Napoleon BGD90NT, BGD90PT Operating Instructions Manual

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22, ANSI Z21.50 FOR VENTED GAS FIREPLACES.
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
!
WARNING
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
BGD90NT
NATURAL GAS
BGD90PT
PROPANE
1
- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH, in Canada.
This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
!
WARNING
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
$10.00
1.28A
W415-0826 / C / 07.11.11
2
TABLE OF CONTENTS
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
3.0 VENTING 8
4.0 INSTALLATION 16
5.0 FRAMING 22
6.0 ELECTRICAL CONNECTION 28
7.0 FINISHING 30
8.0 REMOTE AND VALVE ACCESS 36
9.0 OPERATION 38
10.0 OPERATING INSTRUCTIONS 42
11.0 ADJUSTMENTS 43
12.0 MAINTENANCE 45
13.0 REPLACEMENTS 47
14.0 TROUBLE SHOOTING 51
15.0 WARRANTY 54
16.0 SERVICE HISTORY 55
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 5
2.3 GENERAL INFORMATION 6
2.4 RATING PLATE INFORMATION 7
3.1 VENTING LENGTHS AND COMPONENTS 8
3.2 TYPICAL VENT INSTALLATION 9
3.3 VENT TERMINAL CLEARANCES 10
3.4 VENTING APPLICATION FLOW CHART 11
3.5 DEFINITIONS 11
3.6 ELBOW VENT LENGTH VALUES 11
3.7 TOP EXIT HORIZONTAL TERMINATION 12
3.8 TOP EXIT VERTICAL TERMINATION 14
4.1 WALL AND CEILING PROTECTION 16
4.1.1 HORIZONTAL INSTALLATION 17
4.1.2 VERTICAL INSTALLATION 17
4.2 USING FLEXIBLE VENT COMPONENTS 18
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 18
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 19
4.2.3 APPLIANCE VENT CONNECTION 20
4.3 MOBILE HOME INSTALLATION 20
4.4 GAS INSTALLATION 21
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES 24
5.2 MINIMUM ENCLOSURE CLEARANCES 26
5.3 MINIMUM MANTEL CLEARANCES 27
6.1 RECEPTACLE WIRING DIAGRAM 29
6.2 OPTIONAL BLOWER INSTALLATION 29
7.1 DOOR REMOVAL 30
7.2 LOG SHIPPING BRACKET 32
7.3 BRICK PANEL INSTALLATION 32
7.4 ANDIRON PLACEMENT 33
7.5 LOG PLACEMENT 34
7.6 CHARCOAL EMBERS 35
7.7 VERMICULITE 35
7.8 GLOWING EMBERS 35
8.1 INNER ACCESS PANEL 36
8.2 BULKHEAD ACCESS PLATE 36
8.3 REMOTE RECEIVER REMOVAL 36
8.4 CONTROL MODULE REMOVAL 37
8.5 VALVE REMOVAL 37
8.6 “AUTO SPARK” BATTERY REMOVAL 37
9.1 GENERAL TRANSMITTER LAYOUT 38
9.2 APPLIANCE OPERATION 38
9.3 HAND HELD REMOTE OPERATIONS 38
9.4 TEMPERATURE DISPLAY 39
9.5 ROOM THERMOSTAT 39
9.6 SMART THERMOSTAT 39
9.7 FLAME HEIGHT 39
9.8 FAN SPEED 40
9.9 CHILD PROOF FUNCTION 40
9.10 NIGHT LIGHTS
9.11 LOW BATTERY / MANUAL BYPASS 40
9.12 IN THE EVENT OF A POWER FAILURE 41
9.13 CONTROL MODULE 41
9.14 TIMED BLOWER 41
11.1 PILOT BURNER ADJUSTMENT 43
11.2 VENTURI ADJUSTMENT 43
11.3 FLAME CHARACTERISTICS 44
11.4 RESTRICTING VERTICAL VENTS 44
12.1 CARE OF GLASS 45
12.2 GLASS / DOOR REPLACEMENT 46
12.3 NIGHT LIGHTTM REPLACEMENT 46
TM 40
W415-0826 / B / 07.11.11
1.0 INSTALLATION OVERVIEW
See the section “FRAMING” for Non-combustible material
See the section “MINIMUM MANTEL CLEARANCES”
See the section “FRAMING” and “MINIMUM ENCLOSURE CLEARANCES” for Drywall (or other combus­tible material)
3
See the section “VENTING” and “INSTALLATION”
See the section
“FRAMING”
See the section “FRAMING”
Side Wall
Rating plate, see “RATING PLATE INFORMATION” section.
