Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
- Do not store or use gasoline or other
fl ammable vapors and liquids in the vicinity of
this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the fi re department.
GDS25P-1
FRENCH
PG. 51
INSTALLATION AND
ADD MANUAL TITLE
OPERATION MANUAL
PRODUCT NAME™
SAFETY BARRIER
ADD PRODUCT IMAGE
Bayfield™
ADD ____ ILLUSTRATED
- Installation and service must be
performed by a qualifi ed installer, service
agency, or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certifi ed kit is used.
INSTALLER:
Leave this manual with the appliance
CONSUMER:
Retain this manual for future reference
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030
CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS:
CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES
CSA /
INTERTEK
LOGO
$10.00
W415-2207 / B / 02.05.18
• Under no circumstances should this appliance be modifi ed.
DANGER
!
WARNING
EN
safety information
• This appliance is hot when operated and
can cause severe burns if contacted.
• Any changes or alterations to this
appliance or its controls can be
dangerous and is prohibited.
• Do not operate appliance before reading and
understanding operating instructions. Failure
to operate appliance according to operating
instructions could cause fi re or injury.
• Ensure the glass door is opened or removed
when lighting the pilot for the fi rst time and
when the gas supply has run out.
• Risk of fi re or asphyxiation do not operate
appliance with fi xed glass removed and never
obstruct the front opening of the appliance.
• Objects placed in front of the appliance must
be kept a minimum of 4 feet (1.22m) from the
front face of the appliance.
• Do not connect 110 volts to the control valve,
with the exception of models; GSST8 and GT8.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during
installation. Sheet metal edges may be sharp.
• Do not burn wood or other materials in this appliance.
• Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing
and operating the appliance. Never obstruct the front opening of the appliance.
• The appliance area must be kept clear and free from combustible materials, gasoline and other
fl ammable vapors and liquids.
• High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at
test pressures above 1/2 psig. Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 psig (35mb).
• The appliance must not be operated at temperatures below freezing (32°F / 0°C). Allow the appliance
to warm to above freezing prior to operation, with the exception of models; GSS36, GSS42; these
appliances are suitable for 0°F / -18°C.
• Children and adults should be alerted to hazards of high surface temperature and should stay
away to avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to accidental contact
burns. A physical barrier is recommended if there are at risk individuals in the house. To
restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers,
young children and other at risk individuals out of the room and away from hot surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from
furniture and draperies.
• Furniture or other objects must be kept a minimum of 4 feet (1.22m) away from the front of the appliance.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot
surfaces.
• Even after the appliance is off, it will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children
from hot surfaces. These screens and guards must be fastened to the fl oor.
• Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior
to operating the appliance.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the
appliance and venting system are kept clean. The appliance and its venting system should be inspected
before use and at least annually by a qualifi ed service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and
free from combustible materials, gasoline and other fl ammable vapors and liquids.
• If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it
serviced. Keep burner and control compartment clean.
!
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals.
2
W415-2207 / B / 02.05.18
• It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.
• If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it serviced. Keep burner and control compartment clean.
• Under no circumstances should this appliance be modified.
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
!
WARNING
!
WARNING
WARNING
• Do not allow wind or fans to blow directly into the appliance. Avoid any drafts that alter burner fl ame
patterns.
• Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this
appliance.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning
appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has
been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person, if equipped.
• Do not strike or slam shut the appliance glass door, if equipped.
• Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As
with all plastic bags, these are not toys and should be kept away from children and infants.
• Carbon or soot should not occur in a vent free appliance as it can distribute into the living area of your
home. If you notice any signs of carbon or soot, immediately turn off your appliance and arrange to have
it serviced by a qualifi ed technician before operating it again.
• If equipped, the screen must be in place (closed) when the appliance is in operation.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating
to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of
the exhaust escaping through these openings can also cause the surrounding combustible materials to
overheat and catch fi re.
• Carbon monoxide poisoning may lead to death; early signs of carbon monoxide poisoning resemble
the fl u, with headache, dizziness and/or nausea. If you have these signs, the heater may not be working
properly. Get fresh air at once! Have heater serviced. Some people; pregnant women, persons with heart
or lung disease, anemia, those under the infl uence of alcohol, those at high altitudes are more affected by
carbon monoxide than others. Failure to keep the primary air opening(s) of the burner(s) clean may result
in sooting and property damage.
• As with any combustion appliance, we recommend having your appliance regularly inspected and
serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and
your family against Carbon Monoxide.(Not applicable for outdoor appliances).
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the
appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting,
discolouration or damage to decorations, a T.V. or other electronic components.
• For appliances equipped with a safety barrier; the barrier is designed to reduce the risk of
burns from the hot viewing glass is provided with this appliance and shall be installed. If the
barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
• Installation and repair should be done by a qualifi ed service person. The appliance should be
inspected before use and at least annually by a professional service person. More frequent
cleaning may be required due to excessive lint from carpeting, bedding material, etc. It
is imperative that control compartments, burners and circulating air passageways of the
appliance be kept clean.
• For outdoor products only: this appliance must not be installed indoors or within any structure that
prevents or inhibits the exhaust gases from dissipating in the outside atmosphere.
• If applicable, the millivolt version of this appliance uses and requires a fast acting thermocouple. Replace
only with a fast acting thermocouple supplied by Wolf Steel Ltd.
safety information
EN
!
FIRE RISK HAZARD / DELAYED IGNITION
High supply pressure will damage the valve / controls.
!
Disconnect the appliance main gas valve/control
from the supply piping when pressure testing that
system at pressures in excess of 1/2 psi (3.5 kPa).
Isolate the appliance with it’s shut off valve during
any pressure testing of the supply piping at
pressures equal to or less than 1/2 psi (3.5 kPa).
