Napoleon GX70NT, GX70NTE, GX70PT, GX70PTE Installation And Operating Instructions Manual

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
EN
OPERATING INSTRUCTIONS
CONFORMS TO AMERICAN NATIONAL STANDARDS: ANSI Z21.50, CERTIFIED TO CANADIAN CSA 2.22 FOR VENTED GAS FIREPLACES.
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
!
WARNING
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
Decorative Product: Not for use as a heating appliance.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
GX70NT & GX70NTE
NATURAL GAS MODEL
GX70PT & GX70PTE
PROPANE GAS MODEL
SAFETY BARRIER
GX70 ILLUSTRATED
!
DANGER
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
FR PG 65
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone (705)721-1212 • Fax (705)722-6031 • www.napoleonfi replaces.com • hearth@napoleonproducts.com
$10.00
BARRIER
1.28F
W415-1519 / C / 11.06.15
2
EN
TABLE OF CONTENTS
NOTE: The camera icon indicates video tutorials are available as additional reference, visit http://www.napoleonfi replaces.com/category/product-support/support-centre/
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 GX70 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 6
2.3 GENERAL INFORMATION 7
2.4 RATING PLATE INFORMATION 8
3.0 VENTING 9
3.1 VENTING LENGTHS AND COMPONENTS FOR DIRECT VENT INSTALLATIONS 10
3.2 TYPICAL VENT INSTALLATION 11
3.3.1 PERISCOPE TERMINATION 12
3.3 SPECIAL VENT INSTALLATIONS 12
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES 13
3.5 VENTING APPLICATION FLOW CHART 14
3.6 DEFINITIONS 14
3.7 ELBOW VENT LENGTH VALUES 14
3.8 TOP EXIT HORIZONTAL TERMINATION 15
3.9 TOP EXIT VERTICAL TERMINATION 17
4.0 INSTALLATION 19
4.1 WALL AND CEILING PROTECTION 19
4.1.1 HORIZONTAL INSTALLATION 20
4.1.2 VERTICAL INSTALLATION 20
4.2 USING FLEXIBLE VENT COMPONENTS 21
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 21
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 22
4.2.3 APPLIANCE VENT CONNECTION 23
4.3 USING RIGID VENT COMPONENTS 23
4.3.1 HORIZONTAL AIR TERMINAL INSTALLATION 23
4.3.2 VERTICAL AIR TERMINAL INSTALLATION 24
4.3.3 RESTRICTING VERTICAL VENTS 24
4.4 MOBILE HOME INSTALLATION 25
4.5 GAS INSTALLATION 26
4.6 OPTIONAL WALL SWITCH (MILLIVOLT ONLY) 26
5.0 FRAMING 27
5.1 MINIMUM FRAMING DIMENSIONS 28
5.2 MINIMUM ENCLOSURE CLEARANCES 30
5.2.1 ALCOVE CLEARANCE TO COMBUSTIBLES ENCLOSURE 31
5.3 RECESSED INSTALLATION 32
5.4 NON-COMBUSTIBLE FACING MATERIAL 33
5.5 MINIMUM COMBUSTIBLE MANTEL CLEARANCES 34
5.6 NAILING TAB INSTALLATION 34
6.1 LOG SHIPPING BRACKET 35
6.2 DECORATIVE PANELS 35
6.0 FINISHING 35
6.3 SAFETY SCREEN / DOOR REMOVAL AND INSTALLATION 36
6.4 LOG PLACEMENT 37
6.5 GLOWING EMBERS 38
6.6 LOGO PLACEMENT 38
6.7 WIRING DIAGRAM (ELECTRONIC) 39
7.0 OPERATION 40
7.1 GX70NT & GX70PT (MILLIVOLT) 40
7.2 GX70NTE & GX70PTE (ELECTRONIC) 41
7.3 GENERAL TRANSMITTER LAYOUT (ELECTRONIC ONLY) 42
7.4 INITIALIZING THE TRANSMITTER/BATTERY HOLDER FOR THE FIRST TIME 42
7.5 TEMPERATURE DISPLAY 43
7.6 FLAME HEIGHT 43
7.7 BLOWER SPEED 43
7.8 NIGHT LIGHT DIMMER CONTROL 44
7.9 CONTINUOUS PILOT / INTERMITTENT PILOT (CPI / IPI) SELECTION 44
7.10 KEY LOCK 44
7.11 LOW BATTERY / MANUAL BYPASS 44
7.12 BATTERY HOLDER/BACKUP INSTALLATION (ELECTRONIC ONLY) 45
8.0 ADJUSTMENT 46
