Napoleon GDS26P-1, GDS26N-1 Installation And Operating Instructions Manual

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED TO CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22 AND ANSI Z21.50 FOR VENTED GAS FIREPLACES.
FOR INDOOR USE ONLY
SAFETY INFORMATION
!
WARNING
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a certifi ed kit is used.
GDS26N-1
NATURAL GAS
GDS26P-1
PROPANE
SAFETY
BARRIER
!
DANGER
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
EN
FR PG 53
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone (705)721-1212 • Fax (705)720-9081 • www.napoleonfi replaces.com • hearth@napoleonproducts.com
$10.00
W415-2183 / B / 02.10.17
EN
2
TABLE OF CONTENTS
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 DIMENSIONS 5
2.2 HARDWARE LIST 5
2.3 GENERAL INSTRUCTIONS 6
2.4 GENERAL INFORMATION 7
2.5 RATING PLATE INFORMATION 7
3.0 VENTING 8
3.1 VENTING LENGTHS AND COMPONENTS 9
3.2 TYPICAL VENT INSTALLATION 10
3.3 SPECIAL VENT INSTALLATIONS 12
3.3.1 PERISCOPE TERMINATION 12
3.3.2 CORNER TERMINATION 12
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES 13
3.5 VENTING APPLICATION FLOW CHART 14
3.6 DEFINITIONS 14
3.7 ELBOW VENT LENGTH VALUES 15
3.8 TOP EXIT HORIZONTAL TERMINATION 15
3.9 REAR EXIT HORIZONTAL TERMINATION 17
3.10 TOP OR REAR EXIT VERTICAL TERMINATION 19
3.11 VERTICAL THROUGH EXISTING CHIMNEY 21
3.12 REAR VENT CONVERSION 22
4.0 INSTALLATION 23
4.1 WALL AND CEILING PROTECTION 23
4.1.1 HORIZONTAL INSTALLATION 24
4.1.2 VERTICAL INSTALLATION 24
4.1.3 APPLIANCE VENT CONNECTION 25
4.1.5 HORIZONTAL AIR TERMINAL INSTALLATION 26
4.1.4 EXTENDED HORIZONTAL AND CORNER TERMINAL INSTALLATION 26
4.1.6 VERTICAL AIR TERMINAL INSTALLATION 27
4.2 MOBILE HOME INSTALLATION 28
4.3 GAS INSTALLATION 28
4.4 MINIMUM CLEARANCE TO COMBUSTIBLES 29
5.0 ELECTRICAL CONNECTION 31
5.1 WIRING DIAGRAM 31
6.0 FINISHING 32
6.1 SAFETY BARRIER AND GLASS DOOR 32
6.2 DOOR GLASS REPLACEMENT 33
6.3 LOG PLACEMENT 33
6.4 VERMICULITE 34
6.5 LOGO PLACEMENT 34
7.0 BLOWER REPLACEMENT 35
8.0 OPERATION 36
8.1 GENERAL TRANSMITTER LAYOUT 37
8.2 INITIALIZING THE TRANSMITTER/BATTERY HOLDER FOR THE FIRST TIME 37
8.3 TEMPERATURE DISPLAY 38
8.4 FLAME HEIGHT 38
8.5 BLOWER SPEED 38
8.6 NIGHT LIGHT DIMMER CONTROL 38
8.7 CONTINUOUS PILOT / INTERMITTENT PILOT (CPI / IPI) SELECTION 39
8.8 KEY LOCK 39
8.9 LOW BATTERY 39
8.10 BATTERY HOLDER/BACKUP INSTALLATION 39
9.0 ADJUSTMENTS 40
9.1 PILOT INJECTOR AND ORIFICE REPLACEMENT 40
9.2 PILOT BURNER ADJUSTMENT 40
9.3 FLAME CHARACTERISTICS 41
9.4 VENTURI ADJUSTMENT 41
9.5 RESTRICTING VERTICAL VENTS 41
10.0 MAINTENANCE 42
10.1 ANNUAL MAINTENANCE 42
10.2 NIGHT LIGHTTM REPLACEMENT 43
10.2.1 BULB REPLACEMENT 43
10.2.2 LENS ASSEMBLY INSTALLATION 43
10.2.3 LENS ASSEMBLY REPLACEMENT 43
10.3 CARE OF GLASS 43
11.0 REPLACEMENTS 44
11.1 OVERVIEW 45
11.2 VALVE TRAIN ASSEMBLY 46
12.0 ACCESSORIES 47
13.0 TROUBLESHOOTING 48
14.0 WARRANTY 50
15.0 SERVICE HISTORY 51
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-2183 / B / 02.10.17
1.0 INSTALLATION OVERVIEW
3
Door, see “SCREEN AND GLASS DOOR INSTALLATION AND REMOVAL” section.
Top vent, see “REAR VENT
EN
CONVERSION” section.
Venting, see “VENTING” section.
SAFETY
BARRIER
Rating Plate, see “RATING PLATE INFORMATION” section.
Blower, see “OPTIONAL BLOWER INSTALLATION” section.
Batteries must be disposed of according to the local laws and regulations. Some batteries may be recycled, and may be accepted for disposal at your local recycling center. Check with your municipality for recycling instructions.
W415-2183 / B / 02.10.17
4
3.2C
!
WARNING
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES OR ALTERATIONS TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi re or injury.
Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance
It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch fi re.
Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage of decorations, a T.V. or other electronic components.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
2.0 INTRODUCTION
EN
W415-2183 / B / 02.10.17
5
2.1 DIMENSIONS
SAFETY BARRIER
2.2 HARDWARE LIST
901mm
35 1/2"
7"
178mm
5 7/8"
4"
102mm
37"
29 1/8"
740mm
935mm
GAS LINE ACESS
POWER CORD
23 9/16"
598mm
(CENTRE OF REAR VENT)
19 3/16"
487mm
149mm
483mm
19"
EN
1
TYPE DESCRIPTION QTY
1 2
NOTE: Only fasteners supplied with the appliance will be illustrated.
1 3/4” SELF TAPPING SCREW 1/4” HEX, 1/2” LONG SHEET METAL SCREW
2
4 3
W415-2183 / B / 02.10.17
6
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER
conform with local codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for example in Massachusetts State:
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or ANSI Z223.1 and NFPA 54 in the United States.
