Napoleon Installation And Operating Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: ANSI Z21.50 • CSA 2.22 FOR VENTED GAS FIREPLACES.
GD19N
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
NATURAL GAS
1
CERTIFIED FOR CANADAAND UNITED STATES USING ANSI/CSA METHODS.
If the information in these instructions
are not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
!
WARNING
GD19P
PROPANE
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
4.3.2 EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INSTALLATION 27
4.3.3 VERTICAL AIR TERMINAL INSTALLATION 28
4.4 VERTICAL THROUGH EXISTING CHIMNEY 29
4.5 MOBILE HOME INSTALLATION 30
4.6 GAS INSTALLATION 31
4.7 OPTIONAL WALL SWITCH 31
5.0 FRAMING 32
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES 33
5.1.1 REAR VENT 34
5.1.2 TOP VENT 34
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 35
5.3 MINIMUM MANTEL CLEARANCES 36
6.0 ELECTRICAL CONNECTION 37
7.0 WIRING DIAGRAM 38
8.0 FINISHING 39
8.1 GLASS DOOR 39
8.2 LOGO PLACEMENT 39
8.3 BURNER INSTALLATION 39
8.4 FACING KIT INSTALLATION/REMOVAL 40
8.4.1 FACING KIT 40
8.4.2 CONTEMPORARY FACING KIT 40
9.0 OPTIONAL BLOWER INSTALLATION 41
10.0 OPERATION 42
10.1 CONTROL FUNCTIONS 43
11.0 ADJUSTMENTS 43
11.1 PILOT INJECTOR AND ORIFICE REPLACEMENT 43
11.2 PRESSURE CHECK 44
11.3 RESTRICTING VERTICAL VENTS 44
12.0 MAINTENANCE 45
12.1 DOOR GLASS REPLACEMENT 46
12.2 CARE OF GLASS 46
12.3 NIGHT LIGHTTM REPLACEMENT 47
12.3.1 BULB REPLACEMENT 47
12.3.2 LENS ASSEMBLY INSTALLATION 47
12.3.3 LENS ASSEMBLY REPLACEMENT 47
13.0 REPLACEMENTS 48
14.0 TROUBLESHOOTING 50
15.0 WARRANTY 52
16.0 SERVICE HISTORY 53
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1004 / B / 08.10.12
1.0 INSTALLATION OVERVIEW
Top vent, see “REAR VENT
CONVERSION” section.
3
Door, see “GLASS DOOR
INST ALLA TION AND
REMOVAL” section.
Rating Plate, see
“RATING PLATE
INFORMATION” section.
Front face, see “FRONT
FACING AND INSET KIT
INSTALLATION” section.
Venting, see “VENTING”
section.
Burner, see “BURNER
INSTALLATION” section.
Blower, see “OPTIONAL
BLOWER INSTALLATION”
section.
W415-1004 / B / 08.10.12
4
2.0 INTRODUCTION
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES OR ALTERATIONS TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS
AND IS PROHIBITED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate
appliance according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges
may be sharp.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance. Toddlers,
young children and others may be susceptible to accidental contact burns. A physical barrier is recommended
if there are at risk individuals in the house. To restrict access to an appliance, install an adjustable safety gate
to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot
surfaces. These screens and guards must be fastened to the fl oor.
• Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
• The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance
• It is imperative that the control compartments, burners and circulating blower and its passageway in the
appliance and venting system are kept clean. The appliance and its venting system should be inspected
before use and at least annually by a qualifi ed service person. More frequent cleaning may be required due
to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from
combustible materials, gasoline and other fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to
inspect the appliance and to replace any part of the control system and any gas control which has been under
water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person.
• Do not strike or slam shut the appliance glass door.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating to
prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust
escaping through these openings can also cause the surrounding combustible materials to overheat and catch
fi re.
• Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all
plastic bags, these are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as
well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against
Carbon Monoxide.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance.
Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or
damage of decorations, a T.V. or other electronic components.
!
WARNING
W415-1004 / B / 08.10.12
3.2B
34 1/8”
7” DIA.
4” DIA.
33 1/8”
5
21 3/4”
19 3/4”
34 1/8”
GAS
LINE
ACCESS
9 1/2”
12”
13”
15 3/8”
26 3/8”
ELECTRICAL
ACCESS
33 7/8”
20
1
/2”
9”
10 1/4”
GAS
LINE
5”
ACCESS
1
2
/2”
1
7” DIA.
4” DIA.
3
/4”
ELECTRICAL
ACCESS
W415-1004 / B / 08.10.12
6
A
A
2.1 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” FROM THE
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth
of Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of an appliance
insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
• A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
!
