Napoleon BHD4PGN, BHD4STGN, BHD4STN, BHD4PN User Manual

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
INSTALLATION AND
EN
OPERATING INSTRUCTIONS
CONFORMS TO AMERICAN NATIONAL STANDARDS: ANSI Z21.50, CERTIFIED TO CANADIAN CSA 2.22 FOR VENTED GAS FIREPLACES.
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
!
WARNING
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
BHD4N
NATURAL GAS
BHD4P
PROPANE
SAFETY BARRIER
BHD4ST ILLUSTRATED
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
FR PG 69
Decorative Product: Not for use as a heating appliance.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone (705)721-1212 • Fax (705)722-6031 • www.napoleonfi replaces.com • ask@napoleonproducts.com
$10.00
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with the appliance and
shall be installed.
BARRIER
1.36D
CERTIFIED
W415-1285 / A / 11.03.14
2
EN
TABLE OF CONTENTS
The camera icon indicates video tutorials are available as additional reference, visit http:// www.napoleonfi replaces.com/category/product-support/support-centre/
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
3.0 VENTING 9
4.0 INSTALLATION 19
5.0 FRAMING 26
6.0 FINISHING 34
7.0 ELECTRICAL CONNECTION 42
8.0 OPERATING INSTRUCTIONS 45
9.0 ADJUSTMENT 47
10.0 MAINTENANCE 49
11.0 REPLACEMENTS 54
12.0 BHD4P OVERVIEW 55
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 6
2.3 GENERAL INFORMATION 7
2.4 RATING PLATE / LIGHTING INSTRUCTION LOCATION 8
3.1 VENTING LENGTHS AND COMPONENTS 10
3.2 TYPICAL VENT INSTALLATIONS 11
3.3 SPECIAL VENT INSTALLATIONS 12
3.3.1 PERISCOPE TERMINATION 12
3.4 VENT TERMINAL CLEARANCES 13
3.5 VENT APPLICATION FLOW CHART 14
3.6 DEFINITIONS 14
3.7 ELBOW VENT LENGTH VALUES 14
3.8 HORIZONTAL TERMINATION 15
3.9 VERTICAL TERMINATION 17
4.1 WALL AND CEILING PROTECTION 19
4.1.1 HORIZONTAL INSTALLATION 20
4.1.2 VERTICAL INSTALLATION 20
4.2 USING FLEXIBLE VENT COMPONENTS 21
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 22
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 23
4.2.3 APPLIANCE VENT CONNECTION 23
4.3 GAS INSTALLATION 24
4.4 MOBILE HOME INSTALLATION 24
4.5 ACCESS PANEL FOR GAS LINE CONNECTION 25
5.1 FRAMING 27
5.1.1 SEE-THRU FRAMING (BHD4ST) 27
5.1.2 PENINSULA FRAMING (BHD4P) 27
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 28
5.3 INSTALLING COMBUSTIBLE BOARD 29
5.3.1 FINISHING SUPPORT ADJUSTMENT 30
5.4 NON-COMBUSTIBLE FACING MATERIAL 31
5.5 ALCOVE ENCLOSURE 32
5.6 MINIMUM MANTEL CLEARANCES 33
5.7 NAILING TAB INSTALLATION 33
6.1 SIDE SAFETY SCREEN REMOVAL / INSTALLATION 34
6.2 END SAFETY SCREEN REMOVAL / INSTALLATION (BHD4P ONLY) 35
6.3 DOOR REMOVAL / INSTALLATION 36
6.4 CONTROL PANEL REMOVAL 37
6.5 END DOOR REMOVAL / INSTALLATION (BHD4P ONLY) 37
6.6 HEARTH PAD INSTALLATION 38
6.7 LOG PLACEMENT 39
6.8 GLASS MEDIA INSTALLATION 41
6.9 LOGO PLACEMENT 42
7.1 HARD WIRING CONNECTION 42
7.2 RECEPTACLE WIRING DIAGRAM 43
7.3 BATTERY BACK-UP INSTALLATION 43
7.4 WIRING DIAGRAM 44
8.1 OPERATING INSTRUCTIONS - FOR YOUR SAFETY READ BEFORE OPERATING 45
8.2 LIGHTING INSTRUCTIONS 45
8.3 ANTI CONDENSATION SWITCH 46
9.1 PILOT BURNER ADJUSTMENT 47
9.2 VENTURI ADJUSTMENT 47
9.3 FLAME CHARACTERISTICS 48
10.1 ANNUAL MAINTENANCE 50
10.2 GLASS / DOOR REPLACEMENT 51
10.3 CARE OF GLASS 51
10.4 BURNER REMOVAL 52
10.4.1 LOG BURNER REMOVAL 52
10.4.2 GLASS BURNER REMOVAL 52
10.4.3 CRADLE BURNER REMOVAL 53
10.5 VALVE TRAIN REPLACEMENT 53
10.6 RESTRICTING VERTICAL VENTS 53
W415-1285 / A / 11.03.14
13.0 BHD4ST OVERVIEW 56
14.0 ACCESSORIES 57
15.0 GLASS BURNER (W100-0160) 58
16.0 LOG /CRADLE BURNER (W100-0161) 59
17.0 GLASS BURNER VALVE TRAIN ASSEMBLY 60
18.0 LOG BURNER VALVE TRAIN ASSEMBLY 61
19.0 TROUBLESHOOTING 62
20.0 WARRANTY 65
21.0 SERVICE HISTORY 66
22.0 NOTES 67
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
1.0 INSTALLATION OVERVIEW
COMBUSTIBLE MATERIAL
Mantel, see “MINIMUM MANTEL CLEARANCES” section
3
EN
Framing, see “FRAMING” section
Venting, see “VENTING” section
Door, see “ END DOOR INSTALLATION” section
Door, see “DOOR REMOVAL/ INSTALLATION” section
Batteries must be disposed of according to the local laws and regulations. Some batteries may be recycled, and may be accepted for disposal at your local recycling center. Check with your municipality for recycling instructions.
SAFETY BARRIER
BHD4P ILLUSTRATED
Rating plate, see “RATING PLATE INFORMATION” section
W415-1285 / A / 11.03.14
4
2.0 INTRODUCTION
EN
W415-1285 / A / 11.03.14
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES OR ALTERATIONS TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance
It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch fi re.
Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage of decorations, a T.V. or other electronic components.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
!
WARNING
3.2C
2.1 DIMENSIONS
8"
203mm
127mm
5"
25 1/8"
638mm
12 13/16"
325mm
5
EN
SAFETY BARRIER
43 1/4"
BHD4P ILLUSTRATED
1099mm
34 3/16" 868mm
38 1/4" 841mm
7 9/16"
192mm
GAS
INLET
8"
203mm
127mm
2 1/16"
53mm
5"
RIGHT SIDE
7 9/16"
192mm
ELECTRICAL
INLET
RIGHT SIDE
LEFT SIDE
25 1/8"
638mm
12 13/16"
325mm
LEFT SIDE
SAFETY BARRIER
45"
BHD4ST ILLUSTRATED
1143mm
34 3/16" 868mm
38 1/4" 841mm
7 9/16"
192mm
GAS
INLET
2 1/16"
53mm
7 9/16"
192mm
ELECTRICAL
INLET
W415-1285 / A / 11.03.14
6
A
A
2.2 GENERAL INSTRUCTIONS
EN
!
WARNING
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUA TE VENTILA TION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” (1219mm) FROM
THE FRONT FACE OF THE APPLIANCE.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35 mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas log.
The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches (914mm).
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
www.ncertied.org
We suggest that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1B
W415-1285 / A / 11.03.14
2.3 GENERAL INFORMATION
7
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
BHD4
NG LP
Altitude (FT) 0-4,500 0-4500
Max. Input (BTU/HR) 30,000 30,000
Max. Output Steady State (BTU/HR) 23,000 23,000
Min. Inlet Gas Supply Pressure
Max. Inlet Gas Supply Pressure
Manifold Pressure (Under Flow Conditions)
When the appliance is installed at elevations above 4,500 ft (1372m), and in the absence of specifi c recommendations from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for each additional 1,000 ft (305m).
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home installation.
4.5" (11mb)
Water Column
7" (17mb)
Water Column
3.5" (9mb)
Water Column
11" (27mb)
Water Column
13" (32mb)
Water Column
10" (25mb)
Water Column
EN
No external electricity (110 volts or 24 volts) is required for the gas system operation. Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
If utilizing one of Wolf Steel's trim or surround kits, follow the framing instructions and the fi nishing instructions, for removal of the top extension.
NOTE: The protective wrap on plated parts is best removed when the assembly is at room temperature but this can be improved if the assembly is warmed, using a hair dryer or similar heat source.
67.9%
BHD4
W415-1285 / A / 11.03.14
8
CC
LA NORME DE SECURITE LA NORME DE SEC
A LA NORME RELATIVE AU CRITÈA LA NORME RELATIVE AU CR
/ /
$33$5(,/87,/,6(5$9(&/(633$5(,/87,/,6(5$9(&/(6
6(8/(0(17$9(&&(77((0(17$9(&&(77(
$
66(0(17
&(7$33$5(,/$8&810$7e5$5(,/$8&810$7e
(175(5(1&217$&7$9((5(1&217$&7$9
$875(48(&(/8,48,875(48(&(
APPAREIL PAR LE FAAPPAREIL PAR LE
352'8,7'e&25$352'8,7'e&25
APPAREIL DE CAPPAREIL DE
COMBCOM
,167$//$7,21'(352
67.9%
HD4
(9$&8$7,2135(&,6(,/(67,03257$17'(%,(1(9$&8$7,2135(&,6(,/(67,03257$17'(%,(1
ANUAL.
EDS FRESH
OPERATION
NS
T
ALLED
PROVISION
TION
N
AIR.
DEZ LE BRULEUR ET LE
ARTIMENT DE
TEZ LE MANU
A
TION ET
INS
TLLA
TION.
AP
AREI
ALIME
W
ARNTALL
A
TION,
ADJUSTMEN
T,A
TER
A
TION,
VICE OR MAINTENANCE
USE PROPERT
Y
DAMAGE,
INJUY OR LOS
ER
T
O OWNER’S
ALL
A
TION
AND
SE
VICE MUST BE PERFORME
Y
A
QUALIFIE
T
ALL
SE
VICE
AGENCY O
GAS SUPPLIE
TE
WHILE O
GASO
2.4 RATING PLATE / LIGHTING INSTRUCTION LOCATION
EN
!
WARNING
ALLOW THE APPLIANCE TO COOL BEFORE PERFORMING ANY MAINTENANCE OR CLEANING.
NOTE: Screen must be removed to access rating plate / lighting instructions.
Both the rating plate and lighting instructions are attached to a cable and located behind the control panel of the appliance. Lift the access plate and control panel up and away from the appliance. With the cable at the bulb end of the slot, wiggle the rating plate out being careful not to tear the instructions.
&(57,),('81'(5+202/2*8(6(/21/(61250(6$16,=E&6$E9(17('*$6),5(3/$&()2<(5*$=9(17,/e
VENTED GAS FIREPLACE. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART
CERTIFIED
CERTIFIED FOR / CERTIFIEE POUR CANADA / USA
REFERENCE # 161746
7+,69(17('*$6),5(3/$&(
IS NOT FOR USE WITH AIR FILTERS. NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS
&(57,),(':,7+7+,681,721/<
WARNING: '2127$''$1<0$7(5,$/
TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER THAN
7+$76833/,('%<7+(0$18)$&785(5
WITH THE APPLIANCE.
'(&25$7,9(352'8&7127)2586($6$
HEATING APPLIANCE
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS: TOP 0” FLOOR 0” SIDES 0” BACK 0”
9(17723 µ 9(176,'(6%27720 µ 9(57,&$/9(17 µ
MANTEL 8”*
7236,'(6%$&.3(567$1'2))63$&(56)25)5$0,1*
MATERIALS. FOR FINISHING MATERIALS SEE OWNER’S MANUAL *MAXIMUM HORIZONTAL EXTENSION / L’EXTENSION HORIZONTALE MAXIMALE: 2”. SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS. SEE OWNER’S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM LENGTHS.
KEEP BURNER AND CONTROL
COMPARTMENT CLEAN. SEE
INSTALLATION AND OPERA TING
WITH ADEQUATE PROVISIONS
GARDEZ LE BRULEUR ET LE
3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI/NFPA 501A. FOYER À GAZ VENTILÉ. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE MAISONS MOBILES ÉQUIPÉES AU GAZ EN VIGEUR AU CANADA OU AUX ÉTATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUC­TION DE MAISONS MANUFACTUREE, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D’ÉTATS-UNIS NE PEUT ETRE APPLIQUÉE, SE REFERER A LA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ CONTRE L’INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A. THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THE CURRENT ANSI Z223.1 OR CSA B149, INSTALLATION CODES. INSTALLER L’APPAREIL SELON LES CODES D’INSTALLATION ANSI Z223.1 OU CSA-B149 EN VIGUER.
MODEL NATURAL GAS /
GAZ NATURAL
0-4500FT (0-1370M) $/7,78'(e/e9$7,21 0-4500FT (0-1370M) 30,000 BTU/H %78+ 5('8&(',1387$/,0(17$7,215e'8,7( ,000 BTU/H
3.5” WATER COLUMN/D’UNE COLONNE D’EAU
PRESSION AU COLLECTEUR
4.5“ WATER COLUMN/D’UNE COLONNE D’EAU 0,1,0806833/<35(6685( 11” WATER COLUMN/D’UNE COLONNE D’EAU
7.0“ WATER COLUMN/D’UNE COLONNE D’EAU 0$;,0806833/<35(6685( 13” WATER COLUMN/D’UNE COLONNE D’EAU
67.9% P.4 67.9%
(/(&75,&$/5$7,1*9+=/(667+$1$03(5(6
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
INSTRUCTIONS MANUAL. APPLIANCE NEEDS FRESH AIR FOR SAFE OPERATION
AND MUST BE INSTALLED
FOR COMBUSTION
AND VENTILATION AIR.
COMPARTIMENT DES
CONTROLES PROPRES.
CONSULTEZ LE MANUEL
D’INFORMATION ET
D’INSTALLATION. PAR
MESURE DE SECURITE.
CET APPAREIL DOIT
ETRE ALIMENTE EN AIR
FRAIS ET AVEC SUFFISANT
D’AIR COMBURANTET
DE VENTILATION.
BHD4N BHD4P
7+($33/,$1&(0867%(9(17('86,1*7+($335235,$7(
1$32/(219(17.,766((2:1(56,167$//$7,210$18$/
)259(17,1*63(&,),&63523(55(,167$//$7,21$1'
5(6($/,1*,61(&(66$5<$)7(56(59,&,1*7+(9(17$,5
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF
LIFE. REFER TO OWNER’S
MANUAL. INSTALLATION AND
SERVICE MUST BE PERFORMED
BY A QUALIFIED INSTALLER,
SERVICE AGENCY OR THE
UN INSTALLATION OU UNE
MODIFICATION INAPPROPRIEE DU REGLAGE, DU SERVICE ET DE L’ENTRETIEN POURRAIENT ETRE
LA CAUSE DE DOMMAGES A LA
PROPRIETE DE BLESSURES
CORPORELLES OU MEME LA
MORT. CONSULTER LE MANUEL
D’INFORMATION, L’INSTALLATION
ET LE SERVICE DOIVENT
ETRE EXECUTES PAR UN
INSTALLATEUR QUALIFIE POUR
LE AZ, UNE ENTREPRISE DE
SERVICE OU LE FOURNISSEUR
DE GAZ SEULEMENT.
BCHD4N BCHD4P
PRESSION D’ALIMENTATION MINIMALE
PRESSION D’ALIMENTATION MAXIMALE
,17$.(6<67(0
SERIAL NUMBER/ NO. DE SÉRIE: BHD4
WARNING:
GAS SUPPLIER.
ATTENTION:
INPUT / ALIMENTATION 30,000 BTU/H
MANIFOLD PRESSURE / 10” WATER COLUMN/D’UNE COLONNE D’EAU
HOT WHILE OPERATING. DO NOT TOUCH. KEEP CHILDREN, CLOTHING, FURNITURE,
GASOLINE OR OTHER FLAMMABLE VAPORS
L’APPAREIL EST CHAUD PENDANT SON FONCTIONNEMENT. LES ENFANTS, LES
VETEMENTS, LES MEUBLES, L’ESSENCE ET
AUTRES LIQUIDES QUI EMETTENT DES GAZ
ETRE TENUS ELOIGNES DE L’APPAREIL.
“This appliance is only for use with the type(s)
of gas indicated on the rating plate and may
be installed in an aftermarket, permanently located, manufactured home (USA only) or
mobile home, where not prohibited by local
codes. See owner’s manual for details. This
appliance is supplied with a conversion kit.”
«Cet appareil doit être utilisé uniquement
avec les types de gaz indiqués sur la plaque
signalétique et peut être installé dans une
maison préfabriquée (É.-U. seulement) ou
mobile installée à demeure si les règlements
l’utilisateur pour plus de renseignements. Une
trousse de conversion est fournie avec cet
MODEL PROPANE / PROPANE MODÈLE
/·$33$5(,/'2,7e9$&8(56(6*$=(187,/,6$17 /·(16(0%/('·e9$&8$7,2135235($1$32/(215e)e5(5 $80$18(/'·,167$//$7,21'(35235,e7$,5(3285 /·(9$&8$7,2135(&,6(,/(67,03257$17'(%,(1 5e,167$//(5(75(6&(//(5/·(9(17$35e6$92,5$6685e
(0$,17,(1'86<67e0('(35,6('·$,5
/(0$,17,(1'86<67e0('(35,6('·$,5
'(6686&Ñ7e6$55,Ë5(6(/21/(6(63$&(856'(
(6686&Ñ7e6$55,Ë5(6(/21/(6(63$&(856'( 'e*$*(0(173285/(60$7(5,$8;'·266$785(6(/21 /$0$18(/'(35235,e7$,5(3285/(60$7e5,$8;'(
FINITION. *L’EXTENSION HORIZONTALE MAXIMALE : 2”.
5e)e5(5$80$18$/'·,16758&7,213285'(6 (;7(16,2163/86*5$1'(65e)e5(5$80$18(/ '·,167$//$7,21'(35235,e7$,5(
·,167$//$7,21'(35235,e7$,5(
CAUTION:
63e&,),&$7,216e/(&75,48(69
60HZ. MOINS DE 12 AMPÈRES.
DO NOT STORE OR USE GASOLINE
AWAY.
