22-23 OPTIONAL FAN INSTALLATION /
GD36 THERMOSTATIC SENSOR CON TROL
23 OPERATION / MAINTENANCE
Operating Instructions
Maintenance
24 ADJUSTMENTS
Pilot Burner Adjustment
Venturi Adjustment
25-26 REPLACEMENTS
Ordering Replacement Parts
Replacement Parts
Vent Kits
Terminal Kits
Accessories
27-28 TROUBLE SHOOTING GUIDE
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
!
WARNING
• Do not burn wood or other materials in this fireplace.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid
burns or clothing ignition. Supervise young children when they are in the same room as the fireplace.
• Clothing or other flammable material should not be placed on or near the fireplace.
• Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the fireplace is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These
screens and guards must be fastened to the floor.
• Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the fireplace and venting
system are kept clean. The fireplace and its venting system should be inspected before use and at least annually by a qualified
service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The fireplace
area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
• Under no circumstances should this fireplace be modified.
• This fireplace must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the fireplace
and to replace any part of the control system and any gas control which has been under water.
• Do not operate the fireplace with the glass door removed, cracked or broken. Replacement of the glass should be done by a
licensed or qualified service person.
• Do not strike or slam shut the fireplace glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf
Steel Ltd.
• Pressure relief doors must be kept closed while the fireplace is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding
combustible materials to overheat and catch fire.
• Only doors / optional fronts certified with the unit are to be installed on the appliance.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
W415-0381 / H / 12.07.07
NAPOLEON® products are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certifi cate.
NAPOLEON® products are designed with superior components and materials, assembled by trained craftsmen who
take great pride in their work. The burner and valve assembly are leak and test-fi red at a quality test station. Once
assembled the complete fi replace is thoroughly inspected by a qualifi ed technician before packaging to ensure that
you, the customer, receives the quality product that you expect from NAPOLEON®.
NAPOLEON® GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
The following materials and workmanship in your new NAPOLEON® gas fi replace are warranted against defects for as long as you own the fi replace. This covers: combustion chamber, heat exchanger, stainless steel burner,
phazer™ logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized
enamelled components and aluminum extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch,
switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and NAPOLEON® will
provide replacement parts free of charge during the fi rst year of the limited warranty.
3
Labour related to warranty repair is covered free of charge during the fi rst year. Repair work, however, requires
the prior approval of an authorized company offi cial. Labour costs to the account of NAPOLEON® are based on
a predetermined rate schedule and any repair work must be done through an authorized NAPOLEON® dealer.
CONDITIONS AND LIMITATIONS
NAPOLEON® warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears
on the warranty registration card fi led with NAPOLEON® -- provided that the purchase was made through an authorized NAPOLEON® dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas fi replace must be installed by a licensed, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included
with the product and all local and national building and fi re codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will
nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain
enamel parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fi replace.
NAPOLEON® warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the fi rst 10 years NAPOLEON®
will replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON® will provide replacement burners at 50% of the current retail price.
In the fi rst year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been
operated in accordance with the operation instructions and under normal conditions.
After the fi rst year, with respect to this President's Limited Lifetime Warranty, NAPOLEON® may, at its discretion, fully discharge all obligations with respect to this warranty by
refunding to the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the fi rst year, NAPOLEON® will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses
are not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON’S responsibility under this warranty is defi ned as above and it shall not in
any event extend to any incidental, consequential or indirect damages.
This warranty defi nes the obligations and liability of NAPOLEON® with respect to the NAPOLEON® gas fi replace and any other warranties expressed or implied with respect to
this product, its components or accessories are excluded.
NAPOLEON® neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON® will not be
responsible for: over-fi ring, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation,
excessive venting confi gurations, insuffi cient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces,
clothes dryers, etc.
Any damages to fi replace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation,
damaging chemicals or cleaners will not be the responsibility of NAPOLEON®.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration
card must be returned within fourteen days to register the warranty.
NAPOLEON® reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICED BY
A QUALIFIED INSTALLER to conform with local codes. In absence of
local codes, install the BGD42 to the current National Fuel Gas Code,
ANSI Z223.1, or the current CAN/CGA B149, Installation Codes.
Installation practices vary from region to region and it is important to
know the specifi cs that apply to your area,
for example: in Massachusetts State:
• The fi replace damper must be removed or welded in the open
position prior to installation of a fi replace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36".
• The appliance is not approved for installation in a bedroom or
bathroom unless the unit is a direct vent sealed combustion
product.
• WARNING: This product must be installed by a licensed plumber
or gas fi tter when installed within the commonwealth of Mas sachusetts.
Mobile home installation must conform with local codes or in the absence
of local codes, install to the current standard for gas equipped mobile
housing CAN/CSA ZA240 MH Series in Canada or the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280, or
the Fire Safety Criteria for Manufactured Home Installations, Sites and
Communities Standard ANSI/NFPA 501A in the United States.
The fi replace and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa). The fi replace
must be isolated from the gas supply piping system by closing its
individual manual shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than 1/2 psig
(3.5 kPa).
When the fi replace is installed directly on carpeting, vinyl tile or
other combustible material other than wood fl ooring, the fi replace
shall be installed on a metal or wood panel extending the full width
and depth.
If the optional fan or blower is installed, the junction box must be
electrically connected and grounded in accordance with local codes.
In the absence of local codes, use the current CSA C22.1 CANADIAN
ELECTRICAL CODE in Canada or the ANSI/NFPA 70 NATIONAL
ELECTRICAL CODE in the United States.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TESTFIRED TO ASSURE ITS OPERATION AND QUALITY! Maximum input
is 28,500 BTU/hr for natural gas and 24,000 BTU/hr for propane.
When the fi replace is installed at elevations above 4,500ft, and in the
absence of specifi c recommendations from the local authority having
jurisdiction, the certifi ed high altitude input rating shall be reduced at
the rate of 4% for each additional 1,000ft.
Maximum output for natural gas is 19,500 BTU/hr at an effi ciency of
68.5% with the fan on, and 16,000 BTU/hr for propane at an effi ciency
of 67% with the fan on. The maximum A.F.U.E. (annual fuel utilization
effi ciency) rating is 64% for natural gas and 61.5% for propane.
Minimum inlet gas supply pressure is 4.5" water column for natural
gas and 11" water column for propane. Maximum inlet gas pressure
is 7" water column for natural gas and 13" water column for propane.
Manifold pressure under fl ow conditions is 3.5" water column for
natural gas and 10" water column for propane.
This fi replace is approved for bathroom, bedroom and bed-sitting room
installations and is suitable for mobile home installation.
No external electricity (110 volts or 24 volts) is required for the
gas system operation.
Expansion / contraction noises during heating up and cooling
down cycles are normal and are to be expected.
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean plated parts. Buff lightly with a
clean dry cloth. The BGD42 is factory equipped with tempered glass.
The glass thickness is 3/16". Use only replacement glass available
from your Napoleon® dealer. DO NOT SUBSTITUTE MATERIALS.
Clean the glass after the fi rst 10 hours of operation with a recommended gas fi replace glass cleaner. Thereafter clean as required.
DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean
permanent discolouration and / or blemishes may result.
Use only accessories designed for and listed with your spe-
cifi c fi replace.
Provide adequate ventilation air. Provide adequate accessibility clearance for servicing and operating the fi replace. Never
obstruct the front opening of the fi replace.