As long as the required clearance to combustibles is maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
WARNING
2.3 GENERAL INSTRUCTIONS
EN
!
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUATE VENTILATION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48 INCHES
(121.9cm) FROM THE FRONT FACE OF THE APPLIANCE.
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THE APPLIANCE MUST NOT BE OPERATED AT TEMPERATURES BELOW FREEZING (32°F / 0°C).
ALLOW THE APPLIANCE TO WARM TO ABOVE FREEZING PRIOR TO OPERATION.
to
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of Massachusetts. The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas log. The appliance off valve must be a “T” handle gas cock. The fl exible connector must not be longer than 3 feet (0.9m). A Carbon Monoxide detector is required in all rooms containing gas fi red appliances. The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
We suggest that our gas hearth products be installed and serviced by professionals
W415-2183 / B / 02.10.17
www.ncertied.org
who are certied in the U.S. by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1C
2.4 GENERAL INFORMATION
SAMPLE
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
Altitude (FT) 0-4,500 0-4,500 Max. Input (BTU/HR) 25,000 25,000 Max. Output Steady State (BTU/HR) 20,500 20,500 Efficiency (w/the fan on) 82% 82%
7
EN
APPLIANCE
NG P
Min. Inlet Gas Supply Pressure Max. Inlet Gas Supply Pressure Manifold Pressure (Under Flow Conditions)
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Never obstruct the front opening of the appliance.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance and shall be installed.
2.5 RATING PLATE INFORMATION
DIRECT VENT VENTED GAS FIREPLACE. APPROVED FOR BEDROOM, BATHROOM & BEDSITTING
ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED
MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME
CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US
STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR
MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
FOR USE WITH BARRIER W565-0156. FOLLOW THE INSTALLATION INSTRUCTIONS
MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG)
9700539 (WSL) 4001657 (NGZ)
PRESSION AU COLLECTEUR: 3.5" D'UNE
4001658 (NAC) 4001659 (WUSA)
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
PRESSION D'ALIMENTATION MIN: 4.5" D'UNE
MAX. SUPPLY PRESSURE: 7" W.C. (NG)
PRESSION D'ALIMENTATION MAX: 7" D'UNE
CAUTION: FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY. WARNING: DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE. THIS VENTED GAS FIREPLACE IS NOT FOR USE WITH AIR FILTERS. DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE ELECTRICAL RATING: BLOWER KIT GS67, 115V
0.5AMP 60HZ THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS INSTALLATION MANUAL FOR VENTING SPECIFICS. MINIMUM AND MAXIMUM VERTICAL VENT LENGTHS ARE 3 FEET AND 40 FEET RESPECTIVELY.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN
LOCATED IN THE INSTALLATION MANUAL
COLONNE D'EAU(GN)
GDS26N
COLONNE D'EAU (GN)
COLONNE D'EAU (GN)
NOT FOR USE WITH SOLID FUEL
MINIMUM AND MAXIMUM HORIZONTAL VENT LENGTHS ARE 10 INCHES AND 20 FEET RESPECTIVELY. PROPER REINSTALLATION AND RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIAL:
A 2" B 5" C 2"
VENT TOP 2" TO CEILING FROM VENT BOTTOM 1" STOVE TOP 12” VENT SIDES 1"
0-4500ft 25,000 BTU/h 17,000 BTU/h
4.5" Water Column (11mb) 11" Water Column (27mb) 13" Water Column (32mb) 13" Water Column (32mb)
3.5" Water Column (9mb) 10" Water Column (25mb)
FOYER À GAZ VENTILÉS À ÉVACUATION DIRECTE. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS MOBILES EQUIPEES AU GAZ, EN
VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A. POUR UNE UTILISER AVEC BARRIÈRE W565-0156.
SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE MANUEL D'INSTALLATION.
CDVS26N GDS26P CDVS26P
ALTITUDE / ELEVATION INPUT / ALIMENTATION
REDUCED INPUT /ALIMENTATION REDUITE
61.3%
P4
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILSE AVEC CET APPAREIL
ATTENTION: UTILISER AVEC LES PORTES VITREES
HOMOLOGUEES SEULEMENT AVEC CETTE UNITE. AVERTISSEMENT: N'AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT. CE FOYER À GAZ VENTILÉS NE DOIT PAS ÊTRE UTILISÉ CONJOINTEMENT AVEC DES FILTRES À AIR. PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPARIEL DE CHAUFFAGE. CLASS.: SOUFFLERIE GS67, 115V 0.5AMP 60HZ L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A WOLF STEEL. REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. LES LONGUEURS VERTICALES MINIMALES ET MAXIMALES SONT 3 PIEDS ET 40 PIEDS RESPECTIVEMENT.
SERIAL NUMBER / NO. DESERIE
0-4500ft 25,000 BTU/h 20,000 BTU/h
61.3%
GDS26
MANIFOLD PRESSURE: 10 INCHES W.C.(LP) PRESSION AU COLLECTEUR: 10" D'UNE
COLONNE D'EAU (P)
MIN SUPPLY PRESSURE: 11" W.C. (LP) PRESSION D'ALIMENTATION MIN: 11" D'UNE
COLONNE D'EAU (P)
MAX. SUPPLY PRESSURE: 13" W.C. (LP) PRESSION D'ALIMENTATION MAX: 13" D'UNE
COLONNE D'EAU (P)
LES LONGUEURS HORIZONTALES MINIMALES ET MAXIMALES SONT 10 POUCES ET 20 PIEDS RESPECTIVEMENT. IL EST IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR ASSURE LE MAINTIEN DU SYSTEME DE PRISE D'AIR.
DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES:
A 2” B 5” C 2"
EVENT SUPERIEUR 2" ENTRE LE DESSUS DU FOYER EVENT INFERIEUR 1" ET LE PLAFOND 12” COTES DE L'EVENT 1"
W385-1963
The rating label is located behind the control door and is chained to the appliance. DO NOT REMOVE. For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
W415-2183 / B / 02.10.17
8
WARNING
3.0 VENTING
EN
!
