Napoleon GD70NT-S, GD70PT-S Installation And Operating Instructions Manual

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS.
GD70NT-S
1
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
!
WARNING
NATURAL GAS
GD70PT-S
PROPANE
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
Phone (705)721-1212 • Fax (705)722-6031 • www.napoleonfi replaces.com • ask@napoleonproducts.com
$10.00
1.28C
W415-0434 / G / 08.08.11
2
TABLE OF CONTENTS
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 5
2.3 GENERAL INFORMATION 6
2.4 RATING PLATE INFORMATION 7
3.0 VENTING 8
3.1 VENTING LENGTHS AND COMPONENTS 9
3.2 TYPICAL VENT INSTALLATION 10
3.3 SPECIAL VENT INSTALLATION 11
3.3.1 PERISCOPE TERMINATION 11
3.4 VENT TERMINAL CLEARANCES 12
3.5 VENTING APPLICATION FLOW CHART 13
3.6 DEFINITIONS 13
3.7 ELBOW VENT LENGTH VALUES 13
3.8 TOP EXIT HORIZONTAL TERMINATION 14
3.9 VERTICAL TERMINATION 16
4.0 INSTALLATION 18
4.1 WALL AND CEILING PROTECTION 18
4.1.1 HORIZONTAL SHIELDING 19
4.1.2 VERTICAL SHIELDING 19
4.2 USING FLEXIBLE VENT COMPONENTS 20
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 20
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 21
4.2.3 APPLIANCE VENT CONNECTION 22
4.3 USING RIGID VENT COMPONENTS 22
4.3.1 HORIZONTAL AIR TERMINAL INSTALLATION 22
4.3.2 VERTICAL AIR TERMINAL INSTALLATION 23
4.4 GAS INSTALLATION 24
4.5 OPTIONAL WALL SWITCH / THERMOSTAT 25
4.6 MOBILE HOME INSTALLATION 25
5.0 FRAMING 26
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES 27
5.2 PROTRUDING FINISH 28
5.3 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 29
5.4 MINIMUM MANTEL CLEARANCES 29
6.0 FINISHING 30
6.1 DOOR INSTALLATION 30
6.2 DOOR CLOSING AND OPENING 31
6.3 LOG SHIPPING BRACKET 31
6.4 DECORATIVE PANELS 31
6.5 CHARCOAL STRIPS 31
6.6 LOG PLACEMENT 31
6.7 CHARCOAL EMBERS 33
6.8 GLOWING EMBERS 33
6.9 LOUVRE INSTALLATION 33
6.10 LOGO PLACEMENT 33
7.0 WIRING DIAGRAM / ELECTRICAL INFORMATION 34
8.0 OPERATION 35
9.0 ADJUSTMENTS 36
9.1 PILOT BURNER ADJUSTMENT 36
9.2 VENTURI ADJUSTMENT 36
9.3 FLAME CHARACTERISTICS 37
9.4 RESTRICTING VERTICAL VENTS 37
10.0 MAINTENANCE 38
10.1 NIGHT LIGHT REPLACEMENT 39
10.2 THERMAL SWITCH REPLACEMENT 39
10.3 BLOWER REPLACEMENT 40
10.4 CARE OF GLASS 40
11.0 REPLACEMENTS 41
12.0 TROUBLE SHOOTING 45
13.0 WARRANTY 47
14.0 SERVICE HISTORY 48
W415-0434 / G / 08.08.11
1.0 INSTALLATION OVERVIEW
Venting, see “VENTING” section.
Louvre, see “LOUVRE INSTALLATION” section.
Logo, see “LOGO PLACEMENT” section.
3
See “FINISHING” section for Log shipping bracket, Decorative panels, Charcoal Strip, Log placement, Char­coal and glowing embers.
Rating plate, see “RATING PLATE INFORMATION” section.
Door, see “DOOR INSTALLATION” section.
W415-0434 / G / 08.08.11
4
2.0 INTRODUCTION
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES TO THIS APPLIANCE OR IT’S CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated
temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic components.
This appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
!
WARNING
Toddlers,
3.1C
W415-0434 / G / 08.08.11
2.1 DIMENSIONS
THE DOOR FOR THIS APPLIANCE IS SOLD SEPARATELY. THE DOOR MUST BE INSTALLED AND
CLOSED BEFORE OPERATION BEGINS. SEE “DOOR INSTALLATION” SECTION FOR FURTHER
!
WARNING
DETAILS.
5
411/2"
36"
2.2 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” FROM THE
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
4" DIA.
7" 4"
ELECTRICAL INLET
LEFT SIDE
!
WARNING
PROVIDE ADEQUA TE VENTILA TION.
FRONT FACE OF THE UNIT.
GAS
INLET
7" DIA.