For safe and proper operation of the fi replace follow the venting
instruction exactly.
Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning.
Provide a means for visually checking the vent connection to
the fi replace after the fi replace is installed.
In order to avoid the possibility of exposed insulation or vapour
barrier coming in contact with the fi replace body, it is recommended that the walls of the fi replace enclosure be 'fi nished',
(i.e. drywall/sheetrock) as would any other outside wall of the
home. This will ensure that clearance to combustibles is maintained within the cavity.
Vent lengths that pass through unheated spaces (attics, garages,
crawl spaces) should be insulated with the insulation wrapped
in a protective sleeve to minimize condensation.
Objects placed in front of the fi replace must be kept a minimum
of 48" away from the front face of the unit.
W415-0381 / H / 12.07.07
INSTALLATION OVERVIEW
5
FIGURE 1
FIGURE 2
W415-0381 / H / 12.07.07
6
VENTING
VENTING LENGTHS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or
American Metal Amerivent venting components. Minimum and
maximum vent lengths, for both horizontal and vertical installations,
and air terminal locations for either system are set out in this manual
and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp
and American Metal Amerivent, follow the installation procedure
provided with the venting components.
All outer pipe joints of these venting systems must be sealed using
Red RTV Hight Temperature Sealant.
Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and American
Metal Amerivent venting systems must not be combined.
A starter adaptor must be used and may be purchased from the corresponding supplier:
For Simpon Dura-Vent, Selkirk Direct Temp and American Metal
Amerivent, follow the installation procedure found on the website for
your venting supplier:
VENTING SUPPLIER WEBSITE ADDRESS
Simpson Dura-Vent www.duravent.com
Selkirk Direct Temp www.selkirkcorp.com
American Metal Amerivent www.americanmetalproducts.com
For vent systems that provide seals on the inner exhaust fl ue, only the
outer air intake joints must be sealed using a red high temperature
silicone (RTV). This same sealant maybe used on both the inner
exhaust and outer intake vent pipe joints of all other approved vent
systems except for the exhaust vent pipe connection to the fi replace
fl ue collar which must be sealed using the black high temperature
sealant W573-0007 (not supplied) Mill Pac.
When using Wolf Steel venting components, use only approved Wolf
Steel rigid / fl exible components with the following termination kits:
WALL TERMINAL KIT GD422, or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT GD410, 8/12 TO 12/12 ROOF TERMINAL KIT GD411,
FLAT ROOF TERMINAL KIT GD412 or PERISCOPE KIT GD401 (for
wall penetration below grade). With fl exible venting, in conjunction
with the various terminations, use either the 5 foot vent kit GD420 or
the 10 foot vent kit GD430.
Minimum clearance to combustible construction from fireplace and vent surfaces:
Sides, back, bottom and 0"
top of the unit
Recessed depth 22"
All around the vent pipe* 2"
Enclosure top 45 1/2"
Ceiling 72" from bottom of unit
*HORIZONTAL VENT SECTIONS: A minimum clearance of 2" all
around the vent pipe on all horizontal runs to combustibles is required.
Use fi restop spacer W010-1778 (supplied).
VERTICAL VENT SECTIONS: A minimum of 1" all around the vent
pipe on all vertical runs to combustibles is required except for clearances in fi replace enclosures. Use fi restop spacer W500-0367 (not
supplied).
Horizontal runs may have a 0" rise per foot in all cases using
SIMPSON DURA-VENT, SELKIRK DIRECT TEMP, AMERICAN
METAL AMERIVENT or NAPOLEON RIGID OR FLEXIBLE venting
components when venting as illustrated in Figures 3, and 4.
For optimum performance it is recommended that all horizontal
runs have a 1" rise per foot when using Napoleon® flexible vent
components.
These vent kits allow for either horizontal or vertical venting of the
fi replace. FIGURES 3 & 5. The maximum allowable horizontal run is
20 feet. The maximum allowable vertical vent length is 40 feet. The
maximum number of 5" vent
The air terminal must remain unobstructed at all times. Examine
the air terminal at least once a year to verify that it is unobstructed and undamaged.
Purge all gas lines with the glass door of the fireplace removed.
Assure that a continuous gas flow is at the burner before reinstalling the door.
Under extreme vent configurations, allow several minutes (5-15)
for the flame to stabilize after ignition.
A terminal shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings. Local codes or regulations may
require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" air gap all
around between the inner liner and outer liner is required for
safe operation. Use a firestop when penetrating interior walls,
floor or ceiling.
W415-0381 / H / 12.07.07
MINIMUM AIR TERMINAL LOCATION CLEARANCES
FIGURE 3
7
3232
3232
3232
Using a soffit heat shield (W585-0096), or equivalent, the distance may be reduced to a minimum of 18”. It is
recommended to maximize the distance to the vinyl clad soffits.
4
**
W415-0381 / H / 12.07.07
8
TYPICAL VENT INSTALLATIONS
NOTE: When terminating vertically, the restrictor plate
W500-0205 must be installed. Refer to Restricting Vertical Vents.
FIGURES 4 a-b
* See venting section
SPECIAL VENT INSTALLATIONS
PERISCOPE TERMINATION
Use the GD401 periscope kit to locate the air termination above
grade. The periscope must be installed so that when fi nal grading
is completed, the bottom air slot is located a minimum of 12" above
grade.
FIGURE 5
W415-0381 / H / 12.07.07
VENTING APPLICATION FLOW CHART
9
HORIZONTAL
TERMINATION
vertical rise
is equal to
or greater
than the
horizontal
run
horizontal
run + vertical rise to
maximum
of 40 feet
vertical rise
is less than
horizontal
run
horizontal
run + vertical rise to
maximum of
24.75 feet
4.2 times the
vertical rise
equal to or
greater than
the horizontal run
VERTICAL
TERMINATION
vertical rise
is equal to
or greater
than the
horizontal
run
horizontal
run + vertical rise to
maximum
of 40 feet
vertical rise
is less than
horizontal
run
horizontal
run + vertical rise to
maximum
of 40 feet
3 times the
vertical
rise equal
to or greater than the
horizontal
run
W415-0381 / H / 12.07.07
10
DEFINITIONS
for the following symbols used in the venting calculations
and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
- total of both horizontal vent lengths (HR) and offsets
H
T
(HO) in feet
HR - combined horizontal vent lengths in feet
HO - offset factor: .03(total degrees of offset - 135°*) in
feet
VT - combined vertical vent lengths in feet
HORIZONTAL TERMINATION
when (HT) < (VT)
Simple venting confi guration (only one 45º and 90° elbow)
The shaded area within the lines represents acceptable
values for HT and V
.
T
For vent confi gurations requiring more than one 45º and 90°
elbow the following formulas apply:
Formula 1: HT < 4.2 V
T
Formula 2: HT + VT < 24.75 feet
Since both formulas are met, this vent confi guration is
acceptable.
W415-0381 / H / 12.07.07
12
VERTICAL TERMINATION
when (HT) < (VT)
Simple venting confi gurations
FIGURE 10
45°
See graph to determine the required vertical rise VT for the
required horizontal run HT.
REQUIRED VERTICAL RISE
IN FEET (VT)
HORIZONTAL VENT RUN PLUS
OFFSETS IN FEET (HT)
Example 3:
V
FIGURE11
2
90°
90°
2
V
H
1
45°
H
V
1
V
2
V
T
H1 = 3 ft
H
2
HR = H1 + H2 = 3 + 2.5 = 5.5 ft
H
O
= .03(45+90+90+90-135)=5.4
HT = HR + HO = 5.5 + 5.4 = 10.9 ft
H
T
Formula 1: H
Formula 2: H
25.9 < 40
Since both formulas are met, this vent confi guration is
acceptable.