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 4” (102mm) EXHAUST / 7” (178mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling. The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for 400°F (204°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.1F
W415-2183 / B / 02.10.17
3.1 VENTING LENGTHS AND COMPONENTS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components. A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
9
EN
VENT
MANUFACTURER
Duravent GDS924N Wolf Steel www.duravent.com
Amerivent 4DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 4DT-AAN Selkirk www.selkirkcorp.com
SuperSeal 4DNA Metal-Fab www.mtlfab.com
* For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel termination kits: wall terminal kit GD175 (7/12’ of venting included), or 1/12 to 7/12 pitch roof terminal kit GD110, 8/12 to 12/12 roof terminal kit GD111, fl at roof terminal kit GD112 or periscope kit GD180 (for wall penetration below grade) in conjunction with the appropriate venting components.
For optimum fl ame appearance and appliance operation, keep the vent length and number of elbows to a minimum. It is recommended that all horizontal runs have a minimum 1/4” (6.4mm) rise per foot /meter. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. Rigid and fl exible venting systems must not be combined. Different venting manufacturers components must not be combined.
STARTER ADAPTER
PART NUMBER
SUPPLIER WEBSITE
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet (6m). The maximum allowable vertical vent length is 40 feet (12m). The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Use an adjustable pipe as the fi nal length of rigid piping to the stove for ease of installation.
8.5B
W415-2183 / B / 02.10.17
10
3.2 TYPICAL VENT INSTALLATION
EN
16" (40.6cm)
MINIMUM
24" (61cm) MAXIMUM
10" (254mm)
MINIMUM
35 1/2"
(90.2cm)
* See "VENTING" section
40 FT (12m)
MAXIMUM
3 FT (1m)
MINIMUM
45 1/2"
(15.6cm)
MINIMUM
PLUS RISE*
35 1/2"
(90.2cm)
W415-2183 / B / 02.10.17
16" (40.6cm)
MINIMUM
11
EN
20" (50.8cm)
MAXIMUM
29 1/8"
(74cm)
MINIMUM
PLUS RISE*
40 FT (12m)
MAXIMUM
3 FT (1m)
MINIMUM
29 1/8"
(74cm)
* See "VENTING" section
W415-2183 / B / 02.10.17
12
9.4B
20" (50.8cm)
MAXIMUM
30”
MINIMUM
12” MINIMUM
INSTALLATION D’UNE ÉVACUA-
TION SUR LE DESSUS
INSTALLATION D’UNE ÉVACUA-
TION À L’ARRIÈRE
30”
MINIMUM
12” MINIMUM
COURSE MAXIMALE DE 10 PI
6" (152mm) MINIMUM D’ÉLÉVATION
REAR EXIT INSTALLATION
12” MINIMUM
3.3 SPECIAL VENT INSTALLATIONS
3.3.1 PERISCOPE TERMINATION
EN
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when fi nal grading is completed, the bottom air slot is located a minimum 12” (30.5cm) above grade. The maximum allowable vent length is 10’ (3.1m).
24"
(61cm)
MINIMUM
12"
(30.5cm)
MIN TO GRADE
12"
(30.5cm) MIN
TO GRADE
24" (61cm)
MINIMUM
35 1/2"
(90.2cm)
3.3.2 CORNER TERMINATION
The maximum vent length for a corner installation is 20" (50.8cm) of horizontal run, in addition to the 45° off­set. In this case zero rise is acceptable. See illustrations below. It is recommended to maintain a 6" (152mm) rise (as illustrated).
6” RISE MINIMUM
W415-2183 / B / 02.10.17
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES
13
COVERED BALCONY APPLICATIONS
R
Q
= 3 feet
MIN
(0.9m)
INSTALLATIONS
CANADA U.S.A.
12” (30.5cm) 12” (30.5cm) Clearance above grade, veranda porch, deck or balcony.
A
B
C
D
E
F
12”
(30.5cm)
12” (30.5cm)* 12” (30.5cm)* Clearance to permanently closed windows.
18” (45.7cm)** 18” (45.7cm)**
18” (45.7cm)** 18” (45.7cm)** Clearance to unventilated soffit.
0” (0mm) 0” (0mm) Clearance to an outside corner wall.
0” (0mm)*** 0” (0mm)***
G
2” (50.8mm)*** 2” (50.8mm)***
3’ (0.9m) 3’ (0.9m)****
H
3’ (0.9m) 3’ (0.9m) **** Clearance to a service regulator vent outlet.
I
12” (30.5cm) 9” (228.6mm)
J
6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet.
K
7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
L
M
N
O
P
Q
R
Δ
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.
*** The periscope requires a minimum 18” (45.cm) clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
† 3 feet above if within 10 feet (3.1m) horizontally.
‡ A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
12”
(30.5cm)††
16” (40.6cm) 16” (40.6cm) Clearance above the roof.
2’ (0.6m)†* 2’ (0.6m)†* Clearance from an adjacent wall including neighbouring buildings.
8’ (2.4m) 8’ (2.4m)
3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
6’ (1.8m) 6’ (1.8m)
In a structure with three walls and a roof, the terminal shall not be located less than 6 feet (1.8m) under a window that opens on a horizontal plane.
9” (228.6mm)ΔClearance to windows or doors that open.
Δ
Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2’ (50.8mm) from the centerline of the terminal.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chim­ney, etc.).
Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum vertical distance of 15’ (4.6m).
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
12”
(30.5cm)****
Clearance under a veranda, porch, deck or balcony.