WARNING
PROVIDE ADEQUA TE VENTILA TION.
FRONT FACE OF THE APPLIANCE.
FIRE RISK. EXPLOSION HAZARD.
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed in
accordance with the current standard CAN/CSA Z240MH
Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location
for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1A
W415-1004 / B / 08.10.12
2.2 GENERAL INFORMATION
S À ÉVA
SERIE DE MAISONS M
DE LA NORME DE SECURITE ET
FR, SECTION 3280. DANS LE
, SE REFERER A LA NOR
ENDIE POUR LES I
ALIMENTATION
EDUCED INPUT /
LIMENTATION REDUITE
TER SERVICING
CE TO COMBUSTIBLE MATERIAL
ATTENTION:
VERTIS
AUCU
AV
MANTEL 2"*
RECESSED DEPTH 13
VENT
NUAL FOR GRE
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION
AND QUALITY!
Altitude0 - 4,500*0 - 4,500*
Maximum Input11,50011,000
Maximum Output8,6008,250
Effi ciency75%75%
Minimum Inlet Gas Supply Pressure4.5” Water Column11” Water Column
Maximum Inlet Gas Supply Pressure7” Water Column13” Water Column
Manifold Pressure Under Flow Conditions3.5” Water Column10” Water Column
* When the appliance is installed at elevations above 4,500ft, and in the absence of specifi c recommendations
from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of
4% for each additional 1,000ft.
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible
for use with other gases, unless a certifi ed kit is used.
7
RATES AND EFFICIENCIES
NATURAL GASPROPANE GAS
Provide adequate accessibility clearance for servicing and operating the appliance.
Never obstruct the front opening of the appliance.
2.3 RATING PLATE INFORMATION
DIRECT VENT VENTED GAS FIREPLACE APPROVED FOR BEDROOM, BATHROOM & BEDSITTING
ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN
ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED
MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME
CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US
STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR
MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
9700539 (WSL) 4001657 (NGZ)
MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG)
4001658 (NAC) 4001659 (WUSA)
PRESSION AU COLLECTEUR: 3.5" D'UNE
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
PRESSION D'ALIMENTATION MIN: 4.5" D'UNE
MAX. SUPPLY PRESSURE: 7" W.C. (NG)
PRESSION D'ALIMENTATION MAX: 7" D'UNE
CAUTION: FOR USE WITH GLASS DOORS CERTIFIED
WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO THE
APPLIANCE, WHICH WILL COME IN CONTACT
WITH THE FLAMES, OTHER THAN THAT SUPPLIED
BY THE MANUFACTURER WITH THE APPLIANCE.
THIS VENTED GAS FIREPLACE IS NOT FOR USE
WITH AIR FILTERS.
ELECTRICAL RATING: BLOWER KIT GS66, 115V
0.5AMP 60HZ THE APPLIANCE MUST BE VENTED
USING THE APPROPRIATE WOLF STEEL VENT KITS.
SEE OWNERS INSTALLATION MANUAL FOR VENTING
SPECIFICS. MINIMUM AND MAXIMUM VERTICAL
VENT LENGTHS ARE 3 FEET AND 35FEET
RESPECTIVELY.
TOP, SIDES & BACK: PER STAND OFF SPACERS
FOR FRAMING MATERIALS. FOR FINISHING
MATERIALS SEE OWNERS MANUAL.
* MAXIMUM HORIZONTAL EXTENSION 2”. SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: ANSI Z21.50b-2009 CSA 2.22b-2009 VENTED GAS FIREPLACE / FOYER AU GAZ AVEC EVACUATION.
COLONNE D'EAU(GN)
COLONNE D'EAU (GN)
COLONNE D'EAU (GN)
NOT FOR USE WITH SOLID FUEL
NATURAL GAS MODEL
GD19N
MINIMUM AND MAXIMUM HORIZONTAL VENT
LENGTHS ARE 8 INCHES AND 20 FEET
RESPECTIVELY. PROPER REINSTALLATION AND
RESEALING IS NECESSARY AFTER SERVICING
THE VENT-AIR INTAKE SYSTEM.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIAL:
TOP 0" MANTEL 2"*
FLOOR 0" RECESSED DEPTH 13"
SIDES 0" VENT 1”
BACK 0”
CDV19N
0-4500ft
11,500 BTU/h
8,000 BTU/h
FOYER À GAZ VENTILÉS À ÉVACUATION DIRECTE. HOMOLOGUE POUR INSTALLATION DANS UNE
CHAMBRE A COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS
UNE MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA
Z240MH SERIE DE MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX
ETATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES,
TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE
APPLIQUEE, SE REFERER A LA NORME RELATIVE AU CRITERE DE MESURES DE SECURITE
CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURES, LES
PROPANE MODEL
ALTITUDE / ELEVATION
INPUT / ALIMENTATION
REDUCED INPUT /
ALIMENTATION REDUITE
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILSE AVEC CET APPAREIL
ATTENTION: UTILISER AVEC LES PORTES VITREES
HOMOLOGUEES SEULEMENT AVEC CETTE
UNITE.AVERTISSEMENT: N'AJOUTEZ PAS A CET APPAREIL
AUCUN MATERIAU DEVANT ENTRER EN CONTACT
AVEC LES FLAMMES AUTRE QUE CELUI QUI EST
FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
CE FOYER À GAZ VENTILÉS NE DOIT PAS ÊTRE
UTILISÉ CONJOINTEMENT AVEC DES FILTRES À AIR.