= 5 ft
= 10 ft
=
V1 +
V2 =
5 + 10 = 15 ft
= 2.5 ft
= .03(one 45º elbow + three 90º elbows - 135º)
+ VT = 10.9 + 15 = 25.9 ft
< V
T
T
10.9 < 15
+ VT < 40 feet
T
90°
1
The shaded area within the lines represents acceptable
values for HT and VT.
For vent confi gurations requiring more than one 45º and one
90° elbow , the following formulas apply:
Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet
W415-0381 / H / 12.07.07
VERTICAL TERMINATION
when (HT) > (VT)
Simple venting confi gurations
FIGURE 12
See graph to determine the required vertical rise VT for the
required horizontal run HT.
REQUIRED
VERTICAL
RISE IN
FEET (VT)
Example 4:
V
1
V
2
V
T
H1 = 6 ft
H
2
HR = H1 + H2 = 6 + 2 = 8 ft
H
O
= .03(45 + 90 + 90 + 90 - 135) = 5.4 ft
HT = HR + HO = 8 + 5.4 = 13.4 ft
H
T
Formula 1: H
Since this formula is not met, this vent confi guration is
unacceptable.
Formula 2: H
15.9 < 40
Since only formula 2 is met, this vent confi guration is
unacceptable and a new fi replace location or vent confi guration will need to be established to satisfy
both formulas.
= 1 ft
= 1.5 ft
=
V1 +
V2 =
1 + 1.5 = 2.5 ft
= 2 ft
= .03(one 45º elbow + three 90º elbow - 135º)
+ VT = 13.4 + 2.5 = 15.9 ft
< 3V
T
T
3VT =
3 x
2.5 = 7.5 ft
13.4 > 7.5
+ VT < 40 feet
T
13
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (HT)
The shaded area within the lines represents acceptable
values for H
and VT.
T
For vent confi gurations requiring more than one 45º and one
90° elbow , the following formulas apply:
Formula 1: HT < 3V
T
Formula 2: HT + VT < 40 feet
45°
H
90°
V
H
1
1
V
2
2
90°
90°
FIGURE 13
V
2
45°
90°
H
H
2
H
V
1
1
45°
3
FIGURE 14
90°
Example 5:
V
1
V
2
V
T
H1 = 1 ft
H
2
H
3
HR = H1 + H2 + H3 = 1 + 1 + 10.75 = 12.75 ft
H
O
= .03(90 + 90 + 90 + 45 + 45 - 135) = 6.75 ft
HT = HR + HO = 12.75 + 6.75 = 19.5 ft
H
T
Formula 1: H
3VT =
Formula 2: H
24 < 40
Since both formulas are met, this vent confi guration is
acceptable.
= 1.5 ft
= 8 ft
=
V1 +
V2 =
1.5 + 8= 9.5 ft
= 1 ft
= 10.75 ft
= .03(three 90° elbows + two 45° elbows - 135°)
+ VT = 19.5 + 4.5= 24 ft
< 3V
T
T
3 x
9.5 = 28.5 ft
19.5 < 28.5
+ VT < 40 feet
T
W415-0381 / H / 12.07.07
90°
14
INSTALLATION
WALL AND CEILING PROTECTION
HORIZONTAL VENT SECTIONS: A minimum clearance of 2" all
around the vent pipe on all horizontal runs to combustibles is required.
Use fi restop spacer W010-1778 (supplied).
VERTICAL VENT SECTIONS: A minimum of 1" all around the vent
pipe on all vertical runs to combustibles is required. Use fi restop
spacer W500-0367 (not supplied).
HORIZONTAL INSTALLATION
This application occurs when venting
through an exterior wall. Having determined
the air terminal location, cut and frame a
hole in an exterior wall with a minimum
opening as required. See Note above.
ADJUSTABLE FIRESTOP INSTALLATION
FIGURE 16c
FIGURE 15
VERTICAL INSTALLATION
FIGURE 17
Apply a bead of caulking all around and place the fi restop top, so
that the vent shield covers the top of the vent within the opening.
NOTE: The fi restop assembly must be installed with the vent
shield to the top.
The length of the vent shield may be cut shorter for combustible
walls that are less than 8 1/2" thick but the vent shield must extend
the full depth of the combustible wall.
Place the fi restop bottom against the fi restop top and secure the
two together. Adjust the assembly to ensure it is tight to the vent.
Secure fi restop to wall. This restricts cold air from being drawn
into the room or around the fi replace. Ensure that both spacer and
shield maintain the required clearance to combustibles. Once the
vent pipe is installed in its fi nal position, apply sealant W573-0002
(not supplied) between the vent pipe and the fi restop spacer. See fi gures 16a-c.
This application occurs when venting through a roof. Installation kits
for various roof pitches are available from your Napoleon® dealer.
See Accessories to order the specifi c kit required.
VENT SHIELD
FIGURE 16a
FIRESTOP TOP
FIRESTOP BOTTOM
FIGURE 16b
W415-0381 / H / 12.07.07
1. Determine the air terminal location, cut and frame 10 3/4" square
openings in the ceiling and the roof to provide the minimum 1" clearance between the vent pipe and any combustible material. Try to
center the vent pipe location midway between two joist to prevent
having to cut them. Use a plumb bob to line up the center of the openings. DO NOT FILL THIS
SPACE WITH ANY TYPE
OF MATERIAL. A vent
pipe shield will prevent any
materials such as insulation, from fi lling up the 1"
air space around the pipe.
Nail headers between the
joist for extra support.
2. Apply a bead of caulking (not supplied) to the framework or
to the Wolf Steel vent pipe shield plate or equivalent (in the case
of a fi nished ceiling), and secure over the opening in the ceiling.
FIGURE 18. A fi restop must be placed on the bottom of each framed
opening in a roof or ceiling that the venting system passes through.
Apply a bead of caulking all around and place a fi restop spacer over
the vent shield to restrict cold air from being drawn into the room or
around the fi replace. Ensure that both spacer and shield maintain
the required clearance to combustibles.
Once the vent pipe / liner is installed in its
fi nal position, apply sealant W573-0002
(not supplied) between the
the fi restop spacer.
3. In the attic, slide the vent pipe
collar down to cover up the open end
of the shield and tighten. This will prevent any materials, such as insulation,
from fi lling up the 1" air space around
the pipe.
FIGURE 18
vent pipe and
VENT
PIPE
COLLAR
VENT PIPE
SHIELD
FIGURE 19
USING FLEXIBLE VENT COMPONENTS
!
WARNING
Do not allow the inside vent pipe to
bunch up on horizontal or vertical
runs and elbows. Keep it pulled tight.
A 1 1/4" air gap between the liner and
outer liner all around is required for
safe operation. A spacer is required
at the start, middle and end of each
elbow to ensure this gap is maintained.
See Figure 20.
Spacers are attached to the inner fl ex
liner at predetermined intervals to
maintain a 1 1/4" air gap to the outer
fl ex pipe. These spacers must not be
removed.
Use only approved flexible vent pipe kits marked:
"Wolf Steel Approved Venting" as identified by the stamp only on the 7” outer
vent pipe.