W415-2207 / B / 02.05.18
3
EN
table of contents
1.0 general information 5
1.1 rates and efficiencies 5
1.2 installation overview 6
1.3 rating plate information 8
1.4 mobile home installation 8
1.5 hardware list 9
1.6 dimensions 10
2.0 venting requirements 11
2.1 typical venting installation 13
2.2 special vent installations 14
2.2.1 periscope termination 14
2.2.2 corner termination 14
2.3 vent terminal clearances 15
2.4 horizontal termination 16
2.5 vertical termination 17
2.6 vertical through existing chimney 18
3.0 installation 19
3.1 horizontal installation 20
3.2 vertical installation 20
3.3 horizontal air terminal installation 21
3.4 extended horizontal and corner air terminal
installation 21
3.5 vertical air terminal Installation 22
3.6 appliance vent connection 23
3.7 gas installation 23
3.8 minimum clearance to combustibles 24
3.9 minimum mantel or shelf clearances 25
4.0 finishing 26
4.1 cast front installation and removal 26
4.2 safety barrier installation and removal 26
4.3 glass door installation and removal 27
4.4 log placement 27
4.5 logo placement 28
5.0 optional blower installation 29
6.0 wiring diagram 31
7.0 operation 32
7.1 general transmitter layout 33
7.2 initializing the transmitter / battery holder
for the first time 33
7.3 temperature display 34
7.4 flame height 34
7.5 blower speed 34
7.6 night light dimmer control 34
7.7 continuous pilot / intermittent pilot
(CPI / IPI) selection 34
7.8 key lock 35
7.9 low battery / manual bypass 35
8.0 adjustment 36
8.1 restricting vertical vents 36
8.2 venturi adjustment 36
8.3 pilot burner adjustment 36
8.4 flame characteristics 37
9.0 maintenance 38
9.1 annual maintenance 39
9.2 night light replacement 40
9.3 pilot injector and orifice replacement 40
9.4 care of glass 41
9.5 care of plated parts 41
10.0 replacements 42
10.1 overview 43
10.2 valve train assembly 44
11.0 accessories 45
12.0 troubleshooting 46
13.0 warranty 49
4
note:
The information throughout this manual is believed to be correct at the time of printing. Wolf Steel
Ltd. reserves the right to change or modify any information within this manual at any time without
notice. Changes, other than editorial, are denoted by a vertical line in the margin.
The camera icon indicates video tutorials are available as additional reference, visit
http://www.napoleonfireplaces.com/category/product-support/support-centre/
W415-2207 / B / 02.05.18
Installer, please fill out the following information:
Customer:
Address:
Date of Installation:
Location of appliance:
Installer:
Dealer/Distributor contact number:
Serial #:
Model:
standard checklist
EN
Natural Gas: GDS25N-1
Propane: GDS25P-1
1.0 general information
For elevations between 2,000ft (610m) and 4,500ft (1372m) above sea level, this appliance must be de-rated by 10%
using the certified high altitude kit. When the appliance is installed at elevations above 4,500ft (1372m), and in the absence
of specific recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be
reduced at the rate of 4% for each additional 1,000ft (305m).
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for
use with other gases, unless a certified kit is used.
The blower power cord must be connected into a properly grounded receptacle. The grounding prong must not
be removed from the cord plug.
This appliance is approved for closet or recessed installations, as well as for bathroom, bedroom and
bed-sitting room installations and is suitable for mobile home installations. The natural gas model can be installed
in a mobile home that is permanently positioned on its site and fueled with natural gas.
note:
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance and must
be installed.
The protective wrap on plated parts is best removed when the assembly is at room temperature but
this can be improved if the assembly is warmed, using a hair dryer or similar heat source.
This appliance is a decorative product. It is not a source of heat and not intended to burn solid fuel.
Batteries must be disposed of according to the local laws and regulations. Some batteries may be
recycled, and may be accepted for disposal at your local recycling center. Check with your
municipality for recycling instructions.
Max. Output (BTU/HR)19,00016,000
Efficiency (w/the fan on)80%80%
Min. Inlet Gas Supply Pressure4.5" Water Column (11mb)11" Water Column (27mb)
Max. Inlet Gas Supply Pressure13" Water Column (17mb)13" Water Column (32mb)
Manifold Pressure (Under Flow Conditions)3.5" Water Column (9mb)10" Water Column (25mb)
GDS25-1
NGP
W415-2207 / B / 02.05.18
5
EN
general information
1.2 installation overview
78
6
5
2
1
3
4
6
SAFETY BARRIER
Recommended installation steps:
1. Determine venting requirements before deciding the final location of the appliance.
2. Place the appliance in its final position.
3. Create hole for appliance venting.
4. Install appliance venting (refer to “venting requirements” and “installation” sections).
5. Install all electrical wirings (refer to “wiring diagram” section).
6. Install gas lines (refer to “gas installation” section).
7. Complete finishing (refer to “finishing” section).
8. Test appliance (refer to “gas installation” section).
W415-2207 / B / 02.05.18
roof joist. If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood fl ooring, the
general information
WARNING
!
• Always light the pilot whether for the first time or if the gas supply has run out, with the glass door opened
or removed.
• Provide adequate clearance for servicing and operating the appliance.
• Provide adequate ventilation.
• Never obstruct the front opening of the appliance.
• Objects placed in front of the appliance must be kept a minimum of 48” (121.9cm) from the front face of
the appliance.
• Surfaces around and especially above the appliance can become hot. Avoid contact when appliance is
operating.
• Fire risk. Explosion hazard.
• High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test
pressures above 1/2 PISG (35mb). Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 PISG (35mb).
• Use only Wolf Steel approved optional accessories and replacement parts with this appliance using nonlisted accessories (blowers, doors, louvres, trims, gas components, venting components, etc.) could result
in a safety hazard and will void the warranty and certification.
• The appliance must not be operated at temperatures below freezing (32ºF/0ºC). Allow the appliance to
warm to above freezing prior to operation.
THIS GAS APPLIANCE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local
codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for
example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of
Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas
log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches (0.9m).
• A carbon monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed
combustion product.
The installation must conform with local codes or, in absence of local
codes, the National Gas and Propane Installation Code CSA B149.1
in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54
in the United States. Suitable for mobile home installation if installed
in accordance with the current standard CAN/CSA Z240MH Series,
for gas equipped mobile homes, in Canada or ANSI Z223.1 and
NFPA 54 in the United States.