Roof must be non-combustible without openings.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
R
= 2 x
MAX
Q
M
G
R
≤ 15 feet
Q
ACTUAL
W415-2183 / B / 02.10.17
MAX
EN
P
(4.6m)
14
For the following symbols used in the venting calculations and examples are: > - greater than > < - less than < H H H V
3.5 VENTING APPLICATION FLOW CHART
EN
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
TOP EXIT
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
REAR EXIT
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.1A
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
3.5 times the
vertical rise equal to
or greater than the
horizontal run
Vertical rise is equal
3.6 DEFINITIONS
- equal to or greater than
W415-2183 / B / 02.10.17
- equal to or less than
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
T
- combined horizontal vent lengths in feet
R
- offset factor: .03 (total degrees of offset - 90°*) in feet
O
- combined vertical vent lengths in feet
T
Vertical Termination
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.2A
14.1
3.7 ELBOW VENT LENGTH VALUES
0.03 0.5 12.7 15° 0.45 6.0 152.4 30° 0.9 11.0 279.4 45° 1.35 16.0 406.4 90°* 2.7 32.0 812.8
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
0
2.5
(0.8)5(1.5)
7.5
(2.3)
10
(3.1)
12.5 (3.8)15(4.6)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
17.5 (5.3)20(6.1)
39 (11.9)
REQUIRED
VERTICAL
RISE IN FEET
(METERS)VT
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
7.5
(2.3)
10
(3.1)
12.5 (3.8)15(4.6)
17.5 (5.3)20(6.1)
FEET (METERS) H
T
FEET INCHES MILLIMETERS
3.8 TOP EXIT HORIZONTAL TERMINATION
(HT) < (VT)
15
EN
15.1A
Simple venting confi guration (only one 90° elbow)
39 (11.9)
REQUIRED
VERTICAL
RISE IN FEET
(METERS)VT
For vent confi gurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet (12.2m)
Example: V1 = 3 FT (0.9m)
V2 = 8 FT (2.4m) VT = V1 + V2= 3 FT (0.9m ) + 8 FT (2.4m) = 11 FT (3.4m) H1 = 2.5 FT (0.8m) H2 = 2 FT (0.6m) HR = H1 + H2 = 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m) HO = .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT (1.7m) HT = HR + HO = 4.5 FT (1.4m) + 5.4 FT (1.6m) = 9.9 FT (3m) HT + VT = 9.9 FT (3m) + 11 FT (3.4m) = 20.9 FT (6.4m)
Formula 1: HT < V
9.9 FT (3m) < 11 FT (3.4m) Formula 2: HT + VT < 40 FT (12.2m)
20.9 FT (6.4m) < 40 FT (12.2m) Since both formulas are met, this vent confi guration is acceptable.
T
See graph to determine the required vertical
for the required horizontal run HT.
rise V
T
40 (12.2)
30 (9.1)
20 (6.1)
10 (3.1)
0
2.5
(0.8)5(1.5)
7.5
(2.3)
10
(3.1)
12.5 (3.8)15(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
The shaded area within the lines represents
acceptable values for H
90°
V
2
90°
H
W415-2183 / B / 02.10.17
90°
V
1
16.1B
and V
T
1
17.5 (5.3)20(6.1)
T
H
2
EN
(HT) > (VT)
for the
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: Formula 2:
Example: V H H H H H H
Formula 1:
4.2 V
10.7
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
Example: V V V H H H H H H H H
Formula 1:
4.2 V
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
16
Simple venting configuration (only one 90° elbow)
VERTICAL RISE
(CENTIMETERS)
See graph to determine the required vertical rise V
REQUIRED
required horizontal run HT.
150 (381)
150 (381)
147
147
(373.4)
(373.4)
100 (254)
100 (254)
T
IN INCHES
V
T
57 (144.8)
57 (144.8)
19 1/2 (49.5)
50 (127)
50 (127)
10”
(25.4)
5
0
(0.6)
5
0
(1.5)
2
(1.5)
2
(0.6)
(3.1)
15
10
10
12.5
(3.1)
(3.8)
(4.6)
12.5
(3.8)
(4.6)
20 (6.1)
15
20 (6.1)
19.5
19.5
(5.9)
(5.9)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
values for H
and VT
T
T
HT < 4.2 V HT + V
= VT = 6 FT (1.8m)
1
= 3 FT (0.9m)
1
= 5 FT (1.5m)
2
= H
+ H
R
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7FT (0.8m)
O
= H
T
+ V
T
= 3FT (0.9m) + 5FT (1.5m) = 8 FT (2.4m)
1
2
+ H
= 8FT (2.4m) + 2.7FT (0.8m) = 10.7FT (3.3m)
R
O
= 10.7FT (3.3m) + 6FT (1.8m) = 16.7FT (5.1m)
T
HT < 4.2 V
HT + V
T
< 24.75 feet (7.5m)
T
T
= 4.2FT (1.3m) x 6FT (1.8m) = 25.2FT (7.7m)
T
FT (3.3m) < 25.2FT (7.7m)
< 24.75 FT (7.5m)
T
16.7FT (5.1m) < 24.75 (7.5m)
90°
V
1
90°
= 4 FT (1.2m)
1
= 1.5 FT (0.5m)
2
= V
+ V
T
= 2 FT (0.6m)
1
= 1 FT (0.3m)
2
= 1 FT (0.3m)
3
= 1.5 FT (0.5m)
4
= H
R
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT (2.5m)
O
= H
T
+ V
T
= 4FT (1.2m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
1
2
+ H2 + H
1
+ H
R
= 13.6 FT (4.2m) + 5.5 FT (1.7m) = 19.1 FT (5.8m)
T
+ H4 = 2FT (0.6m) + 1FT (0.3m) + 1FT (0.3m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
3
= 5.5 FT (1.7m) + 8.1 FT (2.5m) = 13.6 FT (4.2m)
O
HT < 4.2 V
13.6 FT (4.2m) < 23.1 FT (7m)
HT + V
19.1FT (5.8m) < 24.75 FT (7.5m)
T
= 4.2 FT (1.3m) x 5.5 FT(1.7m) = 23.1 FT (7m)
T
< 24.75 FT (7.5m)
T
V
1
W415-2183 / B / 02.10.17
H
1
90°
H
1
90°
90°
16.1_2B
H
2
90°
H
V
2
H
H
2
3
4
3.9 REAR EXIT HORIZONTAL TERMINATION
(HT) < (VT)
17
Simple venting configuration
(only two 90° elbows)
See graph to determine the required vertical rise V
horizontal run H
40 (12.2)
38.3 (11.7)
REQUIRED
30 (9.1)
VERTICAL
RISE IN
20 (6.1)
FEET
(METERS) V
T
10 (3.1)
1.6 (0.5)
0
(0.8)5 (1.5)
1.6
(0.5)
2.5
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable values for H
and HT
For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: H Formula 2: HT + V
Example:
= 9 FT (2.7m)
V
1
V
= 6 FT (1.8m)
2
= V
V
T
1
= 3 FT (0.9m)
H
1
H
= 2 FT (0.6m)
2
= 1.5 FT (0.5m)
H
3
H
= H
R
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT (2.5m)
H
O
= H
H
T
H
+ V
T
T
Formula 1: H
14.6 FT (4.5m) < 15 FT (4.6m) Formula 2: HT + V
29.6 FT (9m) < 40 FT (12.2m)
< V
T
T
< 40 feet (12.2m)
T
+ V
= 9FT (2.7m) + 6FT (1.8m) = 15FT (4.6m)
2
+ H2 + H
1
+ H
R
= 14.6FT (4.5m) + 15FT (4.6m) = 29.6 FT (9m)
= 3FT (0.9m) + 2FT (0.6m) + 1.5FT (0.5m) = 6.5FT (2m)
3
= 6.5FT (2m) + 8.1FT (2.5m) = 14.6FT (4.5m)
O
< V
T
T
< 40 FT (12.2m)
T
H
1
Since both formulas are met, this vent configuration is acceptable.