18
24"
18"
11"
5
/8"
1
37
/4"
16"
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of a appliance insert or gas log.
The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
FIRE RISK. EXPLOSION HAZARD.
W415-0434 / G / 08.08.11
6
A
A
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
2.3 GENERAL INFORMATION
www.ncertied.org
We suggest that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1A
FOR YOUR SA TISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
GD70
NG LP
Altitude (FT) 0-4,500 0-4,500
Max. Input (BTU/HR) 35,000 33,000
Max. Output (BTU/HR) 28,350 26,400
Effi ciency (w/the fan on) 81% 80%
A.F.U.E. 64% 65%
Min. Inlet Gas Supply Pressure 4.5" Water Column 11" Water Column
Max. Inlet Gas Supply Pressure 7" Water Column 13" Water Column
Manifold Pressure (Under Flow Conditions) 3.5" Water Column 10" Water Column
When the appliance is installed at elevations above 4,500ft, and in the absence of specifi c recommendations from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for each ad- ditional 1,000ft.
No external electricity (110 volts or 24 volts) is required for the gas system operation.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected. Change in fl ame appearance from “HI” to “LO” is more evident in natural gas than in propane.
8” is the minimum bend radius allowed for the 7” diameter fl exible air liner.
W415-0434 / G / 08.08.11
2.4 RATING PLATE INFORMATION
AU GAZ AVEC ÉVACUATIOAU GAZ AVEC ÉVACUA
MAISON MOBILE SI SON INSTALLATIO
ON MOBILE SI SON INSTALLATIO
SÉCURITÉ CONTRE L'INCENDIE SÉCURITÉ CONTRE L'INCENDIE
MANUFACTMANUFAC
INPUT / ALIMENTATION RÉDUITEPUT / ALIMENTATION R
OUTPUT /
OUTPUT / RENDEMEN
AFUE
ESSUS, CÔTÉS ET ARRIÈRE: SELON LESSUS, CÔTÉS ET ARRIÈRE: SELON
ÉRER AU MANUEL D'INSTRUC
DE PROPRIÉTAIRE PPROPRIÉTAIRE P
4
4001657 (NG
4
)01659 (WUSA)
ER / APPAREIL DE CHER / APPAREIL DE C
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.33-2009, ANSI Z21.88-2009 VENTED GAS FIREPLACE HEATER / APPAREIL DE CHAUFFAGE ALIMENTÉ AU GAZ ET VENTILÉ.
VENTED GAS FIREPLACE HEATER. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
9700539 (WSL) 4001657 (NGZ) 4001658 (NAC) 4001659 (WUSA)
GD70-N / CDV70N MODEL GD70-P / CDV70P
0-4500FT (0-1370m) ALTITUDE / ÉLÉVATION 0-4500FT (0-1370m) 35,000 BTU/h INPUT / ALIMENTATION 33,000 BTU/h 23,000 BTU/h REDUCED INPUT / ALIMENTATION RÉDUITE 23,000 BTU/h 24,500 BTU/h OUTPUT / RENDEMENT 23,400 BTU/h
3.5" WATER COLUMN/D'UNE COLONNE D'EAU MANIFOLD PRESSURE / PRESSION AU COLLECTEUR 10" WATER COLUMN/D'UNE COLONNE D'EAU
4.5" WATER COLUMN/D'UNE COLONNE D'EAU MINIMUM SUPPLY PRESSURE / PRESSION D'ALIMENTATION MINIMALE 11" WATER COLUMN/D'UNE COLONNE D'EAU
7.0" WATER COLUMN/D'UNE COLONNE D'EAU MAXIMUM SUPPLY PRESSURE / PRESSION D'ALIMENTATION MAXIMALE 13" WATER COLUMN/D'UNE COLONNE D'EAU 70% FAN OFF/VENTILATEUR ARRÊTÉ 70% FAN ON/VENTILATEUR FONCTIONNE 71% FAN ON/VENTILATEUR FONCTIONNE 64% AFUE 65%
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT
WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS / DÉGAGEMENTS MINIMAUX DES MATÉRIAUX COMBUSTIBLES:
TOP/ DESSUS 0 RECESSED DEPTH / PROFONDEUR D'ENCASTRÉ 18” FLOOR / PLANCHER 0 VENT / ÉVENT 1" SIDES / CÔTÉS 0 MANTEL / MANTEAU 2" * BACK / ARRIÈRE 0 TOP, SIDES AND BACK: PER STAND OFF SPACERS FOR FRAMING MATERIALS. FOR FINISHING MATERIALS SEE OWNERS MANUAL / DESSUS, CÔTÉS ET ARRIÈRE: SELON LES ESPACEURS DE DÉGAGEMENT POUR LES MATÉRIAUX D’OSSATURE SELON LE MANUEL DE PROPRIÉTAIRE POUR LES MATÉRIAUX DE FINITION.
