Napoleon Installation And Operating Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
SAFETY BARRIER
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
EN
OPERATING INSTRUCTIONS
CERTIFIED TO CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22 AND ANSI Z21.50, FOR VENTED GAS FIREPLACES.
GX70NTE
FOR INDOOR USE ONLY
SAFETY INFORMATION
!
WARNING
If the information in these instructions
are not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this appliance
and shall be installed for the protection of children
and other at-risk individuals.
NATURAL GAS MODEL
GX70PTE
PROPANE GAS MODEL
!
DANGER
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
FR
PG
55
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
NOTE: The camera icon indicates video tutorials are available as additional reference,
visit http://mynapoleon.napoleonproducts.com/download/index/44/1
EN
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 6
2.3 GENERAL INFORMATION 7
2.4 RATING PLATE INFORMATION 8
3.0 VENTING 9
3.1 VENTING LENGTHS AND COMPONENTS FOR DIRECT VENT INSTALLATIONS 10
3.2 TYPICAL VENT INSTALLATION 11
3.3 SPECIAL VENT INSTALLATIONS 11
3.3.1 PERISCOPE TERMINATION 11
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES 12
3.5 VENTING APPLICATION FLOW CHART 13
3.6 DEFINITIONS 13
3.7 ELBOW VENT LENGTH VALUES 13
3.8 TOP EXIT HORIZONTAL TERMINATION 14
3.9 TOP EXIT VERTICAL TERMINATION 16
4.0 INSTALLATION 18
4.1 WALL AND CEILING PROTECTION 18
4.1.1 HORIZONTAL INSTALLATION 19
4.1.2 VERTICAL INSTALLATION 19
4.2 USING FLEXIBLE VENT COMPONENTS 20
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 20
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 21
4.2.3 APPLIANCE VENT CONNECTION 21
4.3 RESTRICTING VERTICAL VENTS 22
4.4 MOBILE HOME INSTALLATION 23
4.5 GAS INSTALLATION 23
5.0 FRAMING 24
5.1 MINIMUM FRAMING DIMENSIONS 25
5.2 MINIMUM ENCLOSURE CLEARANCES 27
5.2.1 ALCOVE CLEARANCE TO COMBUSTIBLES ENCLOSURE 28
5.3 RECESSED INSTALLATION 29
5.4 NON-COMBUSTIBLE FACING MATERIAL 30
5.5 MINIMUM COMBUSTIBLE MANTEL CLEARANCES 31
5.6 NAILING TAB INSTALLATION 31
6.0 FINISHING 32
6.1 LOG SHIPPING BRACKET 32
6.2 DECORATIVE PANELS 32
6.3 SAFETY SCREEN / DOOR REMOVAL AND INSTALLATION 32
6.4 FRONT HOOD INSTALLATION 33
6.5 LOG PLACEMENT 34
6.5.1 GLOWING EMBERS 35
6.5.2 CHARCOAL EMBERS 35
7.0 WIRING DIAGRAM 35
7.1 RECEPTACLE WIRING DIAGRAM 35
7.2 ELECTRONIC WIRING DIAGRAM 35
7.2.1 WIRING REQUIREMENTS 36
8.0 OPERATION 37
8.1 GENERAL TRANSMITTER LAYOUT 38
8.2 INITIALIZING THE TRANSMITTER/BATTERY HOLDER FOR THE FIRST TIME 38
8.3 TEMPERATURE DISPLAY 39
8.4 FLAME HEIGHT 39
8.5 BLOWER SPEED 39
8.6 NIGHT LIGHT DIMMER CONTROL 39
8.7 CONTINUOUS PILOT / INTERMITTENT PILOT (CPI / IPI) SELECTION 40
8.8 KEY LOCK 40
8.9 LOW BATTERY 40
8.10 BATTERY HOLDER/BACKUP INSTALLATION 40
9.0 ADJUSTMENT 41
9.1 PILOT BURNER ADJUSTMENT 41
9.2 VENTURI ADJUSTMENT 41
9.3 FLAME CHARACTERISTICS 42
10.0 MAINTENANCE 42
10.2 DOOR GLASS REPLACEMENT 43
10.1 ANNUAL MAINTENANCE 43
10.3 CARE OF GLASS 44
10.4 NIGHT LIGHT REPLACEMENT 44
10.5 BLOWER REPLACEMENT 45
11.0 REPLACEMENTS 45
12.0 OVERVIEW 46
12.1 VALVE TRAIN ASSEMBLY 47
13.0 ACCESSORIES 48
14.0 TROUBLESHOOTING 49
15.0 WARRANTY 51
16.0 SERVICE HISTORY 52
17.0 NOTES 53
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1519 / H / 03.22.17
TABLE OF CONTENTS
1.0 INSTALLATION OVERVIEW
materials such as tile,
See the section “MINIMUM
ENCLOSURE CLEARANCES” for
drywall (or other combustible material).
See the section “VENTING”
and “INSTALLATION”.
See the section
“MINIMUM MANTEL
CLEARANCES”
3
EN
See the section
“FRAMING”
See the section
“NON-COMBUSTIBLE
FINISHING”.