SOUFFLERIE GS66, 115V 0.5AMP 60HZ
CLASS:
L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT
L'ENSEMBLE D'EVACUATION PROPRE A
WOLF STEEL. REFERER AU MANUEL
D'INSTALLATION DE PROPRIETAIRE POUR
L'EVACUATION PRECISE. LES LONGUEURS
VERTICALES MINIMALES ET MAXIMALES
SONT3 PIEDS ET 35 PIEDS RESPECTIVEMENT.
DESSUS, COTES & ARRIERE: SELON LES ESPACEURS DE DEGAGEMENT POUR LES MATERIAUX D’OSSATURE
SELON LE MANUEL DE PROPRIETAIRE POUR LES MATERIAUX DE FINITION.
* L’EXTENSION HORIZONTAL MAXIMALE 2”. REFERER AU MANUEL D’INSTRUCTION POUR DES EXTENSIONS
PLUS GRANDES.
SERIAL NUMBER / NO. DESERIE
GD19P
0-4500ft
11,000 BTU/h
GD19
SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.
MANIFOLD PRESSURE: 10 INCHES W.C.(LP)
PRESSION AU COLLECTEUR: 10" D'UNE
LES LONGUEURS HORIZONTALES MINIMALES ET
MAXIMALES SONT 8 POUCES ET 20 PIEDS
RESPECTIVEMENT.
IL EST IMPORTANT DE BIEN REINSTALLER ET
RESCELLER L'EVENT APRES AVOIR ASSURE LE
MAINTIEN DU SYSTEME DE PRISE D'AIR.
RATING PLATE LOCATION: The rating label is located behind the control panel and is chained to the
appliance. DO NOT REMOVE.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
W415-1004 / B / 08.10.12
8
3.0 VENTING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 4” EXHAUST / 7” AIR INTAKE VENT PIPE SYSTEM.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
!
WARNING
Refer to the section applicable to your installation.
7.1A
3.1 VENTING LENGTHS AND COMPONENTS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal
locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk Direct
Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red
high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe
joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must
be sealed using the black high temperature sealant Mill Pac. High temperature sealant must be ordered separately.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following
termination kits: wall terminal kit GD222, GD222R, or 1/12 to 7/12 pitch roof terminal kit GD110, 8/12 to 12/12 roof terminal
kit GD111, fl at roof terminal kit GD112 or periscope kit GD201 (for wall penetration below grade). With fl exible venting, in
conjunction with the various terminations, use either the 5 foot vent kit GD220 or the 10 foot vent kit GD330.
W415-1004 / B / 08.10.12
For optimum flame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not
be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20
feet. The maximum allowable vertical vent length is 40 feet. The maximum number of vent connections is two horizontally
or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
3.2 TYPICAL VENT INSTALLATION
9
8.1
16" MINIMUM
24" MAXIMUM
10" MINIMUM
33 1/8"
* See "VENTING" section
43 1/8"
MINIMUM
PLUS RISE*
35 FT
MAXIMUM
3 FT
MINIMUM
33 1/8"
W415-1004 / B / 08.10.12
10
16" MINIMUM
20" MAXIMUM
* See "VENTING" section
26 3/8"
MINIMUM
PLUS RISE*
35 FT
MAXIMUM
3 FT
MINIMUM
26 3/8"
W415-1004 / B / 08.10.12
3.3 SPECIAL VENT INSTALLATIONS
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when
fi nal grading is completed, the bottom air slot is located a minimum 12” above grade. The maximum allowable
vent length is 10’ for a fi replace and 8’ for a stove.
11
24" MINIMUM
3.3.2 CORNER TERMINATION
The maximum vent length for a corner installation is 20" of horizontal run, in addition to the 45° offset. In this
case zero rise is acceptable. See illustrations below. It is recommended to maintain a 6" rise.