8.1 PILOT BURNER ADJUSTMENT 46
8.2 VENTURI ADJUSTMENT 46
9.0 MAINTENANCE 47
9.1 FLAME CHARACTERISTICS 47
9.2 ANNUAL MAINTENANCE 48
9.3 CARE OF GLASS 48
10.0 REPLACEMENTS 49
10.1 NIGHT LIGHT REPLACEMENT 49
10.2 DOOR GLASS REPLACEMENT 50
10.3 BLOWER REPLACEMENT 51
11.0 GX70 OVERVIEW 52
12.0 GX70NT/PT MILLIVOLT VALVE TRAIN ASSEMBLY 53
13.0 GX70NTE/PTE ELECTRONIC VALVE TRAIN ASSEMBLY 54
14.0 GX70 ACCESSORIES 55
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1519 / C / 11.06.15
1.0 INSTALLATION OVERVIEW
3
See the section “MINIMUM ENCLOSURE CLEARANCES” for drywall (or other combustible material).
See the section “MINIMUM MANTEL CLEARANCES”
See the section “NON-COMBUSTIBLE FINISHING”.
EN
See the section “VENTING” and “INSTALLATION”.
See the section “FRAMING”
See the section “FRAMING - MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES” for non-combustible
materials such as tile, marble, granite, etc.
IMPORTANT: Extra support may be required.
Side Wall
See the section “RATING PLATE INFORMATION
Batteries must be disposed of according to the local laws and regulations. Some batteries may be recycled, and may be accepted for disposal at your local recycling center. Check with your municipality for recycling instructions.
SAFETY BARRIER
GX70 ILLUSTRATED
W415-1519 / C / 11.06.15
4
2.0 INTRODUCTION
EN
!
WARNING
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES TO THIS APPLIANCE OR IT’S CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures
on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic components.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be
installed.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and
at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
This appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
3.1D
W415-1519 / C / 11.06.15
2.1 GX70 DIMENSIONS
SAFETY BARRIER
34 5/8”
879mm
34 5/8"
879mm
5
EN
11 13/16"
299mm
5"
127mm
203mm
8"
GX70 ILLUSTRATED
1 15/16"
50mm
18 1/2"
470mm
7 3/16"
182mm
GAS INLET
11 5/16"
288mm
35"
890mm
W415-1519 / C / 11.06.15
6
A
A
2.2 GENERAL INSTRUCTIONS
EN
!
WARNING
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUA TE VENTILA TION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” (1219mm) FROM
THE FRONT FACE OF THE APPLIANCE.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35 mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas log.
The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches (914mm).
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
www.ncertied.org
We suggest that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1B
W415-1519 / C / 11.06.15
2.3 GENERAL INFORMATION
7
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
RA TES AND EFFICIENCIES
GX70
NG LP
Altitude (FT) 0-4,500 0-4500 Max. Input (BTU/HR) 35,000 32,000 Min. Inlet Gas Supply Pressure 4.5" (11mb) w.c. 11" (27mb) w.c. Max. Inlet Gas Supply
Pressure Manifold Pressure (Under Flow
Conditions)
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home installation.
No external electricity (110 volts or 24 volts) is required for the gas millivolt system operation.(MILLIVOLT ONLY)
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
7" (17mb) w.c. 13" (32mb) w.c.
3.5" (9mb) w.c. 10" (25mb) w.c.