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing
of that system at test pressures in excess of 1/2 psig (35 mb).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (35 mb). When installed
with a blower or fan, the junction box must be electrically connected and grounded in accordance with local codes. In the
absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI / NFPA 70 National
Electric Code in the United States. In the case where the blower is equipped with a power cord, it must be connected into a
properly grounded receptacle. The grounding prong must not be removed from the cord plug.
The following does not apply to inserts; as long as the required clearance to combustibles is maintained, the most desirable
and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat
created. The location of windows, doors and, the traffi c fl ow in the room where the appliance is to be located should be
considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
EN
appliance shall be installed on a metal or wood panel extending the full width and depth, unless otherwise tested.
W415-2207 / B / 02.05.18
7
SAMPLE
EN
general information
1.3 rating plate information
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2016, CERTIFIED TO / CERTIFIE CSA 2.22-2016 VENTED DECORATIVE GAS APPLIANCE / FOYER À GAZ VENTILÉ.
APPROVED FOR BEDROOM, BATHROOM & BEDSITTING ROOM INSTALLATION. SUITABLE
FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT
STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA
OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND
SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. FOR
USE WITH BARRIER W010-3295. FOLLOW THE INSTALLATION INSTRUCTIONS
LOCATED IN THE INSTALLATION MANUAL
9700539 (WSL) 4001657 (NGZ)
MANIFOLD PRESSURE: 3.5” W.C. (NG)
4001658 (NAC) 4001659 (WUSA)
PRESSION AU COLLECTEUR: 3.5" D'UNE
COLONNE D'EAU(GN)
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
FOR USE WITH GLASS DOORS CERTIFIED
WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO
THE APPLIANCE, WHICH WILL COME IN
CONTACT WITH THE FLAMES, OTHER THAN
THAT SUPPLIED BY THE MANUFACTURER
WITH THE APPLIANCE.
ELECTRICAL RATING: 115V 1.5AMP 60HZ
THE APPLIANCE MUST BE VENTED USING
THE APPROPRIATE WOLF STEEL VENT
KITS. SEE OWNERS INSTALLATION MANUAL
FOR VENTING SPECIFICS. MINIMUM AND
MAXIMUM VERTICAL VENT LENGTHS ARE 3
FEET AND 40 FEET RESPECTIVELY.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE. ONTARIO L4M 0G8 CANADA
NOT FOR USE WITH SOLID FUEL
MINIMUM AND MAXIMUM HORIZONTAL
VENT LENGTHS ARE 10 INCHES AND 20
FEET RESPECTIVELY. PROPER REINSTALLATION AND RESEALING IS NECESSARY
AFTER SERVICING THE VENT-AIR INTAKE
SYSTEM.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIAL:
A4"
B2"
C2"
VENT TOP 2" TO CEILING FROM
VENT BOTTOM 1" STOVE TOP 48”
VENT SIDES 1"
GDS25N
MODEL
HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, UNE SALLE DE BAIN ET
UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON
INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE
MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS
DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES,
TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT
ETRE APPLIQUEE, SE REFERER A LA NORME RELATIVE AU CRITERE DE MESURES DE
SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS
MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A. POUR UNE
UTILISER AVEC BARRIÈRE W010-3295. SUIVEZ LES INSTRUCTIONS D'INSTALLATION
GDS25P
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE
UTILSE AVEC CET APPAREIL
UTILISER AVEC LES PORTES VITREES
HOMOLOGUEES SEULEMENT AVEC CETTE
UNITE.
AVERTISSEMENT: N'AJOUTEZ PAS A CET
APPAREIL AUCUN MATERIAU DEVANT
ENTRER EN CONTACT AVEC LES FLAMMES
AUTRE QUE CELUI QUI EST FOURNI AVEC
CET APPAREIL PAR LE FABRICANT.
CLASS.: 115V 1.5AMP 60HZ L'APPAREIL
DOIT EVACUER SES GAZ EN UTILISANT
L'ENSEMBLE D'EVACUATION PROPRE A
WOLF STEEL. REFERER AU MANUEL
D'INSTALLATION DE PROPRIETAIRE POUR
L'EVACUATION PRECISE. LES LONGUEURS
VERTICALES MINIMALES ET MAXIMALES
SONT3 PIEDS ET 40 PIEDS
RESPECTIVEMENT.
SERIAL NUMBER / NO. DESERIE
SE TROUVENT DANS LE MANUEL D'INSTALLATION.
GDS25
MANIFOLD PRESSURE: 10” W.C. (LP)
PRESSION AU COLLECTEUR: 10" D'UNE
MIN SUPPLY PRESSURE: 11" W.C.(LP)
PRESSION D'ALIMENTATION MIN: 11"
D'UNE COLONNE D'EAU (P)
MAX. SUPPLY PRESSURE: 13" W.C. (LP)
PRESSION D'ALIMENTATION MAX: 13"
D'UNE COLONNE D'EAU (P)
LES LONGUEURS HORIZONTALES MINIMALES ET
MAXIMALES SONT 10 POUCES ET 20 PIEDS
RESPECTIVEMENT.
IL EST IMPORTANT DE BIEN REINSTALLER ET
RESCELLER L'EVENT APRES AVOIR ASSURE LE
MAINTIEN DU SYSTEME DE PRISE D'AIR.
DEGAGEMENTS MINIMAUX DES MATERIAUX
COMBUSTIBLES:
A4"
B2"
C2"
EVENT SUPERIEUR 2" ENTRE LE DESSUS
DU FOYER
EVENT INFERIEUR 1" ET LE PLAFOND 48”
COTES DE L'EVENT 1"
This illustration is for referece only. Refer to the rating plate on the appliance for accurate information.
note:
The rating plate must remain with the appliance at all times. It must not be removed.
COLONNE D'EAU(P)
AFUE: 64%
W385-1962 / A
1.4 mobile home installation
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home
Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas
indicated on the rating plate.
This mobile/manufactured home listed appliance comes factory equipped with a means to secure the appliance. Built
in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the base.
Use appropriate fasteners, inserted through the holes in the base to secure. For free standing products contact your
local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must
be fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and
the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting the
appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible
for use with other gases, unless a certifi ed kit is used.
Conversion Kits
This appliance is fi eld convertible between Natural Gas (NG) and Propane (P).