12"
MINIMUM
TO GRADE
12"
MINIMUM
TO GRADE
24" MINIMUM
33 1/8"
9.4A
6” RISE
MINIMUM
20” MAXIMUM
W415-1004 / B / 08.10.12
12
3.4 VENT TERMINAL CLEARANCES
COVERED BALCONY APPLICATIONS
Q
M
R
G
P
INSTALLATIONS
Q
R
R
MIN
MAX
MAX
= 3 feet
= 2 x
Q
feet
ACTUAL
CANADAU.S.A.
A12”12”Clearance above grade, veranda porch, deck or balcony.
B12”
Δ
9”
Δ
Clearance to windows or doors that open.
C12” *12” *Clearance to permanently closed windows.
D18” **18” **
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ from
the centerline of the terminal.
E18” **18” **Clearance to unventilated soffi t.
F0”0”Clearance to an outside corner wall.
G
H3’3’ ****
0” ***0” ***Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” ***2” ***Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum
vertical distance of 15’.
I3’3’ ****Clearance to a service regulator vent outlet.
J12”9”Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K6’3’ †Clearance to a mechanical air supply inlet.
L7’ ‡7’ ****Clearance above a paved sidewalk or paved driveway located on public property.
M12” ††12” ****Clearance under a veranda, porch, deck or balcony.
N16”16”Clearance above the roof.
O2’ †*2’ †*Clearance from an adjacent wall including neighbouring buildings.
P8’8’Roof must be non-combustible without openings.
Q3’3’See chart for wider wall dimensions.
R6’6’
In a structure with three walls and a roof, the terminal shall not be located less than 6 feet under a window that opens on a horizontal plane.
Δ
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18” clearance from an inside corner.
****This is a recommended distance. For additional requirements check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
12.6B
W415-1004 / B / 08.10.12
3.5 VENTING APPLICATION FLOW CHART
TOP EXIT
13
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 35 feet
Horizontal Termination
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet
4.2 times the
vertical rise equal to
or greater than the
horizontal run
REAR EXIT
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 35 feet
Vertical Termination
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 35 feet
3 times the vertical
rise equal to or
greater than the
horizontal run
13.3
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 35 feet
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
HR - combined horizontal vent lengths in feet
HO - offset factor: .03 (total degrees of offset - 90°*) in feet
VT - combined vertical vent lengths in feet
Since both formulas are met, this vent configuration is acceptable.
W415-1004 / B / 08.10.12
16.6_2A
17
(HT) > (VT)
Simple venting configuration
(only two 90° elbows)
See graph to determine the required vertical rise V
required horizontal run H
150
147
REQUIRED
VERTICAL
100
RISE IN
INCHES V
T
66
50
12
0
2.557.51012.51517.520
3.4
1
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: H
Formula 2: HT + V
Example:
V
= 4 FT
1
V
= 1.5 FT
2
V
= V
T
1
H
= 2 FT
1
H
= 1 FT
2
H
= 1 FT
3
H
= 1.5 FT
4
H
= H
R
1
H
= .03 (four 90° elbows + one 45° elbow - 90°)
O
= .03 (90 + 90 + 90 + 90 + 45 - 90) = 9.45 FT
H
= H
T
R
H
+ V
T
T
< 3.5V
T
+ V
= 4 + 1.5 = 5.5 FT
2
+ H2 + H3 + H
+ H
= 5.5 + 9.45 = 14.95 FT
O
= 14.95 + 5.5 = 20.45 FT
T
< 24.75 feet
T
= 2 + 1 + 1 + 1.5 = 5.5 FT
4
Û
H
2
V
1
H
1
Û
Û
for the
.
T
T
19.25
T
Û
H
4
V
2
Û
H
3
Formula 1: HT < 3.5V
3.5VT = 3.5 x 5.5 = 19.25 FT
T
14.95 < 19.25
Formula 2: HT + V
20.45 < 24.75
< 24.75 FT
T
Since both formulas are met, this vent configuration is acceptable.
16.6_3A
W415-1004 / B / 08.10.12
18
3.10 TOP OR REAR EXIT VERTICAL TERMINATION
(HT) < (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run HT.
