horizontal framing.
The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2” thick but the vent shield must extend the full depth of the combustible wall.
. Apply a bead of caulking (not supplied) around the corner edge of the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your manual baggie).
!
WARNING
CAULKING
FIRESTOP
SPACER
VENT
SHIELD
DETERMINE THE CORRECT HEIGHT
FINISHING MATERIAL
B. Once the vent pipe is installed in its fi nal position, apply high temperature sealant W573-0007 (not supplied) between the pipe and the fi restop.
20.2
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for various roof pitches are available from your authorized dealer / distributor. See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1“ clearance between the vent pipe and any combustible material. Try to center the vent pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings. A vent pipe shield will prevent any materials such as insulation, from fi lling up the 1” air space around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a fi nished ceiling), and secure over the opening in the ceiling. A fi restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a restop spacer over the vent shield to restrict cold air from being drawn into the room or around the fi replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply sealant between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1” air space around the pipe.
10 3/4” 10 3/4”
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
21.1
CAULKING
COLLAR
VENT
PIPE
SHIELD
VENT
PIPE
W415-1089 / 08.08.12
4.2 USING FLEXIBLE VENT COMPONENTS
!
WARNING
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
For safe and proper operation of the appliance, follow the venting instructions exactly. All inner fl ex pipe and outer fl ex pipe joints may be sealed using high
ELBOW
SPACERS
temperature sealant W573-0002 (not supplied) or the high temperature sealant W573-0007 Mill Pac (not supplied). However, the high temperature sealant W573-0007 Mill Pac (not supplied) must be used on the joint connecting the inner fl ex pipe and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
19
“Wolf Steel Approved Venting” as identifi ed by the stamp only on the outer fl ex pipe.
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION
A. Stretch the inner fl ex pipe to the required length taking into
account the additional length needed for the fi nished wall surface. Apply a heavy bead of the high temperature sealant W573-0007 Mill Pac (not supplied) to the inner sleeve of the air terminal. Slip the vent pipe a minimum of 2” over the inner sleeve of the air terminal and secure with 3 #8 screws.
B. Using the outer fl ex pipe, slide over the outer combustion
air sleeve of the air terminal and secure with 3 #8 screws. Seal using high temperature sealant W573-0002 (not supplied).
C. Insert the vent pipes through the fi restop maintaining the required
clearance to combustibles. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).
D. If more vent pipe needs to be used to reach the fi replace, couple
them together as illustrated. The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use noncombustible strapping to maintain the minimum clearance to combustibles.
#10x2"
SCREWS
HI-TEMP
SEALANT
OUTER
FLEX PIPE
22.1
CAULKING
INNER FLEX
PIPE
OUTER FLEX
2" OVERLAP
HIGH TEMPERATURE
#8 X 1/2” SELF DRILLING
SCREWS & WASHERS
INNER COUPLER
INNER FLEX PIPE
PIPE
SEALANT
OUTER COUPLER
FLEX PIPE
OUTER
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its return fl ange.
23.1A
W415-1089 / 08.08.12
20
4.2.2 VERTICAL AIR TERMINAL INSTALLATION
!
WARNING
MAINTAIN A MINIMUM 2” SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
A. Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
B. Stretch the inner ex pipe to the required length. Slip the inner
ex pipe a minimum of 2” over the inner pipe of the air terminal
connector and secure with 3 #8 screws. Seal using a heavy bead of high temperature sealant W573-0007 (not supplied).
C. Repeat using the outer fl ex pipe, using a heavy bead of high
temperature sealant W573-0002 (not supplied).
D. Thread the air terminal connector / vent pipe assembly down
through the roof. The air terminal must be positioned vertically and plumb. Attach the air terminal connector to the roof support, ensuring that the top of the air terminal is 16” above the highest point that it penetrates the roof.
E. Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector leaving a min. 3/4” of the air terminal connector showing above the top of the fl ashing. Slide the fl ashing underneath the sides and upper edge of the shingles. Ensure that the air terminal connector is properly centred within the fl ashing, giving a 3/4” margin all around. Fasten to the roof. Do not nail through the lower portion of the fl ashing. Make weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the fl ashing with roofi ng material.
F. Aligning the seams of the terminal and air terminal connector, place
the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal. Secure with the three screws provided.
G. Apply a heavy bead of weatherproof caulking 2” above the fl ashing.
Install the storm collar around the air terminal and slide down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved.
H. If more vent pipe needs to be used to reach the appliance see
“HORIZONTAL AIR TERMINAL INSTALLATION” section.
ROOF SUPPORT
INNER PIPE
AIR
TERMINAL
CONNECTOR
HIGH TEMPERATURE SEALANT
INNER FLEX PIPE
OUTER FLEX PIPE
2”
AIR I NL ET BASE
CAULKING
STORM COLLAR
WEA THER SEALANT
W415-1089 / 08.08.12
FLASHING
24.1
4.3 MOBILE HOME
A
This appliance is also certifi ed to be installed as an OEM (Original Equipment Manufacturer) installation in a manufactured home (U.S. only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate.
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit. Built in appliances are equipped with 1/4” diameter holes located in the front left and right corners of the base. Use #10 hex head screws, inserted through the holes in the base to secure. For free standing products contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must be fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting the appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
conversion kit is supplied with the mobile home appliance.
Conversion Kits This appliance is fi eld convertible between Natural Gas (NG) and Propane (LP). To convert from one gas to another consult your Authorized dealer/distributor.
21
4.4 ACCESS PANEL FOR GAS LINE CONNECTION
A. Unscrew the 4 screws that hold the Access
Panel to the fi rebox.
B. Remove the Gasket (careful not to tear).
29.1
Access Panel
Gasket
W415-1089 / 08.08.12
22
4.5 GAS INSTALLATION
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Installation and servicing to be done by a qualifi ed installer.
A. Move the appliance into position and secure. B. If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance.
C. Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States.
D. When exing any gas line, support the gas valve so that the lines are not bent or kinked. E. The gas line ex-connector should be installed to provide suf cient movement for shifting the burner
assembly on it’s side to aid with servicing components.
F. Check for gas leaks by brushing on a soap and water solution. Do not use open ame.
!
WARNING
SPARKS OR OPEN FLAMES.
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
30.1A
5.0 FRAMING
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE
APPLIANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH
ANY OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO
COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY.
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN
AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH
SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK
OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE
INSULATION AND OTHER MATERIALS ARE SECURED.
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS
LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS, OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING
ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE
FURNACE AT 750°C AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, THEY MUST BE
W415-1089 / 08.08.12
!
WARNING
RISK OF FIRE!
COULD RESULT.
BASE.
INSTALLED.
71.1
23
It is best to frame your appliance after it is positioned and the vent system is installed. Frame to local building codes.
It is not necessary to install a hearth extension with this appliance.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the fi nished fl oor materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower access door and the installation of many decorative fl ashing accessories.
Combustible materials may be installed fl ush with the front of the appliance but must not cover any of the black face- areas of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas.
!
WARNING
DO NOT BUILD INTO THIS AREA - IT MUST BE LEFT
CLEAR TO PROVIDE ADEQUATE CLEARANCE FOR
THE VENT IN THIS 14” WIDE AREA CENTERED
ALONG THE FRONT OF THE APPLIANCE. NO
COMBUSTIBLES ARE ALLOWED.
NOTE: Three braces are required (as nailers) if using optional 4-sided frame kit.
84”*
3 ½” MAX
14” MIN
1 ½”
MAX
20 ¼”**
41”*
40 ¾”
* Allow for fi nished fl oor and hearth thickness when setting these dimensions. ** When constructing the enclosure allow for fi nishing material thickness to maintain clearances.