To convert from one gas to another, consult your Authorized dealer/distributor.
note:
Conversion kits are not available for Vent Free appliances.
8
W415-2207 / B / 02.05.18
1.5 hardware list
general information
EN
1
DescriptionQuantity
1/4” Hex Head Screw3
1
1 3/4” Pan Head Screw4
2
note:
Only fasteners supplied with the appliance are illustrated.
2
W415-2207 / B / 02.05.18
9
25 5/8"
651mm
23 5/8"
600mm
17 1/2"
445mm
23 1/2"
597mm
12 3/4"
324mm
Ø
4"
102mm
Ø
7"
178mm
SAFETY BARRIER
EN
general information
1.6 dimensions
FRONT VIEW
RIGHT SIDE VIEW
TOP VIEW
10
W415-2207 / B / 02.05.18
2.0 venting requirements
WARNING
!
• Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
• If venting is included with spacers, the vent system must be supported every 3’(0.9m) for both vertical and horizontal runs.
Use support ring assembly W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to
combustibles for both vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to
maintain an even air gap to the outer pipe. This gap is required for safe operation. A spacer is required at the start, middle,
and end of each elbow to ensure this gap is maintained. These spaces must not be removed.
This appliance uses a 4” (102mm) exhaust / 7” (178mm) air intake vent pipe system. Refer to the section applicable
to your installation.
For safe and proper operation of the appliance, follow the venting instructions exactly. Deviation from the minimum vertical
vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes
(5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through
unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize
condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for
400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.
note:
If for any reason the vent air intake system is disassembled, re-install per the instructions provided for the initial installation.
note:
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
alternate constructions such as a chimney as part of the vent system is not permitted.
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components.
Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles
and air terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Simpson Dura-Vent,
Selkirk Direct Temp, American Metal Amerivent and Metal-Fab, follow the installation procedure provided with the venting
components or on the website for your venting supplier. A starter adaptor must be used with the following vent systems and
may be purchased from the corresponding supplier:
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high
temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all
other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed
using the black high temperature sealant Mill Pac. High temperature sealant must be ordered separately.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following termination kits: wall terminal kit GD-222, GD-222R, or 1/12 to 7/12 pitch roof terminal kit GD-110, 8/12 to 12/12 roof terminal
kit GD-111, fl at roof terminal kit GD-112 or periscope kit GD-201 (for wall penetration below grade). With fl exible venting, in
conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD-220 or the 10 foot (3.1m) vent kit GD-330.
For stoves only: wall terminal kit GD-175 (venting included).
Starter Adapter Part Number SupplierWebsite
W415-2207 / B / 02.05.18
11
!
WARNING
• Risk of fire. Maintain specified air space clearances to vent pipe and appliance.
• If venting is included with spacers, the vent system must be supported every 3’(0.9m) for both vertical and horizontal runs. Use support ring assembly W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air gap to the outer pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this gap is maintained. These spaces must not be removed.
This appliance uses a 4” (102mm) exhaust / 7” (178mm) air intake vent pipe system. Refer to the section applicable to your installation.
For safe and proper operation of the appliance, follow the venting instructions exactly. Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for 400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance flue collar which must be sealed using the black high temperature sealant Mill Pac. High temperature sealant must be ordered separately.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab, follow the installation procedure provided with the venting components or on the website for your venting supplier. A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
note:
If for any reason the vent air intake system is disassembled, re-install per the instructions provided for the initial installation.
note:
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
This template must be used in conjunction with templates 7.1.1 or 7.1.2, depending on termination shape (i.e. round, or round and square). See appropriate templates folder.
EN
venting requirements
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not
be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20
feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” rise per foot or 0mm rise per meter however for optimum performance it is recommended
that all horizontal runs have a minimum 1/4” rise per foot or 21mm rise per meter using fl exible venting. For safe and proper
operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings
and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” (31.8mm) air gap
all around between the inner liner and outer liner is required for safe operation.
12
W415-2207 / B / 02.05.18
2.1 typical venting installation
24” (61cm) MIN.
REGARDLESS OF
HORIZONTAL VENT
LENGTH
25 5/8”
(65.1cm)
venting requirements
16” (40.6cm)
EN
40FT (12m)
MAX
3FT (1m)
MIN
24” (61cm)
MAXIMUM
25 5/8”
(65.1cm)
WARNING
!
• The maximum horizontal run with a 57” (1.45m) vertical rise immediately above the appliance is 20 feet
(6.1m).
W415-2207 / B / 02.05.18
13
EN
venting requirements
2.2 special vent installations
2.2.1 periscope termination
Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum of 12” (305mm) above grade. The maximum allowable vent length is
10’ (3.1m) for a fi replace and 8’ (2.4m) for a stove.
WARNING
!
• Below grade installation maximum
8ft (2.4m) vent length.
• Use GD201 periscope kit.
• Horizontal run not to exceed vertical rise.
12”
(305mm) MIN
TO GRADE
24” (610mm) MIN.
REGARDLESS OF OF
HORIZONTAL VENT
LENGTH
25 5/8”
(651mm)
2.2.2 corner termination
SAFETY
BARRIER
24” (610mm)
MAX.
14
W415-2207 / B / 02.05.18
2.3 vent terminal clearances
Covered balcony applications
venting requirements
R
EN
††*
Q
S
P
G
Q
= 3 feet
MIN
(0.9m)
INSTALLATIONS
CANADAU.S.A.
12” (30.5cm)12” (30.5cm)Clearance above grade, veranda porch, deck or balcony.
A
Δ
12” (30.5cm)
B
12” (30.5cm)*12” (30.5cm)*Clearance to permanently closed windows.
C
D
E
F
G
H
I
J
K
L
M
18”
(45.7cm)**
12” (30.5cm)**12” (30.5cm)**Clearance to unventilated soffi t.
0” (0mm)0” (0mm)Clearance to an outside corner wall.
0” (0mm)***0” (0mm)***
2” (51mm)***2” (51mm)***Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
3’(0.9m)3’(0.9m)****
3’ (0.9m)3’ (0.9m)****Clearance to a service regulator vent outlet.
12” (30.5cm)9” (229mm)Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
6’ (1.8m)3’ (0.9m) †Clearance to a mechanical air supply inlet.
