CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACES HEATERS.
BGD40-N
NATURAL GAS
1
BGD40-P
PROPANE
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
SAFETY INFORMATION
!
WARNING
If the information in these instructions are
not followed exactly, a fi re or explosion
may result causing property damage,
personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 4Y8 Canada /
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-0811 / A / 04.28.10
Page 3
1.0 INSTALLATION OVERVIEW
Venting, see “VENTING”
section.
3
Top, see “COUNTER TOP / BAR
INSTALLATION” section.
Bricks, see “BASE
BRICK PANEL
INSTALLATION” section.
Louvre, see “LOUVRE
INSTALLATION” section.
Rating plate, see “RATING
PLATE INFORMATION”
section.
Door, see ”DOOR INSTALLATION”
section.
Door, see ”END DOOR
INSTALLATION” section.
W415-0811 / A / 04.28.10
Page 4
4
2.0 INTRODUCTION
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate
appliance according to operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal
edges may be sharp.
• Do not burn wood or other materials in this appliance.
• Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is
recommended if there are at risk individuals in the house. To restrict access to an appliance or stove,
install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the
room and away from hot surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and
draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot
surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children
from hot surfaces. These screens and guards must be fastened to the fl oor.
• Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the
appliance and venting system are kept clean. The appliance and its venting system should be inspected
before use and at least annually by a qualifi ed service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and
free from combustible materials, gasoline and other fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appli-
ance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service techni-
cian to inspect the appliance and to replace any part of the control system and any gas control which
has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person.
• Do not strike or slam shut the appliance glass door.
• This appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
• Pressure relief doors must be kept closed while the appliance is operating to prevent exhaust fumes
containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping
through these openings can also cause the surrounding combustible materials to overheat and catch
fi re.
• Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As
with all plastic bags, these are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your
family against Carbon Monoxide.
!
WARNING
3.1
W415-0811 / A / 04.28.10
Page 5
2.1 DIMENSIONS
2.1.1 PENINSULA
5
38"
1
32
/2"
2.1.2 OPEN-END
38"
1
/2"
32
37
38
36"
5
5" DIA.
8" DIA.
221/8"
GAS
1
6
/2"
1
/4"
4
5
/8"
2 1/2"
/8"
5" DIA.
8" DIA.
INLET
ELECTRICAL
INLET
221/8"
221/8"
GAS
6 1/2"
1
4
/4"
INLET
2.1.3 SEE-THRU
38"
1
32
/2"
36"
37 5/8"
38 5/8"
36"
40
2 1/2"
ELECTRICAL
INLET
5" DIA.
8" DIA.
221/8"
25
221/8"
1
/8"
GAS
1
6
/2"
1
/4"
4
5
/8"
2 1/2"
INLET
221/8"
ELECTRICAL
INLET
W415-0811 / A / 04.28.10
Page 6
6
A
A
2.2 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” FROM THE
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING
GAS LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE
PRESSURE TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
!
WARNING
PROVIDE ADEQUA TE VENTILA TION.
FRONT FACE OF THE UNIT.
FIRE RISK. EXPLOSION HAZARD.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth
of Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of a appliance
insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches.
• A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed in
accordance with the current standard CAN/CSA Z240MH
Series, for gas equipped mobile homes, in Canada or
NSI Z223.1 and NFPA 54 in the United States.
s long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
W415-0811 / A / 04.28.10
Page 7
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
C
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
If the optional fan or blower is installed, the junction box must be electrically connected and grounded in
accordance with local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI/
NFPA 70 National Electrical code in the United States.
2.3 GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
Altitude (FT)0-4,5000-4500
Max. Input (BTU/HR)30,00030,000
Max. Output Steady State (BTU/HR)20,40020,400
Min. Inlet Gas Supply Pressure4.5" Water Column11" Water Column
Max. Inlet Gas Supply Pressure7" Water Column13" Water Column
Manifold Pressure (Under Flow Conditions)3.5" Water Column10" Water Column
7
4.1
APPLIANCE
NGLP
This appliance is approved for bathroom, bedroom and bed-sitting room
installations and is suitable for mobile home installation.
No external electricity (110 volts or 24 volts) is required for the gas system
operation. Expansion / contraction noises during heating up and cooling
down cycles are normal and are to be expected.
If utilizing one of Wolf Steel's trim or surround kits, follow the framing
instructions and the fi nishing instructions, for removal of the top extension.
NOTE: The protective wrap on plated parts is best removed when the assembly is at room temperature but this
can be improved if the assembly is warmed, using a hair dryer or similar heat source.
2.4 RATING PLATE INFORMATION
For rating plate
location, see
“INSTALLATION
OVERVIEW”
section.
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.3 3 - 2002, ANSI Z21.88-2002 VENTED GAS FIREPLACE HEATER / FOYER DE CHAUFFAGE AU GAZ AVEC EVAC UATION
DIRECT VENT GAS FIREPLACE. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTA L L ATION. SUITABLE FOR MOBILE HOME INSTALLA TION IF INSTALLED IN ACCORDANCE WITH THE
CURRENT ST A ND ARD C A N/ C S A Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATE S THE MANUFACTURED HOME CONTRUCTION AND S A FE T Y STANDARD,TITLE 24
CFR, PAR T 3280. WHEN THIS US ST ANDARD IS NOTAPPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTAL LA TIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
FOYER A GAZ VENTILE DIRECT. HOMOLOGUE POUR INST A L L ATION DANS UNE CHAMBRE A COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INST A L LATION DANS UNE MAISON MOBILE
SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/ C SA Z240MH SERIE D E MAISON S MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETA TS-UNIS DE LA NORME DE
SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ET ATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A L A NORME
RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INST ALLATIONS DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.
MODEL BGD40 - N
MODEL BCDV400 - N
MANIFOLD PRESSURE:
PRESSION AU COLLECTEUR:
MINIMUM SUPPLY PRESSURE:
PRESSION D'ALIMENTATION MINIMALE:
MAXIMUM SUPPLY PRESSURE:
PRESSION D'ALIMENTATION MAXIMAL:
NOT FOR USE WITH SOLID FUEL. FOR USE WITH COVERS AND
GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING:
DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT
WITH THE FLAMES, OTHER THAN THA T SUP PLIE D BYTHE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS /
DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES:
TOP, FLOOR, SIDES & BACK
DESSUS, PLANCHER, COTES & ARRIERE
VENT / EVENT1"
MANTLE HEIGHT / HAUTEUR DU MANTEAU5"
MAXIMUM HORIZONT AL EXT ENSION / L'EXT ENSIO N HORIZONT ALE MAXIMALE: 3". SEE INSTRUC-
*
TION MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES
EXTENSIONS PLUS GRANDES.
MINIMUM AND MAXIMUM HORIZONTAL VENT LENGTHS ARE 10 INCHES AND 20 FEET RESPECTIVELY. LES LONGUEURS HORIZONTALES MINIMALE ET MAXIMALE SONT 10 POUCES ET 20 PIEDS
RESPECTIVEMENT.
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET
APPAREIL. UTILISER AVEC LES COUVERTURES ET LES PORTES
VITREES HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT:
CONTACT AVEC LES FLAMMES AUTRE Q UE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE
FABRICANT.
THEAPPLIANCE MUST BE VENTED USING THEAPPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS
0
INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS
NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.
L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A WOLF
25¼"
STEEL. REFERER AU MANUEL D'INSTALL ATION DE PROPRIETAIRE POUR L'EV ACUATION PRECISE. IL
EST IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENTAPRES AVOIR ASSURE LE MAINTIEN
DU SYSTEME DE PRISE D'AIR.
*
ELECTRICAL RATING / CLASSIFICATION: 115V, 0.82AMP, 60HZ
OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: GZ-550KT
N'AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN
66.8%
BGD40
0-4500FT (0-1370m)
30,000 BTU/h
20,000 BTU/h
MANIFOLD PRESSURE:
MINIMUM SUPPLY PRESSURE:
MAXIMUM SUPPLY PRESSURE:
BGD40 / BCDV400
MODEL BGD40 - P
MODEL BCDV400 - P
10" D'UNE COLONNE D'EAU
11" D'UNE COLONNE D'EAU
13" D'UNE COLONNE D'EAU
10" WATER COLUMN
11" WATER COLUMN
13" WATER COLUMN
W385-0249
W415-0811 / A / 04.28.10
Page 8
8
3.0 VENTING
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 5” EXHAUST / 8” AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Vent lengths that pass
through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation wrapped in
a protective sleeve to minimize condensation. Provide a means for visually checking the vent connection to
the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when
penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
3.1 VENTING LENGTHS AND COMPONENTS
7.2
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab
venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and
air terminal locations for either system are set out in this manual and must be adhered to. For Simpson DuraVent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided
with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the
corresponding supplier:
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a
red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent
pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar
which must be sealed using the black high temperature sealant Mill Pac.