40
35
30
REQUIRED
VERTICAL
RISE IN
FEET V
T
20
17.5
10
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and HT
For vent configurations requiring one or more 90° elbows (top exit) or one 90° elbow (rear exit),
the following formulas apply:
Formula 1: HT < V
Formula 2: HT + V
T
< 35 feet
T
17.5
for the
T
T
Example:
V
= 3 FT
1
V
= 6 FT
2
V
= 8 FT
3
V
= V
+ V2 + V3 = 3 + 6 + 8 = 17 FT
T
1
H
= 2 FT
1
H
= 2.5 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
= H
H
T
H
+ V
T
Formula 1: HT < 3.5 V
12.6 < 17
Formula 2: HT + V
29.6 < 35
= 2 + 2.5 = 4.5 FT
1
2
+ H
= 4.5 + 8.1 = 12.6 FT
R
O
= 12.6 + 17 = 29.6 FT
T
T
< 35 FT
T
Since both formulas are met, this vent configuration is acceptable.
90°
V
3
90°
H
2
V
H
1
V
1
2
90°
90°
18.4
W415-1004 / B / 08.10.12
19
(HT) > (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run H
20
REQUIRED
VERTICAL
RISE IN
FEET V
10
T
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and HT
For vent configurations requiring more than one 90° elbows (top exit) or one 90° elbow (rear exit),
the following formulas apply:
Formula 1: H
Formula 2: HT + V
< 3 V
T
T
< 35 feet
T
Example:
V
= 2 FT
1
V
= 1 FT
2
V
= 1.5 FT
3
V
= V
+ V2 + V3 = 2 + 1 + 1.5 = 4.5 FT
T
1
H
= 6 FT
1
H
= 2 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
T
H
+ V
T
= 6 + 2 = 8 FT
1
2
+ H
= 8 + 8.1 = 16.1 FT
R
O
= 16.1 + 4.5 = 20.6 FT
T
90°
90°
V
1
H
1
V
H
2
90°
for the
.
T
2
T
2530
V
3
T
90°
Formula 1: HT < 3.5 V
3.5 V
16.1 < 13.5
T
=3 x 4.5 = 13.5 FT
T
Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + V
20.6 < 35
< 35 FT
T
Since only formula 2 is met, this vent configuration is unacceptable and a new fireplace location or vent configuration will
need to be established to satisfy both formulas.
18.4_2A
W415-1004 / B / 08.10.12
20
Example:
= 1.5 FT
V
1
V
= 5 FT
2
= V
V
H
H
H
H
H
= .03 (360° + 45° - 90°) = 6.75 FT
H
H
Formula 1:
HT < 3 V
3 V
19.5 = 19.5
+ V2 = 1.5 + 1 + 5 = 6.5 FT
T
1
= 1 FT
1
= 1 FT
2
= 10.75 FT
3
= H
+ H2 + H3 = 1 + 1 + 10.75 = 12.75 FT
R
1
= .03 (four 90° elbows + one 45° elbow - 90°)
O
= H
+ H
T
+ V
T
= 12.75 + 6.75 = 19.5 FT
R
O
= 19.5 + 6.5 = 26 FT
T
T
=3 x 6.5 = 19.5 FT
T
90°
V
H
1
Formula 2:
H
+ V
< 35 FT
T
T
26 < 35
Since both formulas are met, this vent configuration is acceptable.
V
2
H
2
45°
1
H
3
90°
90°
18.4_3
W415-1004 / B / 08.10.12
3.11 REAR VENT CONVERSION
In order to convert the venting confi guration from a top exit to a rear exit, remove components as illustrated:
When reinstalling in the alternate position: Check gaskets for tears, replace if necessary to ensure a
proper seal.
Outer Top
7” Top Access Plate
7” Cover Plate
7” Gasket
21
4” Cover Plate
4” Gasket
7” Collar
7” Gasket
4” Collar
4” Gasket
W415-1004 / B / 08.10.12
22
4.0 INSTALLATION
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
!
WARNING
EXACTLY.
WHICH MUST BE SEALED USING MILL PAC.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
68.2A
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
For optimum performance it is recommended that horizontal runs have a minimum 1" per rise per foot when
using Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent, or Wolf Steel rigid or fl exible vent
components.
WARNING
70.1
W415-1004 / B / 08.10.12
4.1.1 HORIZONTAL INSTALLATION
A
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall.
Having determined the correct height for the air terminal
location, cut and frame a hole in the exterior wall as
illustrated to accommodate the fi restop assembly.
Dry fi t the fi restop assembly before proceeding to
ensure the brackets on the rear surface fi t to the
inside surface of the horizontal framing.
The length of the vent shield may be cut shorter
for combustible walls that are less than 8 1/2” thick
but the vent shield must extend the full depth of the
combustible wall.
. Apply a bead of caulking (not supplied) around the corner edge of
the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your
manual baggie).
!
WARNING
CAULKING
FIRESTOP
SPACER
23
VENT
SHIELD
DETERMINE
THE
CORRECT
HEIGHT
FINISHING
MATERIAL
B. Once the vent pipe is installed in its fi nal position, apply high temperature sealant W573-0007 (not supplied) between the pipe and the fi restop.