7’ (2.1m) ‡7’ (2.1m) ****Clearance above a paved sidewalk or paved driveway located on public property.
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
9” (229mm) ΔClearance to windows or doors that open.
18”
(45.7cm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15’ (4.6m).
note:
Wall terminals are for illustration purposes only. Size and
shapes may vary.
R
= 2 x
MAX
Q
ACTUAL
R
MAX
≤ 15 feet
(4.6m)
16” (40.6cm)16” (40.6cm)Clearance above the roof.
N
2’ (0.6m)†*2’ (0.6m) †*Clearance from an adjacent wall including neighbouring buildings.
O
8’ (2.4m)8’ (2.4m)
P
3’ (0.9m)3’ (0.9m)See chart for wider wall dimensions.
Q
6’ (1.8m)6’ (1.8m)
R
12” (30.5cm)12” (30.5cm)Clearance under a covered balcony
S
ΔThe terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18 inches clearance from an inside corner.
****This is a recommended distance. For additional requirements, check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements, check local codes.
††*Permitted only if the balcony is fully open on a minimum of one side.
Roof must be non-combustible without openings.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
note:
Clearances are to be in accordance with local
installation codes and the requirements of the gas
supplier. In their absence, clearances are to be as
listed above and are based on national codes.
W415-2207 / B / 02.05.18
15
EN
venting requirements
2.4 horizontal termination
39’ 2”
V
V+H ≤ 40 ft. (For longer vent runs, a power
vent is required).
H ≤ 20 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
5 1/2 elbow zone
30’
4 1/2 elbow zone
3 1/2 elbow zone
2 1/2 elbow zone
1 1/2 elbow zone*
20’
4”
MAXIMUM
57”
24”
MINIMUM
0’
Centre of
Base of Air
Collar
15’
10’
5’
0’
10”
24”
MAXIMUM
5’
10’
15’
20’
25’
H
* 1 1/2 elbows constitute the 45°
elbow directly off the appliance
and an additional 90° elbow.
16
W415-2207 / B / 02.05.18
2.5 vertical termination
venting requirements
EN
V
20’
40’
30’
V+H ≤ 40 ft. (For longer vent runs, a power
vent is required).
H ≤ 20 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
6 1/2 elbow zone
5 1/2 elbow zone
4 1/2 elbow zone
3 1/2 elbow zone
2 1/2 elbow zone
1 1/2 elbow zone*
3’
MINIMUM
0’
Centre of
Base of Air
Collar
15’
10’
5’
0’
4”
MINIMUM
5’
10’
15’
20’
25’
H
* 1 1/2 elbows constitute the 45°
elbow directly off the appliance
and an additional 90° elbow.
W415-2207 / B / 02.05.18
17
!
WARNING
EN
venting requirements
2.6 vertical through existing chimney
• Risk of fi re.
• Co-axial to co-linear venting confi gurations must only be used in a non-combustible chimney or enclosure.
Installation in a combustible enclosure could result in a fi re.
This appliance is designed to be attached to a 3” (76.2mm) co-linear aluminum fl ex vent system running the full
length of a masonry chimney.
The fl ex liners accommodate any contours of a
masonry chimney, however, it is necessary to keep
the fl exible liners as straight as possible. The inlet
air collar of the termination cap must be connected
to the air intake fl ex liner and the exhaust collar
must be connected to the exhaust fl exible liner.
Both Simpson Duravent and Selkirk co-linear to
co-axial adaptors have been approved on this
appliance
AIR
INTAKE
TERMINATION
EXHAUST
FLUE
FLEX
LINER
note:
A vent adaptor will be required directly off the appliance.
Different manufacturer’s venting
components must not be combined.
Once the preferred manufacturer’s
appliance adaptor has been attached, the
remainder of the system must be that of
the same manufacturer.
The only exception to this rule is to use
Wolf Steel’s approved 3” (76.2mm) fl ex
liner and co-linear termination.
* Measured from appliance fl ue collar
to termination fl ue collar
* 40 FT (12.2m)
MAX.
10 FT (3.1m)
MIN
COAXIAL TO
CO-LINEAR
ADAPATOR
APPLIANCE
VENT ADAPTOR
18
W415-2207 / B / 02.05.18
3.0 installation
!
WARNING
• Ensure to unpack all loose materials from inside the fi rebox prior to connecting the gas and electrical supply
• If your appliance is supplied with a remote, ensure the remote receiver is in the “OFF” position prior
to connecting the gas and electrical supply to the appliance.
• For safe and proper operation of the appliance, follow the venting instructions exactly.
• The appliance exhaust fl ue collar must be sealed using Mill Pac. All exhaust and intake vent pipe joints
must be sealed using red RTV high temp silicone sealant (W573-0002) (not supplied) or black high temp Mill
Pac (W573-0007) (not supplied).
• If using pipe clamps to connect rigid vent components, a minimum of 3 screws must also be used to ensure
the connection cannot slip off.
• Do not clamp the fl exible vent pipe.
• Risk of fi re, explosion, or asphyxiation. Improper support of the entire venting system may allow vent to sag
and separate. Use vent run supports and connect vent sections per installation instructions.
• Risk of fi re, do not allow loose materials or insulation to touch the vent pipe. Remove insulation to allow for the
installation of the attic shield and to maintain clearances to combustibles.
• Do not fi ll the space between the vent pipe and enclosure with any type of material. Do not pack insulation
or combustibles between ceiling fi restops. Always maintain specifi ed clearances around venting and fi restop
systems. Install wall shields and fi restops as specifi ed. Failure to keep insulation or other materials away from
vent pipe may cause fi re.
EN
W415-2207 / B / 02.05.18
19
This application occurs when venting through a roof. Installation kits for
WARNING
EN
installation
3.1 horizontal installation
!
• The fi restop assembly must be installed with the vent shield to the top.
• Terminals must not be recessed into a wall or siding more than the depth of the return fl ange of the mounting
plate.
This application occurs when venting through an exterior
wall. Having determined the correct height for the air
terminal location, cut and frame a hole in the exterior wall,
as illustrated, to accommodate the fi restop assembly. Dry
fi t the fi restop assembly before proceeding to ensure the
brackets on the rear surface fi t to the inside surface of the
horizontal framing.