See the section
“RATING PLATE
INFORMATION”.
Side
Wall
SAFETY BARRIER
See the section
“FRAMING MINIMUM
CLEARANCE TO
COMBUSTIBLE
ENCLOSURES” for
non-combustible
marble, granite, etc.
IMPORTANT: Extra
support may be
required.
Batteries must be disposed of according to the local laws and regulations. Some batteries may be
recycled, and may be accepted for disposal at your local recycling center. Check with your
municipality for recycling instructions.
W415-1519 / H / 03.22.17
4
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and
!
WARNING
2.0 INTRODUCTION
EN
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND ARE PROHIBITED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to
operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns
or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is
recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an
adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot
surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These
screens and guards must be fastened to the fl oor.
• Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the
appliance.
• The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
• The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance
and to replace any part of the control system and any gas control which has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a
licensed or qualifi ed service person.
• Do not strike or slam shut the appliance glass door.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes
containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also
cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts certifi ed with the unit are to be
installed on the appliance.
• Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these
are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a
Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures
on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic
components.
• A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be
installed.
• If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
•
at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of
the appliance be kept clean.
• The millivolt version of this appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple
supplied by Wolf Steel Ltd.
3.1E
W415-1519 / H / 03.22.17
2.1 DIMENSIONS
SAFETY BARRIER
34 5/8”
879mm
11 13/16"
299mm
5
EN
5"
127mm
203mm
8"
1 15/16"
50mm
18 1/2"
470mm
7 3/16"
182mm
GAS
INLET
11 5/16"
288mm
35"
890mm
W415-1519 / H / 03.22.17
6
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
•
•
•
•
•
•
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed
in accordance with the current standard CAN/CSA
Z240MH Series, for gas equipped mobile homes, in
Canada or ANSI Z223.1 and NFPA 54 in the United
States.
As long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
WARNING
2.2 GENERAL INSTRUCTIONS
EN
!
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUATE VENTILATION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48 INCHES
(121.9cm) FROM THE FRONT FACE OF THE APPLIANCE.
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THE APPLIANCE MUST NOT BE OPERATED AT TEMPERATURES BELOW FREEZING (32°F / 0°C).
ALLOW THE APPLIANCE TO WARM TO ABOVE FREEZING PRIOR TO OPERATION.
to
This product must be installed by a licensed plumber or gas fi tter when installed within the
commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an
appliance insert or gas log.
The appliance off valve must be a “T” handle gas cock.
The fl exible connector must not be longer than 3 feet (0.9m).
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
We suggest that our gas
hearth products be installed
and serviced by professionals
W415-1519 / H / 03.22.17
www.ncertied.org
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1C
2.3 GENERAL INFORMATION
7
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION
AND QUALITY!
RATES AND EFFICIENCIES
NGP
Altitude (FT)0-4,5000-4500
Max. Input (BTU/HR)35,00032,000
Min. Inlet Gas Supply Pressure 4.5" (11mb) w.c.11" (27mb) w.c.
Max. Inlet Gas Supply Pressure13" (32mb) w.c.13" (32mb) w.c.
When the appliance is installed at elevations above 4,500 ft (1371m), and in the absence of specific
recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be
reduced at the rate of 4% for each additional 1,000 ft (305m).
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is suitable for
mobile home installation.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be
expected.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified kit is used.
NATURALELECTRONIC IGNITION
PROPANEELECTRONIC IGNITION
EN
W415-1519 / H / 03.22.17
8
W385-2070 / A
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
FOYER À GAZ VENTILÉ DIRECT. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER,
UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI
SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS
MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE
SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280.
DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME
RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS
DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.
POUR
UNE UTILISER AVEC BARRIÈRE W565-0144. SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE MANUEL D'INSTALLATION.
DIRECT VENT GAS FIREPLACE. SUITABLE FOR BEDROOM, BATHROOM AND BED-SITTING ROOM
INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE
WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES,
IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND
SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED
HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
FOR USE WITH BARRIER
W565-0144. FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
MANIFOLD PRESSURE: 3.5" (9MB) WATER COLUMN MANIFOLD PRESSURE: 10" (25MB) WATER COLUMN
PRESSION AU COLLECTEUR: 3.5" (9 MB) D'UNE COLONNE D'EAU PRESSION AU COLLECTEUR: 10" (25MB) D'UNE COLONNE D'EAU
MINIMUM SUPPLY PRESSURE: 4.5" (11MB) WATER COLUMN MINIMUM SUPPLY PRESSURE: 11" (27MB) WATER COLUMNPRESSION D'ALIMENTATION MINIMALE: 4.5" (11MB) D'UNE COLONNE D'EAU PRESSION D'ALIMENTATION MINIMALE: 11" (27MB) D'UNE COLONNE D'EAUMAXIMUM SUPPLY PRESSURE: 7.0" (17MB) WATER COLUMN MAXIMUM SUPPLY PRESSURE: 13" (32MB) WATER COLUMN
PRESSION D'ALIMENTATION MAXIMALE: 7.0" (17MB) D'UNE COLONNE D'EAU PRESSION D'ALIMENTATION MAXIMALE: 13" (32MB) D'UNE COLONNE D'EAUP4: 61.3% P4: 69.2%
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS
CERTIFIED WITH THIS UNIT ONLY.