W415-0811 / A / 04.28.10
Page 9
9
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following
termination kits: wall terminal kit GD422-1, GD422R-1, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12 roof
terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With fl exible
venting, in conjunction with the various terminations, use either the 5 foot vent kit GD420 or the 10 foot vent kit GD430.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a
minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must
not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run
is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” rise per foot however for optimum performance it is recommended that all horizontal
runs have a minimum 1/4” rise per foot using fl exible venting. For safe and proper operation of the appliance, follow
the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family
dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” air gap
all around between the inner liner and outer liner is required for safe operation.
8.3
W415-0811 / A / 04.28.10
Page 10
10
3.2 TYPICAL VENT INSTALLATIONS
16" MIN
24" MAX
38" MIN
PLUS
RISE*
When venting, the horizontal run must be kept to
a maximum of 20 feet. If a 20 foot horizontal run
is required, the appliance must have a minimum
vertical rise immediately off the appliance of 57".
40 FT
MAX
34"
MIN
37 3/4"
When terminating vertically, the vertical rise is a
minimum 34" and a maximum 40 feet above the
appliance.
When installing with no vertical rise, ensure that the vent pipe does not slope downward.
* See "VENTING" section.
W415-0811 / A / 04.28.10
Page 11
3.3 SPECIAL VENT INSTALLATIONS
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum of 12” above grade. The maximum allowable vent length is 10’.
11
12" MIN
TO
GRADE
24" MIN REGARDLESS
OF HORIZONTAL VENT
LENGTH
37 3/4"
MIN
9.5
W415-0811 / A / 04.28.10
Page 12
12
3.4 VENT TERMINAL CLEARANCES
COVERED BALCONY APPLICATIONS
Q
M
R
G
P
Q
R
R
MIN
MAX
MAX
= 3 feet
= 2 x
Q
feet
ACTUAL
INSTALLATIONS
CANADAU.S.A.
A12”12”Clearance above grade, veranda porch, deck or balcony.
B12”
Δ
9”
Δ
Clearance to windows or doors that open.
C12” *12” *Clearance to permanently closed windows.
D18” **18” **
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ from
the centerline of the terminal.
E12” **12” **Clearance to unventilated soffi t.
F0”0”Clearance to an outside corner wall.
G
H3’3’ ****
0” ***0” ***Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” ***2” ***Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum
vertical distance of 15’.
I3’3’ ****Clearance to a service regulator vent outlet.
J12”9”Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K6’3’ †Clearance to a mechanical air supply inlet.
L7’ ‡7’ ****Clearance above a paved sidewalk or paved driveway located on public property.
M12” ††12” ****Clearance under a veranda, porch, deck or balcony.
N16”16”Clearance above the roof.
O2’ †*2’ †*Clearance from an adjacent wall including neighbouring buildings.
P8’8’Roof must be non-combustible without openings.
Q3’3’See chart for wider wall dimensions.
R6’6’
The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
Δ
*Recommended to prevent condensation on windows and thermal breakage
**it is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18 inches clearance from an inside corner.
****This is a recommended distance. For additional requirements check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
12.1A
W415-0811 / A / 04.28.10
Page 13
3.5 VENT APPLICATION FLOW CHART
13
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
HR - combined horizontal vent lengths in feet
HO - offset factor: .03 (total degrees of offset - 135°*) in feet
VT - combined vertical vent lengths in feet
* The fi rst 45° and 90°offset has a zero value and is shown in the formula as -45° and - 90° respectively or
-135° when combined.
15.2
W415-0811 / A / 04.28.10
Page 14
14
3.8 HORIZONTAL TERMINATION
(HT) < (VT)
Simple venting confi guration (only one 45° and 90° elbow)
See graph to determine the required vertical
rise VT for the required horizontal run H
40
39
REQUIRED
VERTICAL
RISE IN
FEET V
30
20
T
10
0
2.557.51012.515
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET H
T
The shaded area within the lines represents
acceptable values for HT and V
For vent confi gurations requiring more than one 45° elbow and 90° elbow, the following formulas apply:
Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet
Example 1:
V
= 8 FT
1
VT = V
H
= 8 FT
1
= 2.5 FT
1
H2 = 2 FT
HR = H1 + H
= 2.5 + 2 = 4.5 FT
2
90°
V
1
H
2
HO = .03 (one 45° elbow + two 90° elbows - 135°) = .03 (225 - 135°) = 2.7 FT
HT = HR + H
HT + V
T
= 4.5 + 2.7 = 7.2 FT
O
= 7.2 + 8 = 15.2 FT
45°
H
1
90°
.
T
17.520
T
Formula 1: HT < V
T
7.2 < 8
Formula 2: HT + VT < 40 FT
15.2 < 40
Since both formulas are met, this vent confi guration is acceptable.
W415-0811 / A / 04.28.10
16.5
Page 15
(HT) > (VT)
15
Simple venting confi guration (only one 45° and 90° elbow)
See graph to determine the required vertical
rise VT for the required horizontal run HT.
150
147”
REQUIRED
VERTICAL
100
RISE IN
INCHES V
T
57”
50
0
515
10
12.5’
HORIZONTAL VENT RUN PLUS
OFFSET IN FEET H
The shaded area within the lines represents
acceptable values for H
and V
T
For vent confi gurations requiring more than one 45° elbow and 90° elbow, the following formulas apply:
Formula 1: HT < 4.2 V
T
Formula 2: HT + VT < 24.75 feet
20
T
T
Example 2:
V
= 4 FT
1
V
= 1.5 FT
2
VT = V1 + V
H
= 2 FT
1
H
= 1 FT
2
H
= 1 FT
3
H
= 1.5 FT
4
HR = H1 + H2 + H3 + H
H
= .03 (one 45° elbow + four 90° elbows - 135°) = .03 (405 - 135°) = 8.1 FT
O
= 4 FT + 1.5 FT = 5.5 FT
2
= 2 + 1 + 1 + 1.5 = 5.5 FT
4
HT = HR + HO = 5.5 + 8.1 = 13.6 FT
H
+ V
= 13.6 + 5.5 = 19.1 FT
T
T
Formula 1: HT < 4.2 V
4.2 V
T
= 4.2 x 5.5 FT = 23.1 FT
T
13.6 < 23.1
Formula 2: H
+ VT < 24.75 FT
T
19.1 < 24.75
Since both formulas are met, this vent confi guration is acceptable.
90°
90°
90°
H
3
H
1
V
H
2
H
4
2
90°
V
1
45°
16.5_2
W415-0811 / A / 04.28.10
Page 16
16
3.9 VERTICAL TERMINATION
(HT) < (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run HT.
40
30
REQUIRED
VERTICAL
20
RISE IN
FEET V
T
10
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for H
and VT
T
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
Formula 1: H
Formula 2: HT + V
< V
T
T
< 40 feet
T
for the
T
T
Example 3:
V
= 5 FT
1
V
= 10 FT
2
V
= V
+ V
T
H
= 3 FT
1
H
= 2.5 FT
2
H
= H
R
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT
H
= H
T
H
+ V
T
Formula 1: H
10.9 < 15
Formula 2: HT + V
25.9 < 40
= 5 + 10 = 15 FT
1
2
+ H
= 3 + 2.5 = 5.5 FT
1
2
+ H
= 5.5 + 5.4 = 10.9 FT
R
O
= 10.9 + 15 = 25.9 FT
T
< V
T
T
< 40 FT
T
Since both formulas are met, this vent configuration is acceptable.
45°
V
2
90°
H
2
V
1
H
1
90°
18.3
90°
W415-0811 / A / 04.28.10
Page 17
17
(HT) > (VT)
Simple venting configurations.