W415-0826 / C / 07.11.11
4
2.0 INTRODUCTION
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES TO THIS APPLIANCE OR IT’S CONTROLS CAN BE DANGEROUS AND IS PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated
temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic components.
This appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
!
WARNING
Toddlers,
3.1C
W415-0826 / B / 07.11.11
2.1 DIMENSIONS
2.2 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
6"
!
WARNING
5
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUA TE VENTILA TION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” FROM THE
FRONT FACE OF THE UNIT.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of a appliance insert or gas log.
The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
W415-0826 / C / 07.11.11
6
A
A
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
www.ncertied.org
s long as the required clearance to combustibles is maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
NOTE: Non-combustible fi nishing material (i.e. Cement board, brick, stone, tile) must be used to fi nish the front of the appliance.
We suggest that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1A
2.3 GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
NG LP
Altitude (FT) 0-4,500 0-4,500
Max. Input (BTU/HR) 50,000 50,000
Max. Output Steady State (BTU/HR) 33,540 34,000
Effi ciency (w/the fan on) 63% 61%
Min. Inlet Gas Supply Pressure 4.5" Water Column 11" Water Column
Max. Inlet Gas Supply Pressure 7" Water Column 13" Water Column
Manifold Pressure (Under Flow Conditions) 3.5" Water Column 10" Water Column
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is certifi ed for mobile home installation. The natural gas model can only be installed in a mobile home that is permanently positioned on its site and fueled with natural gas.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convert­ible for use with other gases, unless kit is used. Not external electricity (110 volts or 24 volts) is required for the gas system operation.
Expansion / contraction noised during heating up and cooling down cycles are normal and are to be expected. Change in fl ame appearance from “HI” to “LO” is more evident in natural gas than in propane.
W415-0826 / B / 07.11.11
2.4 RATING PLATE INFORMATION
/ APPAREIL DE CHAUFFAGE ALIM
ON IF INSTALLED IN ACCORDANCE WITH
IS US STANDARD IS NOT APPLICA
PLATE AND MAY BE INSTAL
ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DAN
UR AU CANADA OU AUX ÉTATS-UNIS DE LA NORME D
APPLIQUÉE, SE RÉFÉRER A LA NORME RELATIVE
501A.
ADA
DE / ÉLÉVAT
T / ALIMENTA TION
INPUT / ALIMENTA TION RÉDUIT
EAU
(0-137
NG THE APPROPRIATE
TS. SEE OWNERS INSTALLATION MANUAL
G SPECIFICS. PROPER REINSTALLATION
NECESSARY AFTER SERVICING THE VENT
KE SY
SERIAL NUMBER/NO.