WARNING:
THIS FIREPLACE USES AND REQUIRES A FAST ACTING THERMOCOUPLE. REPLACE
ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD.
DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES,
OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE. MINIMUM CLEARANCE
TO COMBUSTIBLE MATERIALS /
DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES:
TOP/ DESSUS 0 RECESSED DEPTH / PROFONDEUR D'ENCASTRE 18"
FLOOR / PLANCHER 0 VENT SIDES / COTES DE L'EVENT 2"
SIDES / COTES 0 VENT TOP / EVENT SUPERIEUR 3"
BACK / ARRIERE 0 VENT BOTTOM / EVENT INFERIEUR 2"
MANTEL / MANTEAU 10
1/2
”
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION
MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES
EXTENSIONS PLUS GRANDES.
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR LES LONGUEURS
D'EVACUATION MINIMALE ET MAXIMALE.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET
APPAREIL. UTILISER AVEC LES PORTES VITREES HOMOLOGUEES
SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT:
CE FOYER UTILISE ET REQUIERT UN THERMOCOUPLE À ACTION RAPIDE.
REMPLACEZ UNIQUEMENT AVEC UN THERMOCOUPLE À ACTION RAPIDE DE WOLF STEEL LTÉE.
N’AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES
AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS
INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS
NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.
L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A NAPOLEON.
REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. IL EST
IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR ASSURE LE MAINTIEN DU
SYSTEME DE PRISE D'AIR.
DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE
PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPPAREIL DE CHAUFFAGE.
ELECTRICAL RATING / CLASSIFICATION: 115V 0.82AMP, 60HZ
OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: EP35
SERIAL NUMBER/NO. DE SERIE:
GX70
GX70NT CX70NT MODEL GX70PT CX70PT
GX70NTE CX70NTE MODEL GX70PTE CX70PTE
A
SAMPLE
2.4 RATING PLATE INFORMATION
EN
WARNING: Allow appliance to cool before performing any maintenance or cleaning.
Both the rating plate and lighting instructions are attached to a chain located on the left side of the control
area near the valve.
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to
the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the
appliance and must be installed.
W415-1519 / H / 03.22.17
3.0 VENTING
WARNING
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
9
!
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0067 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5” (127mm) EXHAUST / 8” (203.2mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent
pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.2C
EN
W415-1519 / H / 03.22.17
10
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must
maximum allowable horizontal run is 20 feet (6.1m). When terminating vertically, the maximum allowable vertical vent
3.1 VENTING LENGTHS AND COMPONENTS FOR DIRECT VENT INSTALLATIONS
EN
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab
venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations,
clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to
all vent systems and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal
Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the
corresponding supplier:
VENT MANUFACTURER
DuraventW175-0170Wolf Steelwww.duravent.com
Amerivent5DSC-N2American Metal www.americanmetalproducts.com
Direct Temp5DT-AASelkirk www.selkirkcorp.com
SuperSeal5DDAMetal-Fabwww.mtlfab.com
procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake
collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the
following termination kits: wall terminal kit GD422-1, GD422R-2, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to
12/12 roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade).
With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD420 or the 10
foot (3.1m) vent kit GD430.
STARTER ADAPTER
PART NUMBER
SUPPLIERWEBSITE
minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged.
not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. When terminating horizontally, the
length is 40 feet (12.2m). The maximum number of vent connections is two horizontally or three vertically (excluding
the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is recommended that
all horizontal runs have a minimum 1/4” rise per foot or 21mm per meter using fl exible venting. For safe and proper
operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼”
(31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
8.3E
W415-1519 / H / 03.22.17
3.2 TYPICAL VENT INSTALLATION
Use the periscope kit to locate the air termination above grade. The periscope
11
OF OUTER 8” (203mm)
DIAMETER VENT PIPE FROM
THE APPLIANCE MUST BE
WRAPPED IN THE 1” (25mm)
THICK INSULATION SLEEVE
15 1/8" (38.4cm)
MINIMUM
WARNING!
THE FIRST TWO FEET
(SUPPLIED).
18" (45.7cm)
MAXIMUM
16" (40.6cm)
MINIMUM
40 FT (12m)
EN
MAXIMUM
3 FT (0.9m)
MINIMUM
34 5/8"
(88cm)
* See "VENTING" section
49 3/4"
(126.4cm)
MINIMUM
PLUS RISE*
TOP VENT
3.3 SPECIAL VENT INSTALLATIONS
3.3.1 PERISCOPE TERMINATION
must be installed so that when fi nal grading is completed, the bottom air slot is
located a minimum 12” (305m) above grade. The maximum allowable vent length
(including both rise and run) is 10’ (3m).
WARNING!
THE FIRST TWO FEET
OF OUTER 8” (203mm)
DIAMETER VENT PIPE FROM
THE APPLIANCE MUST BE
WRAPPED IN THE 1” (25mm)
THICK INSULATION SLEEVE
(SUPPLIED).