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION MANUAL
FOR GREATER EXTENSIONS. RÉFÉRER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES. SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS. RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR LES LONGUEURS D'ÉVACUATION MINIMALE ET MAXIMALE.
STEADY STATE EFFICIENCY / EFFICACITÉ CONSTANTE
FOYER DE CHAUFFAGE AU GAZ AVEC ÉVACUATION. HOMOLOGUÉ POUR INSTALLATION DANS UNE
CHAMBRE À COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE MAISONS MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA NORME DE SÉCURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE APPLIQUÉE, SE RÉFÉRER À LA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS
001657 (NGZ) 001659 (WUSA
RENDEMENT
AFUE
UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ AVEC CET APPAREIL. UTILISER AVEC LES PORTES VITRÉES HOMOLOGUÉES SEULEMENT AVEC CETTE UNITÉ.
AVERTISSEMENT:
CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM. L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'ÉVACUATION PROPRE À WOLF STEEL. RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR L'ÉVACUATION PRÉCISE. IL EST IMPORTANT DE BIEN RÉINSTALLER ET RESCELLER L'ÉVENT APRÈS AVOIR ASSURÉ LE MAINTIEN DU SYSTÈME DE PRISE D'AIR. ELECTRICAL RATING / CLASSIFICATION: 115V 0.82AMPS, 60HZ OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: GZ550-KT, GD65
SERIAL NUMBER /NO. DE SERIE:
MANUFACTURÉS, LES SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A.
71% FAN OFF/VENTILATEUR ARRÊTÉ
N’AJOUTEZ PAS À CET APPAREIL AUCUN MATÉRIAU DEVANT ENTRER EN
GD70
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
WOLF STEEL LTD.
W385-0290 / H
7
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
W415-0434 / G / 08.08.11
8
3.0 VENTING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 4” EXHAUST / 7” AIR INTAKE VENT PIPE SYSTEM.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial installation.
!
WARNING
Refer to the section applicable to your installation.
7.1A
W415-0434 / G / 08.08.11
3.1 VENTING LENGTHS AND COMPONENTS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
PART 4”/7” SUPPLIER WEBSITE
Duravent W175-0053 Wolf Steel www.duravent.com
Amerivent 4DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 4DT-AAN Selkirk www.selkirkcorp.com
SuperSeal 4DNA Metal-Fab www.mtlfab.com
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature sealant Mill Pac. High temperature sealant must be ordered separately.
9
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following
termination kits: wall terminal kit GD222R, or 1/12 to 7/12 pitch roof terminal kit GD110, 8/12 to 12/12 roof terminal kit GD111, fl at roof terminal kit GD112 or periscope kit GD201 (for wall penetration below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD220 or the 10 foot vent kit GD330.
For optimum flame appearance and appliance performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” rise per foot however for optimum performance it is recommended that all horizontal runs have a minimum 1” rise per foot using fl exible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” air gap all around between the inner liner and outer liner is required for safe operation.
8.7
W415-0434 / G / 08.08.11
10
3.2 TYPICAL VENT INSTALLATION
16” MINIMUM
WARNING!
24” MAXIMUM
13 3/4” MIN
36”
* See “VENTING” section
THE FIRST TWO FEET OF
OUTER 7” DIAMETER VENT
PIPE FROM THE APPLIANCE
MUST BE WRAPPED IN THE 1”
THICK INSULATION SLEEVE
49 3/4”
MINIMUM
PLUS RISE*
(SUPPLIED).
3 FEET
MINIMUM
40 FEET
MAXIMUM
36”
45.6
W415-0434 / G / 08.08.11
3.3 SPECIAL VENT INSTALLATION
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when fi nal grading is completed, the bottom air slot is located a minimum 12” above grade. The maximum allowable vent length (including both rise and run) is 10’.
11
12” MIN TO GRADE
30” MIN
36”
9.3A
W415-0434 / G / 08.08.11
12
3.4 VENT TERMINAL CLEARANCES
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
Q
R
R
INSTALLATIONS
MIN
MAX
MAX
= 3 feet
= 2 x
Q
 feet
ACTUAL
CANADA U.S.A. A 12” 12” Clearance above grade, veranda porch, deck or balcony. B 12”
Δ
Δ
9”
Clearance to windows or doors that open.
C 12” * 12” * Clearance to permanently closed windows.
D 18” ** 18” **
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ from the center line of the terminal.
E 12” ** 12” ** Clearance to unventilated sof t.
F 0” 0” Clearance to an outside corner wall.
G
H 3’ 3’ ****
0” *** 0” *** Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” *** 2” *** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15’.
I 3’ 3’ **** Clearance to a service regulator vent outlet.
J 12” 9” Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K 6’ 3’ † Clearance to a mechanical air supply inlet.