See graph to determine the required vertical rise V
required horizontal run H
20
19
REQUIRED
VERTICAL
RISE IN
FEET V
10
T
3
0
5101520
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
values for H
and VT
T
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
Formula 1: H
Formula 2: HT + V
Example 4:
V
= 1 FT
1
V
= 1.5 FT
2
V
= V
T
1
H
= 6 FT
1
H
= 2 FT
2
H
= H
R
1
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT
H
= H
T
R
H
+ V
T
T
< 3V
T
T
< 40 feet
T
+ V
= 1 + 1.5 = 2.5 FT
2
+ H
= 6 + 2 = 8 FT
2
+ H
= 8 + 5.4 = 13.4 FT
O
= 13.4 + 2.5 = 15.9 FT
45°
H
1
90°
V
.
T
1
90°
for the
T
2530
H
2
T
V
2
90°
Formula 1: HT < 3V
3VT = 3 x 2.5 = 7.5 FT
T
13.4 > 7.5
Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + V
15.9 < 40
< 40 FT
T
Since only formula 2 is met, this vent configuration in unacceptable and a new fireplace location or vent configuration
will need to be established to satisfy both formulas.
90°
Example 5:
= 1.5 FT
V
1
V
= 8 FT
2
V
= V
+ V
T
H
= 1 FT
1
H
= 1 FT
2
= 10.75 FT
H
3
H
= H
R
H
= .03 (three 90° elbows + two 45° elbows - 135°)
O
= .03 (270 + 90 - 135°) = 6.75 FT
H
= H
T
+ V
H
T
Formula 1: H
3VT = 3 x 9.5 = 28.5 FT
= 1.5 + 8 = 9.5 FT
1
2
+ H2 + H3 = 1 + 1 + 10.75 = 12.75 FT
1
+ H
= 12.75 + 6.75 = 19.5 FT
R
O
= 19.5 + 9.5 = 29 FT
T
< 3V
T
T
45°
H
1
V
1
90°
H
2
H
3
45°
19.5 < 28.5
Formula 2: HT + V
29 < 40
< 40 FT
T
Since both formulas are met, this vent configuration is acceptable.
18.3_2
W415-0811 / A / 04.28.10
V
2
90°
Page 18
18
4.0 PENINSULA INSTALLATION
4.1 VENTING
Refer to "VENTING" section. All venting must have a minimum clearance of 2" to combustible material on the
top and 1" to the sides and bottom.
4.2 FRAMING
!
WARNING
RISK OF FIRE!
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE APPLI-
ANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH ANY
OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO COMBUSTIBLES IS
MAINTAINED WITHIN THE CAVITY.
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN AIR
SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH SAGGING
OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK OPENING
INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE INSULATION AND
OTHER MATERIALS ARE SECURED.
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO MAIN-
TAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS LISTED
MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS CONSISTING
ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS, OR ANY COM-
BINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING ASTM E 136,
STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE FURNACE AT
750°C AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
BASE.
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, THEY MUST BE INSTALLED.
71.1
It is best to frame your appliance after it is positioned and the vent
system is installed. Use 2x4's and frame to local building codes.
To install the appliance face fl ush with the fi nished wall, position
the framework to accommodate the thickness of the fi nished wall.
A = 22 1/8" minus fi nishing material thickness each side.
2 1/2”
6 1/8”
38 5/8”
A
THE UNIT IS
NOT LOAD
BEARING
38 1/4”
22 1/8”
W415-0811 / A / 04.28.10
Page 19
19
Care should be taken to maintain suffi cient clearance for
the vent installation. A horizontal vent installation requires
a minimum height of 45" using fl exible vent pipe, to the
underside of the enclosure top including the 2" clearance
to combustibles
4.3 COUNTER TOP / BAR INSTALLATION
When fi nishing the appliance, combustible material
may rest directly on the top extension.
NOTE: Maximum weight tolerance is 400 lbs,
provided that it is evenly distributed across the
top extensions of the appliance.
2" CLEARANCE TO COMBUSTIBLES
7"
45"
MINIMUM
20" MINIMUM INSIDE DIMENSION
7"
In order to achieve a counter top or bar type
appearance with the minimum height allowed,
framing must be non-combustible and may be done
with metal studding attached to the top extension
sides or the upper frame of the appliance.
* The top extension may be removed if noncombustible framing is faced with a non-combustible
material placed fl ush with the front face of the
appliance and extending from the top of the
appliance. (Example: cement board - not supplied).
Combustible counter / bar tops must maintain a
minimum of 38" from the base of the appliance to the
underside of the top.
NOTE: Wolf Steel trim and/or surround kits
will not totally cover the top extension of the
appliance. In order to obtain a smooth transition
from the trim / surround to the wall, it is
recommended that the top extension be removed
and the appliance be installed following the
above procedure.
W415-0811 / A / 04.28.10
Page 20
20
4.4 BRICK PANEL INSTALLATION
Install the base panels as illustrated. The side panel sits under the bracket tab. Holding the side panel in
position, bend down the tab to secure.
STEP 4
STEP 3STEP 2STEP 1
RETAINER
STEP 5
4.5 FACING
Combustible materials may be installed fl ush with the
front of the appliance but must not cover any of the black
face-areas of the appliance. Non-combustible material
(brick, stone or ceramic tile) may protrude in these areas.
It is not necessary to install a hearth extension with this
appliance.
When roughing in the appliance, raise the appliance
to accommodate for the thickness of the fi nished fl oor
materials, (tile, carpeting, hard wood) which if not planned
for will interfere with the opening of the lower access
door and the installation of many decorative fl ashing
accessories.
Objects placed in front of the appliance should be kept a
minimum of 48" away from the glass front face.
4.6 FINISHING
Refer to "FINISHING" section for complete instructions regarding mantel requirements and installations, log
placement, glass door and upper and lower louvre attachments.
DETAIL 5
DRYWALL
5" MIN
DRYWALL
W415-0811 / A / 04.28.10
Page 21
5.0 OPEN-END INSTALLATION
5.1 VENTING
Refer to "VENTING" section. All venting must have a minimum clearance of 2" to combustible material on the
top and 1" to the sides and bottom.
5.2 FRAMING
!
WARNING
RISK OF FIRE!
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE APPLI-
ANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH ANY
OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO COMBUSTIBLES IS
MAINTAINED WITHIN THE CAVITY.
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN AIR
SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH SAGGING
OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK OPENING
INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE INSULATION AND
OTHER MATERIALS ARE SECURED.
21
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO MAIN-
TAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS LISTED
MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS CONSISTING
ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS, OR ANY COM-
BINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING ASTM E 136,
STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE FURNACE AT
750°C AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
BASE.
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, THEY MUST BE INSTALLED.
71.1
It is best to frame your appliance after it is positioned and the
vent system is installed. Use 2x4's and frame to local building
codes.
NOTE: The one side stud must be steel.
LEFT CORNER Appliance ILLUSTRATED
To install the appliance face fl ush with the fi nished wall,
position the framework to accommodate the thickness of
the fi nished wall.
STEEL
STUD
2 1/2”
6 1/2”
A
38 5/8”
38 1/4”
THE UNIT IS NOT
LOAD BEARING
A = 25 1/8" minus fi nishing material thickness
each side.
W415-0811 / A / 04.28.10
Page 22
22
5.3 BRICK PANEL INSTALLATION
Install the base panels as illustrated in steps 1-4, see "PENINSULA
INSTALLATION PROCEDURE" section. The side panel sits under the
bracket tab. Holding the side panel in position, bend down the tab to
secure. DETAIL 6.
STEP 5
RETAINER
5.4 FACING
Combustible materials may be installed fl ush with the front of the appliance but must not cover any of the black
face-areas of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in these
areas.
It is not necessary to install a hearth extension with this appliance.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the fi nished fl oor
materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower
access door and the installation of many decorative fl ashing accessories.
Objects placed in front of the appliance should be kept a minimum of 48" away from the glass front faces.
5.5 FINISHING
FINISHING MUST BE DONE USING A NON-COMBUSTIBLE MATERIAL PLACED FLUSH WITH THE
FRONT FACE OF THE APPLIANCE AND EXTENDING FROM THE TOP OF THE APPLIANCE SUCH AS
CEMENT BOARD, CERAMIC TILE, MARBLE, ETC. WHEN FINISHING TO THE APPLIANCE. DO NOT
USE WOOD OR DRYWALL. ANY FIRE RATED DRYWALL IS NOT ACCEPTABLE.
Refer to "FINISHING" section for complete instructions
regarding mantel requirements and installations, log
placement, glass door and upper and lower louvre
attachments. A minimum of 3" of cement board or noncombustible equivalent must be installed against the side
edge of the appliance.