34 5/8"
(88cm)
12" (30.5cm)
MIN. TO
GRADE
30" (76.2cm)
MINIMUM
34 5/8"
(88cm)
9.3B
W415-1519 / H / 03.22.17
12
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES
EN
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
Q
= 3 feet
MIN
(0.9m)
R
= 2 x
MAX
Q
ACTUAL
R
MAX
INSTALLATIONS
CANADAU.S.A.
12” (30.5cm)12” (30.5cm)Clearance above grade, veranda porch, deck or balcony.
A
Δ
12” (30.5cm)
B
12” (30.5cm)*12” (30.5cm) *Clearance to permanently closed windows.
C
D
E
F
G
H
I
J
K
L
M
18”
(45.7cm)**
12” (30.5cm)**12” (30.5cm)**Clearance to unventilated soffi t.
0” (0mm)0” (0mm)Clearance to an outside corner wall.
0” (0mm)***0” (0mm)***
2” (51mm)***2” (51mm)***Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
3’(0.9m)3’(0.9m)****
3’ (0.9m)3’ (0.9m)****Clearance to a service regulator vent outlet.
12” (30.5cm)9” (229mm)Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
6’ (1.8m)3’ (0.9m) †Clearance to a mechanical air supply inlet.
7’ (2.1m) ‡7’ (2.1m) ****Clearance above a paved sidewalk or paved driveway located on public property.
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
9” (229mm)Clearance to windows or doors that open.
18”
(45.7cm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15’ (4.6m).
≤ 15 feet
(4.6m)
16” (40.6cm)16” (40.6cm)Clearance above the roof.
N
2’ (0.6m)†*2’ (0.6m) †*Clearance from an adjacent wall including neighbouring buildings.
O
8’ (2.4m)8’ (2.4m)
P
3’ (0.9m)3’ (0.9m)See chart for wider wall dimensions.
Q
6’ (1.8m)6’ (1.8m)
R
12” (30.5cm)12” (30.5cm)Clearance under a covered balcony
S
ΔThe terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18 inches clearance from an inside corner.
****This is a recommended distance. For additional requirements check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††*Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
W415-1519 / H / 03.22.17
Roof must be non-combustible without openings.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
12.1E
3.5 VENTING APPLICATION FLOW CHART
For the following symbols used in the venting calculations and examples are:
> - greater than
>
< - less than
<
H
H
H
V
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
13
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
TOP EXIT
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
EN
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.3A
3.6 DEFINITIONS
- equal to or greater than
- equal to or less than
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
T
- combined horizontal vent lengths in feet
R
- offset factor: .03 (total degrees of offset - 90°*) in feet
O
- combined vertical vent lengths in feet
T
3.7 ELBOW VENT LENGTH VALUES
FEET INCHES MILLIMETERS
14.1
15.1A
W415-1519 / H / 03.22.17
14
0
2.5
(0.8)5(1.5)
7.5
(2.3)
10
(3.1)
12.5 (3.8)15(4.6)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
17.5(5.3)20(6.1)
39 (11.9)
REQUIRED
VERTICAL
RISE IN FEET
(METERS)VT
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
7.5
(2.3)
10
(3.1)
12.5 (3.8)15(4.6)
17.5
(5.3)20(6.1)
FEET (METERS) H
T
3.8 TOP EXIT HORIZONTAL TERMINATION
EN
(HT) < (VT)
Simple venting confi guration (only one 90° elbow)
REQUIRED
40 (12.2)
39 (11.9)
30 (9.1)
See graph to determine the required vertical
for the required horizontal run HT.
rise V
T
VERTICAL
RISE IN FEET
20 (6.1)
(METERS)VT
10 (3.1)
0
2.5
(0.8)5(1.5)
7.5
(2.3)
10
(3.1)
12.5
(3.8)15(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
The shaded area within the lines represents
acceptable values for H
T
For vent confi gurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet (12.2m)
and V
17.5
(5.3)20(6.1)
T
Example:
V1 = 3 FT (0.9m)
V2 = 8 FT (2.4m)
VT = V1 + V2= 3 FT (0.9m ) + 8 FT (2.4m) = 11 FT (3.4m)
H
H2 = 2 FT (0.6m)
HR = H1 + H2 = 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m)
HO = .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT (1.7m)
H
H
Formula 1: HT < V
9.9 FT (3m) < 11 FT (3.4m)
Formula 2: HT + VT < 40 FT (12.2m)
20.9 FT (6.4m) < 40 FT (12.2m)
Since both formulas are met, this vent confi guration is acceptable.
= 2.5 FT (0.8m)
1
= HR + HO = 4.5 FT (1.4m) + 5.4 FT (1.6m) = 9.9 FT (3m)
T
+ VT = 9.9 FT (3m) + 11 FT (3.4m) = 20.9 FT (6.4m)
T
T
90°
V
90°
1
16.1B
90°
H
2
V
2
H
1
W415-1519 / H / 03.22.17
(HT) > (VT)
Simple venting configuration (only one 90° elbow)
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1:
Formula 2:
Example:
V
H
H
H
H
H
H
Formula 1:
4.2 V
10.7
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
Example:
V
V
V
H
H
H
H
H
H
H
H
Formula 1:
4.2 V
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
15
See graph to determine the required vertical rise VT for the
.