90PT
MANIFOLD PRESSURE /
PRESSION AU COLLECTEUR
MINIMUM SUPPLY PRESSURE /
SSION D'ALIMENTATION MINIMALE
AXIMUM SUPPLY PRESS
PRESSION D'ALIMENTATION MA
PROPANE MOD
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.33-2009, ANSI 21.88-2009 VENTED GAS FIREPLACE HEATER / APPAREIL DE CHAUFFAGE ALIMENTÉ AU GAZ ET VENTILÉ
GAS FIRE VENTED DECORATIVE APPLIANCE. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. CERTIFIED FOR MOBILE HOME INST ALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE (S) OF GAS INDICATED ON THE RATING PLATE AND MAY BE INSTALLED IN AN AFTER MARKET, PERMANENTLY LOCATED, MANUFACTURED HOME OR MOBILE HOME, WHERE NOT PROHIBITED BY LOCAL CODES. FOYER DE CHAUFFAGE AU GAZ AVEC ÉVACUATION. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI
9700539 (WSL) 4001657 (NGZ) 4001658 (NAC) 4001659 (WUSA)
VENTED GAS FIREPLACE NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY. WARNING:
THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS:
TOP 0 RECESSED DEPTH 29 1/2" FLOOR 0 VENT 2" SIDES 0 MANTEL 4" * BACK 0 TOP, SIDES & BACK: PER STAND OFF SPACERS FOR FRAMING MATERIALS. FOR FINISHING MATERIALS SEE OWNERS MANUAL * MAXIMUM HORIZONTAL EXTENSION. SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS. SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS. ELECTRICAL RATING: 115V 0.82AMP, 60HZ
WOLF STEEL LTD.
24 NAPOLEON ROAD. BARRIE, ONTARIO L4M 0G8 CANADA
SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE MAISONS MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA OU AUX ÉT ATS-UNIS DE LA NORME DE SECURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE APPLIQUÉE, SE RÉFÉRER A LA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A.
NATURAL MODELS PROPANE MODELS
DO NOT ADD ANY MATERIAL TO
GD90NT
3.5" WATER COLUMN/D'UNE COLONNE D'EAU
4.5" WATER COLUMN/D'UNE COLONNE D'EAU
7.0" WATER COLUMN/D'UNE COLONNE D'EAU
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE
WOLF STEEL VENT KITS. SEE OWNERS INSTALLATION MANUAL
FOR VENTING SPECIFICS. PROPER REINSTALLATION AND
RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR
BGD90NT
0-4500FT (0-1370M)
50, 000 BTU/H 37, 000 BTU/H
SERIAL NUMBER/NO. DE SÉRIE: GD/BGD90
ALTITUDE / ÉLÉVATION INPUT / ALIMENTA TION
REDUCED INPUT / ALIMENTA TION RÉDUITE
MANIFOLD PRESSURE /
PRESSION AU COLLECTEUR
MINIMUM SUPPLY PRESSURE /
PRESSION D'ALIMENTATION MINIMALE
MAXIMUM SUPPLY PRESSURE /
PRESSION D'ALIMENTATION MAXIMALE
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'ÉVACUATION PROPRE A WOLF STEEL. RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR L'ÉVACUATION PRÉCISE. IL EST IMPORTANT DE BIEN RÉINSTALLER ET
INTAKE SYSTEM.
RESCELLER L'ÉVENT APRÈS AVOIR ASSURÉ LE MAINTIEN DU SYSTÉME DE PRISE D'AIR.
BGD90PT
0-4500FT (0-1370M) 50, 000 BTU/H 37, 000 BTH/H
10" WATER COLUMN/D'UNE COLONNE D'EAU
11" WA TER COLUMN/D'UNE COLONNE D'EAU
13" WATER COLUMN/ D'UNE COLONNE D'EAU
GD90PT
UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRÉ UTILISÉ AVEC CET APPAREIL. UTILISER AVEC LES PORTES VITRÉES HOMOLOGUÉES SEULEMENT AVEC CETTE UNITÉ.
AVERTISSEMENT:
APPAREIL AUCUN MATÉRIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
DÉGAGEMENTS MINIMAUX DES MATÉRIAUX COMBUSTIBLES:
DESSUS 0 PROFONDEUR D'ENCASTRÉ 29 1/2" PLANCHER 0 ÉVENT 2" CÔTES 0 MANTEAU 4" * ARRIÉRE 0 DESSUS, COTÉS & ARRIÈRE: SELON LES ESPACEURS DE DÉGAGEMENT POUR LES MATÉRIAUX D'OSSATURE SELON LE MANUEL DE PROPRIÉTAIRE POUR LES MATÉRIAUX DE FINITION. * L'EXTENSION HORIZONTALE MAXIMALE: 2". RÉFÉRER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES. RÉFÉRER AU MANUEL D'INSTALLA TION DE PROPRIÉTAIRE. CLASSIFICATION: 115V 0.82AMP, 60HZ
N'AJOUTEZ PAS A CET
W385-0345 / F
7
W415-0826 / C / 07.11.11
8
3.0 VENTING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
For safe and proper operation of the fi replace follow the venting instruction exactly. Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for visually checking the vent connection to the fi replace after the fi replace is installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
!