DETAIL 6
!
WARNING
STEP 6
DRYWALL
DRYWALL
W415-0811 / A / 04.28.10
NONCOMBUSTIBLE
3"
5"
MIN
Page 23
6.0 SEE-THRU INSTALLATION
6.1 VENTING
Refer to "VENTING" section. All venting must have a minimum clearance of 2" to combustible material on the
top and 1" to the sides and bottom.
6.2 FRAMING
!
WARNING
RISK OF FIRE!
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE APPLI-
ANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH ANY
OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO COMBUSTIBLES IS
MAINTAINED WITHIN THE CAVITY.
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN AIR
SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH SAGGING
OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK OPENING
INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE INSULATION AND
OTHER MATERIALS ARE SECURED.
23
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO MAIN-
TAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS LISTED
MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS CONSISTING
ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS, OR ANY COM-
BINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING ASTM E 136,
STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE FURNACE AT
750°C AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
BASE.
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, THEY MUST BE INSTALLED.
71.1
It is best to frame your appliance after it is positioned and the vent
system is installed. Use 2x4's and frame to local building codes.
See "BAR TYPE / COUNTER TOP INSTALLATION" section.
38 1/4”
A
A = 22 1/8" minus fi nishing material
thickness, each side.
2 1/2”
6 1/2”
41 1/8”
W415-0811 / A / 04.28.10
Page 24
24
6.3 BRICK PANEL INSTALLATION
Install the base panels as illustrated in steps 1-4, see
"PENINSULA INSTALLATION PROCEDURE" section. Both
side panels sit under the bracket tab. Holding the side panel
in position, bend down the tab to secure. DETAIL 6.
RETAINER
STEP 5
6.4 FACING
Combustible materials may be installed fl ush with the front of the appliance but must not cover any of the
black face-areas of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in
these areas.
It is not necessary to install a hearth extension with this appliance.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the fi nished fl oor
materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower
access door and the installation of many decorative fl ashing accessories.
Objects placed in front of the appliance should be kept a minimum of 48" away from the glass front faces.
6.5 FINISHING
Refer to "FINISHING" section for complete instructions
regarding mantel requirements and installations, log
placement, glass door and upper and lower louvre
attachments.
DETAIL 5 & 6
RETAINER
STEP 6
DRYWALL
DRYWALL
W415-0811 / A / 04.28.10
5"
MIN
Page 25
7.0 FRAMING
7.1 MINIMUM CLEARANCE TO COMBUSTIBLES
Minimum clearance to combustible construction from appliance and vent surfaces:
Sides, back, bottom, and top 0"
Vent pipe side, bottom and top* 2"
Recessed depth (corner installation) 25¼"
Ceiling 54" from bottom of appliance.
Enclosure 38" from bottom of appliance.
* HORIZONTAL VENT SECTIONS: A minimum clearance of 1" at the bottom and sides and 2" at the top of the
vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-2116 (supplied). * VERTICAL VENT SECTIONS: A minimum clearance of 1" all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. Use fi restop spacer W500-0367 (not
supplied).
Horizontal Vent Off ApplianceVertical Vent Off Appliance
25
A = 43" using fl exible vent components.
7.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
B = 45" using fl exible vent components.
W415-0811 / A / 04.28.10
Page 26
26
7.3 MINIMUM MANTEL CLEARANCES
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
Combustible mantel
clearance can vary
according to the mantel
depth. Use the graph to
help evaluate the clearance
needed. The three-sided
top extension piece may be
removed if non-combustible
framing is faced with a noncombustible material.
!
WARNING
11”
11” MANTEL
7” MANTEL
7”
TOP OF
APPLIANCE
73.1
Dashed lines are suitable mantel sizes and clearances
when a non-combustible facing is used.
32 1/2”
W415-0811 / A / 04.28.10
Page 27
8.0 INSTALLATION
FOLLOW THE VENTING INSTRUCTIONS EXACTLY.
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
WHICH MUST BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
!
WARNING
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
27
8.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearance to combustible materials from the vent pipe, see "MINIMUM CLEARANCE TO
COMBUSTIBLES" section.
68.2
WARNING
70.1
W415-0811 / A / 04.28.10
Page 28
28
8.1.1 HORIZONTAL INSTALLATION
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall. Having
determined the correct height for the air terminal location, cut and frame
a hole in the exterior wall as illustrated to accommodate the fi restop
assembly.
The length of the vent shield may be cut shorter for
combustible walls that are less than 8 1/2” thick but
the vent shield must extend the full depth of the
combustible wall.
A. Apply a bead of caulking (not supplied) all around and
place the fi restop top, so that the vent shield covers the
top of the vent within the opening.
B. Place the fi restop bottom against the fi restop top and secure the
two together. Adjust the assembly to ensure it is tight to the vent.
Secure fi restop to wall. This restricts cold air from being drawn
into the room or around the appliance. Ensure that both spacer
and shield maintain the required clearance to combustibles.
Once the vent pipe is installed in its fi nal position,
apply sealant W573-0002 (not supplied) between
the vent pipe and the fi restop spacer as illustrated.
!
WARNING
FIRESTOP
SPACER
CAULKING
CAULKING
DETERMINE
THE
CORRECT
HEIGHT
FINISHING
MATERIAL
VENT
SHIELD
FIRESTOP
FIRESTOP
BOTTOM
TOP
20.3
W415-0811 / A / 04.28.10
Page 29
8.1.2 VERTICAL INSTALLATION
A
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor. See
accessories to order specifi c kits required.
29
. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1“ clearance
between the vent pipe and any combustible material. Try to center the vent
pipe location midway between two joists to prevent having to cut them. Use
a plumb bob to line up the center of the openings. A vent pipe shield will
prevent any materials such as insulation, from fi lling up the 1” air space
around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a fi nished ceiling),
and secure over the opening in the ceiling. A fi restop must be placed on the
bottom of each framed opening in a roof or ceiling that the venting system passes
through. Apply a bead of caulking all around and place a fi restop spacer over
the vent shield to restrict cold air from being drawn into the room or around the
fi replace. Ensure that both spacer and shield maintain the required clearance to
combustibles. Once the vent pipe is installed in its fi nal position, apply sealant
between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten.
This will prevent any materials, such as insulation, from fi lling up the 1” air space around the
pipe.
8.2 USING FLEXIBLE VENT COMPONENTS
10 1/2"
FIRESTOP
UNDERSIDE OF
VENT PIPE
SHIELD
SHIELD
21.1
10 1/2"
JOIST
CAULKING
VENT
PIPE
COLLAR
VENT
PIPE
!
WARNING
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
ELBOW
SPACERS
For safe and proper operation of the appliance, follow the venting
instructions exactly.
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high
temperature sealant W573-0002 (not supplied) or the high temperature
sealant W573-0007 Mill Pac (not supplied). However, the high temperature
sealant W573-0007 Mill Pac (not supplied) must be used on the joint
connecting the inner fl ex pipe and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
“Wolf Steel Approved Venting” as identifi ed
by the stamp only on the outer fl ex pipe.
22.1
W415-0811 / A / 04.28.10
Page 30
30
8.2.1 HORIZONTAL AIR TERMINAL INSTALLATION
A.Stretch the inner fl ex pipe to the required length taking into
account the additional length needed for the fi nished wall
surface. Slip the vent pipe a minimum of 2” over the
inner sleeve of the air terminal and secure with 3 #8
screws. Apply a heavy bead of the high temperature
sealant W573-0007 Mill Pac (not supplied).
B.Using the outer fl ex pipe, slide over the outer combustion
air sleeve of the air terminal and secure with 3 #8 screws.
Seal using high temperature sealant W573-0002 (not
supplied).
C.Insert the vent pipes through the fi restop maintaining the
required clearance to combustibles. Holding the air terminal
(lettering in an upright, readable position), secure to the exterior
wall and make weather tight by sealing with caulking (not
supplied).
#10x2"
SCREWS
HI-TEMP
SEALANT
CAULKING
INNER FLEX
PIPE
OUTER FLEX
2" OVERLAP
HIGH TEMPERATURE
#8 X 1/2” SELF DRILLING
SCREWS & WASHERS
INNER COUPLER
PIPE
SEALANT
OUTER COUPLER
D.If more vent pipe needs to be used to reach the fi replace, couple
them together as illustrated. The vent system must be
supported approximately every 3 feet for both vertical and
horizontal runs. Use noncombustible strapping to maintain
the minimum clearance to combustibles.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth
of its return fl ange.