T
147 (373.4)
required horizontal run H
150 (381)
EN
REQUIRED
VERTICAL RISE
IN INCHES
(CENTIMETERS)
V
T
57 (144.8)
15.125 (38.4)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
Formula 1: H
3VT = 3FT (0.9m) x 4.5FT (1.4m) = 13.5FT (4.1m)
< 3V
T
T
< 40 feet (12.2m)
T
+ H
= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
1
2
+ H
= 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m)
R
O
= 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6 FT (6.3m)
T
< 3V
T
T
90°
90°
V
H
2
H
V
1
1
V
2
90°
3
16.1FT (4.9m) > 13.5FT (4.1m)
Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + VT < 40 feet (12.2m)
20.6FT (6.3m) < 40 (12.2m)
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration
will need to be established to satisfy both formulas.
18.1_2B
(9.1)
T
90°
17
EN
W415-1519 / H / 03.22.17
18
WARNING
WARNING
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
(NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR WHICH MUST
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, A MINIMUM OF 3 SCREWS MUST ALSO
4.0 INSTALLATION
EN
!
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE, ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
EXACTLY.
ALL EXHAUST AND INTAKE VENT PIPE JOINTS MUST BE SEALED USING RED RTV HIGH TEMP
SILICONE SEALANT (W573-0002) (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC (W573-0007)
BE SEALED USING MILL PAC.
BE USED TO ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2D
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
70.1
W415-1519 / H / 03.22.17
4.1.1 HORIZONTAL INSTALLATION
VENT
DETERMINE
THE
CORRECT
HEIGHT
FIRESTOP
SPACER
FINISHING
MATERIAL
CAULKING
VENT
SHIELD
WARNING
19
!
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall.
Having determined the correct height for the air terminal
location, cut and frame a hole in the exterior wall as
illustrated to accommodate the fi restop assembly.
Dry fi t the fi restop assembly before proceeding to
ensure the brackets on the rear surface fi t to the
inside surface of the horizontal framing.
The length of the vent shield may be cut shorter
for combustible walls that are less than 8 1/2”
(215.9mm) thick but the vent shield must extend
the full depth of the combustible wall.
NOTE : Do not fi ll the air space between the fi restop spacer and the
exterior wall with any type of insulating material (i.e., spray foam).
A. Apply a bead of caulking (not supplied) around the corner edge of
the inside surface of the fi restop assembly, fi t the fi restop
assembly to the hole and secure using the 4 screws (supplied in your manual baggie).
EN
B. Once the vent pipe is installed in its fi nal position, apply red RTV silicone (W573-0002) (not supplied)
between the pipe and the fi restop.
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor.
See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1" (25mm)
clearance between the vent pipe and any combustible material. Try to
center the vent pipe location midway between two joists to prevent
having to cut them. Use a plumb bob to line up the center of the
openings. A vent pipe shield will prevent any materials such as
insulation, from fi lling up the 1" (25mm) air space around the pipe.
Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the
Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished
ceiling), and secure over the opening in the ceiling. A fi restop must be placed
on the bottom of each framed opening in a roof or ceiling that the venting
system passes through. Apply a bead of caulking all around and place a
fi restop spacer over the vent shield to restrict cold air from being drawn into the
room or around the fi replace. Ensure that both spacer and shield maintain the required
clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply
Mill Pac sealant (W573-0007) (not supplied) or red RTV silicone (W573-0002) (not
supplied) between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1" (25mm)
air space around the pipe.
20.2C
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
VENT
PIPE
SHIELD
21.1B
W415-1519 / H / 03.22.17
CAULKING
PIPE
COLLAR
20
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high temperature
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
WARNING
A. Stretch the inner fl ex pipe to the required length taking into account
B.
C.
D.
The air terminal mounting plate may be recessed into the exterior wall
or siding no greater than the depth of its return fl ange.
HI-TEMP
SEALANT
ADD FASTENER TYPE
4.2 USING FLEXIBLE VENT COMPONENTS
EN
!
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
For safe and proper operation of the appliance, follow the venting instructions
exactly.
Elbow
Spacers
“Wolf Steel Approved Venting” or “E2” as identifi ed by the stamp on the fl ex pipes.
red RTV silicone W573-0002 (not supplied) or the high temperature sealant W5730007 Mill Pac (not supplied). However, the high temperature sealant W573-0007
Mill Pac (not supplied) must be used on the joint connecting the inner fl ex pipe
and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
22.1C
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION
the additional length needed for the fi nished wall surface. Apply
a heavy bead of the Mill Pac sealant (W573-0007) (not
supplied) to the inner sleeve of the air terminal. Slip the
vent pipe a minimum of 2” (50.8mm) over the inner
sleeve of the air terminal and secure with a minimum
of 3 screws.
Using the outer fl ex pipe, slide over the outer
combustion air sleeve of the air terminal and secure with
a minimum of 3 screws. Seal using red RTV silicone
(W573-0002) (not supplied).