The length of the vent shield may be cut shorter for
combustible walls that are less than 8 1/2” (215.9mm)
thick but the vent shield must extend the full depth of the
combustible wall.
note:
Do not fi ll the air space between the fi restop spacer and the
exterior wall with any type of insulating material (i.e. spray foam).
A. Assemble the shield to the spacer as shown, using the 3
shorter screws supplied.
B. Place the fi restop top so that the vent shield covers the top of
the vent within the opening. Ensure that both spacer and shield
maintain the required clearance to combustibles.
C. Secure the spacer in place using the 4 longer screws supplied.
Once the vent pipe is installed in its fi nal position, apply sealant between the pipe and the fi restop spacer.
3.2 vertical installation
CAULKING
FIRESTOP
SPACER
CAULKING
10 11/16”
ADD
(27.14cm)
VENT
SHIELD
note:
The above is for illustration purposes only. Vents
do not always pass through center of frame.
HEIGHT
HIGH
FINISHING
MATERIAL
10 11/16”
ADD
(27.14cm)
WIDTH
WIDE
DETERMINE
THE
CORRECT
HEIGHT
various roof pitches are available from your authorized dealer / distributor.
See the “accessories” section to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening,
as illustrated, in the ceiling and the roof to provide the minimum 1"
(25mm) clearance between the vent pipe and any combustible material.
Try to center the vent pipe location midway between two joists to
prevent having to cut them. Use a plumb bob to line up the center of
the openings. A vent pipe shield will prevent any materials such as
insulation, from fi lling up the 1" (25mm) air space around the pipe. Nail
headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the
Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished
ceiling), and secure over the opening in the ceiling. A fi restop must be
placed on the bottom of each framed opening in a roof or ceiling that
the venting system passes through. Apply a bead of caulking all around
and place a fi restop spacer over the vent shield to restrict cold air from
being drawn into the room or around the fi replace. Ensure that both
spacer and shield maintain the required clearance to combustibles.
Once the vent pipe is installed in its fi nal position, apply Mill Pac sealant
(W573-0007) (not supplied) or red RTV silicone (W573-0002) (not
supplied) between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end
of the shield and tighten. This will prevent any materials, such as
insulation, from fi lling up the 1" (25mm) air space around the pipe.
Vent Pipe
Shield
Vent
Pipe
Shield
Firestop
underside
of joist
Caulking
Vent
Pipe
Collar
20
W415-2207 / B / 02.05.18
3.3 horizontal air terminal installation
A. Stretch the inner fl ex pipe to the required length taking
depth of its return fl ange.
ADD FASTENER TYPE
Pipe
Telescopic sleeve
Venting
TOP VENT
20" (51cm)
Coupler
REAR VENT
Air terminal
Air terminal
Telescopic sleeve
20" (51cm)
Coupler
Venting
WARNING
!
• Terminals must not be recessed into a wall or siding more than the depth of the return flange of the
mounting plate.
• Do not allow the inner flex pipe to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight.
into account the additional length needed for the fi nished
wall surface. Apply a heavy bead of the red RTV silicone
(W573-0002) (not supplied) to the inner sleeve of the air
terminal. Slip the vent pipe a minimum of 2” (50.8mm)
over the inner sleeve of the air terminal and secure with a
minimum of 3 screws.
B. Using the outer fl ex pipe, slide over the outer combustion
air sleeve of the air terminal and secure with a minimum
of 3 screws. Seal using red RTV silicone (W573-0002)
(not supplied).
C. Insert the vent pipes through the fi restop maintaining
the required clearance to combustibles. Holding the air
terminal (lettering in an upright, readable position), secure
to the exterior wall and make weather tight by sealing
with caulking (not supplied).
D. If more vent pipe needs to be used to reach the fi replace,
E. Stove Appliances Only: From inside the house, using
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the
couple them together, as illustrated. The vent system
must be supported approximately every 3 feet (0.9m) for
both vertical and horizontal runs. Use non-combustible
strapping to maintain the minimum clearance to
combustibles.
Red RTV Silicone (W573-0002) (not supplied), seal
between the vent pipe and the fi restop. Then slide the black trim collar over the vent pipe up to the
fi restop.
Type 1 (x3)
Caulking
Screws
(Supplied)
Red RTV Silicone
Outer Flex
Pipe
ADD GRAPHIC
installation
Type 2 (x4)
Inner Flex
Pipe
Outer Rigid Pipe
2" (50.8mm) Overlap
Red RTV Silicone
Inner Flex
Outer Flex Pipe
Screws
Inner Coupler
Outer Coupler
Outer Rigid
Outer Flex
Pipe
Pipe
EN
3.4 extended horizontal and corner air terminal installation
FOR REAR VENT ONLY: A 45° corner installation can have 0” (0mm)
rise between the appliance combustion air collar and the air terminal.
In this case, vent lengths must be kept to a maximum of 24” (61cm).
For longer vent lengths, a minimum vertical rise of 24” (61cm) is required.
A. Follow the instructions for "horizontal air terminal installation" section.
B. Continue adding components alternating inner rigid pipe and outer
rigid pipe. Ensure that all inner rigid pipe and elbows have sufficient
vent spacers attached and each component is sealed and securely
fastened to the one prior. Attach the inner telescopic sleeve to the
vent run. Repeat using the outer telescopic sleeve. Seal and secure
as before. To facilitate completion, attach inner and outer couplers
to the air terminal.
C. Install the air terminal. See “horizontal air terminal installation” section.
Extend the outer telescopic sleeve; connect to the air terminal assembly.
Fasten with self tapping screws and seal.
AIR TERMINAL
20" (508mm)
COUPLER
TELESCOPIC SLEEVE
VENTING
Add Image
W415-2207 / B / 02.05.18
21
air terminal installation” section.
!
WARNING
EN
installation
3.5 vertical air terminal Installation
• Maintain a minimum 2” (51mm) space between the air inlet base and the storm collar.
note:
Fastening hardware provided with appropriate roof terminal and liner kits.
A. Fasten the roof support to the roof using 6 screws. The roof support is
optional. In this case, the venting is to be adequately supported using
either an alternate method suitable to the authority having jurisdiction or
the optional roof support.