OUTER
FLEX PIPE
INNER
FLEX PIPE
23.1
OUTER
FLEX PIPE
W415-0811 / A / 04.28.10
Page 31
8.2.2 VERTICAL AIR TERMINAL INSTALLATION
!
WARNING
MAINTAIN A MINIMUM 2” SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
A.Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately
supported using either an alternate method suitable to the authority
having jurisdiction or the optional roof support.
B.Stretch the inner fl ex pipe to the required length. Slip the
inner fl ex pipe a minimum of 2” over the inner pipe of the air
terminal connector and secure with 3 #8 screws. Seal using
a heavy bead of high temperature sealant W573-0007 (not
supplied).
31
C.Repeat using the outer fl ex pipe, using a heavy bead of
high temperature sealant W573-0002 (not supplied).
D.Thread the air terminal connector / vent pipe assembly down through
the roof. The air terminal must be positioned vertically and plumb.
Attach the air terminal connector to the roof support, ensuring that the
top of the air terminal is 16” above the highest point that it penetrates
the roof.
E.Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” of the air terminal connector showing above
the top of the fl ashing. Slide the fl ashing underneath the sides and
upper edge of the shingles. Ensure that the air terminal connector
is properly centred within the fl ashing, giving a 3/4” margin all
around. Fasten to the roof. Do not nail through the lower portion
of the fl ashing. Make weather-tight by sealing with caulking. Where
possible, cover the sides and top edges of the fl ashing with roofi ng
material.
F.Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure
the vent pipe goes into the hole in the terminal. Secure with the
three screws provided.
ROOF SUPPORT
INNER PIPE
AIR
TERMINAL
CONNECTOR
HIGH
TEMPERATURE
SEALANT
INNER FLEX PIPE
OUTER FLEX PIPE
2”
AIR INLET
BASE
CAULKING
STORM COLLAR
G. Apply a heavy bead of weatherproof caulking 2” above the
fl ashing. Install the storm collar around the air terminal and slide
down to the caulking. Tighten to ensure that a weather-tight seal
between the air terminal and the collar is achieved.
H.If more vent pipe needs to be used to reach the appliance see “HORIZONTAL
AIR TERMINAL INSTALLATION” section.
WEA THER
SEALANT
FLASHING
24.1
W415-0811 / A / 04.28.10
Page 32
32
8.2.3 APPLIANCE VENT CONNECTION
A. Install the inner fl ex pipe to the appliance. Secure with 3 screws
and fl at washers. Seal the joint and screw holes using the high
temperature sealant W573-0007 (not supplied).
B. Install the outer fl ex pipe to the appliance. Attach and seal
the joints using the high temperature sealant W573-0002 (not
supplied).
8.3 GAS INSTALLATION
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
!
WARNING
AS SPARKS OR OPEN FLAMES.
#8 X 1/2”
SELF
DRILLING
SCREWS
2” OVERLAP
HIGH TEMPERATURE
SEALANT
28.2
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Installation and servicing to be done by a qualifi ed installer. Do not use open fl ame.
7.3.1
• Move the appliance into position and secure.
7.3.2
• If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.
7.3.3
• Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
7.3.4
• When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
7.3.5
• The gas line fl ex-connector should provide suffi cient movement to permit shifting the burner assembly
on it’s side.
7.3.6
• Check for gas leaks by brushing on a soap and water solution.
W415-0811 / A / 04.28.10
30.1A
Page 33
8.4 OPTIONAL WALL SWITCH INSTALLATION
!
WARNING
DO NOT CONNECT EITHER THE WALL SWITCH, THERMOSTAT OR GAS VALVE DIRECTLY TO 110
VOLT ELECTRICITY.
For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient
location. Route a 2 strand, solid core millivolt wire from the valve to the wall switch or millivolt thermostat. The
recommended maximum lead length depends on wire size:
WIRE SIZE MAX. LENGTH
14 gauge 100 feet
16 gauge 60 feet
18 gauge 40 feet
Disconnect the existing wires from terminals 1 and 3 (from the
ON/OFF switch) and replace with the leads from the wall switch / millivolt thermostat.
33
3
2
1
50.1
W415-0811 / A / 04.28.10
Page 34
34
9.0 FINISHING
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., PROVIDED THAT THESE MATERIALS DO NOT GO
BELOW THE SPECIFIED DIMENSION AS ILLUSTRATED.
DO NOT STRIKE, SLAM OR SCRATCH GLASS. DO NOT OPERATE APPLIANCE WITH GLASS
FACING AND/OR FINISHING MATERIAL MUST NEVER OVERHANG INTO THE APPLIANCE OPENING.
9.1 DOOR INSTALLATION
GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED.
!
WARNING
RISK OF FIRE!
REMOVED, CRACKED, BROKEN OR SCRATCHED.
!
WARNING
72.1A
THE DOOR LATCHES ARE PART OF A SAFETY SYSTEM AND MUST BE PROPERLY ENGAGED. DO
NOT OPERATE THE APPLIANCE WITH LATCHES DISENGAGED.
FACING AND/OR FINISHING MATERIALS MUST NOT INTERFERE WITH AIR FLOW THROUGH AIR
OPENINGS, LOUVRES OPENINGS, OPERATION OF LOUVRES OR DOORS OR ACCESS FOR
SERVICE. OBSERVE ALL CLEARANCES WHEN APPLYING COMBUSTIBLE MATERIALS.
BEFORE DOOR IS REMOVED TURN THE APPLIANCE OFF AND WAIT UNTIL APPLIANCE IS COOL TO
THE TOUCH. DOORS ARE HEAVY AND FRAGILE SO HANDLE WITH CARE.
DOOR OPENING AND CLOSING: The upper louvres must be removed to allow the door to be opened or
closed. To access the lower door latch, open the valve control door. Release the top and bottom door latches,
located at the right side of the door.
9.2 END DOOR INSTALLATION
Ensure that the door is properly clipped onto the steel lip to prevent overheating, glass breakage and / or
discoloration of the upper trim.
To install the door(s), hook it over the steel lip located above the door opening.
Secure with screws along the bottom of the door. Tighten screws snugly. Do not over-tighten.
When using a non-combustible
fi nishing material, the stand-offs
may be removed, by removing the
set screw in the centre and sliding
the stand-offs out of the mounting
clips.
* The top extension may be
removed if non-combustible
framing is faced with a noncombustible material placed fl ush
with the front face of the appliance
and extending from the top of the
appliance. Example: Cement
board (not supplied). Combustible
counter / bar tops must maintain a
minimum of 38" from the base of
the appliance to the underside of the top.
NOTE: Wolf Steel trim and/or surround kits will not
totally cover the top extension of the appliance. In
order to obtain a smooth transition from the trim /
surround to the wall, it is recommended that the top
extension be removed and the appliance be installed
following the above procedure.
END HEAT
SHIELD SHOWN
35
9.4 LOUVRE INSTALLATION
A
B
C
CLIPS
A
HOOD
Attach the hood by
pressing the top fl ange
into the clips along the
top of the louvre opening. Secure using a
screw through the centre
slot.
CENTRE SLOT
SLOT
TAB
B
UPPER LOUVRES
Insert the louvre tabs
into the slots located
at the top left and right
corners of the unit.
SLOT
HINGE CLIP
C
LOWER LOUVRES
Insert the hinge clips
into the slots located at
the bottom left and right
corners of the unit. To
remove the louvres, pull
the back tabs of the clips
forward, while pushing
the louvre assembly
back. Lift the clip.
57.2
W415-0811 / A / 04.28.10
Page 36
36
9.5 LOG PLACEMENT
FAILURE TO POSITION THE LOGS IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE
ONLY LOGS SPECIFICALLY APPROVED WITH THIS APPLIANCE MAY RESULT IN PROPERTY
LOGS MUST BE PLACED IN THEIR EXACT LOCATION IN THE APPLIANCE. DO NOT MODIFY THE
PROPER LOG POSITIONS, SINCE APPLIANCE MAY NOT FUNCTION PROPERLY AND DELAYED
THE LOGS ARE FRAGILE AND SHOULD BE HANDLED WITH CARE.
PhazerTM logs, glowing and charcoal embers, exclusive to Wolf Steel Ltd. appliances, provide a unique and
realistic glowing effect that is different in every installation. Take the time to carefully position the embers for a
maximum glowing effect.