Insert the vent pipes through the fi restop maintaining the
required clearance to combustibles. Holding the air terminal
(lettering in an upright, readable position), secure to the exterior
wall and make weather tight by sealing with caulking (not
supplied).
If more vent pipe needs to be used to reach the fi replace,
couple them together as illustrated. The vent system must be
supported approximately every 3 feet (0.9m) for both vertical
and horizontal runs. Use non-combustible strapping to
maintain the minimum clearance to combustibles.
SCREWS
(SUPPLIED)
HI-TEMP
SEALANT
OUTER
FLEX PIPE
CAULKING
INNER FLEX
PIPE
2" (50.8mm) OVERLAP
HIGH TEMPERATURE
INNER
FLEX PIPE
OUTER FLEX PIPE
SEALANT
SCREWS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE
W415-1519 / H / 03.22.17
23.1D
4.2.2 VERTICAL AIR TERMINAL INSTALLATION
A.
B.
C.
D.
E.
F.
G.
H.
24.1D
WARNING
A. Install the inner exhaust fl ue collar to the appliance. Secure
B.
21
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
NOTE : Fastening hardware provided with appropriate roof terminal and liner kits.
Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case the
venting is to be adequately supported using either an alternate
method suitable to the authority having jurisdiction or the optional
roof support.
Stretch the inner fl ex pipe to the required length. Slip the inner
fl ex pipe a minimum of 2” (51mm) over the inner pipe of the
air terminal connector and secure with a minimum of
3 screws. Seal using a heavy bead of Mill Pac sealant
(W573-0007) (not supplied).
Repeat using the outer fl ex pipe, using a heavy bead of red
RTV silicone (W573-0002) (not supplied) and a minimum of
3 screws.
Thread the air terminal connector / vent pipe assembly
down through the roof. The air terminal must be positioned vertically
and plumb. Attach the air terminal connector to the roof support,
ensuring that the top of the air terminal is 16” (40.6cm) above the
highest point that it penetrates the roof.
Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” (19mm) of the air terminal connector showing
above the top of the fl ashing. Slide the fl ashing underneath the
sides and upper edge of the shingles. Ensure that the air terminal
connector is properly centered within the fl ashing, giving a 3/4”
(19mm) margin all around. Fasten to the roof. Do not nail through
the lower portion of the fl ashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and top edges of the
fl ashing with roofi ng material.
Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure
the vent pipe goes into the hole in the terminal. Secure with 3
screws.
Apply a heavy bead of weatherproof caulking 2” (51mm)
above the fl ashing. Install the storm collar around the air
terminal and slide down to the caulking. Tighten to ensure that
a weather-tight seal between the air terminal and the collar is
achieved.
If more vent pipe needs to be used to reach the appliance see
“HORIZONTAL AIR TERMINAL INSTALLATION” section.
4.2.3 APPLIANCE VENT CONNECTION
!
ROOF SUPPORT
INNER PIPE
AIR
TERMINAL
CONNECTOR
MILL PAC
SEALANT
(W572-0007)
INNER FLEX PIPE
OUTER FLEX PIPE
2” (51mm)
AIR INLET
BASE
CAULKING
STORM COLLAR
WEATHER
SEALANT
FLASHING
EN
with a minimum of 3 #8 screws. Seal the joint and screw
holes using Mill Pac sealant (W573-0007) (not supplied).
Install the outer fl ex pipe to the appliance. Attach and seal
the joints using a red RTV silicone and a minimum of 3 #8
screws.
#8 X 1/2”
SELF
DRILLING
SCREWS
28.1D
2” (50.8mm)
OVERLAP
HIGH TEMP
SEALANT
W415-1519 / H / 03.22.17
22
!
WARNING
3. LEAST RESTRICTION
4.3 RESTRICTING VERTICAL VENTS
EN
TURN OFF GAS AND ELECTRICAL SUPPLY BEFORE SERVICING THE APPLIANCE.
APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE IS COOL.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTION EXACTLY.
TO AVOID DANGER OF SUFFOCATION KEEP THE PACKAGING BAG AWAY FROM BABIES AND
CHILDREN. DO NOT USE IN CRIBS, BED, CARRIAGES OR PLAY PENS. THIS BAG IS NOT A TOY.
Vertical installations may display a very active flame. If this appearance is not desirable, the exhaust outlet may
be restricted with a Wolf Steel approved restrictor kit. This kit is not recommended for short vertical vent runs.
Depending on the model and/or year of your appliance, mounting holes may not exist.
A.If mounting holes exist, remove the screws from the firebox top, align the restrictor plate as illustrated
and secure.
B.If mounting holes do not exist, align the restrictor plate as illustrated and secure using the two #8x1/2
hex head sheet metal screws (supplied).
C. Ensure the plate will pivot at the slot up into the exhaust outlet.
D. Depending on the amount of restriction desired, the restrictor plate can be left flat for most restriction or
bent up for varying degrees of restriction.
KNOT BEFORE THROWING AWAY.
MOUNTING
SCREWS
RESTRICTOR
EXHAUST COLLAR
#8 x ½ HEX HEAD
SHEET METAL
SCREW
TOP VIEW
FIREBOX TOP
RESTRICTOR
3
2
1
FIREBOX TOP
1. MOST RESTRICTION
2. MODERATE RESTRICTION
W415-1519 / H / 03.22.17
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the appliance.