EN
When the appliance is installed at elevations above 4,500 ft (1372m), and in the absence of specifi c recommendations from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for each additional 1,000 ft (305 m).
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance and must be installed.
W415-1519 / C / 11.06.15
8
FIREPLACE / FOYER À GAZ VENTILÉ.CE / FOYER À GAZ VENTILÉ.
UNE UTILISER AVEC B UNE UTILISER AVEC B
D'INSTALLATION S D'INSTALLATION
4001657 (NGZ)4001657 (NGZ)
40016594001659
(
)SA)
ALTITUDE / ELEVATIONALTITUDE / ELEVATION
0-4500
32,0
WATER COLUMN WATER COLUMN
D'UNE COLONNE D'EAU D'UNE COLONNE D'EAU
0" (17MB) WATER COLUMN 0" (17MB) WATER COLUMN
:P4:
61.3%
6969
IONS. REFERER AU MANUEL D'INSTRUCTIO
MODEL GX70PT C MODEL GX70PT C
2.4 RATING PLATE INFORMATION
WARNING: Allow appliance to cool before performing any maintenance or cleaning
EN
Both the rating plate and lighting instructions are attached to a chain located on the left side of the control area near the valve.
DIRECT VENT GAS FIREPLACE. SUITABLE FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
W565-0144. FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING:
ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD. DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE. MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS / DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES: TOP/ DESSUS 0 RECESSED DEPTH / PROFONDEUR D'ENCASTRE 18" FLOOR / PLANCHER 0 VENT SIDES / COTES DE L'EVENT 2" SIDES / COTES 0 VENT TOP / EVENT SUPERIEUR 3" BACK / ARRIERE 0 VENT BOTTOM / EVENT INFERIEUR 2" MANTEL / MANTEAU 10 * MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES.
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTI.
FOR USE WITH BARRIER
9700539 (WSL) 4001657 (NGZ) 4001658 (NAC) 4001659 (WUSA)
GX70NT CX70NT MODEL GX70PT CX70PT GX70NTE CX70NTE MODEL GX70PTE CX70PTE
35,000 BTU/h INPUT / ALIMENTATION 32,000 BTU/h 21,000 REDUCED INPUT / ALIMENTATION REDUITE 22,000
PRESSION AU COLLECTEUR: 3.5" (9 MB) D'UNE COLONNE D'EAU PRESSION AU COLLECTEUR: 10" (25MB) D'UNE COLONNE D'EAU MINIMUM SUPPLY PRESSURE: 4.5" (11MB) WATER COLUMN MINIMUM SUPPLY PRESSURE: 11" (27MB) WATER COLUMN PRESSION D'ALIMENTATION MINIMALE: 4.5" (11MB) D'UNE COLONNE D'EAU PRESSION D'ALIMENTATION MINIMALE: 11" (27MB) D'UNE COLONNE D'EAU MAXIMUM SUPPLY PRESSURE: 7.0" (17MB) WATER COLUMN MAXIMUM SUPPLY PRESSURE: 13" (32MB) WATER COLUMN PRESSION D'ALIMENTATION MAXIMALE: 7.0" (17MB) D'UNE COLONNE D'EAU PRESSION D'ALIMENTATION MAXIMALE: 13" (32MB) D'UNE COLONNE D'EAU P4: 61.3% P4: 69.2%
THIS FIREPLACE USES AND REQUIRES A FAST ACTING THERMOCOUPLE. REPLACE
1/2
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS. REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR LES LONGUEURS D'EVACUATION MINIMALE ET MAXIMALE.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
0-4500FT (0-1370m) ALTITUDE / ELEVATION 0-4500FT (0-1370m)
MANIFOLD PRESSURE: 3.5" (9MB) WATER COLUMN MANIFOLD PRESSURE: 10" (25MB) WATER COLUMN
"
FOYER À GAZ VENTILÉ DIRECT. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER,
UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.
UNE UTILISER AVEC BARRIÈRE W565-0144. SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE MANUEL D'INSTALLATION.