!
WARNING
DAMAGE OR PERSONAL INJURY.
IGNITION MAY OCCUR.
76.1A
LOCATING SCREWS
LOCATING
STUDS
9.5.1Looking at the unit from the valve side, place
the fi bre burner onto the locating screws
on the pan burner as illustrated above. It is
important not to cover any burner ports with
the fi bre burner.
9.5.2Place log #1 diagonally across the textured
burner onto the pins. The texture is
designed to cradle the underside of the log.
9.5.3Depending on the type of installation, the
view of the log positioning will reverse. Here
the lower end of log #2 rests near the back
left corner of the fi rebox on the locating pin.
The upper end sits on top of log #1, inside
the groove on log #2.
W415-0811 / A / 04.28.10
9.5.4 Log # 3 is made up of two pieces, a and b.
Piece #3a is the base of log #3. The base
sits diagonally in the designated area located
between logs #1 and fi ts tight up against #2.
Page 37
37
9.5.5When pieces #3a and #3b are attached
to create log #3, the upper end of log #3
should rest in the groove, on top of log # 2.
The slot in the underside of piece #3b fi ts
over #3a. Place the end of piece #3b onto
the pin.
9.5.7Like log #3, log #5 also comes in two
pieces. The base (#5a) slopes outwards
between logs #2 and #4.
As with pieces #3a & b, piece #5b fi ts over
piece #5a. Place the end of piece #5b onto
the pin.
Log colours may vary. During the initial use of the appliance, the colours will become more uniform as colour
pigments burn in during the heat activated curing process.
Positioning the logs improperly will cause fl ame impingement and carboning.
Blocked burner ports can cause an incorrect fl ame pattern, carbon deposits and delayed ignition. PhazerTM
logs glow when exposed to direct fl ame. Use only certifi ed PhazerTM logs available from your authorized
dealer / distributor.
9.5.6As with log # 1, log #4 is also cradled by the
texture of the burner and the pin in the
base. Position log #4 so that the lower end
fi ts onto the pin. The upper end rests against
the moulded locator on the top of log # 1.
9.5.8The upper end of log #5 rests in the groove,
on top of log #4 and creates the fi nal
appearance of the log set.
9.6 CHARCOAL EMBERS
Randomly place the charcoal embers along the front and sides of the log support tray in a realistic manner.
Fine dust found in the bottom of the bag should not be used.
NOTE: Charcoal embers are not to be placed on the burner.
9.7 LOGO PLACEMENT
Remove the backing of the logo supplied and place on the glass viewing
door, as indicated.
32.1
½"
LOGO
½"
W415-0811 / A / 04.28.10
Page 38
38
black
white
red
BLOWER
THERMAL
SWITCH
VARIABLE
SPEED
SWITCH
10.0 OPTIONAL BLOWER INSTALLATION
!
WARNING
RISK OF FIRE AND ELECTRICAL SHOCK.
TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THIS APPLIANCE.
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH
THIS APPLIANCE. USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS
COMPONENTS, VENTING COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL
VOID THE WARRANTY AND CERTIFICATION.
ENSURE THAT THE FAN’S POWER CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE
APPLIANCE TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE. DO NOT RUN THE POWER
CORD BENEATH THE APPLIANCE.
THE WIRE HARNESS PROVIDED IN THE BLOWER KIT IS A UNIVERSAL HARNESS. WHEN
INSTALLED, ENSURE THAT ANY EXCESS WIRE IS CONTAINED, PREVENTING IT FROM MAKING
CONTACT WITH MOVING OR HOT OBJECTS.
INST ALLATION TO BE DONE BY A QUALIFIED INSTALLER and must be electrically connected and grounded in accordance with local codes. In the absence of
local codes, use the current CSA C22.1 CANADIANELECTRICALCODE in Canada or the
ANSI/NFPA 70 NATIONALELECTRICALCODE in the United States.
51.5
Remove the blower from its mounting bracket and attach to the bracket supplied with
the appliance. This bracket is found secured on the mounting stud located at the bottom of the vent side wall. The blower bracket contains two holes that allow the blower
to be positioned away from the intended gas supply hole.
Position the vibration reducing pad,
centred, onto the threaded stud, piercing
a hole into the pad. The blower must be
able to be positioned entirely onto the pad.
Tilt the blower onto its side and slide it
past the controls. Position the blower
under the clip and onto the stud. Secure
with a wing nut.
Remove the "Z" shaped mounting bracket secured to the burner, by the pilot. Remove the thermal switch from the bracket supplied in the blower kit and attach to
the mounting bracket. Attach the connectors from the black and white wires to the
thermal switch. Replace bracket and switch in the location it was removed from.
BGNV / BCNV ONL Y:
Remove the bracket from the top right side of the fi rebox. Remove the
thermal switch from the bracket supplied in the blower kit and
install the thermal switch into the bracket removed from the
fi rebox top. Then replace the bracket / switch in the location it
was removed.
Connect the two ends of the unattached wires by the bracket to
the thermal switch.
Connect the opposite ends of the wires to the red and black
leads of the blower harness.
MOUNTING
BRACKET
Do not overtighten thermal switch or distort housing. Attach the connectors from the black and red wires to the blower.
Attach and secure the variable speed switch using the nut provided. Plug the harness cord into the receptacle.
W415-0811 / A / 04.28.10
Page 39
A
The wire harness provided in this kit is a universal harness. When installed, ensure that any excess wire is contained,
preventing it from making contact with moving or hot objects.
Drywall dust will penetrate into the blower bearings, causing irreparable damage. Care must be taken to prevent drywall
dust from coming into contact with the blower or its compartment. Any damage resulting from this condition is not covered
by the warranty policy.
Because the blower is thermally activated, when turned on, it will automatically start approximately 10 minutes after lighting the appliance and will run for approximately 30 - 45 minutes after the appliance has been turned off. Use of the fan
increases the output of heat.
51.4
39
11.0 OPERATION
!
WARNING
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT
CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH
THE GLASS DOOR OPENED OR REMOVED.
Ensure that a continuous gas flow is at the burner before installing the door. When lit for the first time, the appliance will
emit an odor for a few hours. This is a normal temporary condition caused by the "burn-in" of paints and lubricants used in
the manufacturing process and will not occur again.
fter extended periods of non-operation such as following a vacation or a warm weather season, the appliance may emit a
slight odor for a few hours. This is caused by dust particles in the heat exchanger burning off. In both cases, open a
window to sufficiently ventilate the room.
FOR YOUR SAFETY READ BEFORE LIGHTING:
A. This appliance is equipped with a pilot which must be lit by hand while following these instructions exactly.
B. Before operating smell all around the appliance area for gas and next to the floor because some gas is heavier than
air and will settle on the floor.
C. Use only your hand to turn the gas control knob. Never use tools. If the knob will not turn by hand, do not try to
repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect
the appliance and replace any part of the control system and any gas control which has been under water.
WHAT TO DO IF YOU SMELL GAS:
Turn off all gas to the appliance.
Open windows.
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a
neighbor's phone. Follow the gas
supplier's instructions.
If you cannot reach your gas supplier,
call the fire department.
GAS KNOB
LIGHTING INSTRUCTIONS:
WARNING: The gas valve has an interlock device which will not allow the pilot burner to be lit until the thermocouple has cooled. Allow approximately 60 seconds for the thermocouple to cool.
When lighting and re-lighting, the gas knob cannot be turned from pilot to off unless the knob is depressed slightly.
1. Stop! Read the above safety information on this label.
2. Turn off all electric power to the appliance.
3. Turn the gas knob clockwise to off.
4. Wait five (5) minutes to clear out any gas. If you smell gas including near the floor. Stop! Follow "B" in the
above safety information on this label. If you don't smell gas go the next step.
5. Turn gas knob counter-clockwise to pilot.
6. Depress slightly and hold gas knob while lighting the pilot with the push button igniter. Keep knob depressed for one
minute, then release. If pilot does not continue to burn, repeat steps 3 through 5.
7. With pilot lit, depress and turn gas knob counter-clockwise to on.
8. If equipped with remote on-off switch / thermostat, main burner may not come on when you turn valve to on. Remote
switch must be in the on position to ignite burner.
9. Turn on all electric power to the appliance.
1. Turn off all electric power to the appliance if service is to be performed.
2. Push in gas control knob slightly and turn clockwise to off. Do not force.
TURN THE CONTROL VALVE TO THE OFF POSITION WHEN HEATER IS NOT IN USE.