W415-1089 / 08.08.12
24
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES
COMBUSTIBLE FRAMING:
Sides, back, bottom of the appliance
COMBUSTIBLE FINISHING:
Sides 2” to front edge of the appliance Enclosure Top 84” from the bottom of the appliance Recessed Depth 20 1/4” Sides of the vent pipe 2”* Bottom of the vent pipe 1” Top of vent pipe 2”* Ceiling 70” from the bottom of the appliance
* HORIZONTAL VENT SECTIONS: A minimum clearance of 1” at the bottom and sides and 2” at the top of the vent pipe in all horizontal runs to combustibles is required except for clearances in appliance enclosures. Horizontal vent sections within enclosures require a minimum clearance of 18” at the top of the vent pipe. See “MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES” section. Use fi restop spacer W010-1800 (supplied) where vent pipe penetrates combustible walls.
* VERTICAL VENT SECTIONS: A minimum clearance of 1” all around the vent pipe on all vertical runs to combustibles is required except for clearances in appliance enclosures. Vertical vent sections within enclosures require a minimum clearance of 4” to the sides of the vent pipe. See “MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES” section. Use fi restop spacer W500-0367 (not supplied) where vent pipe penetrates combustible ceilings or fl oors.
0” to stand-offs
OUTSIDE
CHASE
20 ¼”
40 ¾”
40 ¾”
INSIDE
CHASE
2”
4”
6”
20 ¼”
2” 4”
9
16
47”
40 ¾”
BACK WALL OF CHASE/ ENCLOSURE (INCLUDING ANY FINISHING MATERIALS)
66 ½”
/16”
33 ¼”
W415-1089 / 08.08.12
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
NON-COMBUSTIBLE
COMBUSTIBLE
BRICK
18”
0” IF NON-COMBUSTIBLE
2”
WOOD HEADER
4”
46”
FINISHING IS USED SUCH AS BRICK AND STONE
25
1”
84”
38”
9 1/2”
NON­COMBUSTIBLE MATERIAL
FRONT HOOD
62”
MINIMUM
PLUS RISE*
1”
For temperature requirements, the enclosure space around and above the appliance must be left unobstructed. It is recommended that the enclosure be ventilated at the top and bottom to circulate the hot air.
* See “VENTING” section.
W415-1089 / 08.08.12
26
COMBUSTIBLE MATERIAL
NON-COMBUSTIBLE MATERIAL SUCH AS TILE, MARBLE, GRANITE, ETC.
47 ½”
2” MIN.
40 ¼”
2” MIN.
A joint compound that is resilient to heat and cracking should be used when taping and mudding seams.
Non-combustible Material Defi nitions
Material which will not ignite and burn. Materials consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof are suitable.
Materials that are reported as passing ASTM E 136, Standard Test Method for Behaviour of Materials in a Vertical Tube Furnace at 750°C and UL763 shall be considered non-combustible materials.
W415-1089 / 08.08.12
5.3 ALCOVE INSTALLATION
27
RECESS OR ALCOVE AREA
ENCLOSURE AREA
APPLIANCE
NOTE: Recesses or alcoves above the appliance can be made as deep as desired provided the minimum clearances to combustibles are maintained.
Non-combustible material can be used, provided the minimum clearances to combustible materials are applied. The minimum enclosure volume must be increased by no less than the volume of the recess. This adjustment
can be made by increasing any or all of the height, width and depth of the enclosure.
71.2
W415-1089 / 08.08.12
28
5.4 MINIMUM MANTEL CLEARANCES
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
Combustible mantel clearance can vary according to the mantel depth. Use the graph to help evaluate the clearance needed.
MANTEL DIMENSIONS
Ref Height Depth
A 38” B 13” 2” C 15” 4” D 17” 6” E 19” 8”
!
WARNING
E
73.1
D
C
B
M
A
N
T E
L
H E
*
H
T
21
19 17
,
15
A
13 11
246810
0
MANTEL DEPTH
W415-1089 / 08.08.12
6.0 FINISHING
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., PROVIDED THAT THESE MATERIALS DO NOT GO
BELOW THE SPECIFIED DIMENSION AS ILLUSTRATED.
DO NOT STRIKE, SLAM OR SCRATCH GLASS. DO NOT OPERATE APPLIANCE WITH GLASS
REMOVED, CRACKED, BROKEN OR SCRATCHED.
FACING AND/OR FINISHING MATERIAL MUST NEVER OVERHANG INTO THE APPLIANCE OPENING.
THE GLASS DOOR ASSEMBLY IS DESIGNED TO PIVOT FORWARD WHEN RELIEVING EXCESS
PRESSURE THAT MIGHT OCCUR. FINISHING OR OTHER MATERIALS MUST NOT BE LOCATED IN
THE OPENING SURROUNDING THE DOOR AS THIS WILL INTERFERE WITH THE DOORS ABILITY TO
RELIEVE THE PRESSURE.
6.1 DOOR REMOVAL / INSTALLATION
!
WARNING
RISK OF FIRE!
29
72.6
!
WARNING
GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED.
THE DOOR LATCHES ARE PART OF A SAFETY SYSTEM AND MUST BE PROPERLY ENGAGED. DO
NOT OPERATE THE APPLIANCE WITH LATCHES DISENGAGED.
FACING AND/OR FINISHING MATERIALS MUST NOT INTERFERE WITH AIR FLOW THROUGH AIR
OPENINGS, LOUVRES OPENINGS, OPERATION OF LOUVRES OR DOORS OR ACCESS FOR
SERVICE. OBSERVE ALL CLEARANCES WHEN APPLYING COMBUSTIBLE MATERIALS.
BEFORE DOOR IS REMOVED TURN THE APPLIANCE OFF AND WAIT UNTIL APPLIANCE IS COOL TO
THE TOUCH. DOORS ARE HEAVY AND FRAGILE SO HANDLE WITH CARE.
75.1
HANDLES
Before the glass door can be removed, the optional face­plate must be removed, see optional faceplate instructions for more information.
The glass door is secured to the top front edge of the fi rebox with two latches. Pull the handles of the latches forward, then lift the latches out from the door frame to release the top of the door. Next, pivot the door forward until the top edge clears the front of the appliance. Care­fully grip the sides of the door lifting it out from the retainer along the bottom of the door.
RETAINERS
W415-1089 / 08.08.12
30
6.2 LOG PLACEMENT
LOGS MUST BE PLACED IN THEIR EXACT LOCA TION IN THE APPLIANCE. DO NOT CHANGE OR MODIFY FROM THE PROPER LOG POSITION, SINCE APPLIANCE MAY NOT FUNCTION PROPERL Y AND DELAYED
THE LOGS ARE FRAGILE AND SHOULD BE HANDLED WITH CARE.
!
WARNING
IGNITION MA Y OCCUR.
The individual logs can be easily identifi ed by the numbers cast on the underside of each log. Phazer that is different in every installation. Take the time to carefully position the glowing embers for a maximum glowing effect. During the initial use of the appliance, log colours may vary. During the initial use of the appli­ance the colours will become more uniform as colour pigments burn in during the heat activated curing pro­cess.
A. Place the rear log (W135-0444) on rear bracket, ensure the log is
B. Place the charcoal strip log (W135-0448) on top of the grate aligning
TM
logs and glowing embers exclusive to Wolf Steel Ltd., provide a unique and realistic glowing effect
seated properly on the rear bracket and located on the center pin.
the notches in the charcoal strip with the grate.
C. Align the hole in the bottom of the front left log (W135-0450) with the
screw and spacer on the left side of the burner. The middle of this log rests against the charcoal strip.
D. Align the hole in the bottom of the front right log (W135-0451) with
the screw and spacer on the right side of the burner. The middle of the log rests against the charcoal strip.
W415-1089 / 08.08.12
Loading...
+ 78 hidden pages