20.2
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor. See
accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1“ clearance
between the vent pipe and any combustible material. Try to center the vent
pipe location midway between two joists to prevent having to cut them. Use
a plumb bob to line up the center of the openings. A vent pipe shield will
prevent any materials such as insulation, from fi lling up the 1” air space
around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a fi nished
ceiling), and secure over the opening in the ceiling. A fi restop must be
placed on the bottom of each framed opening in a roof or ceiling that the
venting system passes through. Apply a bead of caulking all around and place a
fi restop spacer over the vent shield to restrict cold air from being drawn into the
room or around the fi replace. Ensure that both spacer and shield maintain the
required clearance to combustibles. Once the vent pipe is installed in its fi nal
position, apply sealant between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1” air space
around the pipe.
9 3/4"
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
VENT
SHIELD
21.1
9 3/4"
CAULKING
VENT
PIPE
COLLAR
PIPE
W415-1004 / B / 08.10.12
24
4.2 USING FLEXIBLE VENT COMPONENTS
!
WARNING
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
For safe and proper operation of the appliance, follow the venting
instructions exactly.
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high
ELBOW
SPACERS
temperature sealant W573-0002 (not supplied) or the high temperature
sealant W573-0007 Mill Pac (not supplied). However, the high temperature
sealant W573-0007 Mill Pac (not supplied) must be used on the joint
connecting the inner fl ex pipe and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
“Wolf Steel Approved Venting” as identifi ed
by the stamp only on the outer fl ex pipe.
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION
A.Stretch the inner fl ex pipe to the required length taking into
account the additional length needed for the fi nished wall
surface. Apply a heavy bead of the high temperature
sealant W573-0007 Mill Pac (not supplied) to the inner
sleeve of the air terminal. Slip the vent pipe a minimum
of 2” over the inner sleeve of the air terminal and
secure with 3 #8 screws.
B.Using the outer fl ex pipe, slide over the outer combustion
air sleeve of the air terminal and secure with 3 #8 screws.
Seal using high temperature sealant W573-0002 (not
supplied).
C.Insert the vent pipes through the fi restop maintaining the required
clearance to combustibles. Holding the air terminal (lettering in
an upright, readable position), secure to the exterior wall and
make weather tight by sealing with caulking (not supplied).
D.If more vent pipe needs to be used to reach the fi replace, couple
them together as illustrated. The vent system must be
supported approximately every 3 feet for both vertical and
horizontal runs. Use noncombustible strapping to maintain
the minimum clearance to combustibles.
#10x2"
SCREWS
HI-TEMP
SEALANT
OUTER
FLEX PIPE
22.1
CAULKING
INNER FLEX
PIPE
OUTER FLEX
2" OVERLAP
HIGH TEMPERATURE
#8 X 1/2” SELF DRILLING
SCREWS & WASHERS
INNER COUPLER
INNER
FLEX PIPE
PIPE
SEALANT
OUTER COUPLER
FLEX PIPE
OUTER
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth
of its return fl ange.
W415-1004 / B / 08.10.12
23.1A
4.2.2 VERTICAL AIR TERMINAL INSTALLATION
!
WARNING
MAINTAIN A MINIMUM 2” SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
A.Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately
supported using either an alternate method suitable to the authority
having jurisdiction or the optional roof support.
B.Stretch the inner fl ex pipe to the required length. Slip the inner
fl ex pipe a minimum of 2” over the inner pipe of the air terminal
connector and secure with 3 #8 screws. Seal using a heavy
bead of high temperature sealant W573-0007 (not supplied).
C.Repeat using the outer fl ex pipe, using a heavy bead of high
temperature sealant W573-0002 (not supplied).
D.Thread the air terminal connector / vent pipe assembly down
through the roof. The air terminal must be positioned vertically and
plumb. Attach the air terminal connector to the roof support, ensuring
that the top of the air terminal is 16” above the highest point that it
penetrates the roof.
E.Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” of the air terminal connector showing above the
top of the fl ashing. Slide the fl ashing underneath the sides and upper
edge of the shingles. Ensure that the air terminal connector is properly
centred within the fl ashing, giving a 3/4” margin all around. Fasten to
the roof. Do not nail through the lower portion of the fl ashing. Make
weather-tight by sealing with caulking. Where possible, cover the sides
and top edges of the fl ashing with roofi ng material.
F.Aligning the seams of the terminal and air terminal connector, place
the terminal over the air terminal connector making sure the vent
pipe goes into the hole in the terminal. Secure with the three
screws provided.