TO TURN OFF GAS
47.2
W415-0811 / A / 04.28.10
Page 40
40
12.0 ADJUSTMENTS
12.1 PILOT BURNER ADJUSTMENT
Adjust the pilot screw to provide properly sized fl ame. Turn in a clockwise
direction to reduce the gas fl ow.
Inlet pressure can be checked by turning screw (A) counter-
THERMOCOUPLE
clockwise until loosened and then placing pressure gauge
tubing over the test point. Gauge should read 7” (minimum 4.5”)
water column for natural gas or 13” (11” minimum) water column for
propane. Check that main burner is operating on “HI”.
Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5” water column for natural gas or 10” water column
for propane. Check that main burner is operating on “HI”.
AFTER TAKING PRESSURE READINGS, TIGHTEN SCREWS
FIRMLY TO SEAL. DO NOT OVER TORQUE. LEAK TEST.
PILOT SCREW
PILOT
BURNER
P
I
L
O
T
39.3
THERMOPILE
B
L
O
I
H
N
O
A
F
O
F
P
L
T
I
O
12.2 VENTURI ADJUSTMENT
This appliance has an air shutter that has been factory set open according
to the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more
yellow flame, but can lead to carboning. Opening the air shutter will cause a
more blue flame, but can cause flame lifting from the burner ports. The
flame may not appear yellow immediately; allow 15 to 30 minutes for the
final flame color to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER!
BGD40
NG
LP
1/4"
7/16"
VENTURI
BURNER
AIR
SHUTTER
OPENING
ORIFICE
49.1
W415-0811 / A / 04.28.10
Page 41
12.3 FLAME ADJUSTMENT
Turn clockwise to
increase fl ame height
I
H
L
O
12.4 FLAME CHARACTERISTICS
It’s important to periodically perform a visual check of the pilot and burner fl ames. Compare them to the illustra-
tions provided. If any fl ames appear abnormal call a service person.
FLAME
ADJUSTMENT
KNOB
ELECTRODE
FLAME
SENSOR
PILOT
BURNER
FLAME MUST ENVELOP
UPPER 3/8” TO 1/2” OF
FLAME SENSOR
P
I
L
O
T
3/8” - 1/2”
41
L
O
F
O
I
H
F
N
O
P
L
T
I
O
12.5 RESTRICTING VERTICAL VENTS
Vertical installations may display a very active fl ame. If
this appearance is not desirable, the vent exit must be
restricted using the optional restrictor vent kit, RP40-KT.
This will reduce the velocity of the exhaust gases,
slowing down the fl ame pattern and creating a more
traditional gentle appearance.
12.5.1 Open the glass viewing door.
12.5.2 Remove the three screws for mounting the
restrictor plate located in the top of the fi rebox.
12.5.3 Line up the holes on vent restrictor plate with
the three holes from which the screws were
removed.
12.5.4 Secure the vent restrictor plate into position
using the three screws removed in step 2.
12.5.5 Replace the viewing door.
54.1
SCREWS
W415-0811 / A / 04.28.10
Page 42
42
13.0 MAINTENANCE
TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE.
APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE HAS COOLED.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation after servicing. This appliance and its venting system
should be inspected before use and at least annually by a qualifi ed service person. The appliance area must
be kept clear and free of combustible materials, gasoline or other fl ammable vapors and liquids. The fl ow of
combustion and ventilation air must not be obstructed.
1.In order to properly clean the burner and pilot assembly, remove the logs, rocks and/or glass to
expose both assemblies.
2.Keep the control compartment, media, burner, air shutter opening and the area surrounding the logs
clean by vacuuming or brushing, at least once a year.
3.Check to see that all burner ports are burning. Clean out any of the ports which may not be burning or
are not burning properly.
4.Check to see that the pilot fl ame is large enough to engulf the fl ame sensor and/or thermocouple /
thermopile as well as reaches the burner.
5.Replace the cleaned logs, rocks or glass. Failure to properly position the media may cause carboning
which can be distributed in the surrounding living area.
6.Check to see that the main burner ignites completely on all openings when turned on. A 5 to 10
second total light-up period is satisfactory. If ignition takes longer, consult your local authorized dealer /
distributor.
7.Check that the gasketing on the sides, top and bottom of the door is not broken or missing. Replace if
necessary.
8.If for any reason the vent air intake system is disassembled, re-install and re-seal per the instructions
provided for the initial installation.
13.1 CARE OF GLASS
MAINTENANCE
MAINTENANCE
MAINTENANCE
DO NOT USE ABRASIVE CLEANERS.
!
WARNING
40.1
DO NOT CLEAN GLASS WHEN HOT! DO NOT USE
ABRASIVE CLEANERS TO CLEAN GLASS.
Buff lightly with a clean dry soft cloth. Clean both sides
of the glass after the fi rst 10 hours of operation with a
recommended fi replace glass cleaner. Thereafter clean
as required. If the glass is not kept clean permanent
discoloration and / or blemishes may result.
W415-0811 / A / 04.28.10
!
WARNING
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
5.1
Page 43
14.0 REPLACEMENTS
FAILURE TO POSITION THE PARTS IN ACCORDANCE WITH THIS MANUAL OR FAILURE TO USE
ONLY PARTS SPECIFICALLY APPROVED WITH THIS APPLIANCE MAY RESULT IN PROPERTY
DAMAGE OR PERSONAL INJURY.
** THIS IS A FAST ACTING THERMOCOUPLE. IT IS AN INTEGRAL SAFETY COMPONENT. REPLACE ONLY WITH
A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD.
Contact your dealer or the factory for questions concerning prices and policies on replacement parts. Normally
all parts can be ordered through your Authorized dealer / distributor.
FOR WARRANTY REPLACEMENT PARTS, A PHOTOCOPY OF THE ORIGINAL INVOICE WILL BE
REQUIRED TO HONOUR THE CLAIM.
When ordering replacement parts always give the following information:
• Model & Serial Number of appliance
• Installation date of appliance
• Part number
• Description of part
• Finish
* IDENTIFIES ITEMS WHICH ARE NOT ILLUSTRATED. FOR FURTHER INFORMATION, CONTACT YOUR
AUTHORIZED DEALER.
15*GD825NVALVE REGULATOR FOR W660-0013 - NATURAL GAS
15*GD825PVALVE REGULATOR FOR W660-0013 - PROPANE
16*RP40-KTRESTRICTOR VENT KIT
17*W175-0205 CONVERSION KIT - NG - LP
17*W175-0206 CONVERSION KIT - LP - NG
18*W573-0007 10.3OZ TUBE HIGH TEMP SEALANT
12
W415-0811 / A / 04.28.10
11
13
14
Page 47
15.0 TROUBLE SHOOTING
!
WARNING
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT,
WITH THE GLASS DOOR OPEN OR REMOVED.
TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE.
APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE HAS COOLED.
DO NOT USE ABRASIVE CLEANERS.
SYMPTOMPROBLEMTEST SOLUTION
Main burner goes out; pilot
stays on.
Main burner goes out; pilot
goes out.
Pilot goes out when the
gas knob is released.
The gas valve has an
interlock device which
will not allow the pilot
burner to be lit until
the thermocouple
has cooled. Allow
approximately 60
seconds for the
thermocouple to cool.
Pilot burning; no gas to
main burner; gas knob
is on ‘HI’; wall switch /
thermostat is on.
Pilot goes out while
standing; Main burner is in
‘OFF’ position.
Main burner fl ame is a
blue, lazy, transparent
fl ame.
Pilot fl ame is not large
enough or not engulfi ng the
thermopile.
Thermopile shorting. -Clean thermopile connection to the valve. Reconnect.
Remote wall switch wire is too
long; too much resistance in
the system.
Faulty thermostat or switch. -Replace.
Refer to “MAIN BURNER GOES OUT; PILOT STAYS ON”
Vent is blocked -Check for vent blockage.
Vent is re-circulating -Check joint seals and installation
Flexible vent has become
disconnected from appliance.
System is not correctly
purged.
Out of propane gas. -Fill the tank.
Pilot fl ame is not large
enough.
Pilot fl ame is not engulfi ng the
thermocouple
Thermocouple shorting / faulty. -Loosen and tighten thermocouple.
Faulty valve. -Replace.