(2.3)
(6.1)
T
EN
20
T
for the required
.
T
7.5 (3.1)
T
10
12.5
15
(4.6)
17.5
(5.3)
(3.8)
90°
H
3
V
2
90°
H
2
V
1
90°
90°
16.3A
W415-2183 / B / 02.10.17
EN
(HT) > (VT)
18
Simple venting configuration
(only two 90° elbows)
See graph to determine the required vertical rise V
12.5 (3.8)
12.25 (3.7)
required horizontal run H
.
T
for the
T
REQUIRED
VERTICAL RISE IN
8.3 (2.54)
FEET
(METERS)V
T
(1.68)
(0.3)
5.5
4.2 (1.3)
1
0
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: H Formula 2: HT + V
< 3.5V
T
T
< 24.75 feet (7.5m)
T
Example:
= 4 FT (1.2m)
V
1
V
= 1.5 FT (0.5m)
2
= V
+ V
V
T
= 2 FT (0.6m)
H
1
H
= 1 FT (0.3m)
2
= 1 FT (0.3m)
H
3
H
= 1.5 FT (0.5m)
4
= H1+ H2+H3+H4= 2FT(0.6m) + 1FT(0.3m) + 1FT(0.3m) + 1.5FT(0.5m) = 5.5 FT(1.7m)
H
R
= .03 (four 90° elbows + one 45° elbow - 90°)
H
O
= .03 (90 + 90 + 90 + 90 + 45 - 90) = 9.45 FT (2.9m)
H
= H
T
H
+ V
T
Formula 1: H
3.5VT = 3.5FT (1.1m) x 5.5FT (1.7m) = 19.25FT (5.9m)
= 4FT (1.2m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
1
2
+ H
= 5.5FT (1.7m) + 9.45FT (2.9m) = 14.95FT (4.6m)
R
O
= 14.95FT (4.6m) + 5.5FT (1.7m) = 20.45FT (6.2m)
T
< 3.5V
T
T
14.95 FT (4.6m) < 19.25 FT (5.9m)
Formula 2: HT + V
20.45 FT (6.2m) < 24.75 FT (7.5m)
< 24.75 FT (7.5m)
T
Since both formulas are met, this vent configuration is acceptable.
2.5
(0.8)5 (1.5)
1
(0.3)
values for H
(1.1)
7.5
10
12.5
15
17.5
(2.3)
(3.1)
(3.8)
3.5
and HT
T
(4.6)
(5.3)
19.25 (5.9)
(6.1)
20
T
90°
H
3
V
2
90°
H
2
V
1
H
1
90°
90°
W415-2183 / B / 02.10.17
16.3_2C
3.10 TOP OR REAR EXIT VERTICAL TERMINATION
for the
(HT) < (VT)
19
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run HT.
40 (12.2)
30 (9.1)
REQUIRED
VERTICAL RISE
IN FEET
(METERS)V
20 (6.1)
T
10 (3.1)
3 (0.9)
0
5
(1.5)
10
(3.1)
15
(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
(METERS) H
T
The shaded area within the lines represents acceptable
values for H
and HT
T
For vent configurations requiring one or more 90° elbows (top exit) or one or more 90° elbows (rear exit), the following formulas apply:
Formula 1: H Formula 2: HT + V
< V
T
T
< 40 feet (12.2m)
T
EN
T
20
(6.1)
Example:
= 5 FT (1.5m)
V
1
V
= 6 FT (1.8m)
2
= 10 FT (3.1m)
V
3
V
= V
+ V2 + V
T
1
= 8 FT (2.4m)
H
1
H
= 2.5 FT (0.8m)
2
= H1+ H2 = 8FT (2.4m) + 2.5FT (0.8m) = 10.5FT (3.2m)
H
R
= .03 (four 90° elbows - 90°)
H
O
= .03 (360° - 90°) = 8.1 FT (2.5m)
H
= H
+ H
T
R
H
+ V
= 18.6FT (5.7m) + 21FT (6.4m) = 39.6FT (12.1m)
T
T
Formula 1: H
18.6 FT (5.7m) < 21 FT (6.4m) Formula 2: HT + V
39.6FT (12.1m) < 40 FT (12.2m)
= 5FT (1.5m) + 6FT (1.8m) + 10FT (3.1m) = 21 FT (6.4m)
3
= 10.5FT (3.2m) + 8.1FT (2.5m) = 18.6FT (5.7m)
O
< 3.5V
T
T
< 40 FT (12.2m)
T
Since both formulas are met, this vent configuration is acceptable.
18.2A
W415-2183 / B / 02.10.17
EN
(HT) > (VT)
Example: V V V H H H H H = .03 (360° + H H
Formula 1: H 3 V
19.5FT (5.9m) Formula 2:
H 26 FT (7.9m)
Since both formulas are met, this vent configuration is acceptable.
20
Simple venting configurations.
REQUIRED
VERTICAL
RISE IN
FEET
(METERS)V
See graph to determine the required vertical rise V
T
20
(6.1)
.