4.4 MOBILE HOME INSTALLATION
Installation and servicing to be done by a qualifi ed installer.
•
•
•
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
•
• The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner
•
WARNING
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
23
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home
Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas
indicated on the rating plate.
Built in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the
base. Use appropriate fasteners, inserted through the holes in the base to secure. For free standing products
contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations,
the appliance must be fastened in place. It is recommended that the appliance be secured in all installations.
Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the
mobile home and prior to lighting the appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certifi ed kit is used.
Conversion Kits
This appliance is fi eld convertible between Natural Gas (NG) and Propane (P).
To convert from one gas to another consult your Authorized dealer/distributor.
4.5 GAS INSTALLATION
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
EN
29.1C
!
SPARKS OR OPEN FLAMES.
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSIONS” SECTION.
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Move the appliance into position and secure.
If equipped with a fl ex connector the appliance is designed to accept a 1/2” (13mm) gas supply.
Without the connector it is designed to accept a 3/8” (9.5mm) gas supply. The appliance is equipped
with a manual shut off valve to turn off the gas supply to the appliance.
Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
Z223.1 / NFPA 54 in the United States.
When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
assembly on its side to aid with servicing components.
Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
30.1A
W415-1519 / H / 03.22.17
24
WARNING
5.0 FRAMING
EN
!
RISK OF FIRE!
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE
APPLIANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH
ANY OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO
COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY.
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN
AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH
SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK
OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE
INSULATION AND OTHER MATERIALS ARE SECURED.
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO
MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS
LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS
CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS,
OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING
ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE
FURNACE AT 1382°F (750°C) AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE
MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
BASE.
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, OR SPECIFIED IN THE
INSTALLATION INSTRUCTIONS, THEY MUST BE INSTALLED.
IF SPECIFIED IN THE INSTALLATION INSTRUCTION FINISHING MUST BE DONE USING A NON-
COMBUSTIBLE MATERIAL SUCH AS NON-COMBUSTIBLE BOARD, CERAMIC TILE, MARBLE, ETC.
DO NOT USE WOOD OR DRYWALL. ANY FIRE RATED DRYWALL IS NOT ACCEPTABLE
71.1C
W415-1519 / H / 03.22.17
5.1 MINIMUM FRAMING DIMENSIONS
NON-COMBUSTIBLE
MATERIAL
25
EN
ENCLOSURE
TOP
FINISHING
MATERIAL
6 3/4"[171mm]
59 1/2"
[151cm]
MIN.
ELECTRICAL
CONNECTION
19" *
[48.3cm]
* Based on a 1/2" (12.7mm) finishing material
34 7/8"
[88.6cm]
3" [76.2mm]
STEEL STUD
1 15/16" [50mm]
7 3/16" [182.6mm]
35 1/2" [90.2cm]
GAS INLET
LOCATION
41 5/8"
[105.7cm]
MIN.
STEEL STUD
W415-1519 / H / 03.22.17
26
It is best to frame your appliance after it is positioned and the vent system is installed. Frame to local building
codes.
EN
It is not necessary to install a hearth extension with this appliance.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the finished floor
materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower
access door and the installation of many decorative flashing accessories.
Non-Combustible material (brick,stone or ceramic tile) may protrude over the black areas of the appliance.
Maintain these minimum clearances to combustibles from appliance and vent surfaces:
Appliance framing:
Non- Combustible Appliance finishing:
Front - 3” (76mm) to sides of appliance opening
- 6 3/4” (171.5mm) above appliance opening
Combustible Appliance finishing:
- 59 1/2” (151.1cm) from bottom of appliance to enclosure top
- 3” (76mm) to top of vent pipe*
- 2” (51mm) to sides and bottom of vent pipe*
Non-combustible finishing material (ie. cement board, brick, stone, tile) must be used to finish the front of
the appliance.
* HORIZONTAL VENT SECTIONS: A minimum of 2" (51mm) at the bottom and sides and 3" (76mm) at
the top of the vent pipe on all horizontal runs to combustibles is required. Use firestop spacer W010-1800
(supplied).
* VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use firestop spacer W500-0096 (not supplied).
OUTSIDE
CHASE
35 1/2"
90.2cm
33 7/8"
86cm
35 1/2 "
90.2cm
47 7/8"
1.2m
18 9/16"
47cm
35 1/2"
90.2cm
152.4mm
6”
INSIDE
CHASE
18 9/16"
47cm
SIDE
WALL
W415-1519 / H / 03.22.17
34 7/8"
[88.6cm]
1" [25mm]
FRAME
49 3/4"[126.4cm]MINIMUM
PLUS RISE *
42 3/8"
[107.6cm]
CEILING
5.2 MINIMUM ENCLOSURE CLEARANCES
[198cm]
ENCLOSURE
HEIGHT
COMBUSTIBLE
MYLAR
SLEEVE
NON-COMBUSTIBLE
MATERIAL
78"
NON-COMBUSTIBLE
BRICK
3"
[76mm]
2"
[51mm]
27
EN
0” (0MM) IF
NON-COMBUSTIBLE
FINISHING MATERIAL
IS USED SUCH AS
BRICK AND STONE
6 3/4"
[883mm]
59 1/2"
[151.1cm]
CEILING
STEEL STUD
FRAME
34 7/8"
[88.6cm]
1" [25mm]
FIRESTOP
ASSEMBLY
49 3/4"
[126.4cm]
MINIMUM
PLUS RISE *
TOP EXIT ENCLOSURE
The appliance requires a minimum enclosure height of 59 1/2" (151.1cm). For temperature requirements, the
enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of the combustible
wall penetration.