Thermostat or switch is
defective
Wall switch wiring is defective. -Disconnect the switch wires & connect a jumper wire
Main burner orifi ce is plugged. -Remove stoppage in orifi ce.
Faulty valve. -Replace.
Gas piping is undersized. -Turn on all gas appliances and see if pilot fl ame fl utters,
Blockage in vent. -Remove blockage. In really cold conditions, ice buildup
Incorrect installation. -Ensure correct location of storm collars.
-Turn up the pilot fl ame.
-Replace pilot assembly.
-Replace thermopile / valve.
-Shorten wire to correct length or wire gauge.
-Re-attach to appliance.
-Cap was not replaced.
-Purge the gas line.
-Turn up the pilot fl ame.
-Gently twist the pilot head to improve the fl ame pattern
around the thermocouple.
-Clean thermocouple and valve connection.
-Replace thermocouple.
-Replace valve.
-Connect a jumper wire across the wall switch terminals;
if main burner lights, replace switch / thermostat.
across terminals 1 & 3; if the main burner lights, check
the wires for defects and/or replace wires.
diminishes or extinguishes, especially when main burner
ignites. Monitor appliance supply working pressure.
-Check if supply piping size is to code. Correct all
undersized piping.
may occur on the terminal and should be removed as
required.
42.3
47
W415-0811 / A / 04.28.10
Page 48
48
SYMPTOMPROBLEMTEST SOLUTION
Pilot will not light.No spark at pilot burner. -Check if pilot can be lit by a match.
-Check that the wire is connected to the push button igniter.
PILOT
BURNER
THERMOPILE
THERMOCOUPLE
Out of propane gas. -Fill the tank.
Spark gap is incorrect. -Spark gap should be 0.150” to 0.175” (5/32” to 11/64”
No gas at the pilot burner. -Check that the manual valve is turned on.
Flames are consistently
Unit is over-fi red or underfi red. -Check pressure readings:
too large or too small.
Carboning occurs.
A
B
L
O
F
O
I
H
P
I
L
O
T
F
N
O
P
L
T
I
O
Flames are very aggressive.Door is ajar. -Tighten screws holding door in place.
Carbon is being
deposited on glass, logs
or combustion chamber
surfaces.
Air shutter has become
blocked.
Flame is impinging on the logs
or combustion chamber.
White / grey fi lm forms.Sulphur from fuel is being
deposited on glass, logs or
combustion chamber surfaces.
Exhaust fumes smelled in
Appliance is spilling. -Ensure exhaust bracket gasket seal.
room, headaches.
Remote wall switch is in
’OFF’ position; main burner
comes on when gas knob
is turned to ‘ON’ position.
Wall switch is mounted upside
down.
Remote wall switch is
grounding.
Remote wall switch wire is
grounding.
Faulty valve. -Replace.
W415-0811 / A / 04.28.10
-Check if the push button igniter needs tightening.
-Replace the wire if the wire insulation is broken or frayed.
-Replace the electrode if the ceramic insulator is cracked
or broken.
-Replace the push button ignitor
approx.) from the electrode tip and the pilot burner. To
ensure proper electrode location, tighten securing nut
(fi nger tight plus 1/4 turn).
-Check the pilot orifi ce for blockage.
-Replace the valve.
-Call the gas distributor.
-Inlet pressure can be checked by turning screw (A)
counter-clockwise 2 or 3 turns and then placing pressure
gauge tubing over the test point. Gauge should read
7” (minimum 4.5”) water column for natural gas or 13”
(minimum 11”) water column for propane. Check with
main burner is operating on ‘HI’.
-Outlet pressure can be checked the same as above
using screw (B). Gauge should read 3.5” water column
for natural gas or 10” water column for propane. Check
that main burner is operating on ‘HI’.
-AFTER TAKING PRESSURE READINGS, BE SURE TO
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL.
DO NOT OVER TORQUE.
-Leak test with a soap and water solution.
-Ensure air shutter opening is free of lint or other
obstructions.
-Check that the logs are correctly positioned.
-Open air shutter to increase the primary air.
-Check the input rate: check the manifold pressure and
orifi ce size as specifi ed by the rating plate values.
-Check that the door gasketing is not broken or missing
and that the seal is tight.
-Check that both vent liners are free of holes and well
sealed at all joints.
-Check that minimum rise per foot has been adhered to
for any horizontal venting.
-Clean the glass with a recommended gas appliance
glass cleaner.
-DO NOT CLEAN GLASS WHEN HOT.
-If deposits are not cleaned off regularly, the glass may
become permanently marked.
-Check door seal and relief fl ap seal.
-Check for chimney blockage.
-Check that chimney is installed to building code.
-Room is in negative pressure; increase fresh air supply.
-Check cap gasket on the fl ue pipe assembly.
-Reverse.
-Replace.
-Check for ground (short); repair ground or replace wire.
42.3_2A
Page 49
16.0 WARRANTY
NAPOLEON® products are manufactured under the strict Standard of the world recognized ISO 9001 : 2008
NAPOLEON® products are designed with superior components and materials assembled by trained
craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fi red at a
quality test station. The complete heater is again thoroughly inspected by a qualifi ed technician before
packaging to ensure that you, the customer, receives the quality product that you expect from NAPOLEON®.
NAPOLEON® GAS FIREPLACE PRESIDENT’S LIFETIME LIMITED WARRANTY
The following materials and workmanship in your new NAPOLEON® gas heater are warranted against
defects for as long as you own the heater. This covers: combustion chamber, heat exchanger, stainless
steel burner, phazer™ logs and embers, rocks, ceramic glass (thermal breakage only), gold plated parts
against tarnishing, porcelainized enameled components and aluminum extrusion trims.*
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves, thermal switch,
switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and NAPOLEON® will
provide replacement parts free of charge during the fi rst year of the limited warranty.*
Labour related to warranty repair is covered free of charge during the fi rst year. Repair work, however,
requires the prior approval of an authorized company offi cial. Labour costs to the account of NAPOLEON®
are based on a predetermined rate schedule and any repair work must be done through an authorized
NAPOLEON® dealer.
* Construction of models vary. Warranty applies only to components included with your specifi c heater.
49
Quality Assurance Certifi cate.
CONDITIONS AND LIMITATIONS
NAPOLEON® warrants its products against manufacturing defects to the original purchaser only. Registering your warranty is not
necessary. Simply provide your proof of purchase along with the model and serial number to make a warranty claim. NAPOLEON®
reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim. Provided that the
purchase was made through an authorized NAPOLEON® dealer your heater is subject to the following conditions and limitations:
This factory warranty is non-transferable and may not be extended whatsoever by any of our representatives.
The gas heater must be installed by a licensed, authorized service technician or contractor. Installation must be done in accordance
with the installation instructions included with the product and all local and national building and fi re codes. This limited warranty does
not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other
manufacturers will nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discoloring caused by excessive heat, abrasive and
chemical cleaners nor chipping on porcelain enamel parts, mechanical breakage of PHAZER™ logs and embers.
NAPOLEON® warrants its stainless steel burners against defects in workmanship and material for life, subject to the following
conditions: During the fi rst 10 years NAPOLEON® will replace or repair the defective parts at our option free of charge. From 10 years
to life, NAPOLEON® will provide replacement burners at 50% of the current retail price.
In the fi rst year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or
workmanship provided that the product has been operated in accordance with the operation instructions and under normal conditions.
After the fi rst year, with respect to this President’s Lifetime Limited Warranty, NAPOLEON® may, at its discretion, fully discharge all
obligations with respect to this warranty by refunding to the original warranted purchaser the wholesale price of any warranted but
defective part(s).
NAPOLEON® will not be responsible for installation, labour or any other expenses related to the reinstallation of a warranted part and
such expenses are not covered by this warranty.
Notwithstanding any provisions contained in the President’s Lifetime Limited Warranty, NAPOLEON’S responsibility under this
warranty is defi ned as above and it shall not in any event extend to any incidental, consequential or indirect damages.
This warranty defi nes the obligations and liability of NAPOLEON® with respect to the NAPOLEON® gas heater and any other
warranties expressed or implied with respect to this product, its components or accessories are excluded.
NAPOLEON® neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of
this product.
NAPOLEON® will not be responsible for: over-fi ring, downdrafts, spillage caused by environmental conditions such as rooftops,
buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting confi gurations, insuffi cient makeup air, or
negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to heater, combustion chamber, heat exchanger, brass trim or other components due to water, weather damage, long
periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON®.
ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT
IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN.