CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
EN
OPERATING INSTRUCTIONS
CONFORMS TO AMERICAN NATIONAL STANDARDS: ANSI Z21.50, CERTIFIED TO CANADIAN CSA 2.22 FOR VENTED GAS FIREPLACES.
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
!
WARNING
If the information in these instructions
are not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
GDS25N
NATURAL GAS
GDS25P
PROPANE
SAFETY BARRIER
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
FR
PG
49
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
Decorative Product: Not for use as a heating appliance.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with the appliance and
BARRIER
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
shall be installed.
1.28E
W415-1332 / A / 11.21.14
2
TABLE OF CONTENTS
EN
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 5
2.3 GENERAL INFORMATION 6
2.4 RATING PLATE INFORMATION 7
3.0 VENTING 8
3.1 VENTING LENGTHS AND COMPONENTS 8
3.2 SPECIAL VENT INSTALLATIONS 10
3.2.1 PERISCOPE TERMINATION 10
3.2.2 CORNER TERMINATION 10
3.3 VENT TERMINAL CLEARANCES 11
3.4 DEFINITIONS 12
3.5 ELBOW VENT LENGTH VALUES 12
3.6 HORIZONTAL TERMINATION 13
3.7 VERTICAL TERMINATION 15
3.8 VERTICAL THROUGH EXISTING CHIMNEY 17
4.0 INSTALLATION 18
4.1 WALL AND CEILING PROTECTION 18
4.1.1 HORIZONTAL INSTALLATION 19
4.1.2 VERTICAL INSTALLATION 19
4.2 HORIZONTAL AIR TERMINAL INSTALLATION 20
4.3 EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INSTALLATION 20
4.4 VERTICAL AIR TERMINAL INSTALLATION 21
4.5 APPLIANCE VENT CONNECTION 22
4.6 GAS INSTALLATION 22
4.7 MOBILE HOME 23
4.8 MINIMUM CLEARANCE TO COMBUSTIBLES 24
4.9 MINIMUM MANTEL OR SHELF CLEARANCES 25
5.0 FINISHING 26
5.1 CAST FRONT INSTALLATION AND REMOVAL 26
5.2 SAFETY BARRIER INSTALLATION AND REMOVAL 26
5.3 GLASS DOOR INSTALLATION AND REMOVAL 27
5.4 LOG PLACEMENT 27
5.5.1 SWITCH FUNCTIONS 28
5.6 LOGO PLACEMENT 28
6.0 OPTIONAL BLOWER INSTALLATION 29
7.0 WIRING DIAGRAM 30
8.0 OPERATION 31
9.0 ADJUSTMENT 32
9.1 RESTRICTING VERTICAL VENTS 32
9.2 VENTURI ADJUSTMENT 32
9.3 FLAME CHARACTERISTICS 33
9.4 ANTI CONDENSATION SWITCH 33
10.0 MAINTENANCE 34
10.1 ANNUAL MAINTENANCE 34
10.2 NIGHT LIGHT REPLACEMENT 35
10.3 PILOT INJECTOR AND ORIFICE REPLACEMENT 35
10.4 CARE OF GLASS 36
10.5 CARE OF PLATED PARTS 36
11.0 REPLACEMENT PARTS 37
12.0 OVERVIEW 38
13.0 ACCESSORIES 39
14.0 VALVE TRAIN ASSEMBLY 40
15.0 VENTING 41
16.0 TROUBLESHOOTING 42
17.0 WARRANTY 44
18.0 SERVICE HISTORY 45
19.0 NOTES 46
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1332 / A / 11.21.14
1.0 INSTALLATION OVERVIEW
Cast, see “CAST FRONT
INST ALLA TION AND
REMOVAL” section.
Door, see “GLASS
DOOR INSTALLATION
AND REMOVAL”
section.
SAFETY BARRIER
3
EN
On/Off, see “SWITCH
FUNCTIONS” section.
Rating plate, see “RATING
PLATE INFORMATION”
section.
Blower, see
“OPTIONAL BLOWER
INSTALLATION”
section.
W415-1332 / A / 11.21.14
4
2.0 INTRODUCTION
EN
!
WARNING
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES TO THIS APPLIANCE OR IT’S CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to
operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns
or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is
recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an
adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot
surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These
screens and guards must be fastened to the fl oor.
• Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the
appliance.
• The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
• The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance
and to replace any part of the control system and any gas control which has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a
licensed or qualifi ed service person.
• Do not strike or slam shut the appliance glass door.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes
containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also
cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts certifi ed with the unit are to be
installed on the appliance.
• Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these
are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a
Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures
on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic
components.
• A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be
installed.
• If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
• Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and
at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of
the appliance be kept clean.
• This appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel
Ltd.