WARNING
This fi replaces uses 8” exhaust / 10” air intake vent pipe system.
Refer to the section applicable to your installation.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial installation.
3.1 VENTING LENGTHS AND COMPONENTS
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the replace fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel fl exible components with the
following termination kits: wall terminal kit GD622R, or 1/12 to 7/12 pitch roof terminal kit GD610, 8/12 to 12/12 roof terminal kit GD611 or fl at roof terminal kit GD612. With fl exible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD620 or the 10 foot vent kit GD630.
For optimum fl ame appearance and fi replace performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.
The minimum allowable vertical vent length is 3 feet maximum allowable vertical vent length is 40 feet. The maximum number of allowable 8” vent connections is three horizontally or vertically (excluding the fi replace and the air terminal connections).
When venting, the horizontal run must be kept to a minimum of 36“ or a maximum of 20 feet. If a 20 foot horizontal run is required, the fi replace must have a minimum vertical rise immediately off the fi replace of 57”. When terminating vertically, the vertical rise is a minimum 36“ and a maximum 40 feet above the fi replace.
7.3A
For optimum performance, it is recommended that all horizontal runs have a minimum 1/4” rise per foot. Provide a means for visually checking the vent connection to the fi replace after the fi replace is installed. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 3/4” air gap between the inner and outer liner all around is required for safe operation. Use a fi restop when penetrating interior walls, fl oor or ceiling.
W415-0826 / B / 07.11.11
8.4
3.2 TYPICAL VENT INSTALLATION
9
16” MINIMUM
16 1/4”
MINIMUM
70 1/4”
24” MAXIMUM
3 FEET
MINIMUM
40 FEET
MAXIMUM
86 1/2”
MINIMUM
PLUS RISE*
70 1/4”
* See “VENTING” section
W415-0826 / C / 07.11.11
10
3.3 VENT TERMINAL CLEARANCES
COVERED BALCONY APPLICATIONS
Q
M
R
G
P
Q
R
R
MIN
MAX
MAX
= 3 feet
= 2 x
Q
 feet
ACTUAL
INSTALLATIONS
CANADA U.S.A. A 12” 12” Clearance above grade, veranda porch, deck or balcony. B 12”
Δ
9”
Δ
Clearance to windows or doors that open.
C 12” * 12” * Clearance to permanently closed windows.
D 18” ** 18” **
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ from the centerline of the terminal.
E 12” ** 12” ** Clearance to unventilated sof t.
F 0” 0” Clearance to an outside corner wall.
G
H 3’ 3’ ****
0” *** 0” *** Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” *** 2” *** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum vertical distance of 15’.
I 3’ 3’ **** Clearance to a service regulator vent outlet.
J 12” 9” Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K 6’ 3’ Clearance to a mechanical air supply inlet.
L 7’ ‡ 7’ **** Clearance above a paved sidewalk or paved driveway located on public property. M 12” †† 12” **** Clearance under a veranda, porch, deck or balcony. N 16” 16” Clearance above the roof. O 2’ †* 2’ †* Clearance from an adjacent wall including neighbouring buildings.
P 8’ 8’ Roof must be non-combustible without openings. Q 3’ 3’ See chart for wider wall dimensions.
R 6’ 6’
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18” clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an open­ing between the terminal and the open side of the structure.
12.3B
W415-0826 / B / 07.11.11
3.4 VENTING APPLICATION FLOW CHART
11
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3.5 DEFINITIONS
For the following symbols used in the venting calculations and examples are: > - greater than > - equal to or greater than < - less than < - equal to or less than HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet HR - combined horizontal vent lengths in feet HO - offset factor: .03 (total degrees of offset - 90°*) in feet VT - combined vertical vent lengths in feet
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet
4.2 times the
vertical rise equal to
or greater than the
horizontal run
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3 times the vertical
rise equal to or
greater than the
horizontal run
13.1
14.1
3.6 ELBOW VENT LENGTH VALUES
FEET INCHES
1° 0.03 0.5 15° 0.45 6.0 30° 0.9 11.0 45° 1.35 16.0 90°* 2.7 32.0
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
15.1
W415-0826 / C / 07.11.11
12
3.7 TOP EXIT HORIZONTAL TERMINATION
(HT) < (VT)
Simple venting confi guration (only one 90° elbow)
See graph to determine the required vertical
rise VT for the required horizontal run HT.
40
39
30
REQUIRED
VERTICAL
20
RISE IN
FEET VT
10
0
2.5 5 7.5 10 12.5 15
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET H
T
The shaded area within the lines represents
acceptable values for HT and V
For vent confi gurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet
Example: V
= 3 FT
1
V
= 8 FT
2
VT = V1 + V H
= 2.5 FT
1
H
= 2 FT
2
HR = H1 + H H
= .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT
O
= 3 FT + 8 FT = 11 FT
2
= 2.5 + 2 = 4.5 FT
2
HT = HR + HO = 4.5 + 5.4 = 9.9 FT HT + V
= 9.9 + 11 = 20.9 FT
T
90°
90°
90°
V
2
H
1
17.5 20
T
H
2
Formula 1: HT < V
T
9.9 < 11 Formula 2: HT + VT < 40 FT
20.9 < 40
Since both formulas are met, this vent confi guration is acceptable.
W415-0826 / B / 07.11.11
V
1
16.1A
13
V
V V V
(HT) > (VT)
Simple venting configuration (only one 90° elbow)
REQUIRED
See graph to determine the required vertical rise VT for the
required horizontal run H
150
147”
100
.
T
VERTICAL
RISE IN
INCHES V
T
57”
50
19 1/2”
0
515
2’
10
12.5’
19.5’
20
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring more than one 90° elbow, the following formulas apply:
< 4.2 V
Formula 1: Formula 2: HT + V
H
T
T
< 24.75 feet
T
90°
H
1
H
2
Example:
= VT = 6 FT
1
H
= 3 FT
1
H
= 5 FT
2
H
= H
+ H
R
H
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7 FT
O
H
= H
T
H
+ V
T
= 3 + 5 = 8 FT
1
2
+ H
= 8 + 2.7 = 10.7 FT
R
O
= 10.7 + 6 = 16.7 FT
T
V
1
90°
Formula 1: HT < 4.2 V
4.2 VT = 4.2 x 6 = 25.2 FT
10.7 < 25.2
Formula 2: HT + V
16.7 < 24.75
Since both formulas are met, this vent configuration is acceptable.
Example:
= 4 FT
1
= 1.5 FT
2
= V
+ V
T
H
= 2 FT
1
H
= 1 FT
2
H
= 1 FT
3
H
= 1.5 FT
4
H
= H
R
H
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT
O
H
= H
T
H
+ V
T
= 4 + 1.5 = 5.5 FT
1
2
+ H2 + H
1
+ H
R
= 13.6 + 5.5 = 19.1 FT
T
+ H4 = 2 + 1 + 1 + 1.5 = 5.5 FT
3
= 5.5 + 8.1 = 13.6 FT
O
Formula 1: HT < 4.2 V
4.2 VT = 4.2 x 5.5 = 23.1 FT
T
< 24.75 FT
T
T
90°
90°
90°
H
1
90°
V
1
V
H
H
2
3
H
4
2
13.6 < 23.1 Formula 2: HT + V
19.1 < 24.75
< 24.75 FT
T
Since both formulas are met, this vent configuration is acceptable.
16.1_2
W415-0826 / C / 07.11.11
14
3.8 TOP EXIT VERTICAL TERMINATION
(HT) < (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run HT.
40
30
REQUIRED
VERTICAL
20
RISE IN FEET V
T
10
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring one or more 90° elbows the following formulas apply: Formula 1: H
Formula 2: HT + V
< V
T
T
< 40 feet
T
for the
T
T
Example: V
= 5 FT
1
V
= 6 FT
2
V
= 10 FT
3
V
= V
+ V2 + V3 = 5 + 6 + 10 = 21 FT
T
1
H
= 8 FT
1
H
= 2.5 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
T
H
+ V
T
Formula 1: HT < V
18.6 < 21 Formula 2: HT + V
39.6 < 40
= 8 + 2.5 = 10.5 FT
1
2
+ H
= 10.5 + 8.1 = 18.6 FT
R
O
= 18.6 + 21 = 39.6 FT
T
T
< 40 FT
T
Since both formulas are met, this vent configuration is acceptable.
V
90°
1
90°
V
3
H
2
V
H
1
2
90°
90°
W415-0826 / B / 07.11.11
15
(HT) > (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run H
20
19
REQUIRED
VERTICAL
RISE IN
FEET V
10
T
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for HT and VT
For vent configurations requiring more than two 90° elbows the following formulas apply: Formula 1: H
Formula 2: HT + V
< 3V
T
T
< 40 feet
T
Example: V
= 2 FT
1
V
= 1 FT
2
V
= 1.5 FT
3
V
= V
+ V2 + V3 = 2 + 1 + 1.5 = 4.5 FT
T
1
H
= 6 FT
1
H
= 2 FT
2
H
= H
+ H
R
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
T
H
+ V
T
= 6 + 2 = 8 FT
1
2
+ H
= 8 + 8.1 = 16.1 FT
R
O
= 16.1 + 4.5 = 20.6 FT
T
90°
H
V
1
1
90°
for the
.
T
H
V
2
T
25 30
V
2
T
3
90°
90°
Formula 1: HT < 3V 3VT = 3 x 4.5 = 13.5 FT
T
16.1 > 13.5 Since this formula is not met, this vent configuration is unacceptable. Formula 2: HT + VT < 40 feet
20.6 < 40
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration will need to be established to satisfy both formulas.
18.1_2A
W415-0826 / C / 07.11.11
16
4.0 INSTALLATION
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
!
WARNING
EXACTLY.
WHICH MUST BE SEALED USING MILL PAC.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
68.2A
WARNING
70.1
W415-0826 / B / 07.11.11
4.1.1 HORIZONTAL INSTALLATION
A
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall as illustrated to accommodate the fi restop assembly. Dry fi t the fi restop assembly before proceeding to ensure the brackets on the rear surface fi t to the inside surface of the horizontal framing.
The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2” thick but the vent shield must extend the full depth of the combustible wall.
. Apply a bead of caulking (not supplied) around the corner edge of the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your manual baggie).
!
WARNING
CAULKING
FIRESTOP
SPACER
17
VENT
SHIELD
DETERMINE THE CORRECT HEIGHT
FINISHING MATERIAL
B. Once the vent pipe is installed in its fi nal position, apply high temperature sealant W573-0007 (not supplied) between the pipe and the fi restop.
20.2
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for various roof pitches are available from your authorized dealer / distributor. See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1“ clearance between the vent pipe and any combustible material. Try to center the vent pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings. A vent pipe shield will prevent any materials such as insulation, from fi lling up the 1” air space around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a fi nished ceiling), and secure over the opening in the ceiling. A fi restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a fi restop spacer over the vent shield to restrict cold air from being drawn into the room or around the replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply sealant between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1” air space around the pipe.
14 1/2" 14 1/2"
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
21.1
CAULKING
VENT
PIPE
SHIELD
VENT
PIPE
COLLAR
W415-0826 / C / 07.11.11