WUSA
INPUT / ALIMENTATION
4
61.3%
4:
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET APPAREIL. UTILISER AVEC LES PORTES VITREES HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT: CE FOYER UTILISE ET REQUIERT UN THERMOCOUPLE À ACTION RAPIDE.
REMPLACEZ UNIQUEMENT AVEC UN THERMOCOUPLE À ACTION RAPIDE DE WOLF STEEL LTÉE. N’AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM. L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A NAPOLEON. REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. IL EST IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR ASSURE LE MAINTIEN DU SYSTEME DE PRISE D'AIR. DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPPAREIL DE CHAUFFAGE. ELECTRICAL RATING / CLASSIFICATION: 115V 0.82AMP, 60HZ OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: EP35
SERIAL NUMBER/NO. DE SERIE:
GX70
POUR
W385-2070
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
W415-1519 / C / 11.06.15
3.0 VENTING
9
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0067 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5” (127mm) EXHAUST / 8” (203.2mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.2C
EN
W415-1519 / C / 11.06.15
10
3.1 VENTING LENGTHS AND COMPONENTS FOR DIRECT VENT INSTALLATIONS
EN
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
PART 5”/8” SUPPLIER WEBSITE
Duravent W175-0170 Wolf Steel www.duravent.com
Amerivent 5DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 5DT-AA Selkirk www.selkirkcorp.com
SuperSeal 5DDA Metal-Fab www.mtlfab.com
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following termination kits: wall terminal kit GD422-1, GD422R-1, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12 roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD420 or the 10 foot (3.1m) vent kit GD430.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is recommended that all horizontal runs have a minimum 1/4” (6.4mm) rise per foot/meter using fl exible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” (31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
8.3A
W415-1519 / C / 11.06.15
3.2 TYPICAL VENT INSTALLATION
11
EN
16" (406MM)
MINIMUM
WARNING!
THE FIRST TWO FEET
OF OUTER 8” (203MM)
DIAMETER VENT PIPE FROM
THE APPLIANCE MUST BE
WRAPPED IN THE 1” (25MM)
THICK INSULATION SLEEVE
(SUPPLIED).
40 FT (12M)
MAXIMUM
3 FT (1M) MINIMUM
34 5/8"
(879MM)
TOP VENT
W415-1519 / C / 11.06.15
EN
12
3.3 SPECIAL VENT INSTALLATIONS
18" (610MM)
MAXIMUM
15 1/8" (384MM)
MINIMUM
34 5/8"
(879MM)
PLUS RISE*
48 1/4"
(1226MM)
MINIMUM
WARNING!
THE FIRST TWO FEET
OF OUTER 8” (178MM)
DIAMETER VENT PIPE FROM
THE APPLIANCE MUST BE WRAPPED IN THE 1” (25MM) THICK INSULATION SLEEVE
(SUPPLIED).
* See "VENTING" section
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum 12" (305m) above grade. The maximum allowable vent length is 10' (3m) for
a fi replace and 8' (2.4m) for a stove.
30" (762MM)
WARNING!
THE FIRST TWO FEET
OF OUTER 8” (178MM)
DIAMETER VENT PIPE FROM
THE APPLIANCE MUST BE WRAPPED IN THE 1” (25MM) THICK INSULATION SLEEVE
(SUPPLIED).
MINIMUM
34 5/8"
(879MM)
12" (305MM)
MINIMUM
TO GRADE
W415-1519 / C / 11.06.15
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES
COVERED BALCONY APPLICATIONS ††*
R
13
EN
Q
S
G
P
Q
= 3 feet
MIN
(0.9m)
R
= 2 x
MAX
Q
ACTUAL
INSTALLATIONS
CANADA U.S.A.
A 12” (305mm) 12” (305mm) Clearance above grade, veranda porch, deck or balcony.
B 12” (305mm)
Δ
9”
(229mm)
Clearance to windows or doors that open.
Δ
C 12” (305mm)* 12” (305mm) * Clearance to permanently closed windows.
D
18”
(457mm)**
18” (457mm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ (0.6m) from the center line of the terminal.
E 12” (305mm)** 12” (305mm)** Clearance to unventilated sof t. F 0” (0mm) 0” (0mm) Clearance to an outside corner wall.
0” (0mm)***
G
2” (51mm)***
0”
(0mm)***
2”
(51mm)***
H 3’(0.9m) 3’ (0.9m)****
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15’ (4.6m).
I 3’ (0.9m) 3’ (0.9m)**** Clearance to a service regulator vent outlet.
J 12” (305mm) 9” (229mm)
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K 6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet. L 7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
M
12”
(305mm)††
12”
(305mm)****
Clearance under a veranda, porch or deck.
N 16” (406mm) 16” (406mm) Clearance above the roof.
O 2’ (0.6m)†* 2’ (0.6m) †* Clearance from an adjacent wall including neighbouring buildings.
P 8’ (2.4m) 8’(2.4m) Roof must be non-combustible without openings.
Q 3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
R 6’ (1.8m) 6’ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
S 12” (305mm) 12” (305mm) Clearance under a covered balcony
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
12.1D
R
MAX
IHHW
(4.6m)
W415-1519 / C / 11.06.15
14
3.5 VENTING APPLICATION FLOW CHART
EN
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
TOP EXIT
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.3A
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are: > - greater than > - equal to or greater than < - less than < - equal to or less than HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet HR - combined horizontal vent lengths in feet HO - offset factor: .03 (total degrees of offset - 90°*) in feet VT - combined vertical vent lengths in feet
3.7 ELBOW VENT LENGTH VALUES
FEET INCHES MILLIMETERS 0.03 0.5 12.7 15° 0.45 6.0 152.4 30° 0.9 11.0 279.4 45° 1.35 16.0 406.4 90°* 2.7 32.0 812.8
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
14.1
15.1A
W415-1519 / C / 11.06.15
3.8 TOP EXIT HORIZONTAL TERMINATION
15
(HT) < (VT)
Simple venting confi guration (only one 90° elbow)
See graph to determine the required vertical
rise VT for the required horizontal run HT.
40 (12.2)
39 (11.9)
REQUIRED
30 (9.1)
VERTICAL
RISE IN FEET
20 (6.1)
(METERS)VT
10 (3.1)
0
2.5
(0.8)5(1.5)
7.5
(2.3)
(3.1)
10
12.5
(3.8)15(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
The shaded area within the lines represents
acceptable values for HT and V
For vent confi gurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet (12.2m)
17.5 (5.3)20(6.1)
T
EN
Example: V1 = 3 FT (0.9m)
V2 = 8 FT (2.4m) VT = V1 + V2= 3 FT (0.9m ) + 8 FT (2.4m) = 11 FT (3.4m) H1 = 2.5 FT (0.8m) H2 = 2 FT (0.6m) HR = H1 + H2 = 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m) HO = .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT (1.7m) HT = HR + HO = 4.5 FT (1.4m) + 5.4 FT (1.6m) = 9.9 FT (3m) HT + VT = 9.9 FT (3m) + 11 FT (3.4m) = 20.9 FT (6.4m)
Formula 1: HT < V
T
9.9 FT (3m) < 11 FT (3.4m) Formula 2: HT + VT < 40 FT (12.2m)
20.9 FT (6.4m) < 40 FT (12.2m) Since both formulas are met, this vent confi guration is acceptable.
90°
V
90°
1
16.1B
90°
H
2
V
2
H
1
W415-1519 / C / 11.06.15
16
V
V V V
(HT) > (VT)
Simple venting configuration (only one 90° elbow)
EN
See graph to determine the required vertical rise VT for the
150 (3810)
147 (3733.8)
required horizontal run H
.