L 7’ ‡ 7’ **** Clearance above a paved sidewalk or paved driveway located on public property. M 12” †† 12” **** Clearance under a veranda, porch or deck. N 16” 16” Clearance above the roof. O 2’ †* 2’ †* Clearance from an adjacent wall including neighbouring buildings.
P 8’ 8’ Roof must be non-combustible without openings. Q 3’ 3’ See chart for wider wall dimensions.
R 6’ 6’
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an open­ing between the terminal and the open side of the structure.
S 12” 12” Clearance under a covered balcony
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
W415-0434 / G / 08.08.11
12.1C
3.5 VENTING APPLICATION FLOW CHART
13
Horizontal Termination
Vertical rise is equal
to or greater than the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are: > - greater than > - equal to or greater than < - less than < - equal to or less than HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet HR - combined horizontal vent lengths in feet HO - offset factor: .03 (total degrees of offset - 90°*) in feet VT - combined vertical vent lengths in feet
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet
4.2 times the
vertical rise equal to
or greater than the
horizontal run
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3 times the vertical
rise equal to or
greater than the
horizontal run
13.1
14.1
3.7 ELBOW VENT LENGTH VALUES
FEET INCHES
1° 0.03 0.5 15° 0.45 6.0 30° 0.9 11.0 45° 1.35 16.0 90°* 2.7 32.0
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
15.1
W415-0434 / G / 08.08.11
14
3.8 TOP EXIT HORIZONTAL TERMINATION
(HT) < (VT)
Simple venting confi guration (only one 90° elbow)
See graph to determine the required vertical
rise V
for the required horizontal run HT.
T
40
39
30
REQUIRED
VERTICAL
20
RISE IN
FEET VT
10
0
2.5 5 7.5 10 12.5 15
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET H
T
The shaded area within the lines represents
acceptable values for HT and V
For vent confi gurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet
Example: V
= 3 FT
1
V
= 8 FT
2
VT = V1 + V H
= 2.5 FT
1
H
= 2 FT
2
HR = H1 + H H
= .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT
O
= 3 FT + 8 FT = 11 FT
2
= 2.5 + 2 = 4.5 FT
2
HT = HR + HO = 4.5 + 5.4 = 9.9 FT HT + V
= 9.9 + 11 = 20.9 FT
T
90°
90°
90°
V
2
H
1
17.5 20
T
H
2
Formula 1: HT < V
T
9.9 < 11 Formula 2: H
+ VT < 40 FT
T
20.9 < 40
Since both formulas are met, this vent confi guration is acceptable.
W415-0434 / G / 08.08.11
V
1
16.1A
15
V
V V V
(HT) > (VT)
Simple venting configuration (only one 90° elbow)
REQUIRED
See graph to determine the required vertical rise VT for the
required horizontal run H
150
147”
100
.
T
VERTICAL
RISE IN
INCHES V
T
57”
50
13.75”
0
515
1.17’
10
12.5’
19.5’
20
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring more than one 90° elbow, the following formulas apply:
< 4.2 V
Formula 1: Formula 2: HT + V
H
T
T
< 24.75 feet
T
90°
H
1
H
2
Example:
= VT = 6 FT
1
H
= 3 FT
1
H
= 5 FT
2
H
= H
+ H
R
H
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7 FT
O
H
= H
T
H
+ V
T
= 3 + 5 = 8 FT
1
2
+ H
= 8 + 2.7 = 10.7 FT
R
O
= 10.7 + 6 = 16.7 FT
T
V
1
90°
Formula 1: HT < 4.2 V
4.2 VT = 4.2 x 6 = 25.2 FT
10.7 < 25.2
Formula 2: HT + V
16.7 < 24.75
Since both formulas are met, this vent configuration is acceptable.
Example:
= 4 FT
1
= 1.5 FT
2
= V
+ V
T
H
= 2 FT
1
H
= 1 FT
2
H
= 1 FT
3
H
= 1.5 FT
4
H
= H
R
H
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT
O
H
= H
T
H
+ V
T
= 4 + 1.5 = 5.5 FT
1
2
+ H2 + H
1
+ H
R
= 13.6 + 5.5 = 19.1 FT
T
+ H4 = 2 + 1 + 1 + 1.5 = 5.5 FT
3
= 5.5 + 8.1 = 13.6 FT
O
Formula 1: HT < 4.2 V
4.2 VT = 4.2 x 5.5 = 23.1 FT
T
< 24.75 FT
T
T
90°
90°
90°
H
1
90°
V
1
V
H
H
2
3
H
4
2
13.6 < 23.1 Formula 2: HT + V
19.1 < 24.75
< 24.75 FT
T
Since both formulas are met, this vent configuration is acceptable.
16.11
W415-0434 / G / 08.08.11
Loading...
+ 33 hidden pages