Napoleon Installation And Operating Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22, ANSI Z21.50 FOR VENTED GAS FIREPLACE HEATERS.
1
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
CERTIFIED FOR CANADAAND UNITED STATES USING ANSI/CSA METHODS.
If the information in these instructions
are not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
!
WARNING
GD80NT
NATURAL GAS
GD80PT
PROPANE
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 27
5.3 ALCOVE FRAMING 29
5.4 MINIMUM MANTEL CLEARANCES 30
6.0 FINISHING 31
6.1 DOOR REMOVAL / INSTALLATION 31
6.2 LOG SHIPPING BRACKET 32
6.3 DECORATIVE BRICK PANEL INSTALLATION 33
6.4 LOG PLACEMENT 34
6.5 GLOWING EMBERS 35
6.6 CHARCOAL EMBERS 35
7.0 OPERATION 36
7.1 GENERAL TRANSMITTER LAYOUT 36
7.2 APPLIANCE OPERATION 36
7.3 HAND HELD REMOTE OPERATIONS 37
7.4 TEMPERATURE DISPLAY 37
7.5 ROOM THERMOSTAT 37
7.6 SMART THERMOSTAT 37
7.7 FLAME HEIGHT 38
7.8 FAN SPEED 38
7.9 CHILD PROOF FUNCTION 38
7.10 NIGHT LIGHTSTM 39
7.11 LOW BATTERY / MANUAL BYPASS 39
7.12 IN THE EVENT OF A POWER FAILURE 39
7.13 CONTROL MODULE 40
7.14 TIMED BLOWER 40
8.0 ELECTRICAL INFORMATION 41
8.1 HARD WIRING CONNECTION 41
9.0 OPERATING INSTRUCTIONS 42
10.1 PILOT BURNER ADJUSTMENT 43
10.0 ADJUSTMENT 43
10.2 VENTURI ADJUSTMENT 43
10.3 FLAME CHARACTERISTICS 44
10.4 AIR CONTROL ROD ACCESS 44
11.0 MAINTENANCE 45
11.1 INNER ACCESS PANEL 45
11.2 NIGHT LIGHTTM REPLACEMENT 46
11.3 BLOWER REPLACEMENT 46
11.4 REMOTE RECEIVER REMOVAL 47
11.5 VALVE REMOVAL 47
11.6 “AUTO SPARK” BATTERY REMOVAL 48
11.7 CARE OF GLASS 48
11.8 RESTRICTING VERTICAL VENTS 48
12.0 REPLACEMENTS 49
13.0 TROUBLESHOOTING 53
14.0 WARRANTY 56
15.0 SERVICE HISTORY 57
W415-0695 / C / 03.19.12
1.0 INSTALLATION OVERVIEW
See the sections
“MINIMUM ENCLOSURE
CLEARANCES” for drywall
(or other combustible
material)
3
See the sections “MINIMUM
ENCLOSURE
CLEARANCES” for
non-combustible material
See the section “MINIMUM
MANTEL AND ENCLOSURE
CLEARANCES”
Side
Wall
See the section
“FRAMING”
See the section
“VENTING” and
“INSTALLATION”
See the section
“INSTALLATION-FRAMING”
Rating plate, see
“RATING PLATE
INFORMATION” section.
W415-0695 / C / 03.19.12
4
2.0 INTRODUCTION
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES TO THIS APPLIANCE OR IT’S CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance
according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be
sharp.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or
clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there
are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable safety gate to keep
toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces.
These screens and guards must be fastened to the fl oor.
• Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
• The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance
and venting system are kept clean. The appliance and its venting system should be inspected before use and at least
annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting,
bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other
fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the
appliance and to replace any part of the control system and any gas control which has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done
by a licensed or qualifi ed service person.
• Do not strike or slam shut the appliance glass door.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust
fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these
openings can also cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts
certifi ed with the unit are to be installed on the appliance.
• Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic
bags, these are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as
having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated
temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a
T.V. or other electronic components.
• This appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by
Wolf Steel Ltd.
!