B. Stretch the inner fl ex pipe to the required length. Slip the inner fl ex
pipe a minimum of 2” (51mm) over the inner pipe of the air terminal
connector and secure with a minimum of three screws, when 4/7, 5/8
and 3/5 venting is used and a minimum of six screws when using 8/10
or 8/11 venting. Seal using a heavy bead of red RTV silicone (W573-
0002) (not supplied).
C. Repeat using the outer fl ex pipe, using a heavy bead of red RTV
silicone (W573-0002) (not supplied) and a minimum of three screws,
when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws
when using 8/10 or 8/11 venting.
D. Thread the air terminal connector / vent pipe assembly down through
the roof. The air terminal must be positioned vertically and plumb.
Attach the air terminal connector to the roof support, ensuring that the
top of the air terminal is 16” (40.6cm) above the highest point that it
penetrates the roof.
E. Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” (19mm) of the air terminal connector showing above
the top of the fl ashing. Slide the fl ashing underneath the sides and
upper edge of the shingles. Ensure that the air terminal connector is
properly centered within the fl ashing, giving a 3/4” (19mm) margin all
around. Fasten to the roof. Do not nail through the lower portion of the
fl ashing. Make weather-tight by sealing with caulking. Where possible,
cover the sides and top edges of the fl ashing with roofi ng material.
F. Aligning the seams of the terminal and air terminal connector, place the
terminal over the air terminal connector making sure the vent pipe goes
into the hole in the terminal. Secure with a minimum of three screws,
when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws
when using 8/10 or 8/11 venting.
G. Apply a heavy bead of weatherproof caulking 2” (51mm) above the
fl ashing. Install the storm collar around the air terminal and slide down
to the caulking. Tighten to ensure that a weather-tight seal between the
air terminal and the collar is achieved.
H. If more vent pipe needs to be used to reach the appliance, see “horizontal
Connector
2” (51mm)
Roof Support
Air
Terminal
Inner Flex Pipe
Inner Pipe
Red RTV
Silicone
(W572-0002)
Outer Flex Pipe
Outer Rigid Pipe
Air Inlet
Base
Caulking
Sto r m Collar
Weather
Sealant
Flashing
22
W415-2207 / B / 02.05.18
3.6 appliance vent connection
A. Attach the adjustable pipe to the last section of rigid pipe. Secure with
!
WARNING
• Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.
screws and seal.
B. Install the inner fl ex pipe to the appliance. Secure with a minimum of
three screws and fl at washers when installing 3”/5”, 4”/7” or 5”/8”
venting, or six screws and fl at washers when installing 8”/10” or
8”/11” venting. Seal the joint and screw holes using Mill Pac sealant
(W573-0007) (not supplied).
C. Run a bead of high temperature red RTV silicone (W573-0002) (not
supplied) around the inside of the air intake collar. Pull the adjustable
pipe a minimum 2” (50.8mm) into the air intake collar.
note:
Always fi nish vent system installation with the appliance vent connection. Ensure that the sealant is not visible on the
exterior pipes once installation is completed. An optional decorative black band may be available with this appliance.
In the event that the venting must be disassembled, care must be taken to reseal the venting.
3.7 gas installation
• Risk of fi re, explosion, or asphyxiation. Ensure there are no ignition sources such as sparks or open fl ames.
• Support gas control when attaching gas supply pipe to prevent damaging gas line.
• Always light the pilot whether for the fi rst time or if the gas supply has run out with the glass door opened
or removed. Purging of the gas supply line should be performed by a qualifi ed service technician. Ensure
that a continuous gas fl ow is at the burner before closing the door. Ensure adequate ventilation. For gas and
electrical locations, see “dimensions” section.
• All gas connections must be contained within the appliance when complete (gas fi replaces only).
• High pressure will damage valve. Disconnect gas supply piping before testing gas line at test pressures above
1/2 PSIG.
• Valve settings have been factory set, do not change.
installation
#8 X 1/2”
Self Drilling
Screws
INSERT
2” (50.8mm)
IMAGE HERE
Overlap
High Temperature
Sealant
EN
Installation and servicing to be done by a qualifi ed installer.
• Move the appliance into position and secure.
• If equipped with a fl ex connector, the appliance is designed to accept a 1/2” (13mm) gas supply. Without the
connector, it is designed to accept a 3/8” (9.5mm) gas supply. The appliance is equipped with a manual shut
off valve to turn off the gas supply to the appliance.
• Connect the gas supply in accordance to local codes. In the absence of local codes, install to the current
CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI Z223.1 / NFPA
54 in the United States.
• When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
• The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner assembly
on its side to aid with servicing components.
W415-2207 / B / 02.05.18
23
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
ENTIRELY OF NON-COMBUSTIBLE MATERIALS (I.E. STEEL STUDS, CEMENT BOARD, ETC.).
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
!
WARNING
EN
installation
3.8 minimum clearance to combustibles
WARNING
!
• Minimum clearance to combustibles must be maintained or a serious fire hazard could result.
• Framing or finishing materials closer than the minimums listed must be constructed entirely of non-combustible materials (i.e. steel studs, cement board, etc.).
• Never obstruct the front opening of the appliance.
As long as clearance to combustibles is kept within the required distances, the most desirable and beneficial
location for a Napoleon® appliance is in the centre of a building, thereby allowing the most efficient use of the
heat created. The location of windows, doors and the traffic flow in the room where the appliance is to be located
should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a floor or roof joist.
A.4” (102mm) B.2” (51mm)* C.2” (51mm)
To ceiling from appliance top 48” (1219mm)
Horizontal vent:
Sides and bottom 1” (25mm)
Top 2” (51mm)
Vertical vent:
All sides 1” (25mm)
*At a distance of 2” (51mm) from the wall, installation or service to the blower may not be practical. A minimum of
5” (127mm) will be required in order to install the blower.
If less than 5” (127mm) clearance is maintained between the back of the appliance and the back wall, it will be
necessary to disconnect the venting and gas pipe to move the appliance out for installation or service of the
blower.
24
W415-2207 / B / 02.05.18
COMBUSTIBLE
MANTE
TRIM M
ETC.) ARE CLEARLY MAINTAINED.