G.Apply a heavy bead of weatherproof caulking 2” above the fl ashing.
Install the storm collar around the air terminal and slide down to the
caulking. Tighten to ensure that a weather-tight seal between the
air terminal and the collar is achieved.
H.If more vent pipe needs to be used to reach the appliance see
“HORIZONTAL AIR TERMINAL INSTALLATION” section.
ROOF SUPPORT
INNER PIPE
AIR
TERMINAL
CONNECTOR
HIGH
TEMPERATURE
SEALANT
INNER FLEX PIPE
OUTER FLEX PIPE
2”
25
AIR I NL ET
BASE
CAULKING
STORM COLLAR
WEA THER
SEALANT
FLASHING
24.1
W415-1004 / B / 08.10.12
26
A
4.2.3 APPLIANCE VENT CONNECTION
A. Install the inner fl ex pipe to the appliance. Secure with 3 screws
and fl at washers. Seal the joint and screw holes using the high
temperature sealant W573-0007 (not supplied).
B. Install the outer fl ex pipe to the appliance. Attach and seal
the joints using the high temperature sealant W573-0002 (not
supplied).
4.3 USING RIGID VENT COMPONENTS
The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use Wolf
Steel Ltd. support ring assembly or equivalent noncombustible strapping to maintain the minimum clearance to
combustibles for both vertical and horizontal runs.
ll inner exhaust and outer intake vent pipe joints may be sealed using either red high temperature silicone
sealant W573-0002 (not supplied) or black high temperature sealant W573-0007 Mill Pac (not supplied) with
the exception of the appliance exhaust fl ue collar which must be sealed using Mill Pac.
#8 X 1/2”
SELF
DRILLING
SCREWS
2” OVERLAP
HIGH TEMP
SEALANT
28.1
25.1
W415-1004 / B / 08.10.12
4.3.1 HORIZONTAL AIR TERMINAL INSTALLATION
27
A.Move the appliance into position.
Measure the vent length required
between terminal and appliance
taking into account the additional
length needed for the fi nished
wall surface and any 1¼” overlaps
between venting components.
#10x2"
SCREWS
CAULKING
OUTER
RIGID
INNER
RIGID
PIPE
PIPE
B.Apply high temperature sealant W573-
0007 (not supplied) to the outer edge of the
inner collar of the appliance. Attach the fi rst
inner rigid pipe component and secure using 3 self
tapping screws. Repeat using the outer rigid pipe.
C.Insert the vent pipes through the fi restop maintaining the required
clearance to combustibles. Holding the air terminal (lettering in an upright,
readable position), secure to the exterior wall and make weather tight by sealing with caulking (not
supplied).
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the
depth of the return fl ange.
2” OVERLAP
HI-TEMP
SEALANT
26.3
4.3.2 EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INSTALLATION
A. Follow the instructions for "HORIZONTAL AIR TERMINAL INSTALLATIONS" section.
B.
Continue adding components alternating inner rigid pipe and outer rigid pipe. Ensure
that all inner rigid pipe and elbows have sufficient vent spacers attached and each
component is sealed and securely fastened to the one prior. Attach the inner telescopic
sleeve to the vent run. Repeat using the outer telescopic sleeve. Seal and secure as
before. To facilitate completion, attach inner and outer couplers to the air terminal.
C. Install the air terminal. See “HORIZONTAL AIR TERMINAL INSTALLATION” section.
AIR TERMINAL
20"
COUPLER
48.1
TELESCOPIC
SLEEVE
VENTING
W415-1004 / B / 08.10.12
28
j
4.3.3 VERTICAL AIR TERMINAL INSTALLATION
NOTE: Before attaching elbows to the collars on the back of the appliance, 1 1/2” will need to be
trimmed off the 4” collar.
REAR VENT APPLICATION: Attach 4” and 7” elbows to the appliance. Secure with 3 screws and seal the
oints and screw heads using high temperature sealant. Proceed to step A
below.
TOP VENT APPLICATION:
A. Move the appliance into position.
B. Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately
supported using either an alternate method suitable to the authority
having jurisdiction or the optional roof support.
C. Apply high temperature sealant W573-0007 (not supplied) to the
D. Apply high temperature sealant W573-0002 (not supplied) to the
E. Thread the air terminal connector / vent pipe assembly down through
F. Remove nails from the shingles, above and to the sides of the air terminal
G. Apply a heavy bead of waterproof caulking 2” above the fl ashing. Install the storm collar around the
H. Continue adding rigid venting sections, sealing and securing as above. Attach the inner collapsed
REAR VENT APPLICATION:
I. Run a bead of high temperature sealant W573-0007 (not supplied) around the outside of the inner
TOP VENT APPLICATION:
J. Run a bead of high temperature sealant W573-0007 (not supplied) around the outside of the inner
K. In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will
outer edge of the inner sleeve of the air terminal. Slip the inner
coupler a minimum of 2” over the sleeve and secure using 3 screws.
outer edge of the of the outside sleeve of the air terminal connector.