WARNING
Toddlers,
3.1C
W415-0695 / C / 03.19.12
46 ¾”
40 ¾”
5"
18 Ǫ”
30"
37 ¼”
7 ³/
16
"
12
7
/16"
GAS
INLET
ELECTRICAL
INLET
ACCESS
PANEL
48 ¼"
8" DIA.
5" DIA.
10 ǫ"
23 ¹/
16
"
27 ¾"
29"
37 ¼"
46 ¼"
2.1 DIMENSIONS
2.2 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” FROM THE
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
!
WARNING
PROVIDE ADEQUA TE VENTILA TION.
FRONT FACE OF THE APPLIANCE.
FIRE RISK. EXPLOSION HAZARD.
5
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth
of Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of a appliance
insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
• A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
W415-0695 / C / 03.19.12
6
A
A
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed in
accordance with the current standard CAN/CSA Z240MH
Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location
for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1A
2.3 GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
APPLIANCE
NGLP
Altitude (FT)0-4,5000-4,500
Max. Input (BTU/HR)43,00043,000
Max. Output Steady State (BTU/HR)33,54034,000
Effi ciency (w/the fan on)78%79%
Min. Inlet Gas Supply Pressure4.5" Water Column11" Water Column
Max. Inlet Gas Supply Pressure7" Water Column13" Water Column
Manifold Pressure (Under Flow Conditions)3.5" Water Column10" Water Column
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is certifi ed for mobile
home installation.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless kit is used. Not external electricity (110 volts or 24 volts) is required for the
gas system operation.
Expansion / contraction noised during heating up and cooling down cycles are normal and are to be expected.
Change in fl ame appearance from “HI” to “LO” is more evident in natural gas than in propane.
W415-0695 / C / 03.19.12
2.4 RATING PLATE INFORMATION
S
N
AGE AU GAZ AVEC
E SALLE DE BAIN ET UN
NSTALLATION CONFORME
ÉQUIPÉES AU GAZ, E
STRUCTION DE M
U CETTE NORME D'ÉTATS-UNIS
DEL
D80
ÉLÉVATION
/ ALIMENTA TION
ALIMENTATION RÉ
FOLD PRESSURE /
RESSION AU COLLECTEUR
MINIMUM SUPPLYPRESSU
ESSION D'ALIMENTATION
AXIMUM SUPPLY P
LIMENTAT
4001657 (NGZ)
4001659 (WUSA)
BE VENTED USING THE
OLEON VENT KITS. SEE
MANUAL FOR VENTIN
REINSTALLA TION A
VENT-AIR INTA
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to
the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
The illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
7
VENTED GAS FIREPLACE HEATER. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM
INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE
CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE
UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART
3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR
MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
NOT FOR USE WITH SOLID
FUEL. FOR USE WITH GLASS
DOORS CERTIFIED WITH THIS
UNIT ONLY.
WARNING
THE APPLIANCE, WHICH WILL COME IN CONTACT
WITH THE FLAMES, OTHER THAN THAT SUPPLIED
BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE
MATERIALS:
TOP 0 RECESSED DEPTH 29"
FLOOR 0 VENT 2"
SIDES 0 MANTEL 8" *
BACK 0
TOP, SIDES & BACK: PER STAND OFF SPACERS
FOR FRAMING MATERIALS. FOR FINISHING
MATERIALS SEE OWNERS MANUAL
* MAXIMUM HORIZONTAL EXTENSION /
L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE
INSTRUCTION MANUAL FOR GREATER
EXTENSIONS.
SEE OWNER'S INSTRUCTION MANUAL FOR
MINIMUM AND MAXIMUM VENT LENGTHS.
ELECTRICAL RATING: 115V 0.82AMP, 60HZ
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.22b-2009, ANSI Z21.50b-2009 VENTED GAS FIREPLACE / APPAREIL ALIMENTÉ AU GAZ ET VENTILÉ
FOYER DE CHAUFFAGE AU GAZ AVEC ÉVACUATION. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE
À COUCHER, UNE SALLE DE BAIN ETUN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON
MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE
MAISONS MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA NORME DE
SECURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24 CFR, SECTION 3280. DANS LE
CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE APPLIQUÉE, SE RÉFÉRER A LA NORME RELATIVE AU
CRITÈRE DE MESURES DE SÉCURITÉ CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT
L'ENSEMBLE D'ÉVACUATION PROPRE A NAPOLEON.
RÉFÉRER AU MANUEL D'INSTALLATION DE
PROPRIÉTAIRE POUR L'ÉVACUATION PRÉCISE. IL
EST IMPORTANT DE BIEN RÉINSTALLER ET
RESCELLER L'ÉVENT APRÈS AVOIR ASSURÉ LE
MAINTIEN DU SYSTÉME DE PRISE D'AIR.
GD80
MANUFACTURÉS, LES SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A.
UN COMBUSTIBLE SOLIDE NE
DOIT PAS ÊTRÉ UTILISÉ AVEC CET
APPAREIL. UTILISER AVEC LES
PORTES VITRÉES HOMOLOGUÉES
SEULEMENT A VEC CETTE UNITÉ.
AVERTISSEMENT:
APPAREIL AUCUN MATÉRIAU DEVANT ENTRER EN
CONTACT AVEC LES FLAMMES AUTRE QUE CELUI
QUI EST FOURNI AVEC CET APPAREIL PAR LE
FABRICANT.
DÉGAGEMENTS MINIMAUX DES MATÉRIAUX
COMBUSTIBLES:
DESSUS 0 PROFONDEUR D’ENCASTRÉ 29"
PLANCHER 0 ÉVENT 2"
CÔTÉS 0 MANTEAU 8" *
ARRIÈRE 0
DESSUS, COTÉS & ARRIÈRE: SELON LES
ESPACEURS DE DÉGAGEMENT POUR LES
MATÉRIAUX D'OSSATURE SELON LE MANUEL DE
PROPRIÉTAIRE POUR LES MATÉRIAUX DE FINITION.
* L'EXTENSION HORIZONTALE MAXIMALE: 2".
RÉFÉRER AU MANUEL D'INSTRUCTION POUR DES
EXTENSIONS PLUS GRANDES. RÉFÉRER AU MANUEL
D'INSTALLATIONDE PROPRIÉTAIRE.
CLASSIFICATION: 115V 0.82AMP, 60HZ
N'AJOUTEZ PAS A CET
W385-0294
W385-0294 / G
W415-0695 / C / 03.19.12
8
3.0 VENTING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5” EXHAUST / 8” AIR INTAKE VENT PIPE SYSTEM.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
!
WARNING
Refer to the section applicable to your installation.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.2B
W415-0695 / C / 03.19.12
3.1 VENTING LENGTHS AND COMPONENTS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab
venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and
air terminal locations for either system are set out in this manual and must be adhered to. For Simpson DuraVent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided
with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the
corresponding supplier:
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a
red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent
pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar
which must be sealed using the black high temperature sealant Mill Pac.
9
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following
termination kits: wall terminal kit GD422-1, GD422R-1, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12 roof
terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With fl exible
venting, in conjunction with the various terminations, use either the 5 foot vent kit GD420 or the 10 foot vent kit GD430.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a
minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must
not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run
is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” rise per foot however for optimum performance it is recommended that all horizontal
runs have a minimum 1/4” rise per foot using fl exible venting. For safe and proper operation of the appliance, follow
the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family
dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” air gap
all around between the inner liner and outer liner is required for safe operation.
8.3
W415-0695 / C / 03.19.12
10
3.2 TYPICAL VENT INSTALLATION
16” MINIMUM
24” MAXIMUM
13”
MINIMUM
40 3/4”
* See “VENTING” section
3 FEET
MINIMUM
40 FEET
MAXIMUM
53 3/4”
MINIMUM
PLUS RISE*
40 3/4”
Horizontal runs may have a 0” rise per foot in all cases using Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Wolf Steel Ltd. rigid or fl exible venting components when venting as illustrated.
If vertical rises greater than 57” are necessary, the increased rise must be deducted from the horizontal run.
W415-0695 / C / 03.19.12
3.3 SPECIAL VENT INSTALLATION
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum 12” above grade. The maximum allowable vent length is 10’ for a
fi replace and 8’ for a stove.