3.1D
W415-1332 / A / 11.21.14
2.1 DIMENSIONS
25 5/8"
651mm
23 5/8"
600mm
17 1/2"
445mm
23 1/2"
597mm
12 3/4"
324mm
Ø
4"
102mm
Ø
7"
178mm
SAFETY BARRIER
2.2 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” (1219mm) FROM
THE FRONT FACE OF THE APPLIANCE.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35 mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
!
WARNING
PROVIDE ADEQUA TE VENTILA TION.
FIRE RISK. EXPLOSION HAZARD.
5
EN
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth
of Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of an appliance
insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches (914mm).
• A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
W415-1332 / A / 11.21.14
A
A
EN
6
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed in
accordance with the current standard CAN/CSA Z240MH
Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location
for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1B
2.3 GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION
AND QUALITY!
GDS25
NGLP
Altitude (FT)0-4,5000-4,500
Max. Input (BTU/HR)24,50023,000
Max. Output (BTU/HR)19,60018,400
Effi ciency (w/the fan on)80%80%
Min. Inlet Gas Supply Pressure4.5" Water Column (11mb)11" Water Column (27mb)
Max. Inlet Gas Supply Pressure7" Water Column (17mb)13" Water Column (32mb)
Manifold Pressure (Under Flow Conditions)3.5" Water Column (9mb)10" Water Column (25mb)
When the appliance is installed at elevations above 4,500ft (1372m), and in the absence of specifi c recommendations
from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for
each additional 1,000ft (305m).
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible
for use with other gases, unless a certifi ed kit is used.
The blower power cord must be connected into a properly grounded receptacle. The grounding prong must not
be removed from the cord plug.
This appliance is approved for closet or recessed installations, as well as for bathroom, bedroom and
bed-sitting room installations and is suitable for mobile home installations. The natural gas model can be
installed in a mobile home that is permanently positioned on its site and fueled with natural gas.
W415-1332 / A / 11.21.14
2.4 RATING PLATE INFORMATION
2
2"
NCE TO COMBUSTIBLE MATERI
ENT TOP2" TO
ENT SIDES
M 0G8 CANA
UN COMBU
UTILSE A
DANS UN
R INSTALLATI
EQUIPEESAU GAZ, EN VIG
CURITE ET DE CONSTRUCT
3280. DANS LE CAS OU C
ERER A LA NORME
CONTRE L'INCENDIE POUR LE
ER AVEC
W010-3295
GDS25P
ELEVATION
0-2000ft
LIMENTATION
UCED INPUT /
ENTATION REDUITE
4001657 (NGZ)
4001659
WUSA)
ONTAL
AND 20
EINSTAL
ARY
E VENT-AIR INTAKE
UTILISER
HOMOL
UN
AV
7
APPROVED FOR BEDROOM, BATHROOM & BEDSITTING ROOM INSTALLATION. SUITABLE
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2014, CER TIFIED TO / CER TIFIE CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT
STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA
OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND
SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. FOR
USE WITH BARRIER W010-3295. FOLLOW THE INSTALLATION INSTRUCTIONS
LOCATED IN THE INSTALLATION MANUAL
9700539 (WSL) 4001657 (NGZ)
MANIFOLD PRESSURE: 3.5” W.C. (NG)
4001658 (NAC) 4001659 (WUSA)
PRESSION AU COLLECTEUR: 3.5" D'UNE
COLONNE D'EAU(GN)
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
FOR USE WITH GLASS DOORS CERTIFIED
WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO
THE APPLIANCE, WHICH WILL COME IN
CONTACT WITH THE FLAMES, OTHER THAN
THAT SUPPLIED BY THE MANUFACTURER
WITH THE APPLIANCE.
ELECTRICAL RATING: 115V 1.5AMP 60HZ
THE APPLIANCE MUST BE VENTED USING
THE APPROPRIATE WOLF STEEL VENT
KITS. SEE OWNERS INSTALLATION MANUAL
FOR VENTING SPECIFICS. MINIMUM AND
MAXIMUM VERTICAL VENT LENGTHS ARE 3
FEET AND 40 FEET RESPECTIVELY.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE. ONTARIO L4M 0G8 CANADA
NOT FOR USE WITH SOLID FUEL
MINIMUM AND MAXIMUM HORIZONTAL
VENT LENGTHS ARE 10 INCHES AND 20
FEET RESPECTIVELY. PROPER REINSTAL-
LATION AND RESEALING IS NECESSARY
AFTER SERVICING THE VENT-AIR INTAKE
SYSTEM.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIAL:
A4"
B2"
C2"
VENTTOP2" TO CEILING FROM
VENT BOTTOM 1" STOVE TOP 48”
VENT SIDES 1"
GDS25N
MODEL
HOMOLOGUE POUR INSTALLA TION DANS UNE CHAMBRE A COUCHER, UNE SALLE DE BAIN ET
UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON
INSTALLA TION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE
MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS
DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES,
TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETA TS-UNIS NE PEUT
ETRE APPLIQUEE, SE REFERER A LA NORME RELATIVE AU CRITERE DE MESURES DE
SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS
MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A. POUR UNE
UTILISER AVEC BARRIÈRE W010-3295. SUIVEZ LES INSTRUCTIONS D'INSTALLATION
GDS25P
SE TROUVENT DANS LE MANUEL D'INSTALLATION.
MANIFOLD PRESSURE: 10” W.C. (LP)
PRESSION AU COLLECTEUR: 10" D'UNE
MIN SUPPLY PRESSURE: 11" W.C.(LP)
PRESSION D'ALIMENTATION MIN: 11"
MAX. SUPPLY PRESSURE: 13" W.C. (LP)
PRESSION D'ALIMENTATION MAX: 13"
COLONNE D'EAU(P)
D'UNE COLONNE D'EAU (P)
D'UNE COLONNE D'EAU (P)
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE
UTILSE AVEC CET APP AREIL
UTILISER AVEC LES PORTES VITREES
HOMOLOGUEES SEULEMENT AVEC CETTE
UNITE.
AVERTISSEMENT: N'AJOUTEZ PAS A CET
APPAREIL AUCUN MATERIAU DEVANT
ENTRER EN CONTACT AVEC LES FLAMMES
AUTRE QUE CELUI QUI EST FOURNI AVEC
CET APPAREIL PAR LE FABRICANT.
CLASS.: 115V 1.5AMP 60HZ L'APPAREIL
DOIT EVACUER SES GAZ EN UTILISANT
L'ENSEMBLE D'EVACUATION PROPRE A
WOLF STEEL. REFERER AU MANUEL
D'INSTALLATION DE PROPRIETAIRE POUR
L'EVACUATION PRECISE. LES LONGUEURS
VERTICALES MINIMALES ET MAXIMALES
SONT3 PIEDS ET 40 PIEDS
RESPECTIVEMENT.
SERIAL NUMBER / NO. DESERIE
GDS25
LES LONGUEURS HORIZONTALES MINIMALES ET
MAXIMALES SONT 10 POUCES ET 20 PIEDS
RESPECTIVEMENT.
IL EST IMPORTANT DE BIEN REINSTALLER ET
RESCELLER L'EVENT APRES AVOIR ASSURE LE
MAINTIEN DU SYSTEME DE PRISE D'AIR.
DEGAGEMENTS MINIMAUX DES MATERIAUX
COMBUSTIBLES:
A4"
B2"
C2"
EVENT SUPERIEUR 2" ENTRE LE DESSUS
DU FOYER
EVENT INFERIEUR 1" ET LE PLAFOND 48”
COTES DE L'EVENT 1"
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to the
model, venting and gas type of the unit.
EN
AFUE: 64%
W385-1962
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for referece only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the
appliance and shall be installed.
W415-1332 / A / 11.21.14
8
3.0 VENTING
EN
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 4” (102mm) EXHAUST / 7” (178mm) AIR INTAKE VENT PIPE SYSTEM.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme
vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a
requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl
spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide
a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
!
WARNING
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
Refer to the section applicable to your installation.
7.1C
3.1 VENTING LENGTHS AND COMPONENTS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal
locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk
Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting
components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding
supplier:
* For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the
installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a
red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent
pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar
which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel termination kits: wall terminal kit GD175
(7/12’ of venting included), or 1/12 to 7/12 pitch roof terminal kit GD1 10, 8/12 to 12/12 roof terminal kit GD111, fl at
roof terminal kit GD112 or periscope kit GD180 (for wall penetration below grade) in conjunction with the appropriate
venting components.
W415-1332 / A / 11.21.14
9
For optimum fl ame appearance and appliance operation, keep the vent length and number of elbows to a
minimum. It is recommended that all horizontal runs have a minimum 1/4” (6.4mm) rise per foot /meter. The
air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged. Rigid and fl exible venting systems must not be combined. Different
venting manufacturers components must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
run is 20 feet (6m). The maximum allowable vertical vent length is 40 feet (12m). The maximum number of vent
connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when
using fl exible venting.
Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning.
Use an adjustable pipe as the fi nal length of rigid piping to the stove for ease of installation.
8.5A
16” (406mm)
24” (610mm) MIN.
REGARDLESS
OF HORIZONTAL
VENT LENGTH
EN
25 5/8”
(651mm)
40FT (12m)
MAX
3FT (1m)
MIN
24” (610mm)
MAXIMUM
25 5/8”
(651mm)
The maximum horizontal run with a 57” (1448mm) vertical rise immediately above the appliance is 20 feet
(6096.00mm).
W415-1332 / A / 11.21.14
EN
10
3.2 SPECIAL VENT INSTALLATIONS
3.2.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum of 12” (304.8mm) above grade. The maximum allowable vent length
is 10’ (3.1m) for a fi replace and 8’ (2.4m) for a stove.
BELOW GRADE INSTALLATION
MAXIMUM 8FT (2.4M) VENT LENGTH
USE GD201 PERISCOPE KIT
HORIZONTAL RUN NOT TO EXCEED
VERTICAL RISE
12”
(305mm) MIN
TO GRADE
24” (610mm) MIN.
REGARDLESS OF OF
HORIZONTAL VENT
LENGTH
25 5/8”
(651mm)
3.2.2 CORNER TERMINATION
9.5B
24” (610mm)
MAX.
SAFETY BARRIER
W415-1332 / A / 11.21.14
3.3 VENT TERMINAL CLEARANCES
11
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
EN
Q
= 3 feet
MIN
(0.9m)
R
= 2 x
MAX
Q
ACTUAL
INSTALLATIONS
CANADAU.S.A.
A12” (305mm)12” (305mm)Clearance above grade, veranda porch, deck or balcony.
B12” (305mm)
Δ
9”
(229mm)
Clearance to windows or doors that open.
Δ
C12” (305mm)* 12” (305mm) * Clearance to permanently closed windows.
D
18”
(457mm)**
18” (457mm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
E12” (305mm)** 12” (305mm)** Clearance to unventilated soffi t.
F0” (0mm)0” (0mm)Clearance to an outside corner wall.
0” (0mm)***
G
2” (51mm)***
0”
(0mm)***
2”
(51mm)***
H3’(0.9m)3’ (0.9m)****
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney,
etc.).
Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase,
etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a
maximum vertical distance of 15’ (4.6m).
I3’ (0.9m)3’ (0.9m)****Clearance to a service regulator vent outlet.
J12” (305mm)9” (229mm)
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other
appliance.
K6’ (1.8m)3’ (0.9m) †Clearance to a mechanical air supply inlet.
L7’ (2.1m) ‡7’ (2.1m) ****Clearance above a paved sidewalk or paved driveway located on public property.
M
12”
(305mm)††
12”
(305mm)****
Clearance under a veranda, porch or deck.
N16” (406mm)16” (406mm)Clearance above the roof.
O2’ (0.6m)†*2’ (0.6m) †*Clearance from an adjacent wall including neighbouring buildings.
P8’ (2.4m)8’(2.4m)Roof must be non-combustible without openings.
Q3’ (0.9m)3’ (0.9m)See chart for wider wall dimensions.
R6’ (1.8m)6’ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
S12” (305mm)12” (305mm)Clearance under a covered balcony
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18 inches clearance from an inside corner.
****This is a recommended distance. For additional requirements check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††*Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
12.1D
R
MAX
IHHW
(4.6m)
W415-1332 / A / 11.21.14
12
3.4 DEFINITIONS
For the following symbols used in the venting calculations and examples are:
EN
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
H
T
HR - combined horizontal vent lengths in feet
HO - offset factor: .03 (total degrees of offset - 135°*) in feet
VT - combined vertical vent lengths in feet
HO = .03 (one 45° elbow + four 90° elbows - 135°) = .03 (405 - 135°) = 8.1 FT (2.5m)
HT = HR + HO = 5.5 FT (1.7m) + 8.1 FT (2.5m) = 13.6 FT (4.2m)
+ VT = 13.6 FT (4.2m) + 5.5 FT (1.7m) = 19.1 FT (5.8m)
H
T
Formula 1: HT < 4.2FT (1.3m) V
T
4.2FT (1.3m) VT = 4.2 FT (1.3m) x 5.5 FT (1.7m)= 23.1 FT (7m)
13.6 FT (4.2m) < 23.1 FT (7M)
Formula 2: HT + VT < 24.75 FT (7.5m)
19.1 FT (5.8m) < 24.75 FT (7.5m)
Since both formulas are met, this vent confi guration is acceptable.
16.5_2A
T
H
4
W415-1332 / A / 11.21.14
3.7 VERTICAL TERMINATION
15
Simple venting configurations.
(HT) < (VT)
See graph to determine the required vertical rise V
required horizontal run HT.
40 (12.2)
30 (9.1)
REQUIRED
VERTICAL
20 (6.1)
RISE IN FEET
(METERS) V
T
10 (3.1)
3 (0.9)
0
5
(1.5)
10
(3.1)
15
(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
values for H
and VT
T
T
20
(6.1)
for the
EN
T
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
Formula 1: H
Formula 2: HT + V
< V
T
T
< 40 feet (12.2m)
T
Example:
V
= 5 FT (1.5m)
1
V
= 10 FT (3.1m)
2
V
= V
+ V
T
H
= 3 FT (0.9m)
1
H
= 2.5 FT (0.8m)
2
H
= H
R
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H
= H
T
H
+ V
T
Formula 1: H
10.9FT (3.3m) < 15 (4.6m)
Formula 2: HT + V
25.9FT (7.9m) < 40 (12.2m)
= 5 FT (1.5m) + 10 FT (3.1m) = 15 FT (4.6m)
1
2
+ H
= 3FT (0.9m) + 2.5FT (0.8m) = 5.5 FT (1.7m)
1
2
+ H
= 5.5 FT (1.7m)+ 5.4 FT (1.m) = 10.9 FT (3.3m)
R
O
= 10.9 FT (3.3m)+ 15 FT (4.6m) = 25.9 FT (7.9m)
T
< V
T
T
< 40 FT (12.2m)
T
45°
90°
H
V
1
H
1
90°
Since both formulas are met, this vent configuration is acceptable.
18.3A
V
2
2
90°
W415-1332 / A / 11.21.14
V
V
V
V
V
V
16
EN
Simple venting configurations.
(HT) > (VT)
20 (6.1)
19 (5.8)
See graph to determine the required vertical rise V
required horizontal run H
.
T
for the
T
REQUIRED
VERTICAL RISE
IN FEET
(METERS) V
10 (3.1)
T
3 (0.9)
0
5
(1.5)
10
(3.1)
15
(4.6)
20
(6.1)
25
(7.6)
(9.1)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H
30
T
The shaded area within the lines represents acceptable
values for H
and VT
T
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
< 3V
Formula 1:
Formula 2: HT + V
Example:
= 1 FT (0.3m)
1
= 1.5 FT (0.5m)
2
= V
T
H
= 6 FT (1.8m)
1
H
= 2 FT (0.6m)
2
H
= H
R
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H
= H
T
H
+ V
T
H
T
T
< 40 feet (12.2m)
T
+ V
= 1 FT (0.3m)+ 1.5 FT (0.5m)= 2.5 FT (0.8m)
1
2
+ H
= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
1
2
+ H
= 8FT (2.4m) + 5.4FT (1.6m) = 13.4FT (4.1m)
R
O
= 13.4FT (4.1m)+ 2.5FT (0.8m) = 15.9FT (4.8m)
T
45°
V
2
90°
H
2
V
H
1
1
90°
90°
Formula 1: H
3VT = 3FT (0.9m) x 2.5FT(0.8m) = 7.5FT (2.3m)
< 3V
T
T
13.4 FT (4.1m) > 7.5 FT (2.3m)
Since this formula is not met, this vent configuration is
Formula 2: HT + V
15.9FT (4.8m) < 40FT (12.2m)
< 40 FT (12.2m)
T
unacceptable.
Since only formula 2 is met, this vent configuration in unacceptable and a new fireplace location or vent
configuration will need to be established to satisfy both formulas.
not be combined. Once the preferred manufacturer’s
appliance adaptor has been attached, the
remainder of the system must be that of the
same manufacturer.
EN
The only exception to this rule is to use Wolf
Steel’s approved 3” (76.2mm) fl ex liner and
co-linear termination.
* Measured from appliance fl ue collar to
termination fl ue collar
7.6A
W415-1332 / A / 11.21.14
18
4.0 INSTALLATION
EN
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
WHICH MUST BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
4.1 WALL AND CEILING PROTECTION
!
WARNING
EXACTLY.
68.2B
!
WARNING
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
70.1
W415-1332 / A / 11.21.14
4.1.1 HORIZONTAL INSTALLATION
A
19
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall.
Having determined the correct height for the air terminal
location, cut and frame a hole in the exterior wall as
illustrated to accommodate the fi restop assembly.
Dry fi t the fi restop assembly before proceeding to
ensure the brackets on the rear surface fi t to the
inside surface of the horizontal framing.
The length of the vent shield may be cut shorter
for combustible walls that are less than 8 1/2”
(215.9mm)thick but the vent shield must extend the
full depth of the combustible wall.
. Assemble the shield to the spacer as shown,
using the 3 shorter screws supplied.
B. Place the fi restop top so that the vent shield covers the top
of the vent within the opening. Ensure that both spacer and
shield maintain the required clearance to combustibles.
C. Secure the spacer in place using the 4 longer screws supplied. Once the vent pipe is installed in its
fi nal position, apply sealant between the pipe and the fi restop spacer.
4.1.2 VERTICAL INSTALLATION
!
WARNING
FIRESTOP
SPACER
VENT
SHIELD
EN
CAULKING
DETERMINE
THE
CORRECT
HEIGHT
FINISHING
MATERIAL
20.5B
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor. See
accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1“ (25mm)
clearance between the vent pipe and any combustible material. Try to center
the vent pipe location midway between two joists to prevent having to cut
them. Use a plumb bob to line up the center of the openings. A vent pipe
shield will prevent any materials such as insulation, from fi lling up the 1”
(25mm) air space around the pipe. Nail headers between the joist for
extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a fi nished ceiling),
and secure over the opening in the ceiling. A fi restop must be placed on the
bottom of each framed opening in a roof or ceiling that the venting system passes
through. Apply a bead of caulking all around and place a fi restop spacer over
the vent shield to restrict cold air from being drawn into the room or around the
fi replace. Ensure that both spacer and shield maintain the required clearance to
combustibles. Once the vent pipe is installed in its fi nal position, apply sealant between the
pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1” (25mm) air
space around the pipe.
VENT PIPE
21.1
FIRESTOP
UNDERSIDE OF
JOIST
CAULKING
SHIELD
VENT
PIPE
COLLAR
VENT
PIPE
SHIELD
W415-1332 / A / 11.21.14
20
4.2 HORIZONTAL AIR TERMINAL INSTALLATION
EN
!
WARNING
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND
ELBOWS. KEEP IT PULLED TIGHT.
A. Stretch the inner fl ex pipe to the required length
taking into account the additional length needed for
the fi nished wall surface. Apply a heavy bead of thehigh temperature sealant W573-0007 Mill Pac (not
supplied) to the inner sleeve of the air terminal. Slip
the vent pipe a minimum of 2” (50.8mm) over the inner
sleeve of the air terminal and secure with 3 #8 screws.
`
B.Using the outer rigid pipe, slide over the outer combustion air
sleeve of the air terminal and secure with 3 #8 screws. Seal
using high temperature sealant W573-0002 (not supplied).
C.Insert the vent pipes through the fi restop maintaining the required clearance to combustibles. Holding the air
terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing
with caulking (not supplied).
D.From inside the house, using silicone, seal between the vent
pipe and the fi restop. Then slide the black trim collar over the
vent pipe up to the fi restop.
#10x2"
SCREWS
HI-TEMP
SEALANT
CAULKING
4" (101.6mm) FLEX PIPE
7" (177.8mm) RIGID
2" (50.8mm) OVERLAP
HIGH TEMP
SEALANT
#8 X 1/2”SELF DRILLING
SCREWS & WASHERS
PIPE
INNER COUPLER
E.If more vent pipe needs to be used to reach the appliance,
couple them together as illustrated. The vent system must
be supported approximately every 3 feet (0.9m) for both
vertical and horizontal runs. Use noncombustible strapping
to maintain the minimum clearance to combustibles.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its
return fl ange.
OUTER
RIGID PIPE
INNER
FLEX PIPE
23.7C
OUTER
RIGID PIPE
4.3 EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INSTALLATION
A 45° corner installation can have 0” (0mm) rise between the appliance
combustion air collar and the air terminal. In this case, vent lengths must be
kept to a maximum of 24” (609.6mm) . For longer vent lengths, a minimum
vertical rise of 24” (609.6mm) is required.
A. Follow the instructions for "HORIZONTAL AIR TERMINAL
INSTALLATION" section.
B. Continue adding components alternating inner and outer vent pipes. Ensure that
all inner vent pipes and elbows have sufficient vent spacers attached and each
component is securely fastened to the one prior. Attach the telescopic sleeve to the
vent run. Secure and seal. To facilitate completion, attach inner and outer couplers to
the air terminal.
C. Install the air terminal. See “HORIZONTAL AIR TERMINAL INSTALLATION” section. Extend the outer
telescopic sleeve; connect to the air terminal assembly. Fasten with self tapping screws and seal.
AIR TERMINAL
20" (508mm)
COUPLER
48.2A
TELESCOPIC SLEEVE
VENTING
W415-1332 / A / 11.21.14
4.4 VERTICAL AIR TERMINAL INSTALLATION
!
WARNING
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
A.Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately
supported using either an alternate method suitable to the authority
having jurisdiction or the optional roof support.
B.Stretch the inner fl ex pipe to the required length. Slip the
inner fl ex pipe a minimum of 2” (51mm) over the inner pipe
of the air terminal connector and secure with 3 #8 screws.
Seal using a heavy bead of high temperature sealant
W573-0007 (not supplied).
21
EN
C.Repeat using the outer fl ex pipe, using a heavy bead of
high temperature sealant W573-0002 (not supplied).
D.Thread the air terminal connector / vent pipe assembly down through
the roof. The air terminal must be positioned vertically and plumb.
Attach the air terminal connector to the roof support, ensuring that the
top of the air terminal is 16” (406mm) above the highest point that it
penetrates the roof.
E.Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” (19mm) of the air terminal connector showing
above the top of the fl ashing. Slide the fl ashing underneath the
sides and upper edge of the shingles. Ensure that the air terminal
connector is properly centred within the fl ashing, giving a 3/4”
(19mm) margin all around. Fasten to the roof. Do not nail through
the lower portion of the fl ashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and top edges of the
fl ashing with roofi ng material.
2” (51mm)
F.Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure
the vent pipe goes into the hole in the terminal. Secure with
the three screws provided.
G.Apply a heavy bead of weatherproof caulking 2” (51mm) above
the fl ashing. Install the storm collar around the air terminal and
slide down to the caulking. Tighten to ensure that a weathertight seal between the air terminal and the collar is achieved.
ROOF SUPPORT
INNER PIPE
AIR
TERMINAL
CONNECTOR
HIGH
TEMPERATURE
SEALANT
INNER FLEX PIPE
OUTER FLEX PIPE
AIR I NL ET
BASE
CAULKING
STORM COLLAR
WEA THER
SEALANT
FLASHING
H.If more vent pipe needs to be used to reach the appliance see “HORIZONTAL
AIR TERMINAL INSTALLATION” section.
24.1A
W415-1332 / A / 11.21.14
22
4.5 APPLIANCE VENT CONNECTION
EN
A. Attach the adjustable pipe to the last section of rigid pipe. Secure
with screws and seal.
B. Install the inner fl ex pipe to the appliance. Secure with 3 screws
and fl at washers. Seal the joint and screw holes using the high
temperature sealant W573-0007 (not supplied).
C. Run a bead of high temperature sealant (not supplied) around the
inside of the air intake collar. Pull the adjustable pipe a minimum 2”
(50.8mm) into the air intake collar.
NOTE: Ensure that the sealant is not visible on the exterior pipes once
installation is completed. An optional decorative black band is available
for this use. In the event that the venting must be disassembled, care
must be taken to reseal the venting.
4.6 GAS INSTALLATION
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH
!
WARNING
AS SPARKS OR OPEN FLAMES.
#8 X 1/2”
SELF
DRILLING
SCREWS
2” (50.8mm)
OVERLAP
HIGH TEMPERATURE
SEALANT
28.5A
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Installation and servicing to be done by a qualifi ed installer. Do not use open fl ame.
A. Move the appliance into position and secure.
B. If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.
C.Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
D. When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
E. Check for gas leaks by brushing on a soap and water solution.
W415-1332 / A / 11.21.14
30.2
4.7 MOBILE HOME
23
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit. Built
in appliances are equipped with 1/4” diameter holes located in the front left and right corners of the base. Use #10
hex head screws, inserted through the holes in the base to secure. For free standing products contact your local
authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must be
fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and
the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting
the appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certifi ed kit is used.
Conversion Kits
This appliance is fi eld convertible between Natural Gas (NG) and Propane (LP).
To convert from one gas to another consult your Authorized dealer/distributor.
29.6
EN
W415-1332 / A / 11.21.14
24
4.8 MINIMUM CLEARANCE TO COMBUSTIBLES
EN
!
WARNING
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS LISTED MUST BE CONSTRUCTED
ENTIRELY OF NON-COMBUSTIBLE MATERIALS (I.E. STEEL STUDS, CEMENT BOARD, ETC.).
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
As long as clearance to combustibles is kept within the required distances, the most desirable and benefi cial
location for a Napoleon® appliance is in the centre of a building, thereby allowing the most effi cient use of
the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be
located should be considered. If possible, you should choose a location where the vent will pass through the
house without cutting a fl oor or roof joist.
A. 4” (102mm) B. 2” (51mm)* C. 2” (51mm)
To ceiling from appliance top 48” (1219mm)
Horizontal vent
Sides and bottom 1” (25mm)
Top 2” (51mm)
Vertical vent
All sides 1” (25mm)
*At a distance of 2” (51mm) from the wall, installation or service to the blower may not be practical. A minimum
of 5” (127mm) will be required in order to install the blower.
If less than 5” (127mm) clearance is maintained between the back of the appliance and the back wall, it will be
necessary to disconnect the venting and gas pipe to move the appliance out for installation or service of the
blower.
W415-1332 / A / 11.21.14
4.9 MINIMUM MANTEL OR SHELF CLEARANCES
25
!
WARNING
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
When the appliance is rear vented, a mantel or shelf may be installed above the GDS25 at a minimum
distance of 8” (203mm).
COMBUSTIBLE
NON-COMBUSTIBLE
BRICK
0” (0mm) IF NONCOMBUSTIBLE
FINISHING IS
USED SUCH AS
BRICK AND STONE
COMBUSTIBLE
MANTEL OR
TRIM MATERIAL
8” (203mm)
MIN.
12” (305mm)
MAX. MANTEL DEPTH
2” (51mm)
EN
2”
(51mm)
1” (25mm)
24.5”
(622mm)
W415-1332 / A / 11.21.14
26
5.0 FINISHING
!
WARNING
EN
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
DO NOT STRIKE, SLAM OR SCRATCH GLASS. DO NOT OPERATE APPLIANCE WITH GLASS
REMOVED, CRACKED, BROKEN OR SCRATCHED.
5.1 CAST FRONT INSTALLATION AND REMOVAL
GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED.
A. Remove safety barrier.
B. Lift the top cast piece off of
the appliance.
C.Detach the front cast piece
from the side pieces by
removing the screws from
the brackets located in the
upper inside corners.
D.Slide the front straight up to
remove.
FRONT
RISK OF FIRE!
!
WARNING
3
72.4
2
SCREWS
BRACKET
FRONT
TAB
Follow the above steps in reverse
in order to reinstall the cast front.
Ensure that the tabs on the
underside of the front fi t behind the
front legs.
NOTE: It is not necessary to
remove the cast front, in order to
remove the door.
DOOR
RETAINER
5.2 SAFETY BARRIER INSTALLATION AND REMOVAL
A barrier designed to reduce the risk of burns from the hot viewing glass, is provided with the
appliance and shall be installed.
A. Lift the top casting up and remove the safety barrier. Remove and discard plastic.
B. Tilt the top of the safety barrier and hook under the top casting, make sure to hold the safety barrier.
C. Slightly lift the bottom of the safety barrier and push onto the unit. Careful not to scratch the bottom
casting.
D.Reverse these steps to remove.
FRONT
LEGS
SAFETY BARRIER
W415-1332 / A / 11.21.14
SAFETY BARRIER
5.3 GLASS DOOR INSTALLATION AND REMOVAL
!
WARNING
DO NOT USE SUBSTITUTE MATERIALS.
GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED.
A. Remove safety barrier.
B. Lift the top cast piece off of the appliance.
C. Pull handle and rotate 90°.
D. Slide the door straight up to remove.
Follow the above steps in reverse in order to reinstall the door.
Ensure that the bottom of the door engages the door retainer before
closing the latches.
27
EN
3
LATCHES
2
DOOR
5.4 LOG PLACEMENT
LOGS MUST BE PLACED IN THE EXACT LOCATION IN APPLIANCE. DO NOT CHANGE FROM THE
PROPER LOG POSITIONS. APPLIANCE MAY NOT FUNCTION PROPERLY.
THE LOGS ARE FRAGILE AND SHOULD BE HANDLED WITH CARE.
It is not necessary to remove the cast front, however, this will make for a more simple log installation.
In order to assemble the log set, the glass door must be removed, see “CAST FRONT / GLASS DOOR
INSTALLATION AND REMOVAL” section.
LOG LOCATING SCREWS
!
WARNING
BRACKET
A. Place the rear log, as shown, onto the rear
log support brackets. Ensure the cutout on
the left underside of the log, fi ts over the pilot-
assembly. Bend the bracket on the left side to
help retain the rear log.
W415-1332 / A / 11.21.14
LOGO
1/2”
1/2”
EN
28
B. Place the hole in the underside of log #2
onto the locating screw, on the left side of the
burner. The fi bre burner is formed to cradle
the centre of the log.
5.5.1 SWITCH FUNCTIONS
FAN
CONTROL
C.Place the hole in the underside of log #3 onto
the locating screw, on the right side of the
burner. The bottom branch of log #3 sits in
front of, and against, the right end of log #2.
D.Reinstall the glass door & front.
MAIN
BURNER
SWITCH
ACCENT
LIGHT
SWITCH
5.6 LOGO PLACEMENT
Remove the backing from the logo and position onto the control door as shown.
W415-1332 / A / 11.21.14
6.0 OPTIONAL BLOWER INSTALLATION
4
5
2
3
1
4
8
9
7
7
29
!
WARNING
RISK OF FIRE AND ELECTRICAL SHOCK.
TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THIS APPLIANCE.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH
THIS APPLIANCE. USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS
COMPONENTS, VENTING COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL
VOID THE WARRANTY AND CERTIFICATION.
BLOWER
A.Cut and remove the tie securing the blower switch wires
to the heat shield.
B.Connect the white wire coming from below the appliance
to the terminal on the blower.
C.Connect the black blower wire to the black wire coming
from below the appliance.
D.Insert the clips on the blower housing into the cutouts in
the rear shield. Push down to lock the clips into position.
E. Secure the blower using the screw and lock washer
supplied.
NOTE: Ensure
that all the wires
are tucked into
the blower switch
housing.
7
7
9
8
1
4
4
EN
2
3
5
SWITCHES
F. Open the switch housing by removing the top screw.
G. Install the thermodisc bracket as shown, using 2 of the screws
supplied. Connect the fl agged leads to the terminals of the
thermodisc.
Remove the knock out from the housing label.
H.Install the variable speed switch (rheostat) into the housing
with the wires facing up. Secure the switch to the housing
using the pal nut and the knob supplied.
I. Connect the male connector on the switch to the female
J. Tuck all of the wires into the housing and close. Secure using
connector coming from the appliance.
the screw removed in step F.
W415-1332 / A / 11.21.14
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.