Slip the outer coupler over the sleeve and secure as before. Trim the
outer coupler even with the inner coupler end.
the roof support and attach, ensuring that a minimum 16” of air
terminal connector will penetrate the roof when fastened. If the attic
space is tight, we recommend threading the Wolf Steel vent pipe
collar or equivalent loosely onto the air terminal connector / vent pipe
assembly as it is passed through the attic. The air terminal connector must be
positioned vertically and plumb.
connector. Place the fl ashing over the air terminal connector and slide it
underneath the sides and upper edge of the shingles. Ensure that the air
terminal connector is properly centered within the fl ashing, giving a 3/4”
margin all around. Fasten to the roof. Do NOT nail through the lower portion of the fl ashing. Make weather-tight by sealing with caulking. Where
possible, cover the sides and top edges of the fl ashing with roofi ng material.
air terminal and slide down to the caulking. Tighten to ensure that a weather-tight seal between the air
terminal connector and the collar is achieved.
telescopic sleeve to the last section of rigid piping. Secure with screws and seal. Repeat using the
outer telescopic sleeve.
elbow. Pull the telescopic sleeve a minimum of 2” onto the elbow. Secure with 3 screws. Repeat with
the outer telescopic sleeve.
collar on the appliance. Pull the telescopic sleeve a minimum of 2” onto the collar. Secure with 3
screws. Repeat with the outer telescopic sleeve.
prevent any materials, such as insulation, from fi lling up the 1” air space around the pipe
AIR
TERMINAL
CONNECTOR
27.1
INNER PIPE
HIGH
TEMPERATURE
SEALANT
INNER RIGID
PIPE
OUTER
RIGID PIPE
VENT
PIPE
COLLAR
VENT
PIPE
SHIELD
W415-1004 / B / 08.10.12
AIR
INTAKE
EXHAUST
FLUE
FLEX
LINER
* 40 FT
MAX.
10 FT
MIN
COAXIAL TO
CO-LINEAR
ADAPATER
APPLIANCE
VENT ADAPTOR
TERMINATION
4.4 VERTICAL THROUGH EXISTING CHIMNEY
!
WARNING
RISK OF FIRE!
CO-AXIAL TO CO-LINEAR VENTING CONFIGURATIONS MUST ONLY BE USED IN A NON-
COMBUSTIBLE CHIMNEY OR ENCLOSURE. INSTALLATION IN A COMBUSTIBLE ENCLOSURE COULD
RESULT IN A FIRE.
This appliance is designed to be attached to a 3” co-linear aluminum fl ex vent system running the full length
of a masonry chimney.
The fl ex liners accommodate any contours of a
masonry chimney, however, it is necessary to keep
the fl exible liners as straight as possible. The inlet air
collar of the termination cap must be connected to
the air intake fl ex liner and the exhaust collar must be
connected to the exhaust fl exible liner.
Both Simpson Duravent and Selkirk co-linear to
co-axial adaptors have been approved on this
appliance (NOTE:A vent adaptor will be required directly off the appliance).
Follow vent manufacturer’s installation instructions.
Different manufacturer’s venting components must
not be combined. Once the preferred manufacturer’s
appliance adaptor has been attached, the
remainder of the system must be that of the
same manufacturer.
29
The only exception to this rule is to use Wolf
Steel’s approved 3” fl ex liner and co-linear
termination.
* Measured from appliance fl ue collar to
termination fl ue collar
7.6
W415-1004 / B / 08.10.12
30
A
4.5 MOBILE HOME INSTALLATION
This appliance is also certifi ed to be installed as an OEM (Original Equipment Manufacturer) installation
in a manufactured home (U.S. only) or mobile home and must be installed in accordance with the
manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR,
Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This
appliance is only for use with the type(s) of gas indicated on the rating plate.
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit. Built
in appliances are equipped with 1/4” diameter holes located in the front left and right corners of the base. Use #10
hex head screws, inserted through the holes in the base to secure. For free standing products contact your local
authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must be
fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and
the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting
the appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certifi ed kit is used.
conversion kit is supplied with the mobile home appliance.
Conversion Kits
This appliance is fi eld convertible between Natural Gas (NG) and Propane (LP).
To convert from one gas to another consult your Authorized dealer/distributor.
29.1
W415-1004 / B / 08.10.12
Loading...
+ 82 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.