11
12”
MINIMUM
TO GRADE
30”
MINIMUM
40 3/4”
9.1A
W415-0695 / C / 03.19.12
12
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES
COVERED BALCONY APPLICATIONS
R
Q
M
G
P
Q
R
R
MIN
MAX
MAX
= 3 feet
= 2 x
Q
feet
ACTUAL
INSTALLATIONS
CANADAU.S.A.
A12”12”Clearance above grade, veranda porch, deck or balcony.
B12”
Δ
9”
Δ
Clearance to windows or doors that open.
C12” *12” *Clearance to permanently closed windows.
D18” **18” **
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ from
the centerline of the terminal.
E12” **12” **Clearance to unventilated soffi t.
F0”0”Clearance to an outside corner wall.
G
H3’3’ ****
0” ***0” ***Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” ***2” ***Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum
vertical distance of 15’.
I3’3’ ****Clearance to a service regulator vent outlet.
J12”9”Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K6’3’Clearance to a mechanical air supply inlet.
L7’ ‡7’ ****Clearance above a paved sidewalk or paved driveway located on public property.
M12” ††12” ****Clearance under a veranda, porch, deck or balcony.
N16”16”Clearance above the roof.
O2’ †*2’ †*Clearance from an adjacent wall including neighbouring buildings.
P8’8’Roof must be non-combustible without openings.
Q3’3’See chart for wider wall dimensions.
R6’6’
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18” clearance from an inside corner.
****This is a recommended distance. For additional requirements check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
12.3B
W415-0695 / C / 03.19.12
3.5 VENTING APPLICATION FLOW CHART
13
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
HR - combined horizontal vent lengths in feet
HO - offset factor: .03 (total degrees of offset - 90°*) in feet
VT - combined vertical vent lengths in feet
Since both formulas are met, this vent configuration is acceptable.
16.1_2
W415-0695 / C / 03.19.12
16
3.9 VERTICAL TERMINATION
(HT) < (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run HT.
40
30
REQUIRED
VERTICAL
20
RISE IN
FEET V
T
10
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring one or more 90° elbows the following formulas apply:
Formula 1: H
Formula 2: HT + V
< V
T
T
< 40 feet
T
for the
T
T
Example:
V
= 5 FT
1
V
= 6 FT
2
V
= 10 FT
3
V
= V
+ V2 + V3 = 5 + 6 + 10 = 21 FT
T
1
H
= 8 FT
1
H
= 2.5 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
T
H
+ V
T
Formula 1: HT < V
18.6 < 21
Formula 2: HT + V
39.6 < 40
= 8 + 2.5 = 10.5 FT
1
2
+ H
= 10.5 + 8.1 = 18.6 FT
R
O
= 18.6 + 21 = 39.6 FT
T
T
< 40 FT
T
Since both formulas are met, this vent configuration is acceptable.
90°
V
3
90°
H
2
V
H
1
V
1
2
90°
90°
18.1
W415-0695 / C / 03.19.12
17
(HT) > (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run H
20
19
REQUIRED
VERTICAL
RISE IN
FEET V
10
T
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring more than two 90° elbows the following formulas apply:
Formula 1: H
Formula 2: HT + V
< 3V
T
T
< 40 feet
T
Example:
V
= 2 FT
1
V
= 1 FT
2
V
= 1.5 FT
3
V
= V
+ V2 + V3 = 2 + 1 + 1.5 = 4.5 FT
T
1
H
= 6 FT
1
H
= 2 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
T
H
+ V
T
= 6 + 2 = 8 FT
1
2
+ H
= 8 + 8.1 = 16.1 FT
R
O
= 16.1 + 4.5 = 20.6 FT
T
90°
H
V
1
1
90°
for the
.
T
H
V
2
T
2530
V
2
T
3
90°
90°
Formula 1: HT < 3V
3VT = 3 x 4.5 = 13.5 FT
T
16.1 > 13.5Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + VT < 40 feet
20.6 < 40
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration will
need to be established to satisfy both formulas.
18.1_2A
W415-0695 / C / 03.19.12
18
4.0 INSTALLATION
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
WHICH MUST BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
!
WARNING
EXACTLY.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
68.2A
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
WARNING
70.1
W415-0695 / C / 03.19.12