NOTE: Eight (8") inches is the minimum bend radius allowed for the
8" diameter fl exible vent pipe.
HORIZONTAL AIR TERMINAL INSTALLATION
1. Stretch the 5" diameter fl exible vent pipe to the required length
taking into account the additional length needed for the fi nished wall
surface. Slip the liner a minimum of 2" over the inner sleeve of the
air terminal and secure with 3 #8 screws. Apply a heavy bead of the
high temperature sealant (W573-0007 not supplied).
2. Using the 8" diameter fl exible
combustion air sleeve of the air terminal and secure with 3 #8 screws.
Seal as before.
FIGURE 21
The air terminal mounting plate may be recessed into the exterior
wall or siding by 1½", the depth of the return fl ange.
For safe and proper operation of the fireplace, follow the venting
instructions exactly.
All inner exhaust and outer intake vent pipe joints may be sealed
using either Red RTV high temp silicone sealant or Black high
temp Mill Pac with the exception of the fireplace exhaust flue
collar which must be sealed using Mill Pac (not supplied).
3. Insert the
the required clearance to combustibles. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall and
make weather tight by sealing with caulking (not supplied).
vent pipe assemblies through the fi restop maintaining
ELBOWS
SPACERS
FIGURE 20
vent pipe, slide over the outer
4. Apply a heavy bead of the high temperature sealant W573-0007
(not supplied), Mill Pac, to the inside of the 5"
1" from the end. Slip the
vent collar and secure with 3 #8 screws.
5. Using the 8" diameter fl exible
0002 (not supplied), slide a minimum of 2" over the fi replace combustion air collar and secure with 3 #8 screws.
6. If more liner needs to be used to reach the fi replace, couple
them together as illustrated. The vent system must be supported
approximately every 3 feet for both vertical and horizontal runs. Use
noncombustible strapping to maintain the minimum 1" clearance to
combustibles.
vent pipe a minimum of 2" over the fi replace
vent pipe approximately
vent pipe, apply sealant W573-
FIGURE 22
7. The vent heat shield
must be installed only when
terminating horizontally. Remove the two screws nearest
the vent collars on the top of
the fi replace. Align the vent
heat shield (supplied) and
secure. Adjust the vent heat
shield to touch the firestop
spacer.
FIGURE 23
VERTICAL AIR TERMINAL INSTALLATION
FIGURE 24a
DO NOT CLAMP
THE FLEXIBLE
LINER
vent pipe a minimum of 2” over the inner
the
sleeve of the air terminal connector and secure
with 3 #8 screws. Seal using a heavy bead of
the high temperature sealant W573-0007 (not
supplied).
3. Repeat using the outer fl ex
4. Thread the air terminal connector / liner as-
sembly down through the roof. The air terminal
must be located vertically and plumb. Attach
the air terminal connector to the roof support,
ensuring that the top of the air terminal is 16”
above the highest point that it penetrates the
roof.
1. Fasten the roof support
to the roof using the screws
provided. The roof support
is optional. In this case the
venting is to be adequately
supported using either an alternate method suitable to the
authority having jurisdiction or
the optional roof support.
2. Stretch the inner
to the required length. Slip
vent pipe
vent pipe.
FIGURE 24b
15
W415-0381 / H / 12.07.07
16
5. Remove nails from the shingles, above and to the sides of
the chimney. Place the fl ashing over the air terminal connector
leaving a min. 3/4” of the air terminal connector showing above
the top of the fl ashing. Slide the fl ashing underneath the sides
and upper edge of the shingles. Ensure that the air terminal connector is properly centred within the fl ashing,
giving a 3/4” margin all around. Fasten to the
roof. Do not nail through the lower portion of
the fl ashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and
top edges of the fl ashing with roofi ng material.
6. Aligning the seams of the terminal
and air terminal connector, place the
terminal over the air terminal connector
making sure the liner goes into the hole in
the terminal. Secure with the three screws
provided.
7. Apply a heavy bead of weatherproof
caulking 2" above the fl ashing. Note: Maintain a minimum 2”
space between the air inlet base and the storm collar. Install the
storm collar around the air terminal and slide down to the caulking. Tighten to ensure that a weather-tight seal between the air
terminal and the collar is achieved.
8. If more liner needs to be used to reach the fi replace, couple
them together as illustrated in Figure 22. The vent system must be
supported approximately every 3 feet for both vertical and horizontal runs. Use noncombustible strapping to maintain a clearance to
combustibles
of 1".
FIGURE 25
USING RIGID VENT COMPONENTS
The vent system must be supported approximately every 3 feet for
both vertical and horizontal runs. Use Wolf Steel vent spacers every
3 feet and either side of each elbow to maintain the minimum 1¼"
clearance between the outer and inner vent pipes. Use Wolf Steel
support ring assembly or equivalent noncombustible strapping to
maintain the minimum clearance to combustibles for both vertical
and horizontal runs.
All inner exhaust and outer intake vent pipe joists may be sealed
using either Red RTV high temp silicone sealant or Black high
temp Mill Pac with the exception of the fireplace exhaust flue
collar which must be sealed using Mill Pac (not supplied).
HORIZONTAL AIR TERMINAL INSTALLATION
1. Move the fi replace into position. Measure the vent length required
between terminal and fi replace taking into account the
additional length needed for the fi nished wall surface and any 1¼" overlaps
between venting components.
FIGURE 27
2. Apply high temperature sealant
W573-0007 (not supplied) Mill Pac to
the outer edge of the 5" inner collar of
the fi replace. Attach the fi rst vent component and secure using 3 self tapping
screws. Repeat using 8" piping.
3. The vent heat shield must be installed only when terminating
horizontally. Remove the two screws nearest the vent collars on the
top of the fi replace. Align the vent shield (supplied) and secure.
Adjust the heat shield to touch the fi restop spacer.
FIREPLACE VENT CONNECTION
1. Install the 5" diameter fl exible
place. Secure with 3 screws and fl at washers. Seal the joint
and screw holes using the high temperature sealant W5730007 (not supplied) Mill Pac.
2. Install the 8" diameter fl exible
Attach and seal the joints with high temperature sealant
W573-0002 (not supplied).
FIGURE 26
4. Holding the air terminal (with the
air deflectors to the top), insert into
both vent pipes with a twisting motion
to ensure that both the terminal sleeves
engage into the vent pipes and sealant.
Secure the terminal to the exterior wall
and make weather tight by sealing with
caulking (not supplied).
The air terminal mounting plate may be
recessed into the exterior wall or siding by 1½", the
depth of the return flange.
EXTENDED HORIZONTAL AIR TERMINAL
INSTALLATION
1. Follow the instructions for
"Horizontal Air Terminal Installations", items 1 to 3.
2. Continue adding components alternating inner and
outer venting. Ensure that all
5" venting and elbows have
suffi cient vent spacers attached
and each component is securely fastened to the
one prior. Attach the 5" telescopic sleeve to the
vent run.
Repeat using a 8" telescopic sleeve. Secure
and seal as before. To facilitate completion, attach
5" and 8" couplers to the air terminal.
3. Install the air terminal. See item 3 of the
Horizontal Air Terminal Installation. Extend the 5" telescopic sleeve;
connect to the air terminal assembly. Fasten with self tapping screws
and seal. Repeat using the 8" telescopic sleeve.
vent pipe liner to the fi re-
vent pipe to the fi replace.
FIGURE 28
FIGURE 29
W415-0381 / H / 12.07.07
17
VERTICAL VENTING INSTALLATION
1. Move the fi replace into position.
2. Fasten the roof support to the roof using the screws provided.
FIGURE 21. The roof support is optional. In this case the venting is
to be adequately supported using either an alternate method suitable
to the authority having jurisdiction or the optional roof support.
3. Apply high temperature sealant W573-0007 (not supplied)
to the outer edge of the inner sleeve of the air terminal. Slip a 5"
diameter coupler a minimum of 2" over the sleeve and secure using
3 screws.
4. Apply high temperature sealant
W573-0007 (not supplied) to the outer
edge of the of the outside sleeve of the
air terminal. Slip a 8" diameter coupler
over the sleeve and secure as before.
FIGURE 25. Trim the 8" coupler even
with the 5" coupler end.
5. Thread the air terminal pipe as-
sembly down through the roof support
and attach, ensuring that a minimum
16" of air terminal will penetrate the
roof when fastened. FIGURE 23.If
the attic space is tight, we recommend threading the Wolf Steel vent
pipe collar or equivalent loosely
onto the air terminal assembly
as it is passed through the attic.
FIGURE 29. The air terminal must be
located vertically and plumb.
6. Remove nails from the shingles,
above and to the sides of the chimney. Place the fl ashing over the air
terminal and slide it underneath the
sides and upper edge of the shingles. Ensure that the air terminal
is properly centered within the fl ashing, giving a 3/4" margin all
around. Fasten to the roof. Do NOT nail through the lower portion
of the fl ashing. Make weather-tight by sealing with caulking. Where
possible, cover the sides and top edges of the fl ashing with roofi ng
material. FIGURE 23.
7. Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure the
inner sleeve goes into the hole in the terminal. Secure with the 3
screws provided.
8. Apply a heavy bead of weatherproof caulking 2" above the
fl ashing. Note: Maintain a minimum of 2" space between the air
inlet base and the storm collar. Install the storm collar around the
air terminal and slide down to the caulking. Tighten to ensure that
a weather-tight seal between the air terminal and the collar is
achieved.
9. Continue adding rigid venting sections, sealing and securing
as above. Attach a 5" collapsed telescopic pipe to the last section
of rigid piping. Secure with screws and seal. Repeat using a 8"
telescopic pipe.
10. Run a bead of high temperature sealant W573-0007 (not supplied) Mill Pac around the outside of the 5" collar on the fi replace.
Pull the adjustable pipe a minimum of 2" onto the collar. Secure with
3 screws. Repeat with the 8" telescopic pipe.
11. In the attic, slide the vent pipe collar down to cover up the open
end of the shield and tighten. This will prevent any materials, such as
insulation, from fi lling up the 1" air space around the pipe.
FIGURE 29
FIGURE 30
RESTRICTING VERTICAL VENTS
FIGURE 31
TOP OF THE
FIREBOX
RESTRICTOR PLATE
Vertical terminations may display a very active fl ame. As this appearance is not desirable, the vent exit must be restricted using restrictor
plate, W500-0205. This reduces the velocity of the exhaust gases,
slowing down the fl ame pattern and creating a more traditional appearance.
Remove the two screws on either side of the exhaust collar inside the
fi rebox. Install the plate as shown. Replace the screws.
GAS INSTALLATION
Proceed once the vent installation is complete.
NOTE: All gas connections must be contained within the fi replace when complete.
1. Move the fi replace into position and secure to the fl oor through
the 1/4" holes located at either side of the base.
2. The fi replace is designed to accept 3/8" gas supply line. The
fi replace is equipped with a 3/8" manual shut-off valve.
3. Connect the gas supply in accordance to local codes. In the
absence thereof, install according to the National Installation Code.
4. When fl exing any gas line, support the gas valve so that the
lines are not bent or kinked.
5. Check for gas leaks by brushing on a soap and water solu-
tion.
Purge all gas lines with the glass door of the stove removed.
Assure that a continuous gas fl ow is at the burner before reinstalling the door.
DO NOT USE OPEN FLAME.
OPTIONAL WALL SWITCH
INSTALLATION
For ease of accessibility, an optional remote wall switch may be
installed in a convenient location.
connected to the gas valve for the wall switch. However if a greater
length is required
electrical hole located at the bottom left side of the unit. The recommended maximum lead length depends on wire size:
WIRE SIZE MAX. LENGTH
14 gauge 100 feet
16 gauge 60 feet
18 gauge 40 feet
Attach the two leads to terminals 1 and 3 located on the gas valve.
route 2-strand (solid core) millivolt wire through the
A 20’ length of millivolt wire is
FIGURE 32
W415-0381 / H / 12.07.07
18
MOBILE HOME INSTALLATION
This appliance is certifi ed to be installed as an OEM (Original Equipment Manufacturer) installation in a manufactured home or mobile
home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appli-
ance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the mobile home appliance.
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit. The fi replace is equipped
with two 1/4" diameter holes located in the front left and right corners of the base. For mobile home installations, the fi replace must be
fastened in place. Use #10 hex head screws, inserted through the holes in the base to secure. Always turn off the pilot and the fuel supply
at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting the fi replace, ensure that the logs are
positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by
local codes.
This fi replace is only for use with the type of gas indicated on the rating plate. This fi replace is not convertible for use with other gases,
unless a certifi ed kit is used.
Conversion Kits
The mobile home appliance is fi eld convertible between Natural Gas (NG) and Propane (LP).
To convert from one gas to another consult your Napoleon dealer/distributor.
FRAMING
Minimum clearance to combustible
construction from fi replace and
vent surfaces:
Sides, back, bottom
and top of the unit 0"
Recessed depth 22"
All around the vent
pipe* 2"
Enclosure top 45 1/2"
Ceiling 72" from bottom of unit
FIGURE 33
*HORIZONTAL VENT SECTIONS: A minimum clearance of 2" all around the vent
pipe on all horizontal runs to combustibles
is required. Use fi restop spacer W010-1778
(supplied).
VERTICAL VENT SECTIONS: A minimum of
1" all around the vent pipe on all vertical runs
to combustibles is required except for clearances in fi replace enclosures. Use fi restop
spacer W500-0367 (not supplied).
Note: In order to avoid the possibility of
exposed insulation or vapour barrier coming in contact with the fi replace body, it is
recommended that the walls of the fi replace
enclosure be “fi nished” (ie: drywall/sheetrock), as
you would fi nish any other outside wall of a home. This
will ensure that clearance to combustibles is maintained
within the cavity.
It is best to frame your fi replace after it is positioned and the vent system
is installed. Use 2x4's and frame to local building codes. FIGURES 33.
It is not necessary to install a hearth extension with this fi replace system.
When roughing in the fi replace, raise the fi replace to accommodate for the thickness
of the fi nished fl oor materials, i.e. tile, carpeting, hard wood, which if not planned for will
interfere with the opening of the lower access door and the installation of many decorative
fl ashing accessories.
Objects placed in front of the fi replace should be kept a minimum of 48" away from the front face.
Combustible materials may be installed fl ush with the front of the fi replace but must not cover or protrude past any of the black face-areas
of the fi replace. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas.
The fi replace requires a minimum enclosure height of 45 1/2“. For temperature requirements, the enclosure space around and above
the fi replace must be left unobstructed.
W415-0381 / H / 12.07.07
FIGURE 34
FIGURE 35a-c
19
NAILING TAB INSTALLATION
1) Attach the nailing tabs to the corner posts using the 2 sheet metal
screws supplied. Secure through the centre of the top and bottom
slots in the nailing tab and then through the existing holes in the
corner posts.
If there are no existing holes, follow these instructions:
Position the nailing tab so that the front face
is offset with the front edge of the corner post
(approx. ½"). Centre the nailing tab vertically
on the corner post.
Figure 36 a.
Drill through the centre of the top and bottom
slots in the nailing tab. Secure using the two
sheet metal screws supplied. This allows the
nailing tab to slide back and forth for desired
framing. Figure 36b.
2) To determine the fi nal location of the nailing
tab you must fi rst determine the thickness of
your fi nishing material (i.e. drywall). This will
determine the dimension from the front edge of
the corner post to the nailing tab. Once the nailing tab is in the desired location, drill through
the centre hole of the nailing tab. Secure with
a sheet metal screw*. Figure 36c.
* Additional set screws may be installed.
FIGURES 36a-c
CORNER
POST
NAILING
TAB
TOPSLOT
NAILING
TAB
A
FINISHING
MATERIAL
C
B
CENTRE
HOLE
W415-0381 / H / 12.07.07
20
MINIMUM MANTEL AND ENCLOSURE CLEARANCES
Combustible mantel clearance can vary according to the mantel
depth. FIGURE 36. Use the graph to help evaluate the clearance
needed. Curtains, above the fi replace, must not be positioned lower
than the 5" distance required for the 2" combustible mantel. These
same requirements apply to any combustibles protruding on either
side of the fi replace.
FIGURES 37a
FIGURES 37b
The fi replace requires a minimum enclosure height of 45 1/2". For
temperature requirements, the enclosure space around and above
the fi replace must be left unobstructed. FIGURE 37.
FIGURES 37c
* See venting section
GLASS/DOOR REPLACEMENT
1. Place the door frame
face down careful not to
scratch the paint.
2. Center the gasketed
glass inside the door
frame with the thick side
of the gasket facing up.
3. Bend the glass re-
tainers located along the
edge of the door frame
over the gasket holding the glass in place.
Careful not to break the
glass.
W415-0381 / H / 12.07.07
FINISHING
L42 LOUVRE INSTALLATION
FIGURE 38
FIGURE 39
A
B
HINGE
CLIP
A
B
UPPER LOUVRES
Insert the louvre tabs into the slots
SLOT
TAB
SLOT
located at the top left and right corners of the unit.
LOWER LOUVRES
Insert the hinge clips into the slots
located at the bottom left and right
corners of the unit.
To remove the louvres, pull the back
tabs of the clips forward, while pushing the louvre assembly back. Lift
the clip.
21
LOGO PLACEMENT
Remove the backing of
the logo supplied and
place on the glass viewing door, as indicated.
½"
FIGURE 40
LOGO
½"
PORCELAIN REFLECTIVE PANELS
1. Remove the upper louvres, and open the glass door. Remove
the logs.
2. Remove the two securing screws located on either fi rebox side.
3. Place the left panel against the left side
of the fi rebox, ensuring that it butts up to
the rear panel. Secure in place using 2 of
the screws previously removed. Repeat for
the right side.
4. Replace the logs, glass door and louvres.
LOG PLACEMENT
PHAZERTM logs and glowing embers, exclusive to Napoleon® Fireplaces, provide a unique and realistic glowing effect that is different
in every installation. Take the time to carefully position the glowing
embers for a maximum glowing effect. Log colours may vary. During
the initial use of the fi replace, the colours will become more uniform as
colour pigments burn in during the heat activated curing process.
FIGURES 43a-e
1. Place the cutout in the bottom of log
assembly. Rest the log against the back wall of the fi rebox.
(W135-0297) behind the pilot
FIGURE 41
GRATE INSTALLATION
FIGURE 42
2. Move the two small logs
tion, lining up the studs located on the burner with the holes on the
bottom of the logs.
(W135-0298 & W135-0299) into posi-
GLOWING EMBERS
3. Tear the glowing embers into pieces and place along the front row
of ports covering all of the burner area in front of the small logs. Care
should be taken to shred the embers into thin, small irregular pieces
as only the exposed edges of the fi bre hairs will glow. The ember
material will only glow when exposed to direct fl ame; however, care
should be taken to not block the burner ports. Blocked burner ports
can cause an incorrect fl ame pattern, carbon deposits and delayed
ignition. PHAZERtm logs glow when exposed to direct fl ame.
The grate for this fi replace has been removed for shipping purposes.
The grate must be installed before the logs are installed.
Remove the packaging from the grate and install onto the two pins
as illustrated.
4. Place the bottom of the left crossover log (W135-0300) onto the
stud on the left side of the log support. The top of the log
should rest in the pocket on the back log.
W415-0381 / H / 12.07.07
22
5. Place the bottom of the right crossover log (W135-0302)
onto the stud on the right side of the log support. The top
of the log should rest in the pocket on the left crossover log
(W135-0300).
OPTIONAL BLOWER INSTALLATION
INSTALLATION TO BE DONE
BY A QUALIFIED INSTALLER
and must be electrically con-
cordance with local codes. In the absence
of local codes, use the current CSA C22.1
CANADIANELECTRICALCODE in Canada or the
FIGURE 44
grounded 2-wire, 60hz power cable to the receptacle / junction box.
At this point, it must be strain relieved
and insulated.
The three slots on the blower mounting bracket allow ease of adjustment
when attaching the blower. For a quiet
running blower, do not allow the assembly to sit on the fi rebox base.
Slide the vibration reducing pad (A) into the clip (C)
and up against the threaded stud (B) at the other end. The blower
must be able to be positioned entirely onto the pad.
Tilt the blower onto its side. Slide it past the controls and into the clip
(C). Secure to the threaded stud using the lock washer and wing
nut provided.
Ensure that the
blower does
not touch the
fi replace base
or the fi rebox.
B
A
FIGURE 46
nected and grounded in ac-
ANSI/NFPA 70 NATIONALELECTRICAL
CODE in the United States
If the fi replace was not previously
equipped with a blower: route a
FIGURE 45
FIGURE 47
CHARCOAL EMBERS
Randomly place the charcoal embers along the front and sides of the
log support tray in a realistic manner. Fine dust found in the bottom
of the bag should not be used.
VERMICULITE
Sprinkle vermiculite around the charcoal embers.
Note: Both charcoal embers and vermiculite are not to be placed
on the burner.
CHARCOAL LUMPS
Place the lumps between the logs in a realistic manner taking care
not to block any of the burner ports.
Attach the connectors from the black
and white wires to the thermodisc and
secure the thermodisc bracket to the
securing stud at the bottom left of the
unit using a lock washer and wing nut.
Ensure that the thermodisc touches
the fi rebox wall.
Attach the connectors from the black
and red wires to the blower.
Attach and secure the variable speed
switch using the nut provided. Plug the
harness cord into the receptacle.
The wire harness provided in this
kit is a universal harness. When
installed, ensure that any excess
wire is contained, preventing it
from making contact with moving
or hot objects.
Because the blower is thermally
activated, when turned on, it
will automatically start approximately 10 minutes after lighting
the fireplace and will run for approximately 30-45 minutes after
the fireplace has been turned
off. Use of the fan increases the output of heat.
Drywall dust will penetrate into the blower bearings, causing
irreparable damage. Care must be taken to prevent drywall dust
from coming into contact with the blower or its compartment.