AVERTISSEMENT:
VOLATILS INFLAMMABLES DOIVENT
CAUTION: DO NOT OPERATE
THE FIREPLACE WITH THE GLASS REMOVED, CRACKED OR BROKEN.
SHOULD BE DONE BY A LICENSED
NE PAS ENTREPOSER NI UTILISER
D’ESSENCE NI D’AUTRES VAPEURS
AVERTISSEMENT: NE PAS
locaux le permettent. Voir la notice de
appareil.»
N’EST PAS EN PLACE, EST CRAQUÉ
FOR YOUR SAFETY:
OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN VICINITY OF THIS
OR ANY OTHER APPLIANCE.
REPLACEMENT OF THE GLASS
OU LIQUIDES INFLAMMABLES
ANS LE VOISINAGE DE CET
APPAREIL OU DE TOUT AUTRE
UTILISER L’APPAREIL SI LE
PANNEAU FRONTAL EN VERRE
&(7)2<(5*$=9(17,/e 1(673$63285/86$*($9(&
LES FILTRES D'AIR.
LES FILTRES D'AIR. UN COMBUSTIBLE SOLIDE NE
N COMBUSTIBLE SOLIDE NE
3$6È75e87,/,6e$9(&&(7
$6È75e87,/,6e$9(&&(7 $33$5(,/87,/,6(5$9(&/(6 3257(9,75e(6+202/2*8e(6 6(8/(0(17$9(&&(77(81,7e
$'9(57,66(0(17N’AJOUTEZ PAS A
'9(57,66(0(17
&(7$33$5(,/$8&810$7e5,$8'(9$17 (175(5(1&217$&7$9(&/(6)/$00(6 $875(48(&(/8,48,(67)2851,$9(&7&(7
APPAREIL PAR LE FABRICANT.
352'8,7'e&25$7,)1(3$687,/,6(5&200(
APPAREIL DE CHAUFFAGE
'e*$*(0(1760,1,0$8;'(60$7e5,$8;
COMBUSTIBLES : DESSUS 0” PLANCHER 0”
&Ñ7e6 µ
ARRIÈRE 0”
'(6686'8&21'8,7'·(9(17 µ &Ñ7e6(7'(66286'8&21'8,7 '·(9(17 µ &21'8,7'·(9(179(57,&$/ µ
TABLETTE 8”*
W385-1936
OR QUALIFIED PERSON.
POUR VOTRE
SECURITE:
APPAREIL.
OU BRISÉ. CONFIEZ LE
REMPLACEMENT DU
PANNEAU À UN
TECHNICIEN
AGRÉÉ.
W415-1285 / A / 11.03.14
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to the model, venting and gas type of the appliance.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
3.0 VENTING
9
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0067 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5” (127mm) EXHAUST / 8” (203.2mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.2C
EN
W415-1285 / A / 11.03.14
10
3.1 VENTING LENGTHS AND COMPONENTS
EN
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
PART 5”/8” SUPPLIER WEBSITE
Duravent W175-0170 Wolf Steel www.duravent.com
Amerivent 5DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 5DT-AA Selkirk www.selkirkcorp.com
SuperSeal 5DDA Metal-Fab www.mtlfab.com
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following termination kits: wall terminal kit GD422-1, GD422R-1, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12 roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD420 or the 10 foot (3.1m) vent kit GD430.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is recommended that all horizontal runs have a minimum 1/4” (6.4mm) rise per foot/meter using fl exible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” (31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
8.3A
W415-1285 / A / 11.03.14
3.2 TYPICAL VENT INSTALLATIONS
11
EN
16" MIN
(406mm)
24" (610mm)
MAX
43" (1092mm)
MIN PLUS
RISE*
When venting, the horizontal run must be kept to a maximum of 20 feet (6m). If a 20 foot (6m) horizontal run is required, the appliance must have a minimum vertical rise off the appliance of 57" (1448mm).
On all horizontal vent runs, ensure that the vent pipe does not slope downward.
40 FT (12m)
MAX
36"
(914mm)
MIN
43" (1092mm)
When terminating vertically, the vertical rise is a minimum 36"(914mm) and a maximum 40 feet (12m) above the appliance.
* See "VENTING" section.
W415-1285 / A / 11.03.14
12
3.3 SPECIAL VENT INSTALLATIONS
3.3.1 PERISCOPE TERMINATION
EN
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when fi nal grading is completed, the bottom air slot is located a minimum of 12” (304.8mm) above grade. The maximum allowable vent length is 10’ (3.1m) for a fi replace and 8’ (2.4m) for a stove.
12"
(305mm)
MIN TO
GRADE
24" (610mm) MIN
REGARDLESS OF
HORIZONTAL VENT
LENGTH
38 1/2"
(978mm) MIN
9.5B
W415-1285 / A / 11.03.14
3.4 VENT TERMINAL CLEARANCES
13
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
EN
Q
= 3 feet
MIN
(0.9m)
R
= 2 x
MAX
Q
ACTUAL
INSTALLATIONS
CANADA U.S.A.
A 12” (305mm) 12” (305mm) Clearance above grade, veranda porch, deck or balcony.
B 12” (305mm)
Δ
9”
(229mm)
Clearance to windows or doors that open.
Δ
C 12” (305mm)* 12” (305mm) * Clearance to permanently closed windows.
D
18”
(457mm)**
18” (457mm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ (0.6m) from the center line of the terminal.
E 12” (305mm)** 12” (305mm)** Clearance to unventilated sof t. F 0” (0mm) 0” (0mm) Clearance to an outside corner wall.
0” (0mm)***
G
2” (51mm)***
0”
(0mm)***
2”
(51mm)***
H 3’(0.9m) 3’ (0.9m)****
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15’ (4.6m).
I 3’ (0.9m) 3’ (0.9m)**** Clearance to a service regulator vent outlet.
J 12” (305mm) 9” (229mm)
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K 6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet. L 7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
M
12”
(305mm)††
12”
(305mm)****
Clearance under a veranda, porch or deck.
N 16” (406mm) 16” (406mm) Clearance above the roof. O 2’ (0.6m)†* 2’ (0.6m) †* Clearance from an adjacent wall including neighbouring buildings. P 8’ (2.4m) 8’(2.4m) Roof must be non-combustible without openings. Q 3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
R 6’ (1.8m) 6’ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
S 12” (305mm) 12” (305mm) Clearance under a covered balcony
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
12.1D
R
MAX
IHHW
(4.6m)
W415-1285 / A / 11.03.14
14
3.5 VENT APPLICATION FLOW CHART
EN
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3.6 DEFINITIONS
Horizontal Termination
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of
(12m)
24.75 feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
TOP EXIT
Vertical rise is equal
maximum of 40 feet
Vertical Termination
to or greater than
the horizontal run
Horizontal run +
vertical rise to
(12m)
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.1A
For the following symbols used in the venting calculations and examples are: > - greater than > - equal to or greater than < - less than < - equal to or less than HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet HR - combined horizontal vent lengths in feet HO - offset factor: .03 (total degrees of offset - 135°*) in feet VT - combined vertical vent lengths in feet
3.7 ELBOW VENT LENGTH VALUES
FEET INCHES MILLIMETERS 1° 0.03 0.5 12.7 15° 0.45 6.0 152.4 30° 0.9 11.0 279.4 45°* 1.35 16.0 406.4 90°* 2.7 32.0 812.8
* The fi rst 45° and 90°offset has a zero value and is shown in the formula as -45° and - 90° respectively or
-135° when combined.
14.2
15.2A
W415-1285 / A / 11.03.14
3.8 HORIZONTAL TERMINATION
15
(HT) < (VT)
Simple venting confi guration (only one 45° and 90° elbow)
REQUIRED
VERTICAL
RISE IN FEET
40 (12.2)
39 (11.9)
30 (9.1)
20 (6.1)
See graph to determine the required vertical
rise VT for the required horizontal run HT.
(METERS) VT
10 (3.1)
0
2.5
(0.8)5 (1.5)
7.5
(2.3)
(3.1)
10
12.5
15
(4.6)
17.5 (5.3)
(3.8)
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
The shaded area within the lines represents
acceptable values for HT and V
T
For vent confi gurations requiring more than one 45° elbow and 90° elbow, the following formulas apply:
Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet (12.2m)
20
(6.1)
EN
Example: V1 = 8 FT (2.4m) VT = V1 = 8 FT (2.4m) H1 = 2.5 FT (0.8m) H2 = 2 FT (0.6m) HR = H1 + H2 = 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m) HO = .03 (one 45° elbow + two 90° elbows - 135°) = .03 (225 - 135°) = 2.7 FT (0.8m) HT = HR + HO = 4.5 FT (1.4m) + 2.7 FT (0.8m) = 7.2 FT (2.2m) HT + VT = 7.2 FT (2.2m) + 8 FT (2.4m) = 15.2 FT (4.6m)
Formula 1: HT < V
T
45°
H
1
7.2 FT (2.2m) < 8 FT (2.4m)
Formula 2: HT + VT < 40 FT (12.2m)
15.2 FT (4.6m) < 40 FT (12.2m) Since both formulas are met, this vent confi guration is acceptable.
90°
16.5A
H
2
V
1
90°
W415-1285 / A / 11.03.14
16
(HT) > (VT)
EN
Simple venting confi guration (only one 45° and 90° elbow)
See graph to determine the required vertical
rise VT for the required horizontal run HT.
150 (3810)
147 (3733.8)
REQUIRED
VERTICAL RISE
100 (2540)
IN INCHES
(MILLIMETERS) VT
57 (1447.8)
50 (1270)
5
0
(1.5)
(3.1)
15
10
12.5
(3.8)
(4.6)
(6.1)
20
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable values for H
and V
T
For vent confi gurations requiring more than one 45° elbow and 90° elbow, the following formulas apply:
Formula 1: HT < 4.2 V Formula 2: HT + VT < 24.75 feet (7.5m)
Example: V1 = 4 FT (1.2m)
V2 = 1.5 FT (0.5m) VT = V1 + V2= 4 FT (1.2m) + 1.5 FT (0.5m) = 5.5 FT (1.7m) H1 = 2 FT (0.6m) H2 = 1 FT (0.3m)
T
90°
H
1
90°
90°
H
3
V
2
H
2
90°
V
1
45°
H3 = 1 FT (0.3m) H4 = 1.5 FT (0.5m)
= H1 + H2 + H3 + H4 = 2FT (0.6m) + 1FT (0.3m) + 1FT (0.3m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
H
R
HO = .03 (one 45° elbow + four 90° elbows - 135°) = .03 (405 - 135°) = 8.1 FT (2.5m)
HT = HR + HO = 5.5 FT (1.7m) + 8.1 FT (2.5m) = 13.6 FT (4.2m) HT + VT = 13.6 FT (4.2m) + 5.5 FT (1.7m) = 19.1 FT (5.8m)
T
H
4
Formula 1: HT < 4.2FT (1.3m) V
4.2FT (1.3m) VT = 4.2 FT (1.3m) x 5.5 FT (1.7m)= 23.1 FT (7m)
13.6 FT (4.2m) < 23.1 FT (7M)
Formula 2: HT + VT < 24.75 FT (7.5m)
19.1 FT (5.8m) < 24.75 FT (7.5m) Since both formulas are met, this vent confi guration is acceptable.
W415-1285 / A / 11.03.14
T
16.5_2A
3.9 VERTICAL TERMINATION
17
Simple venting configurations.
(HT) < (VT)
See graph to determine the required vertical rise V
required horizontal run HT.
40 (12.2)
30 (9.1)
REQUIRED
VERTICAL
20 (6.1)
RISE IN FEET
(METERS) V
T
3 (0.9)
10 (3.1)
0
5
(1.5)
10
(3.1)
15
(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
values for H
and VT
T
T
20
(6.1)
for the
EN
T
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply: Formula 1: H Formula 2: HT + V
< V
T
T
< 40 feet (12.2m)
T
Example: V
= 5 FT (1.5m)
1
V
= 10 FT (3.1m)
2
V
= V
+ V
T
H
= 3 FT (0.9m)
1
H
= 2.5 FT (0.8m)
2
H
= H
R
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H
= H
T
H
+ V
T
Formula 1: HT < V
10.9FT (3.3m) < 15 (4.6m) Formula 2: HT + V
25.9FT (7.9m) < 40 (12.2m)
= 5 FT (1.5m) + 10 FT (3.1m) = 15 FT (4.6m)
1
2
+ H
= 3FT (0.9m) + 2.5FT (0.8m) = 5.5 FT (1.7m)
1
2
+ H
= 5.5 FT (1.7m)+ 5.4 FT (1.m) = 10.9 FT (3.3m)
R
O
= 10.9 FT (3.3m)+ 15 FT (4.6m) = 25.9 FT (7.9m)
T
T
< 40 FT (12.2m)
T
45°
90°
H
V
1
H
1
90°
Since both formulas are met, this vent configuration is acceptable.
18.3A
V
2
2
90°
W415-1285 / A / 11.03.14
18
V V V
V V V
EN
Simple venting configurations.
(HT) > (VT)
20 (6.1)
19 (5.8)
See graph to determine the required vertical rise V
required horizontal run H
.
T
for the
T
REQUIRED
VERTICAL RISE
IN FEET
(METERS) V
10 (3.1)
T
3 (0.9)
0
5
(1.5)
10
(3.1)
15
(4.6)
20
(6.1)
25
(7.6)
(9.1)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H
30
T
The shaded area within the lines represents acceptable
values for H
and VT
T
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
< 3V
Formula 1: Formula 2: HT + V
Example:
= 1 FT (0.3m)
1
= 1.5 FT (0.5m)
2
= V
T
H
= 6 FT (1.8m)
1
H
= 2 FT (0.6m)
2
H
= H
R
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H
= H
T
H
+ V
T
H
T
T
< 40 feet (12.2m)
T
+ V
= 1 FT (0.3m)+ 1.5 FT (0.5m)= 2.5 FT (0.8m)
1
2
+ H
= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
1
2
+ H
= 8FT (2.4m) + 5.4FT (1.6m) = 13.4FT (4.1m)
R
O
= 13.4FT (4.1m)+ 2.5FT (0.8m) = 15.9FT (4.8m)
T
45°
V
2
90°
H
2
V
H
1
1
90°
90°
Formula 1: H 3VT = 3FT (0.9m) x 2.5FT(0.8m) = 7.5FT (2.3m)
< 3V
T
T
13.4 FT (4.1m) > 7.5 FT (2.3m) Since this formula is not met, this vent configuration is
Formula 2: HT + V
15.9FT (4.8m) < 40FT (12.2m)
< 40 FT (12.2m)
T
unacceptable.
Since only formula 2 is met, this vent configuration in unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas.
Example:
= 1.5 FT (0.5m)
1
= 8 FT (2.4m)
2
= V
+ V
T
H
= 1 FT (0.3m)
1
H
= 1 FT (0.3m)
2
H
= 10.75 FT (3.3m)
3
H
= H
R
H
= .03 (three 90° elbows + two 45° elbows - 135°)
O
= .03 (270 + 90 - 135°) = 6.75 FT (2.1m)
H
= H
T
H
+ V
T
Formula 1: H 3VT = 3 x 9.5 = 28.5 FT (8.7m)
= 1.5 FT (0.5m) + 8 FT (2.4m) = 9.5 FT (2.9m)
1
2
+ H2 + H3 = 1FT(0.3m) + 1FT(0.3m) + 10.75FT(3.3m) = 12.75FT(3.9m)
1
+ H
= 12.75 FT (3.9m) + 6.75 FT (2.1m) = 19.5 FT (5.9m)
R
O
= 19.5FT (5.9m) + 9.5FT (2.9m) = 29 FT (8.8m)
T
< 3V
T
T
45°
90°
H
2
V
45°
H
1
1
H
3
V
2
90°
90°
19.5 FT (5.9m) < 28.5 (8.7m)
Formula 2: HT + V 29 FT (8.8m) < 40 FT (12.2m)
< 40 FT (12.2m)
T
Since both formulas are met, this vent configuration is acceptable.
18.3_2B
W415-1285 / A / 11.03.14
4.0 INSTALLATION
19
!
WARNING
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
EXACTLY.
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
WHICH MUST BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2B
EN
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For optimum performance it is recommended that all horizontal runs have a minimum of 1/4” (6mm) rise per foot/meter using fl exible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
For clearance to combustible materials from the vent pipe, see "MINIMUM CLEARANCE TO COMBUSTIBLES" section.
NOTE: The fi restop / vent shield supplied with this appliance must be used when passing through a combustible wall or fl oor.
WARNING
70.1
W415-1285 / A / 11.03.14
20
A
4.1.1 HORIZONTAL INSTALLATION
EN
This application occurs when venting through an exterior wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall as illustrated to accommodate the fi restop assembly. Dry fi t the fi restop assembly before proceeding to ensure the brackets on the rear surface fi t to the inside surface of the horizontal framing.
The vent shield is telescopic and must be adjusted to shield the full depth of the combustible wall penetration. The length of the vent shield may be cut shorter for combustible walls that are less than 6" (152mm) thick.
A. Apply a bead of caulking (not supplied) around the corner edge of the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your manual baggie).
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
!
WARNING
CAULKING
FIRESTOP
SPACER
VENT
SHIELD
DETERMINE THE CORRECT HEIGHT
FINISHING
MATERIAL
B. Once the vent pipe is installed in its fi nal position, apply high temperature sealant W573-0007 (not supplied) between the pipe and the fi restop.
20.7
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for various roof pitches are available from your authorized dealer / distributor. See accessories to order specifi c kits required.
. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1“ (25mm)
W415-1285 / A / 11.03.14
clearance between the vent pipe and any combustible material. Try to center the vent pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings. A vent pipe shield will prevent any materials such as insulation, from fi lling up the 1” (25mm) air space around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a fi nished ceiling), and secure over the opening in the ceiling. A fi restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a fi restop spacer over the vent shield to restrict cold air from being drawn into the room or around the replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply sealant between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1” (25mm) air space around the pipe.
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
SHIELD
21.1
CAULKING
VENT
PIPE
COLLAR
VENT
PIPE
4.2 USING FLEXIBLE VENT COMPONENTS
21
!
WARNING
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
For safe and proper operation of the appliance, follow the venting instructions exactly. All inner fl ex pipe and outer fl ex pipe joints may be sealed using high
ELBOW
SPACERS
temperature sealant W573-0002 (not supplied) or the high temperature sealant W573-0007 Mill Pac (not supplied). However, the high temperature sealant W573-0007 Mill Pac (not supplied) must be used on the joint connecting the inner fl ex pipe and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
“Wolf Steel Approved Venting” as identifi ed by the stamp only on the outer fl ex pipe.
22.1
EN
W415-1285 / A / 11.03.14
22
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION
EN
A. Stretch the inner fl ex pipe to the required length taking into
account the additional length needed for the fi nished wall surface. Apply a heavy bead of the high temperature sealant W573-0007 Mill Pac (not supplied) to the inner sleeve of the air terminal. Slip the vent pipe a minimum of 2” (50.8mm) over the inner sleeve of the air terminal and secure with 3 #8 screws.
CAULKING
INNER FLEX
PIPE
2" (50.8mm) OVERLAP
OUTER FLEX PIPE
B. Using the outer fl ex pipe, slide over the outer combustion
air sleeve of the air terminal and secure with 3 #8 screws. Seal using high temperature sealant W573-0002 (not
#10x2"
SCREWS
HIGH TEMPERATURE
SEALANT
supplied).
C. Insert the vent pipes through the fi restop maintaining the required
clearance to combustibles. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).
HI-TEMP
SEALANT
D. If more vent pipe needs to be used to reach the fi replace, couple
them together as illustrated. The vent system must be supported approximately every 3 feet (0.9m) for both vertical and horizontal runs. Use noncombustible strapping to
FLEX PIPE
OUTER
#8 X 1/2” SELF DRILLING
SCREWS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE INNER FLEX PIPE
maintain the minimum clearance to combustibles.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its return fl ange.
23.1B
E. The vent shield must be installed only when terminating horizontally. Remove the two screws nearest the vent collars on the top of the appliance. Align the vent heat shield (supplied) and secure. Adjust the vent heat shield to touch the fi restop spacer, as shown below.
W415-1285 / A / 11.03.14
A
A
4.2.2 VERTICAL AIR TERMINAL INSTALLATION
!
WARNING
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
. Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
B. Stretch the inner fl ex pipe to the required length. Slip the
inner fl ex pipe a minimum of 2” (51mm) over the inner pipe of the air terminal connector and secure with 3 #8 screws. Seal using a heavy bead of high temperature sealant W573-0007 (not supplied).
23
EN
C. Repeat using the outer ex pipe, using a heavy bead of
ROOF SUPPORT
high temperature sealant W573-0002 (not supplied).
D. Thread the air terminal connector / vent pipe assembly down through
INNER PIPE
the roof. The air terminal must be positioned vertically and plumb. Attach the air terminal connector to the roof support, ensuring that the top of the air terminal is 16” (406mm) above the highest point that it penetrates the roof.
AIR
TERMINAL
CONNECTOR
HIGH
E. Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector leaving a min. 3/4” (19mm) of the air terminal connector showing above the top of the fl ashing. Slide the fl ashing underneath the sides and upper edge of the shingles. Ensure that the air terminal connector is properly centred within the fl ashing, giving a 3/4”
TEMPERATURE SEALANT
INNER FLEX PIPE
OUTER FLEX PIPE
(19mm) margin all around. Fasten to the roof. Do not nail through the lower portion of the fl ashing. Make weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the ashing with roofi ng material.
2” (51mm)
F. Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal. Secure with the three screws provided.
AIR I NL ET BASE
CAULKING
STORM COLLAR
WEA THER SEALANT
G. Apply a heavy bead of weatherproof caulking 2” (51mm) above
the fl ashing. Install the storm collar around the air terminal and slide down to the caulking. Tighten to ensure that a weather-
FLASHING
tight seal between the air terminal and the collar is achieved.
H. If more vent pipe needs to be used to reach the appliance see “HORIZONTAL
AIR TERMINAL INSTALLATION” section.
24.1A
4.2.3 APPLIANCE VENT CONNECTION
. Install the inner fl ex pipe to the appliance. Secure with 3 screws and
at washers. Seal the joint and screw holes using the high temperature
B. Install the outer fl ex pipe to the appliance. Attach and seal the joints using
sealant W573-0007 (not supplied).
TEMPERATURE
SEALANT
the high temperature sealant W573-0002 (not supplied).
28.2A
#8 X 1/2”
SELF
DRILLING
SCREWS
HIGH
2” (50.8mm) OVERLAP
HIGH TEMPERATURE SEALANT
W415-1285 / A / 11.03.14
2” (50.8mm)
OVERLAP
#8 X 1/2”
SELF
DRILLING
SCREWS
24
A
4.3 GAS INSTALLATION
EN
!
WARNING
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Installation and servicing to be done by a qualifi ed installer. Do not use open ame.
Move the appliance into position and secure.
If equipped with a fl ex connector the appliance is designed to accept a 1/2” (13mm) gas supply. Without the connector it is designed to accept a 3/8” (9.5mm) gas supply. The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance.
Connect the gas supply in accordance to local codes. In the absence of local codes, install to the current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States.
• When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
Check for gas leaks by brushing on a soap and water solution.
SPARKS OR OPEN FLAMES.
30.1A
4.4 MOBILE HOME INSTALLATION
This appliance is also certifi ed to be installed as an OEM (Original Equipment Manufacturer) installation in a manufactured home (U.S. only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate.
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit. Built in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the base. Use #10 hex head screws, inserted through the holes in the base to secure. For free standing products contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must be fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting the appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
conversion kit is supplied with the mobile home appliance.
Conversion Kits This appliance is fi eld convertible between Natural Gas (NG) and Propane (LP). To convert from one gas to another consult your Authorized dealer/distributor.
29.1A
W415-1285 / A / 11.03.14
4.5 ACCESS PANEL FOR GAS LINE CONNECTION
25
A. Remove the screen and door from the appliance, see "SIDE SCREEN REMOVAL / DOOR REMOVAL"
section.
B. Remove media and media tray from the applaince, see "CRADLE BURNER REMOVAL" section. C. Unscrew the 2 screws that hold the access panel to the fi rebox. D. Remove the gasket (careful not to tear).
Access
Panel
Gasket
EN
W415-1285 / A / 11.03.14
26
5.0 FRAMING
EN
!
WARNING
RISK OF FIRE!
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE
APPLIANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH
ANY OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO
COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY.
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN
AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH
SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK
OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE
INSULATION AND OTHER MATERIALS ARE SECURED.
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS
LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS
CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS,
OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING
ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE
FURNACE AT 1382° F (750°C) AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE
MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
BASE.