T
REQUIRED
VERTICAL RISE
100 (2540)
IN INCHES
(MILLIMETERS) V
T
57 (1447.8)
14 (355.6)
50 (1270)
5
0
(1.5)
1.17 (0.4)
(3.1)
15
10
12.5 (3.8)
(4.6)
19.5’ (5.9)
20 (6.1)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT
The shaded area within the lines represents acceptable
values for H
and VT
T
For vent configurations requiring more than one 90° elbow, the following formulas apply:
H
Formula 1: Formula 2: HT + V
< 4.2 V
T
T
< 24.75 feet (7.5m)
T
90°
H
1
H
2
Example:
= VT = 6 FT (1.8m)
1
H
= 3 FT (0.9m)
1
H
= 5 FT (1.5m)
2
H
= H
+ H
R
H
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7FT (0.8m)
O
HT = HR + HO = 8FT (2.4m) + 2.7FT (0.8m) = 10.7FT (3.3m) H
+ V
T
= 3FT (0.9m) + 5FT (1.5m) = 8FT (2.4m)
1
2
= 10.7FT (3.3m) + 6FT (1.8m) = 16.7FT (5.1m)
T
V
1
90°
Formula 1: HT < 4.2 V
4.2 VT = 4.2FT (1.3m) x 6FT (1.8m) = 25.2FT (7.7m)
10.7 FT (3.3m) < 25.2 FT (7.7m)
Formula 2: HT + V
16.7 FT (5.1m) < 24.75 FT (7.5m)
Since both formulas are met, this vent configuration is acceptable.
Example:
= 4 FT (1.2m)
1
= 1.5 FT (0.5m)
2
= V
+ V
T
H
= 2 FT (0.6m)
1
H
= 1 FT (0.3m)
2
H
= 1 FT (0.3m)
3
H
= 1.5 FT (0.5m)
4
H
= H
R
H
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT (2.5m)
O
H
= H
T
H
+ V
T
= 4FT (1.2m) + 1.5FT (0.5m) = 5.5FT (1.7m)
1
2
+ H2 + H
1
+ H
R
= 13.6FT (4.2m) + 5.5FT (1.7m) = 19.1FT (5.8m)
T
+ H4 = 2FT (0.6m) + 1FT (0.3m) + 1FT (0.3m) + 1.5FT (0.5m) = 5.5FT (1.7m)
3
= 5.5FT (1.7m) + 8.1FT (2.5m) = 13.6FT (4.2m)
O
Formula 1: HT < 4.2 V
4.2 VT = 4.2FT (1.3m) x 5.5FT (1.7m) = 23.1FT (7m)
T
< 24.75 FT (7.5m)
T
T
90°
90°
90°
H
1
90°
V
1
V
H
H
2
3
H
4
2
13.6 FT (4.2m) < 23.1 FT (7m) Formula 2: HT + V
19.1 FT (5.8m) < 24.75 FT (7.5m)
< 24.75 FT (7.5m)
T
Since both formulas are met, this vent configuration is acceptable.
16.11A
W415-1519 / C / 11.06.15
3.9 TOP EXIT VERTICAL TERMINATION
17
(HT) < (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run HT.
40 (12.2)
30 (9.1)
REQUIRED
VERTICAL
RISE IN FEET
(METERS) V
T
3 (0.9)
20 (6.1)
10 (3.1)
0
5
(1.5)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring one or more 90° elbows the following formulas apply: Formula 1: H
Formula 2: HT + V
< V
T
T
< 40 feet (12.2m)
T
10
(3.1)
15
(4.6)
20
(6.1)
for the
T
EN
T
Example: V
= 5 FT (1.5m)
1
V
= 6 FT (1.8m)
2
V
= 10 FT (3.1m)
3
V
= V
+ V2 + V3 = 5FT (1.5m) + 6FT (1.8m) + 10FT (3.1m) = 21FT (6.4m)
T
1
H
= 8 FT (2.4m)
1
H
= 2.5 FT (0.8m)
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT (2.5m)
H
= H
T
H
+ V
T
Formula 1: HT < V
18.6FT (5.7m) < 21FT (6.4m) Formula 2: HT + V
39.6FT (12.1m) < 40FT (12.2m)
= 8FT (2.4m) + 2.5FT (0.8m) = 10.5 FT (3.2m)
1
2
+ H
= 10.5FT (3.2m) + 8.1FT (2.5m) = 18.6FT (5.7m)
R
O
= 18.6FT (5.7m) + 21FT (6.4m) = 39.6FT (12.1m)
T
T
< 40 FT (12.19m)
T
Since both formulas are met, this vent configuration is acceptable.