C
Any damage resulting from this condition is not covered by the
warranty policy.
FIGURE 49
FIGURE 48
OPTIONAL FAN INSTALLATION
ELECTRICAL INSTALLATION TO BE DONE
BY A QUALIFIED INSTALLER and must be
connected and grounded in accordance
with local codes. In the absence of local
codes, use the current CSA C22.1 CA-
NADIANELECTRICALCODE in Canada or
the ANSI/NFPA 70 NATIONALELECTRI-
CALCODE in the United States.
To safely install the fan, turn off
the electricity fi rst.
If the fi replace was not previously equipped with a fan: route
a grounded 2-wire, 60hz power
cable to the junction box. At this point, it must be strain relieved and
insulated.
W415-0381 / H / 12.07.07
FIGURE 50
The wire harness provided in this kit is a
universal harness. When installed, ensure
that any excess wire is contained, preventing it from making contact with moving or
hot objects.
To ease installation of the fan, remove the
hinge screen and valve control door (lower
louvres) from the base of the fi replace.
Position the vibration reducing pad into the
clip and onto the threaded stud at the other
end, piercing a hole into the pad. The fan assembly must be able to
be positioned entirely onto the pad.
Slide the fan assembly past the controls and into the clip. Secure
using the lock washer and nut provided.
Plug the harness cord into the receptacle.
FIGURE 51
GD36 THERMOSTATIC SENSOR CONTROL
This optional kit is meant to be used only in conjunction with the GD65
Fan Kit, shown above, which may be
ordered from your Wolf Steel / Napoleon® dealer.
With the thermostatic sensor option,
the fan, when turned on, becomes
thermally activated, and will automatically run approximately 15-30 minutes
after the fi replace has been lit and for
approximately 30-45 minutes after the
fi replace has been turned off.
Use of the fan increases the output of heat.
FIGURE 52
OPERATION / MAINTENANCE
OPERATING INSTRUCTIONS
When lit for the fi rst time, the fi replace will emit a slight odour for a few
hours. This is a normal temporary condition caused by the curing of
the logs and the "burn-in" of internal paints and lubricants used in the
manufacturing process and will not occur again.
FOR YOUR SAFETY READ BEFORE LIGHTING:
A. This fi replace is equipped with a pilot which must be lit by hand
while following these instructions exactly.
B. Before operating smell all around the fi replace area for gas and
next to the fl oor because some gas is heavier than air and will
settle on the fl oor
C. Use only your hand to turn the gas control knob. Never use tools.
If the knob will not turn by hand, do not try to repair it. Call a qualifi ed service technician. Force or attempted repair may result in a
fi re or explosion.
D. Do not use this fi replace if any part has been under water. Imme-
diately call a qualifi ed service technician to inspect the fi replace
and replace any part of the control system and any gas control
which has been under water.
LIGHTING INSTRUCTIONS
WARNING: The gas valve has an interlock device which will not allow the pilot burner to be lit until the thermocouple has cooled. Allow
approximately 60 seconds for the thermocouple to cool.
When lighting and re-lighting, the gas knob cannot be turned from pilot
to off unless the knob is depressed slightly.
1. Stop! Read the above safety information on this label.
2. Turn off all electric power to the fi replace.
3. Turn the gas knob clockwise to off.
4. Wait fi ve (5) minutes to clear out any gas. If you smell gas includ-
ing near the fl oor. Stop! Follow "B" in the above safety information
on this label. If you don't smell gas go the next step.
TO TURN OFF GAS
1. Turn off all electric power to the fi replace if service is to be performed.
MAINTENANCE
Turn off the gas and electrical power before servicing the
fireplace.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing. This fi replace and its venting
system should be inspected before use and at least annually by a
qualifi ed service person. The fi replace area must be kept clear and
free of combustible materials, gasoline or other fl ammable vapours
and liquids. The fl ow of combustion and ventilation air must not be
obstructed.
1. In order to properly clean the burner and pilot assembly, remove
the logs to expose both assemblies.
2. Keep the control compartment, logs, burner, air shutter opening
and the area surrounding the logs clean by vacuuming or brushing,
at least once a year.
Unplug the power cord from the receptacle. Connect all wires as
shown.
Attach and secure the sensor assembly bracket to
the securing stud located
next to the receptacle/
junction box at the bottom
left of the unit using the
lock washer and wing nut.
Ensure that the thermodisc
touches the fi rebox wall.
Plug the power cord back into the receptacle.
When installed, ensure that any excess wire is contained, preventing it
from making contact with moving or hot objects.
After extended periods of non-operation such as following a vacation or
a warm weather season, the fi replace may emit a slight odour for a few
hours. This is caused by dust particles in the heat exchanger burning
off. In both cases, open a window to suffi ciently ventilate the room.
Purge the gas line with the glass door removed. Assure that a continuous gas flow is at the burner before re-installing the door.
FIGURE 53
WHAT TO DO IF YOU SMELL GAS
• Turn off all gas to the fi replace.
• Open windows.
• Do not try to light any appliance.
• Do not touch any electric switch; do not use
any phone in your building.
• Immediately call your gas supplier from a neighbour's
phone. Follow the gas supplier's instructions.
• If you cannot reach
your gas supplier,
call the fi re department.
5. Turn gas knob counter-clockwise to pilot.
6. Depress slightly and hold gas knob while lighting the pilot with
the push button igniter. Keep knob depressed for one minute, then
release. If pilot does not continue to burn, repeat steps 3 through 5.
7. With pilot lit, depress and turn gas knob counter-clockwise
to on.
8. If equipped with remote on-off switch/thermostat, main burner
may not come on when you turn valve to on. Remote switch must
be in the on position to ignite burner.
9. Turn on all electric power to the fi replace.
2. Push in gas control knob slightly and turn clockwise
to off. Do not force.
3. Check to see that all burner ports are burning. Clean out any of the
ports which may not be burning or are not burning properly.
4. Check to see that the pilot fl ame is large enough to engulf the
thermocouple and thermopile and reaches toward the burner with
the third jet.
5. Replace the cleaned logs.
6. Check to see that the main burner ignites completely on all open
when the gas knob for the burner is turned on. A 5 to 10 second total
light-up period is satisfactory. If ignition takes longer, consult your
Napoleon® dealer / distributor.
7. Check that the gasketing on the sides, top and bottom of the door
is not broken or missing. Replace if necessary.
GAS KNOB
ings
W415-0381 / H / 12.07.07
23
24
ADJUSTMENTS
PILOT BURNER ADJUSTMENT
Adjust the pilot screw to provide properly sized fl ame. Turn in a
clockwise direction to reduce the gas fl ow.
FIGURE 54
Closing the air shutter will cause a more yellow fl ame, but can lead
to carboning. Opening the air shutter will cause a more blue fl ame,
but can cause fl ame lifting from the burner ports. The fl ame may not
appear yellow immediately; allow 15 to 30 minutes for the fi nal fl ame
colour to be established.
FIGURE 57
FIGURE 55
FLAME CHARACTERISTICS
It is important to periodically perform a visual check of the pilot
and the burner fl ames. Conpare them to the fi gures shown. If any
fl ames appear abnormal call a qualifi ed service technician.
FIGURE 56
VENTURI ADJUSTMENT
Air shutters have been factory set open according to the chart
below:
AIR SHUTTER
Air shutter adjustment must only be done by a qualified
installer!