!
WARNING
25
EN
3.9 minimum mantel or shelf clearances
WARNING
!
• Risk of fire!
• Maintain all specified air space clearances to combustibles.
• Failure to comply with these instructions may cause a fire or cause the appliance to overheat.
• Ensure all clearances (i.e. back, side, top, vent, hearth, mantel, front, etc.) are clearly maintained.
When the appliance is rear vented, a mantel or shelf may be installed above the GDS25-1 at a minimum distance
of 8” (203mm).
installation
EN
L OR
ATERIAL
8” (203mm)
MIN.
12” (305mm)
MAX. MANTEL DEPTH
2” (51mm)
COMBUSTIBLE
NON-COMBUSTIBLE
BRICK
1” (25mm)
0” (0mm) IF NONCOMBUSTIBLE
FINISHING IS
USED SUCH AS
BRICK AND STONE
24 1/2”
(622mm)
2”
(51mm)
W415-2207 / B / 02.05.18
25
Retainer
Door
Tab
Front
Bracket
Screws
Front
Front Legs
!
WARNING
GLASS MAY BE HOT, DO NOT TOUCH GLASS UNTIL COOLED.
the appliance.
from the side pieces by removing the screws from the brackets located in the upper inside corners.
remove.
FRONT
SCREWS
BRACKET
3
2
DOOR
RETAINER
FRONT
LEGS
TAB
FRONT
!
WARNING
RISK OF FIRE!
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
REMOVED, CRACKED, BROKEN OR SCRATCHED.
72.4
casting.
WARNING
EN
4.0 finishing
!
• Risk of fi re!
• Never obstruct the front opening of the appliance.
• Do not strike, slam, or scratch. Do not operate appliance with glass removed, cracked, or scratched.
4.1 cast front installation and removal
WARNING
!
• Glass may be hot.
• Do not touch glass until cooled.
A. Remove safety barrier.
B. Lift the top cast piece off of
the appliance.
C.Detach the front cast piece
from the side pieces by
removing the screws from the
brackets located in the upper
inside corners.
D.Slide the front straight up to
remove.
Follow the above steps in reverse in
order to reinstall the cast front. Ensure
that the tabs on the underside of the
front fit behind the front legs.
note:
It is not necessary to remove the cast front in
order to remove the door.
4.2 safety barrier installation and removal
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance
and shall be installed.
A. Lift the top casting up and remove the safety barrier. Remove and discard plastic.
B. Tilt the top of the safety barrier and hook under the top casting, make sure to hold the safety barrier.
C. Slightly lift the bottom of the safety barrier and push onto theappliance. Careful not to scratch the bottom
casting.
D.Reverse these steps to remove.
SAFETY BARRIER
SAFETY BARRIER
26
W415-2207 / B / 02.05.18
LATCHES
DOOR
4.3 glass door installation and removal
WARNING
!
• Do not substitute materials.
A. Remove safety barrier.
B. Lift the top cast piece off of the appliance.
C. Pull handle and rotate 90°.
D. Slide the door straight up to remove.
Follow the above steps in reverse in order to reinstall the door.
Ensure that the bottom of the door engages the door retainer
before closing the latches.
finishing
EN
4.4 log placement
WARNING
!
• Logs must be placed in the exact location in appliance. Do not change from the proper log positions, as
appliance may not function properly.
• The logs are fragile and should be handled with care.
It is not necessary to remove the cast front, however, this will make for a more simple log installation.
In order to assemble the log set, the glass door must be removed, see “cast front / glass door installation and
removal” section.
BRACKET
LOG LOCATING SCREWS
A. Place the rear log, as shown, onto the rear log
support brackets. Ensure the cutout on the left
underside of the log, fits over the pilotassembly. Bend the bracket on the left side to help
retain the rear log.
W415-2207 / B / 02.05.18
27
MAIN
BURNER
SWITCH
ACCENT
LIGHT
SWITCH
FAN
CONTROL
LOGO
1/2”
1/2”
C.Place the hole in the underside of log #3 onto
the locating screw, on the right side of the burner. The bottom branch of log #3 sits in front of, and against, the right end of log #2.
D.Reinstall the glass door & front.
EN
finishing
B. Place the hole in the underside of log #2
onto the locating screw, on the left side of the
burner. The fibre burner is formed to cradle the
centre of the log.
4.5 logo placement
Remove the backing from the logo and position onto the control door as shown.
C.Place the hole in the underside of log #3 onto
the locating screw, on the right side of the
burner. The bottom branch of log #3 sits in
front of, and against, the right end of log #2.
D.Reinstall the glass door & front.
W415-2207 / B / 02.05.18
28
5.0 optional blower installation
WARNING
!
• Ensure the appliance is completely cool before starting installation.
• To avoid danger of suffocation, keep the packaging bag away from babies and children. Do not use in
cribs, beds, carriages, or play pens. This bag is not a toy. Knot before throwing away.
A. Disconnect power supply from the appliance.
B. Open the control door located at the bottom front of the appliance (FIG. 1).
C. Remove the 2 screws holding the left control box cover (FIG. 2).
D. Slide the control box cover forward and remove from the appliance (FIG. 3 and 4).
FIG. 1FIG. 2
EN
FIG. 3
FIG. 4
W415-2207 / B / 02.05.18
29
EN
optional blower installation
E. Access blower wire leads. Remove 2 insulation connectors from blower wire leads.
F. Route the blower wire through the rear hole of the housing (FIG. 5 and 6).
G. Snap bushing over blower wire and press into rear hole of housing.
H. Place blower housing close to the rear of the appliance. Route wire through hole in blower housing and
connect the spade connectors to blower (FIG. 7).
I.Align the blower to the rear side of the control box and fasten it with 2 screws included with the kit (FIG. 8).
J. Re-install control box side cover to the control box using the 2 screws previously removed in Step C.
K. Close the control door (FIG. 9).
L. Reconnect power supply to the appliance.
FIG. 5
FIG. 7
FIG. 6
BUSHING
Rear Hole
Wire Harness
FIG. 8
Spade Connectors
FIG. 9
30
W415-2207 / B / 02.05.18
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.