90°
V
3
90°
H
2
V
H
1
V
1
2
90°
90°
18.1A
W415-1519 / C / 11.06.15
18
EN
Simple venting configurations.
(HT) > (VT)
20 (6.1)
19 (5.8)
See graph to determine the required vertical rise V
required horizontal run H
.
T
for the
T
REQUIRED
VERTICAL
RISE IN FEET
(METERS) V
T
3 (0.9)
10 (3.1)
0
5
(1.5)
10
(3.1)
15
(4.6)
20
(6.1)
25
(7.6)
(9.1)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
values for H
and VT
T
For vent configurations requiring more than two 90° elbows the following formulas apply: Formula 1: H
Formula 2: HT + V
< 3V
T
T
< 40 feet (12.2m)
T
Example: V
= 2 FT (0.6m)
1
V
= 1 FT (0.3m)
2
V
= 1.5 FT (0.5m)
3
V
= V1+V2+V3= 2FT (0.6m) + 1FT (0.3m) + 1.5FT (0.5m) = 4.5FT (1.4m)
T
H
= 6 FT (1.8m)
1
H
= 2 FT (0.6m)
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT (2.5m)
H
= H
T
H
+ V
T
= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
1
2
+ H
= 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m)
R
O
= 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6 FT (6.3m)
T
90°
H
V
1
1
90°
V
H
2
V
2
3
90°
90°
Formula 1: HT < 3V 3VT = 3FT (0.9m) x 4.5FT (1.4m) = 13.5FT (4.1m)
T
16.1FT (4.9m) > 13.5FT (4.1m) Since this formula is not met, this vent configuration is unacceptable. Formula 2: HT + VT < 40 feet (12.2m)
20.6FT (6.3m) < 40 (12.2m)
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration will need to be established to satisfy both formulas.
18.1_2B
30
T
W415-1519 / C / 11.06.15
4.0 INSTALLATION
19
!
WARNING
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
EXACTLY.
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
WHICH MUST BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2B
EN
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
WARNING
70.1
W415-1519 / C / 11.06.15
20
4.1.1 HORIZONTAL INSTALLATION
EN
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall as illustrated to accommodate the fi restop assembly. Dry fi t the fi restop assembly before proceeding to ensure the brackets on the rear surface fi t to the inside surface of the horizontal framing.
The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2” (215.9mm) thick but the vent shield must extend the full depth of the combustible wall.
A. Apply a bead of caulking (not supplied) around the corner edge of the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your manual baggie).
!
WARNING
CAULKING
FIRESTOP
SPACER
VENT
SHIELD
DETERMINE THE CORRECT HEIGHT
FINISHING MATERIAL
B. Once the vent pipe is installed in its fi nal position, apply high temperature sealant W573-0007 (not supplied) between the pipe and the fi restop.
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for various roof pitches are available from your authorized dealer / distributor. See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1" (25mm) clearance between the vent pipe and any combustible material. Try to center the vent pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings. A vent pipe shield will prevent any materials such as insulation, from fi lling up the 1" (25mm) air space around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf Steel
vent pipe shield plate or equivalent (in the case of a fi nished ceiling), and secure over the opening in the ceiling. A fi restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a fi restop spacer over the vent shield to restrict cold air from being drawn into the room or around the fi replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply sealant between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1" (25mm) air space around the pipe.
W415-1519 / C / 11.06.15
20.2A
FIRESTOP
UNDERSIDE OF
VENT PIPE
SHIELD
SHIELD
JOIST
CAULKING
VENT
PIPE
COLLAR
VENT
PIPE