FIGURE 58
VENTURI COVER
To access the air shutter, remove the two screws that secure the cover
to the air housing, taking care not to damage the gasket.
NOTE: Ensure burner is seated onto orifi ce.
NG 1/4"
LP 7/16 "
These settings are for the maximum horizontal vent run.- Adjustment may be required depending on fuel type, vent confi guration
and altitude.
W415-0381 / H / 12.07.07
REPLACEMENTS
Contact your dealer for questions concerning prices and
availability of replacement parts. Normally all parts can be
ordered through your Napoleon dealer or distributor.
1 W357-0001 PIEZO IGNITER
2 W680-0004 THERMOPILE
3 W680-0005 THERMOCOUPLE**
4 W010-0800 NATURAL GAS PILOT ASSEMBLY
4 W010-0801 PROPANE GAS PILOT ASSEMBLY
5 W455-0069 NATURAL GAS PILOT INJECTOR
5 W455-0067 PROPANE GAS PILOT INJECTOR
6 W725-0025 NATURAL GAS VALVE
6 W725-0026 PROPANE VALVE
7* W385-0245 NAPOLEON® LOGO
8* W750-0112 20FT OF WIRE
9 W010-0864 PAN BURNER
10 GL-658 LOG SET
11* W361-0016 GLOWING EMBERS
12* W550-0001 CHARCOAL EMBERS
13* W550-0002 CHARCOAL LUMPS
14 W135-0297 REAR LOG (#1)
15 W135-0300 LEFT CROSSOVER LOG (#4)
16 W135-0302 RIGHT CROSSOVER LOG (#6)
17 W135-0298 SMALL LEFT LOG (#2)
18 W135-0299 SMALL RIGHT LOG (#3)
19 W010-1819 BLACK DOOR C/W GLASS
20 W455-0026 #38 NATURAL GAS ORIFICE
20 W455-0003 #54 PROPANE GAS ORIFICE
21* W361-0014 VERMICULITE
22 W010-1778 ADJUSTABLE FIRESTOP
23* W500-0205 RESTRICTOR PLATE
24 W585-0138 VENT HEAT SHIELD, TOP PIECE
25 W655-0222 VENT HEAT SHIELD, BOTTOM PIECE
26 W185-0020 GRATE
** WARNING: THIS IS A FAST ACTING THERMOCOUPLE. IT IS AN INTEGRAL
SAFETY COMPONENT. REPLACE ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD.
The gas valve has
an interlock device
which will not allow
the pilot burner to be
lit until the thermocouple has cooled.
Allow approximately
60 seconds for the
thermocouple to
cool.
Pilot burning; no gas
to main burner; gas
knob is on 'HI'; wall
switch / thermostat
is on.
Pilot will not light.- check if pilot can be lit by a match
Pilot goes out while
standing; Main burner
is in 'OFF' position.
Flames are consistently too large or too
small. Carboning occurs.
Pilot fl ame is not large enough or
not engulfi ng the thermopile
Thermopile shorting- clean thermopile connection to the valve. Reconnect.
Remote wall switch wire is too
long; too much resistance in the
system.
Faulty thermostat or switch.
Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"
Vent is blocked
Vent is re-circulating
5" fl exible vent has become disconnected from fi replace.
System is not correctly purged.
Out of propane gas.- fi ll the tank.
Pilot fl ame is not large enough- turn up the pilot fl ame.
Pilot fl ame is not engulfi ng the
thermocouple.
Thermocouple shorting / faulty.
Faulty valve.
Thermostat or switch is defective.
Wall switch wiring is defective.
Main burner orifi ce is plugged.- remove stoppage in orifi ce.
Faulty valve.
No spark at pilot burner
Out of propane gas
Spark gap is incorrect
No gas at the pilot burner
Gas piping is undersized.- turn on all gas appliances and see if pilot fl ame fl utters, diminishes or extin-
Unit is over-fi red or under-fi red.
- turn up pilot fl ame.
- replace pilot assembly.
- replace thermopile / valve.
- shorten wire to correct length or wire gauge.
- replace.
- check for vent blockage.
- check joint seals and installation.
- re-attach to fi replace.
- purge the gas line with the glass door removed.
- gently twist the pilot head to improve the fl ame pattern around the thermocouple.
- loosen and tighten thermocouple.
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- replace.
- connect a jumper wire across the wall switch terminals; if main burner lights,
replace switch / thermostat.
- disconnect the switch wires & connect a jumper wire across terminals 1 & 3; if
the main burner lights, check the wires for defects and / or replace wires.
- replace.
- check that the wire is connected to the push button igniter.
- check if the push button igniter needs tightening.
- replace the wire if the wire insulation is broken or frayed.
- replace the electrode if the ceramic insulator is cracked or broken.
- replace the push button igniter.
- fi ll the tank.
- spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.) from the electrode
tip and the pilot burner. To ensure proper electrode location, tighten securing nut
(fi nger tight plus 1/4 turn).
- check that the manual valve is turned on.
- check the pilot orifi ce for blockage.
- replace the valve.
- call the gas distributor.
guishes, especially when main burner ignites. Monitor appliance supply working
pressure.
- check if supply piping size is to code. Correct all undersized piping.
- check pressure readings:
Inlet pressure can be checked by turning screw (A) counter-clockwise 2 or 3
turns and then placing pressure gauge tubing over the test point. Gauge should
read 7" (minimum 4.5") water column for natural gas or 13" (11" minimum) water
column for propane. Check that main burner is operating on "HI".
Outlet pressure can be checked the same as above using screw (B). Gauge
should read 3.5" water column for natural gas or 10" water column for propane.
Check that main burner is operating on "HI".
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOT OVERTORQUE.
Leak test with a soap and water solution.
W415-0381 / H / 12.07.07
28
SYMPTOMPROBLEMTEST SOLUTION
Flames are very aggressive.
Main burner fl ame is
a blue, lazy, transparent fl ame.
Carbon is being deposited on glass, logs
or combustion chamber surfaces.
White / grey film
forms.
Remote wall switch is
in "OFF" position; main
burner comes on when
gas knob is turned to
"ON" position.
Door is ajar
Venting action is too great.-restrict vent exit with restrictor plate, W500-0205.
Blockage in vent.
Incorrect installation.
Air shutter has become blocked
Flame is impinging on the logs
or combustion chamber.
Sulphur from fuel is being deposited on glass, logs or combustion
chamber surfaces.
Wall switch is mounted upside
down
Remote wall switch is grounding.
grounding.
Faulty valve.
- fi t door assembly into the lower support brackets and secure the four door
latches.
- remove blockage. In extremely cold conditions, ice buildup may occur on the
terminal and should be removed as required.
- refer to Figure 23 to ensure correct location of storm collars.
- ensure air shutter opening is free of lint or other obstructions.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifi ce size as specifi ed
by the rating plate values.
- check that the door gasketing is not broken or missing and that the seal is
tight.
- check that both 5" and 8" vent liners are free of holes and well sealed at all
joints.
- check that minimum rise per foot has been adhered to for any horizontal
venting.
- clean the glass with a recommended gas fi replace glass cleaner. DO NOT
CLEAN GLASS WHEN HOT.
If deposits are not cleaned off regularly, the glass may become permanently
marked.
- reverse.
- replace.
- check for ground (short); repair ground or replace wire.Remote wall switch wire is
- replace.
W415-0381 / H / 12.07.07
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.