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, OR SPECIFIED IN THE
INSTALLATION INSTRUCTIONS. THEY MUST BE INSTALLED.
FINISHING MUST BE DONE USING A NON-COMBUSTIBLE MATERIAL PLACED FLUSH WITH THE
It is best to frame your appliance after it is positioned and the vent system is installed. When roughing in the appliance, raise the appliance to accommodate for the thickness of the fi nished fl oor
materials, i.e. tile, carpeting and hard wood.
FINISHING MUST BE DONE USING COMBUSTIBLE
FRONT FACE OF THE UNIT AND EXTENDING FROM THE TOP OF THE UNIT SUCH AS
CEMENT BOARD, CERAMIC TILE, MARBLE, ETC. DO NOT USE WOOD OR DRYWALL.
ANY FIRE RATED DRYWALL IS NOT ACCEPTABLE.
71.1B
Maintain these minimum clearances to combustibles from appliance and vent surfaces: Combustible Appliance framing:
- 1/4" (6.4mm) to the sides of appliance
- 8 1/4" (210mm) to the top of appliance
Combustible Appliance fi nishing:
- 0" (0mm) above the appliance opening
- 50" (1270mm) from bottom of appliance to enclosure top
- 3" (76mm) to top of vent pipe*
- 2" (51mm) to sides and bottom of vent pipe*
- 0" (0mm) to the sides and top of appliance Combustible fi nishing material (ie. Combustible board, brick, stone, tile) must be used to fi nish around the front of the appliance.
*HORIZONTAL VENT SECTIONS: A minimum clearance of 3” (76mm) to the top and 2” (51mm) to the sides and bottom of the vent pipe on all horizontal runs to combustibles is required, see "MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES" section. Use fi restop assembly W010-2985.
*VERTICAL VENT SECTIONS: A minimum of 2” (51mm) all around the vent pipe on all vertical runs to combustibles is required. Use fi restop spacer W010-2985.
W415-1285 / A / 11.03.14
46 1/2"
[1181mm]
A
B
5.1 FRAMING
5.1.1 SEE-THRU FRAMING (BHD4ST)
A: MIN 22 5/8" (575mm) MAX 24 1/8" (613mm)
5.1.2 PENINSULA FRAMING (BHD4P)
27
EN
46 1/2"
[1181mm]
A
45 1/2"
[1156mm]
A: MIN 22 5/8" (575mm) MAX 24 1/8" (613mm)
B: MIN 42 1/2" (1080mm) MAX 43 1/2" (1105mm)
NOTE: All framing dimensions are based on the fi nishing material supports position. Framing may change depending on the fi nishing material thickness. (See "FINISHING SUPPORT ADJUSTMENT" section).
W415-1285 / A / 11.03.14
28
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
IMPORTANT: The BHD4 requires a minimum inside enclosure height of 50" (1270mm), measured from the
EN
bottom of the appliance. For temperature requirements, this area must be left unobstructed.
11 3/4"
[298mm]
COMBUSTIBLE
NON-COMBUSTIBLE
BRICK
3" [76mm]
50"
[1270mm]
MINIMUM
ENCLOSURE
38 1/4"
[972mm]
SAFETY BARRIER
6" [152mm]
MINIMUM WALL
SEE THRU ONLY
* Within the appliance enclosure a minimum 3” (76mm) clearance between the top of the vent pipe and combustible materials is required. All other clearances within the enclosure, including where the vent pipe exits the enclosure are subject to 2” (51mm)to the sides and bottom and 3” (76mm) to the top for horizontal and 2” (51mm) for vertical.
** See venting section.
NOTE: THIS APPLIANCE IS NOT LOAD BEARING.
45" [1143mm]
FIRESTOP
2"
[51mm]
43" [1092mm] MINIMUM
RISE
IMPORTANT: The fi restop assembly provided must be used when the vent pipes pass through any walls or are terminated horizontally.
W415-1285 / A / 11.03.14
5.3 INSTALLING COMBUSTIBLE BOARD
29
!
WARNING
THE SURFACE ABOVE THE APPLIANCE GETS VERY HOT. IF PROPER FINISHING MATERIALS ARE
NOT USED, CRACKING CAN OCCUR.
BHD4ST BHD4P
SIDE
WALL
6” (152mm)
MIN. TO A
SIDE WALL
SAFETY BARRIER
45"
(1143mm)
38 1/4" (972mm)
SAFETY BARRIER
38 1/4" (972mm)
43 1/4"
(1099mm)
EN
6” (152mm)
MIN. TO A
SIDE WALL
Joint Compound where required
Joint compounds such as Durabond 90 and tapes that are resilient to heat and cracking should be used when taping and mudding seams.
Setting tiles and grouting
We recommend you use tiles with a dry butt joint to be installed using a two-part mortar with an acrylic latex additive, such as Mapei Kerabond/Kerlastic, to allow for slight movement in the normal operation of the appliance. If grout is used between the tiles, a polymer-based grout, such as Mapei Ultracolour plus, is recommended.
Primer/Paint
For a painted surface, use a 100% acrylic latex primer and fi nish coat. Paints may discolour.
W415-1285 / A / 11.03.14
30
1/2"
(13mm)
MIN
1 1/2"
(38mm)
MAX
5.3.1 FINISHING SUPPORT ADJUSTMENT
Depending on the fi nishing material we have allowed from 0" (0mm) to 3/4" (19mm) of adjustment after the
EN
1/2" (13mm) combustible board has been installed. Loosen the 8 screws on each nishing support. Adjust the nishing support to the desired position.
NOTE: Peninsula models have one end support that can also be adjusted by loosening the two screws.
BA
SIDE VIEW
NOTE: Framing dimension "A" and "B" will be affected as the fi nishing supports are adjusted outwards, refer to "FRAMING" section".
FINISHING MATERIAL
FINISH SUPPORT
POSITION
1/4" (6mm) 1/2" (13mm)
1/2" (13mm) 1/4" (6mm)
3/4" (19mm) Flush 0" (0mm)
1/2"
Combustible
Board
Finish
support
1/2"
Combustible
Board
Finish
support
1/2"
Combustible
Board
Finish
support
1/4"
Finishing
Material
1/2"
Finishing
Material
3/4"
Finishing
Material
W415-1285 / A / 11.03.14