CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE.
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED UNDER AMERICAN NATIONAL STANDARDS, ANSI Z21.11.2, VOLUME II FOR UNVENTED ROOM HEATERS.
1
GVF42P
PROPANE
GVF42N
NATURAL GAS
CERTIFIED FOR THE UNITED STATES USING ANSI METHODS.
SAFETY INFORMATION
!
WARNING
If the information in these instructions are
not followed exactly, a fi re or explosion
may result causing property damage,
personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
- This is an unvented gas-fi red heater that
uses air (oxygen) from the room in which it is
installed. Provisions for adequate combustion
and ventilation air must be provided. Refer to
section “ COMBUSTION AND VENTILATION AIR
PROVISIONS”.
This appliance may be installed in an aftermarket,
permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases.
VENT FREE MILLIVOLT
SYSTEM
!
WARNING
HOT GLASS WILL CAUSE
DO NOT TOUCH GLASS UNTIL
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
BURNS.
COOLED.
$10.00
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin
W415-0379 / E / 04.24.12
1.0 INSTALLATION OVERVIEW
Louvres, see “L42
LOUVRE INSTALLATION”
section.
3
Hood, see “HOOD”
section.
Rating Plate, see
“RATING PLATE
INFORMATION”
section.
Logo, see “LOGO
PLACEMENT” section.
Logs, see “LOG PLACEMENT”
section.
W415-0379 / E / 04.24.12
4
2.0 INTRODUCTION
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
• Under no circumstances should this appliance be modifi ed.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate
appliance according to operating instructions could cause fi re or injury.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges
may be sharp.
• Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing and
operating the appliance. Never obstruct the front opening of the appliance.
• If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it
serviced. Keep burner and control compartment clean.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance. Toddlers,
young children and others may be susceptible to accidental contact burns. A physical barrier is recommended
if there are at risk individuals in the house. To restrict access to an appliance, install an adjustable safety gate
to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and
draperies.
• Ensure you have incorporated adequate safety measures to protect infants/toddlers from touching hot
surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from
hot surfaces. These screens and guards must be fastened to the fl oor.
• Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the
appliance are kept clean. The appliance should be inspected before use and at least annually by a qualifi ed
service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding
material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other
fl ammable vapours and liquids.
• Furniture or other objects must be kept a minimum of 4 feet away from the front of the appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has been
under water.
• Do not allow fans to blow directly into the appliance. Avoid any drafts that alter burner fl ame patterns.
• Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this appliance.
• Carbon or soot should not occur in a vent free appliance as it can distribute into the living area of your home.
If you notice any signs of carbon or soot, immediately turn off your appliance and arrange to have it serviced
by a qualifi ed technician before operating it again.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all
plastic bags, these are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as
well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against
Carbon Monoxide.
• If equipped, the screen must be in place (closed) when the appliance is in operation.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance.
Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or
damage to decorations, a T.V. or other electronic components.
!
WARNING
3.4B
W415-0379 / E / 04.24.12
2.1 DIMENSIONS
35 ½"
38 ½"
5½"
3"
16 ½"
20"
22"
42"
2¼"
2.2 GENERAL INSTRUCTIONS
* CARBON MONOXIDE POISONING MAY LEAD TO DEATH
EARLY SIGNS OF CARBON MONOXIDE POISONING RESEMBLE THE FLU, WITH HEADACHE,
DIZZINESS AND/OR NAUSEA. IF YOU HAVE THESE SIGNS, THE HEATER MAY NOT BE WORKING
PROPERLY. GET FRESH AIR AT ONCE! HAVE HEATER SERVICED.
SOME PEOPLE---PREGNANT WOMEN, PERSONS WITH HEART OR LUNG DISEASE, ANEMIA,
THOSE UNDER THE INFLUENCE OF ALCOHOL, THOSE AT HIGH ALTITUDES--- ARE MORE
AFFECTED BY CARBON MONOXIDE THAN OTHERS.
!
WARNING
5
IT IS RECOMMENDED THAT PERSONS WITH RESPIRATORY PROBLEMS NOT USE VENT FREE
APPLIANCES
THE APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS INDICATED ON THE RATING PLATE.
THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES.
OBJECTS PLACED IN FRONT OF THE HEATER SHOULD BE KEPT A MINIMUM OF 48” AWAY FROM
THE FRONT FACE OF THE APPLIANCE.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH
THIS APPLIANCE. USING NON-LISTED ACCESSORIES AND REPLACEMENT PARTS (BLOWERS,
LOUVRES, TRIMS, GAS COMPONENTS, VENT COMPONENTS, ETC.) COULD RESULT IN A SAFETY
HAZARD AND WILL VOID THE LIMITED LIFETIME WARRANTY.
NOT DESIGNED FOR USE WITH A GLASS DOOR. SCREEN MUST BE CLOSED WHEN APPLIANCE IS
IN OPERATION.
THIS APPLIANCE MUST NOT BE INSTALLED IN A BEDROOM OR BATHROOM.
This gas appliance should be installed and serviced by a qualifi ed installer to conform with local codes.
Installation practices vary from region to region and it is important to know the specifi cs that apply to your
area, for example: in Massachusetts State:
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36“.
• The appliance is not approved for installation in a bedroom or bathroom unless the appliance is a direct
vent sealed combustion product.
• A carbon monoxide detector is required in all rooms containing gas fi red appliances.
• WARNING: This product must be installed by a licensed plumber or gas fi tter when installed within the
commonwealth of Massachusetts.
• Un-vented room appliance shall be installed in accordance with 527 CMR 30.00 and 248 CMR 3.00
through 7.00.
• Sellers of un-vented propane or natural gas-fi red space / room appliances shall provide to each purchaser
a copy of 527 CMR 30.00 upon the sale of the appliance from http://www.napoleonfi replaces.com/
Webshare/installation_manuals/mass_requirements.pdf
In absence of local codes, install the appliance to the current National Fuel Gas Code, ANSI Z223.1
Installation Code which can be obtained from:
American National Standards Institute Inc. or National Fire Protection Association Inc.
1430 Broadway Batterymarch Park
New York, NY 10018 Quincy, MA 02269
W415-0379 / E / 04.24.12
6
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The appliance
must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When installed with a blower the junction box must be electrically connected and grounded in accordance
with local codes. In the absence of local codes, use the current ANSI / NFPA 70 National Electric Code. In
the case where the blower is equipped with a power cord it must
be connected into a properly grounded receptacle. The grounding
prong must not be removed from the cord plug.
As long as the required clearance to combustibles is maintained,
the most desirable and benefi cial location for the appliance is in
the center of a building, thereby allowing the most effi cient use of
the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
Institute
Specialists
®
(NFI) as NFI Gas
considered.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth. NOTE:
This does not apply to stoves.
* Air shortage caused by an inadequate air supply, improper log positions, the addition of foreign or
unapproved materials or the failure to properly maintain the appliance, may result in incomplete combustion of
the fuel. Incomplete combustion results in soot being deposited inside the fi rebox as well as surfaces outside
the appliance. If any soot deposits are observed, shut off the appliance immediately and arrange for it to be
serviced by a qualifi ed technician.
4.2D
2.3 GENERAL INFORMATION
FOR YOUR SATISFACTION, ALL BURNER ASSEMBLIES HAVE BEEN TEST-FIRED TO ASSURE THEIR
OPERA TIONS AND QUALITY!
Altitude (FT)0-2,000*0-2,000*
Max. Input (BTU/HR)30,00030,000
Max. Output (BTU/HR)99.9%99.9%
Effi ciency (w/the fan on)99.9%99.9%
Min. Inlet Gas Supply Pressure4.5" Water Column11" Water Column
Max. Inlet Gas Supply Pressure7" Water Column13" Water Column
Manifold Pressure (Under Flow Conditions)3.5" Water Column10" Water Column
* When the appliance is installed at elevations above 2,000ft, and in the absence of specifi c recommendations from
the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for each
additional 1,000ft.
This appliance is only for use with the type of gas indicated on the rating plate. For rating plate information, see “RA TING PLA TE INFORMATION” section. This appliance is not convertible for use with other gases, unless a certifi ed kit is
used.
NO EXTERNAL ELECTRICITY (1 10 VOLTS OR 24 VOL TS) IS REQUIRED FOR THE GAS SYSTEM OPERATION.
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance is equipped with a pilot light safety system referred to as an oxygen depletion sensor and is designed to
turn off the appliance if not enough fresh air is available.
APPLIANCE
NGLP
Use only accessories designed for and listed with your specifi c appliance.
Not designed for use with a glass door. Screens must be closed when appliance is in operation.
W415-0379 / E / 04.24.12
2.4 RATING PLATE INFORMATION
ISSAAGAGA
EQUEQU
AA
TETE
COCO
OVEOV
SS
TT
ALLAL
AA
TIOTIO
ALTITUDE
#820637#820637
SITS
#8
#8214
BE CLOSEE CLOSE
NFORMATION MANUAL PRONFORMATION MANUAL
4
)4001657 (NGZ
4001659 (WUSA4001659 (WUSA
7
THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET,
PERMANENTLY LOCA TED, MANUF ACTURED (MOBILE) HOME, WHERE
NOT PROHIBITED BY LOCAL CODES. THIS APPLIANCE IS ONLY FOR USE
WITH THE TYPE OF GAS INDICATED ON THE RATING PLATE. THIS
APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES.
MINIMUM SUPPLY PRESSURE: 4.5" WATER COLUMNMINIMUM SUPPLY PRESSURE: 11" WATER COLUMNMAXIMUM SUPPLY PRESSURE: 7.0" WATER COLUMNMAXIMUM SUPPLY PRESSURE: 13" WATER COLUMNSIT CONTROL: #820637 SIT CONTROL: #820636
OPERATING PILOT OXYPROTECTOR: #8214 OPERATING PILOT OXYPROTECTOR: #8404
**0-2000FT (0-610m) ALTITUDE 0-2000FT (0-610m)**
CERTIFIED UNDER: ANSI Z21.1 1.2a-2008 VOLUME II, UNVENTED ROOM HEATER
ALTITUDE
INPUT
MANIFOLD PRESSURE: 3.5" WATER COLUMN MANIFOLD PRESSURE: 10" WATER COLUMN
EDUCED INPUT
214
THIS IS A GAS-FIRED UNVENTED ROOM HEATER THAT REQUIRES
ADEQUATE COMBUSTION AND VENTILATION AIR. THIS U NIT IS NOT
APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM
INSTALLATION.
I
001657 (NGZ
** ABOVE 2,000FT, CONSULT LOCAL AUTHORITY HAVING JURISDICTION
NOT FOR USE WITH SOLID FUEL.
WARNING: FIREPLACE SCREENS MUST BE CLOSED WHILE IN OPERATION.DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN
CONTACT WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE. DONOT USE BLOWER INSERT, HEAT EXCHANGER INSERT OR OTHER
ACCESSORIES NOT APPROVED FOR USE WITH THIS HEATER. IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTAINANCE CAN CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE. REFER TO THE OWNER'S INFORMATION MANUAL PROVIDED WITH THIS APPLIANCE. INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER,
SERVICE AGENCY OR THE GAS SUPPLIER.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS:
TOP / SIDES / BACK / FLOOR 0”
RECESSED DEPTH 22“
MANTEL 2”*
WOLF STEEL L TD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
MAXIMUM HORIZONTAL EXTENSION: 2". SEE INSTRUCTION MANUAL FOR GREA TER
EXTENSIONS.
ELECTRICAL RATING: 115V 0.82AMP, 60HZ
OPTIONAL FAN KIT: GZ550-KT
SERIAL NUMBER: G/CVF42
W385-0248 / G
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to
the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
W415-0379 / E / 04.24.12
8
A
A
3.0 INSTALLATION
3.1 COMBUSTION AND VENTILATION AIR PROVISIONS
This appliance shall not be installed in a confi ned space or unusually tight construction unless provisions are
provided for adequate combustion and ventilation air.
The National Fuel Gas Code, ANSI Z223.1 / NFPA 54 defi nes a confi ned space as a space whose volume is
less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances
installed in that space and an unconfi ned space as a space whose volume is not less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space.
Rooms communicating directly with the space in which the appliances are installed, through openings not
furnished with doors are considered a part of the unconfi ned space.
The GVF42 is rated at 30,000 BTUs per hour for natural gas and 30,000 BTUs for propane and therefore requires a minimum unconfi ned space of 1,500 cubic feet.
3.2 DETERMINING CONFINED OR UNCONFINED SPACE
To determine the volume of the room where the appliance is to be installed, multiply the width x the length x
the ceiling height of that room measured in feet. If any adjoining rooms are connected by grilles or openings
such as kitchen pass-throughs, etc., the volume of those rooms may be added to the total.
Multiply the room volume by 1000 and divide this amount by 50 to determine the maximum BTU/hr that the
space can support with adequate combustion and ventilation air.
dd the Btu/hr of all fuel burning appliances located within the space such as gas furnace, gas water
appliance, etc. Do not include direct vent gas appliances which draw their input and output air from and to the
outdoors.
17.1A
!
WARNING
IF THE AREA IN WHICH THE APPLIANCE MAY BE OPERATED IS SMALLER THAN THAT DEFINED AS
AN UNCONFINED SP ACE OR IF THE BUILDING IS OF UNUSUALLY TIGHT CONSTRUCTION, PROVIDE
ADEQUA TE COMBUSTION AND VENTILATION AIR BY ONE OF THE METHODS DESCRIBED IN THE
NA TIONAL FUEL GAS CODE ANSI Z223.1/ NFPA 54 , AIR FOR COMBUSTION AND VENTILATION, OR THE
APPLICABLE LOCAL CODE.
IF THE AREA IN WHICH THE APPLIANCE MAY BE OPERATED DOES NOT MEET THE REQUIRED VOLUME
FOR INDOOR COMBUSTION AIR, COMBUSTION AND VENTILATION AIR SHALL BE PROVIDED BY ONE
OF THE METHODS DESCRIBED IN THE ANSI Z223.1 / NFPA 54, THE INTERNA TIONAL FUEL GAS CODE,
OR APPLICABLE LOCAL CODES.
Unusually tight construction is defi ned as construction where:A) Walls and ceilings exposed to the outside atmosphere have a continuous water vapour retarder with a
rating of 1 perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed, and
B) Weather stripping has been added on openable windows and doors, and
C) Caulking or sealants are applied to areas such as joints around window and door frames, between sole
plates and fl oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical,
and gas lines, and at other openings.
n unvented room appliance is recommended for use as a secondary heat source rather than as a primary
source. Gas combustion produces water vapour which could occur at the rate of approximately one ounce of
water for every 1,000 BTU/hr of gas input. During the cold weather season, indoor humidity levels tend to be
low. Consequently, this water vapour can enhance the living space. However if a problem should occur:
A) Ensure suffi cient combustion and circulation air
B) Use a dehumidifi er
C) Do not use the unvented room appliance as a primary heat source
Without suffi cient fresh air for proper operation, poor fuel combustion can result. Carbon Monoxide is a result
of poor combustion.
If additional fresh air is required, use one of the methods described in the National Fuel Gas Code, ANSI
Z223.1 / NFPA54 or the applicable local code.
W415-0379 / E / 04.24.12
Room Volume = Length x Width x Height
LENGTH
HEIGHT
ROOM 2
ROOM 1
WIDTH
Max BTU/hr = Room Volume x 1000 / 50
If for example:
The length of the rooms is 10 feet,
The width of Room 1 is 10 feet,
The width of Room 2 is 15 feet,
The height of the rooms is 8 feet.
The volume of Room 1: 10x10x8 = 800 cubic feet
The volume of Room 2: 10x15x8 = 1200 cubic feet
19.1B
EXAMPLE 1:
In this example, because there is no door to the adjoining room, the volume of the adjoining room may be
added to the volume of the room with the heater to get a total unconfi ned space.
9
The total unconfi ned space: 800 + 1200 = 2000 cubic feet.
Maximum BTU/h: 2000x1000 = 40,000 BTU/h
50
19.2
If there are no more fuel burning appliances within this space then the 30,000 BTU/h input of the appliance is
suitable to be installed. This also assumes that the construction of this space is not unusually tight.
EXAMPLE 2:
If in this example a solid door separates Room 1 from Room 2, the volume of Room 2 could not be used. In
this case the maximum BTU/h would be:
Maximum BTU/h: 800x1000 = 16,000 BTU/h
50
19.3
This would be considered a confi ned space since it can not support the 30,000 BTU/h input of the appliance
and it would be necessary to provide adequate combustion and ventilation air to Room 1.
W415-0379 / E / 04.24.12
10
3.3 GAS INSTALLATION
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Installation and servicing to be done by a qualifi ed installer.
A. Move the appliance into position and secure.
B. If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.
C.Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
D. When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
E. The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner
assembly on it’s side to aid with servicing components.
F.Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.
!
WARNING
SPARKS OR OPEN FLAMES.
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
30.1A
3.4 OPTIONAL WALL SWITCH / THERMOSTAT
!
WARNING
DO NOT CONNECT EITHER THE WALL SWITCH, THERMOSTAT OR GAS VALVE DIRECTLY TO 110
VOLT ELECTRICITY.
For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient
location. Route a 2 strand, solid core millivolt wire from the valve to the wall switch or millivolt thermostat. The
recommended maximum lead length depends on wire size:
WIRE SIZE MAX. LENGTH
14 gauge 100 feet
16 gauge 60 feet
18 gauge 40 feet
Disconnect the existing wires from terminals 1 and 3 (from the
ON/OFF switch) and replace with the leads from the wall switch / millivolt thermostat.
3
2
1
50.1
W415-0379 / E / 04.24.12
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.