(7.6)
19 (5.8)
3 (0.9)
T
20 (6.1)
10 (3.1)
required horizontal run H
5
0
(1.5)
10
(3.1)
15
(4.6)
for the
T
25
30
(9.1)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H
The shaded area within the lines represents acceptable
values for H
and HT
T
For vent configurations requiring more than two 90° elbows (top exit) or one 90° elbow (rear exit), the following formulas apply:
Formula 1: H Formula 2: HT + V
Example:
= 2 FT (0.6m)
V
1
V
= 1 FT (0.3m)
2
= 1.5 FT (0.5m)
V
3
= V
V
T
1
H
= 6 FT (1.8m)
1
= 2 FT (0.6m)
H
2
H
= H
R
1
= .03 (four 90° elbows - 90°)
H
O
= .03 (360° - 90°) = 8.1 FT (2.5m)
H
= H
T
R
H
+ V
T
T
Formula 1: H
3.5 V
16.1FT (4.9m) < 13.5 FT (4.1m)
< 3 V
T
T
< 40 feet (12.2m)
T
+ V2 + V3 = 2FT (0.6m) + 1FT (0.3m) + 1.5FT (0.5m) = 4.5 FT (1.4m)
+ H
= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
2
+ H
= 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m)
O
= 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6FT (6.3m)
< 3.5 V
T
T
= 3FT (0.9m) x 4.5FT (1.4m) = 13.5 FT (4.1m)
T
90°
90°
V
V
1
H
1
V
H
2
2
90°
3
90°
Since this formula is not met, this vent configuration is unacceptable. Formula 2: HT + V
16.1FT (4.9m) < 13.5 (4.1m)
< 40 FT (12.2m)
T
Since only formula 2 is met, this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas.
18.2_2B
T
= 1.5 FT (0.5m)
1
= 5 FT (1.5m)
2
= V
+ V2 = 1.5FT (0.5m)+ 5FT (1.5m) = 6.5 FT (2m)
T
1
= 1 FT (0.3m)
1
= 1 FT (0.3m)
2
= 10.75 FT (3.3m)
3
= H
+ H2 + H3 = 1FT (0.3m) + 1FT (0.3m) + 10.75FT (3.3m) = 12.75FT (3.9m)
R
1
= .03 (four 90° elbows + one 45° elbow - 90°)
O
= H
+ H
T
R
+ V
= 19.5FT (5.9m) + 6.5FT (2m) = 26 FT (7.9m)
T
T
< 3 V
T
T
T
+ V
< 40 FT (12.2m)
T
T
45° - 90°) = 6.75 FT (2.1m)
= 12.75FT (3.9m) + 6.75FT (2.1m) = 19.5 FT (5.9m)
O
= 3FT (0.9m) x 6.5FT (2m) = 19.5FT (5.9m)
= 19.5FT (5.9m)
< 40 FT (12.2m)
W415-2183 / B / 02.10.17
V
2
90°
H
2
45°
V
1
H
1
H
3
90°
90°
18.2_3A
3.11 VERTICAL THROUGH EXISTING CHIMNEY
This appliance is designed to be attached to a 3” (76.2mm) co-linear aluminum fl ex vent system running the full length of a masonry chimney.
The fl ex liners accommodate any contours of a masonry chimney, however, it is necessary to keep the fl exible liners as straight as possible. The inlet air collar of the termination cap must be connected to the air intake fl ex liner and the exhaust collar must be connected to the exhaust fl exible liner.
Both Simpson Duravent and Selkirk co-linear to co-axial adaptors have been approved on this appliance (
directly off the appliance
Follow vent manufacturer’s installation instructions.
Different manufacturer’s venting components must not be combined. Once the preferred manufacturer’s appliance adaptor has been attached, the remainder of the system must be that of the same manufacturer.
The only exception to this rule is to use Wolf Steel’s approved 3” (76.2mm) fl ex liner and co-linear termination.
WARNING
* Measured from appliance fl ue collar to termination fl ue collar
21
!
RISK OF FIRE!
CO-AXIAL TO CO-LINEAR VENTING CONFIGURATIONS MUST ONLY BE USED IN A
NON-COMBUSTIBLE CHIMNEY OR ENCLOSURE. INSTALLATION IN A COMBUSTIBLE ENCLOSURE
COULD RESULT IN A FIRE.
TERMINATION
NOTE: A vent adaptor will be required
).
AIR
INTAKE
EXHAUST
FLUE
FLEX
LINER
* 40 FT (12.2m)
10 FT (3.1m)
EN
MAX.
MIN
COAXIAL TO
CO-LINEAR
ADAPATOR
APPLIANCE
VENT ADAPTOR
7.6B
W415-2183 / B / 02.10.17
22
3.12 REAR VENT CONVERSION
In order to convert the venting configuration from a top exit to a rear exit, remove components as illustrated:
EN
When reinstalling in the alternate position: Check gaskets for tears, replace if necessary to ensure a proper seal.
Outer Top
2
7" (178mm)
Collar
7'' (178mm)
Gasket
4'' (102mm)
Collar
4'' (102mm)
Gasket
3
4
5
6
4'' (102mm)
Gasket
7
8
4'' (102mm) Cover Plate
Knockout
1
10
9
7'' (178mm) Cover Plate
7'' (178mm)
Gasket
Rear Shield
SAFETY BARRIER
W415-2183 / B / 02.10.17
- Remove the rear shield and the knockout
- Remove the outer top.
- Replace components 3 through 6 onto the rear of the appliance.
- Replace components 7 through 10 onto the top of the appliance.
- Before replacing the rear shield, slide the vent pipe through the rear shield a few inches, secure 4'' (102mm) and 7'' (178mm) to the collars.
- Slide the rear shield along the vent pipe and re-secure to the appliance.
- Complete vent installation.
4.0 INSTALLATION
WARNING
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, A MINIMUM OF 3 SCREWS MUST ALSO
WARNING
23
!
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE, ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
EXACTLY.
ALL EXHAUST AND INTAKE VENT PIPE JOINTS MUST BE SEALED USING RED RTV HIGH TEMP
SILICONE SEALANT (W573-0002) (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC (W573-0007)
(NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR WHICH MUST
BE SEALED USING MILL PAC.
BE USED TO ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2D
EN
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
For optimum performance it is recommended that horizontal runs have a minimum 1" (25mm) per rise per foot when using Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent, or Wolf Steel rigid or flexible vent components.
70.1
W415-2183 / B / 02.10.17
24
WARNING
ADD FASTENER TYPE
This application occurs when venting through a roof. Installation kits for various roof pitches are available from your authorized dealer / distributor. See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1" (25mm) clearance between the vent pipe and any combustible material. Try to center the vent pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings. A vent pipe shield will prevent any materials such as insulation, from fi lling up the 1" (25mm) air space around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the
Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished ceiling), and secure over the opening in the ceiling. A fi restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a fi restop spacer over the vent shield to restrict cold air from being drawn into the room or around the fi replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply Mill Pac sealant (W573-0007) (not supplied) or red RTV silicone (W573-0002) (not supplied) between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1" (25mm) air space around the pipe.
21.1B
CAULKING
VENT PIPE
SHIELD
FIRESTOP
UNDERSIDE OF
JOIST
VENT
PIPE
COLLAR
VENT
PIPE
SHIELD
4.1.1 HORIZONTAL INSTALLATION
EN
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
This application occurs when venting through an exterior wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall as illustrated to accommodate the fi restop assembly. Dry fi t the fi restop assembly before proceeding to ensure the brackets on the rear surface fi t to the inside surface of the horizontal framing.
The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2” (215.9mm) thick but the vent shield must extend the full depth of the combustible wall.
A. Assemble the shield to the spacer as
shown, using 3 screws.
B. Place the fi restop top so that the vent shield
covers the top of the vent within the opening. Ensure that both spacer and shield maintain the required clearance to combustibles.
C. Secure the spacer in place using 4 screws. Once the
vent pipe is installed in its fi nal position, apply sealant between the pipe and the fi restop spacer.
4.1.2 VERTICAL INSTALLATION
!
RETURN FLANGE OF THE MOUNTING PLATE.
TYPE 1 (X4)
VENT
SHIELD
FIRESTOP
SPACER
CAULKING
FINISHING MATERIAL
TYPE 2 (X3)
DETERMINE THE CORRECT HEIGHT
20.5C
W415-2183 / B / 02.10.17
9"
(228.6mm)
4.1.3 APPLIANCE VENT CONNECTION
A.
B.
C.
NOTE: Ensure that the sealant is not visible on the exterior pipes once installation is completed. An optional decorative black band is available for this use. In the event that the venting must be disassembled, care must be taken to reseal the venting.
NOTE : Fastening hardware provided with appropriate kit.
25
Attach the adjustable pipe to the last section of rigid pipe. Secure with screws and seal.
Install the inner fl ex pipe to the appliance. Secure with 3 screws. Seal the joint and screw holes using Mill Pac sealant (W573-0007) (not supplied).
Run a bead of Red RTV Silicone (W573-0002) (not supplied) around the inside of the air intake collar. Pull the adjustable pipe a minimum 2” (50.8mm) into the air intake collar.
SCREWS
EN
2” (50.8mm) OVERLAP
HIGH TEMPERATURE SEALANT
28.3C
W415-2183 / B / 02.10.17
26
A.
B.
C.
the required clearance to combustibles. Holding the
D.
E.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its return fl ange.
7" (177.8mm) RIGID PIPE
HI-TEMP
SEALANT
SCREWS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE
INNER FLEX PIPE
OUTER
FLEX PIPE
HI-TEMP
SEALANT
NOTE : Fastening hardware provided with appropriate kit.
WARNING
4.1.4 HORIZONTAL AIR TERMINAL INSTALLATION
EN
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND
ELBOWS. KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX AT PREDETERMINED INTERVALS TO MAINTAIN AN
EVEN AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A
SPACER IS REQUIRED AT THE START, MIDDLE, AND END OF EACH ELBOW TO ENSURE THIS GAP
IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
All 4" (102mm) flexible vent pipe and 7" (178mm) rigid vent pipe joints must be sealed using either high temperature sealant W573-0002 (not supplied) or the high temperature sealant W573-0007 Mill Pac (not supplied). However, the high temperature sealant W573-0007 Mill-Pac (not supplied) must be used on the joint connecting the 4" (102mm) flexible vent pipe and the exhaust flue collar.
Stretch the inner fl ex pipe to the required length taking
into account the additional length needed for the fi nished wall surface. Apply a heavy bead of Mill Pac sealant (W573-0007) (not supplied) to the inner sleeve of the air terminal. Slip the vent pipe a minimum of 2” (50.8mm) over the inner sleeve of the air terminal and secure with 3 screws.
Using the outer rigid pipe, slide over the outer combustion air
sleeve of the air terminal and secure with 3 screws. Seal using Red RTV Silicone (W573-0002) (not supplied).
Insert the vent pipes through the fi restop maintaining
!
SCREWS
(SUPPLIED)
CAULKING
4" (101.6mm) FLEX PIPE
2" (50.8mm) OVERLAP
HIGH TEMP
SEALANT
air terminal (lettering in an upright, readable position),
W415-2183 / B / 02.10.17
secure to the exterior wall and make weather tight by sealing with caulking (not supplied).
From inside the house, using Red RTV Silicone
(W573-0002) (not supplied), seal between the vent pipe and the fi restop. Then slide the black trim collar over the vent pipe up to the fi restop.
If more vent pipe needs to be used to reach the
appliance, couple them together as illustrated. The vent system must be supported approximately every 3 feet (0.9m) for both vertical and horizontal runs. Use noncombustible strapping to maintain the minimum clearance to combustibles.
23.7E
4.1.5 EXTENDED HORIZONTAL AND CORNER TERMINAL INSTALLATION
A 45° corner installation can have 0” (0mm) rise between the appliance
A.
B.
C.
D.
E.
F.
G.
H.
WARNING
combustion air collar and the air terminal. In this case, vent lengths must be kept to a maximum of 24” (60.9cm) . For longer vent lengths, a minimum vertical rise of 24” (60.9cm) is required.
A. Follow the instructions for "HORIZONTAL AIR TERMINAL INSTALLATION" section.
B. Continue adding components alternating inner and outer vent pipes. Ensure that all inner vent pipes and elbows have sufficient vent spacers attached and each component is securely fastened to the one prior. Attach the telescopic sleeve to the vent run. Secure and seal. To facilitate completion, attach inner and outer couplers to the air terminal.
C. Install the air terminal. See “HORIZONTAL AIR TERMINAL INSTALLATION” section. Extend the outer telescopic sleeve; connect to the air terminal assembly. Fasten with screws and seal.
4.1.6 VERTICAL AIR TERMINAL INSTALLATION
!
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
NOTE : Fastening hardware provided with appropriate roof terminal and liner kits.
Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case the
venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
Stretch the inner fl ex pipe to the required length. Slip the inner
fl ex pipe a minimum of 2” (51mm) over the inner pipe of the air terminal connector and secure with a minimum of
3 screws. Seal using a heavy bead of Mill Pac sealant (W573-0007) (not supplied).
Repeat using the outer fl ex pipe, using a heavy bead of red
RTV silicone (W573-0002) (not supplied) and a minimum of 3 screws.
Thread the air terminal connector / vent pipe assembly
down through the roof. The air terminal must be positioned vertically and plumb. Attach the air terminal connector to the roof support, ensuring that the top of the air terminal is 16” (40.6cm) above the highest point that it penetrates the roof.
Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector leaving a min. 3/4” (19mm) of the air terminal connector showing above the top of the fl ashing. Slide the fl ashing underneath the sides and upper edge of the shingles. Ensure that the air terminal connector is properly centered within the fl ashing, giving a 3/4” (19mm) margin all around. Fasten to the roof. Do not nail through the lower portion of the fl ashing. Make weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the fl ashing with roofi ng material.
Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal. Secure with 3 screws.
Apply a heavy bead of weatherproof caulking 2” (51mm)
above the fl ashing. Install the storm collar around the air terminal and slide down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved.
If more vent pipe needs to be used to reach the appliance see
“HORIZONTAL AIR TERMINAL INSTALLATION” section.
AIR TERMINAL
20" (508mm) COUPLER
48.2A
ROOF SUPPORT
AIR
TERMINAL
CONNECTOR
2” (51mm)
TELESCOPIC SLEEVE
VENTING
INNER PIPE
MILL PAC
SEALANT
(W572-0007)
INNER FLEX PIPE
OUTER FLEX PIPE
AIR INLET BASE
CAULKING
STORM COLLAR
WEATHER SEALANT
24.1D
FLASHING
W415-2183 / B / 02.10.17
27
EN
28
29.1C
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the appliance.
Installation and servicing to be done by a qualifi ed installer.
• current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner
WARNING
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
4.2 MOBILE HOME INSTALLATION
EN
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate.
Built in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the base. Use appropriate fasteners, inserted through the holes in the base to secure. For free standing products contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must be fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting the appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
Conversion Kits This appliance is fi eld convertible between Natural Gas (NG) and Propane (P). To convert from one gas to another consult your Authorized dealer/distributor.
4.3 GAS INSTALLATION
!
SPARKS OR OPEN FLAMES.
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSIONS” SECTION.
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Move the appliance into position and secure. If equipped with a fl ex connector the appliance is designed to accept a 1/2” (13mm) gas supply. Without the connector it is designed to accept a 3/8” (9.5mm) gas supply. The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance. Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
Z223.1 / NFPA 54 in the United States. When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
assembly on its side to aid with servicing components. Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
30.1A
W415-2183 / B / 02.10.17
4.4 MINIMUM CLEARANCE TO COMBUSTIBLES
29
Minimum clearance to combustible construction from appliance and vent surfaces:
A - 2" (51mm) B - 5" (127mm) C - 2" (51mm)
Combustible Framing:
- 1" (25mm) to bottom and sides of the vent pipe*
- 2" (51mm) to top of the vent pipe*
NOTE: Appliance should not be installed directly on carpeting.
Rear Exit:
- 47 1/2" (120.7cm) to ceiling from base of the appliance
Top Exit:
- 51" (129.5cm) to ceiling from base of the appliance**
* HORIZONTAL VENT SECTIONS: A minimum clearance of 1" (25mm) at the bottom and sides and 2" (51mm) at the top of the vent pipe in all
horizontal runs to combustibles is required. Use firestop spacer W010-1313 and shield W585-0267 (supplied). * VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is required. Use firestop
spacer W010-1313 (supplied). ** For top vent vertical termination, see "REAR EXIT" for specific clearances. At a distance of 2" (51mm) from the wall, installation or service to the blower may not be practical. A minimum
of 5" (127mm) will be required in order to install or service the blower.
BACK WALL
BACK WALL
SIDE WALL
SIDE WALL
EN
W415-2183 / B / 02.10.17
30
5” (127mm)
1” (25mm)
2” (51mm)
47 1/2”
(120.7cm)
35 1/2”
(90.2cm)
5” (127mm)
BRICK
COMBUSTIBLE
NON-COMBUSTIBLE
29 1/8” (74cm)
MINIMUM
PLUS RISE ***
0” (0mm) IF NON-COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE.
12” (30.5cm)
MANTEL, SHELF,
OR CEILING
5” (127mm)
EN
REAR EXIT
MANTEL, SHELF,
OR CEILING
12” (30.5cm)
47 1/2”
(120.7cm)
(90.2cm)
35 1/2”
The appliance requires a minimum ceiling height of 47 1/2" (120.7cm) for a rear vent. For temperature requirements, the space around and above the appliance must be left unobstructed.
TOP EXIT
MANTEL, SHELF,
OR CEILING
15 1/2” (39.4cm)
COMBUSTIBLE
COMBUSTIBLE
2” (51mm)
NON-COMBUSTIBLE
BRICK
2” (51mm)
0” (0mm) IF NON-COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE.
1” (25mm)
29 1/8” (74cm)
MINIMUM
PLUS RISE ***
NON-COMBUSTIBLE
BRICK
2” (51mm)
0” (0mm) IF NON-COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE.
1” (25mm)
51”
(129.5cm)
35 1/2”
(90.2cm)
The appliance requires a minimum ceiling height of 51" (129.5cm) for a top vent horizontal termination. For top vent vertical termination, see "REAR EXIT" for specific clearances. For temperature requirements, the space around and above the appliance must be left unobstructed.
*** See "VENTING" section.
W415-2183 / B / 02.10.17
45 1/2”
(115.6cm)
MINIMUM
PLUS RISE ***
Loading...
+ 76 hidden pages