* See "MINIMUM FRAMING DIMENSION" section for details on reducing vent pipe top clearances.
These parameters also apply to the illustrations found in the "MINIMUM ENCLOSURE
CLEARANCES" section.
W415-1519 / H / 03.22.17
28
FINISHING MATERIAL
5.2.1 ALCOVE CLEARANCE TO COMBUSTIBLES ENCLOSURE
EN
78"
[198cm]
ENCLOSURE
HEIGHT
NON-COMBUSTIBLE
MATERIAL
59 1/2"
[151.1cm]
CEILING
COMBUSTIBLE
MAX.
4 1/2"
[114mm]
7 1/2"
[191mm]
MYLAR
SLEEVE
STEEL STUD
FRAME
COMBUSTIBLE
NON-COMBUSTIBLE
BRICK
3"
[76mm]
2"
[51mm]
FIRESTOP
ASSEMBLY
0” (0MM) IF
NON-COMBUSTIBLE
IS USED SUCH AS
BRICK AND STONE
42 3/8"
[107.6cm]
34 7/8"
[88.6cm]
1" [25mm]
49 3/4"
[126.4cm]
MINIMUM
PLUS RISE *
* See venting section.
IMPORTANT: THE FIRESTOP ASSEMBLY PROVIDED MUST BE USED WHEN THE VENT PIPES PASS
THROUGH ANY COMBUSTIBLE WALL, FLOOR OR CEILING.
NOTE: THE MINIMUM ENCLOSURE VOLUME MUST BE INCREASED BY NO LESS THAN THE VOLUME OF
THE RECESS. THIS ADJUSTMENT CAN BE MADE BY INCREASING ANY OR ALL OF THE HEIGHT, WIDTH,
AND DEPTH OF THE ENCLOSURE.
W415-1519 / H / 03.22.17
5.3 RECESSED INSTALLATION
SAFETY SCREEN
B
A
C
SAFETY SCREEN
B
A
C
D
WARNING
29
!
INSTALLING A TELEVISION ABOVE A FIREPLACE MAY CAUSE DISCOLOURATION, MELT OR
DAMAGE THE ELECTRONIC DEVICE. USE THE INDICATED CLEARANCE AND REFER TO THE
INSTRUCTIONS OF THE TELEVISION MANUFACTURER FOR FURTHER INFORMATION .
WARNING: Non-combustible facing materials must not project more than 4" (102mm) from the face
of the door (all three sides). If greater projections are desired, increase the clearance to the sides and
top by 2" (51mm) for every addtional 1" (25mm) of projection. If using an optional surround, the same
rule applies, starting from the top of the surround. Ensure clearances are maintained for surround
removal, as it must lift off the appliance for maintenance.
NON-COMBUSTIBLE
MATERIAL
EN
MINIMUM CLEARANCES CHART
A
B
C
Before placing anything above a heat source, it is advisable to follow proper clearances and
manufacturer’s instructions.
A.When a mantel is installed between the appliance and an electronic device or other materials, the
effect of direct heat on the electronics or other materials will be reduced. Follow mantel height and
depth instructions for proper clearances. NOTE: Increasing the horizontal length of the mantel will further reduce the intensity of heat on the electronics.
B.Refer to “MINIMUM MANTEL CLEARANCES” section for more detailed mantel clearance
information.
4 1/2" (114mm) MAX
7 1/2" (190mm) MIN
42 5/8" (108.3cm) MIN
W415-1519 / H / 03.22.17
30
NON-COMBUSTIBLE FACING MATERIAL
5.4 NON-COMBUSTIBLE FACING MATERIAL
EN
WARNING: Non-combustible facing material must not project more than 4” (101.6mm) from the face of the
door (all four sides). If greater projections are desired, increase the clearance to the sides and top by 2”
(50.8mm) for every additional 1” (25.4mm) of projection. If using an optional surround, the same rule applies,
starting from the top of the surround. Ensure clearances are maintained for surround removal, as it must lift
off the appliance for maintenance.
A
B
A
B
3”(76.2mm)
2” (50.8mm)
0” (0mm)
OPTIONAL
SURROUND
6” (152.4mm)
5” (127mm)
4” (101.6mm)
TOP OF
3”(76.2mm)
2” (50.8mm)
0” (0mm)
4” (101.6mm)
APPLIANCE
DOOR
SECTION A - ASECTION B - B
71.6
6” (152.4mm)
5” (127mm)
TOP OF
APPLIANCE
DOOR
W415-1519 / H / 03.22.17
Loading...
+ 78 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.