Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
- Do not store or use gasoline or other
fl ammable vapors and liquids in the vicinity of
this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the fi re department.
B30PTR-1 / B30PTRE-1
FRENCH
PG. 69
INSTALLATION AND
ADD MANUAL TITLE
OPERATION MANUAL
Product Name / Code
(MUST use title from Price Book)
SAFETY BARRIER
ADD PRODUCT IMAGE
Ascent™ 30
ADD ____ ILLUSTRATED
- Installation and service must be
performed by a qualifi ed installer, service
agency, or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certifi ed kit is used.
INSTALLER:
Leave this manual with the appliance
CONSUMER:
Retain this manual for future reference
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030
CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES
CSA /
INTERTEK
LOGO
FOR INDOOR USE ONLY
CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS:
IF INSTALLATION + OPERATION, ADD SERIAL
NUMBER LABEL HERE
IF SEPARATE MANUALS, ADD “PLACE
BARCODE LABEL ON THE OWNER’S MANUAL”
$10.00
W415-1768 / B / 08.10.18
EN
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals.
!
WARNING
safety information
• This appliance is hot when operated and
can cause severe burns if contacted.
• Any changes or alterations to this
appliance or its controls can be
dangerous and is prohibited.
• Do not operate appliance before reading and
understanding operating instructions. Failure
to operate appliance according to operating
instructions could cause fi re or injury.
• Ensure the glass door is opened or removed
when lighting the pilot for the fi rst time and
when the gas supply has run out.
• Risk of fi re or asphyxiation, do not operate
appliance with fi xed glass removed and never
obstruct the front opening of the appliance.
• Do not connect 110 volts to the control valve,
with the exception of models; GSST8 and
GT8.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during
installation. Sheet metal edges may be sharp.
• Do not burn wood or other materials in this appliance.
• Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing
and operating the appliance.
• High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at
test pressures above 1/2 psig. Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 psig (35mb).
• The appliance must not be operated at temperatures below freezing (32°F / 0°C). Allow the appliance
to warm to above freezing prior to operation, with the exception of models; GSS36, GSS42; these
appliances are suitable for 0°F / -18°C.
• Children and adults should be alerted to hazards of high surface temperature and should stay
away to avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to accidental contact
burns. A physical barrier is recommended if there are at risk individuals in the house. To
restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers,
young children and other at risk individuals out of the room and away from hot surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from
furniture and draperies.
• Furniture or other objects must be kept a minimum of 4 feet (1.22m) away from the front of the appliance.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot
surfaces.
• Even after the appliance is off, it will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children
from hot surfaces. These screens and guards must be fastened to the fl oor.
• Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior
to operating the appliance.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the
appliance and venting system are kept clean. The appliance and its venting system should be inspected
before use and at least annually by a qualifi ed service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and
free from combustible materials, gasoline and other fl ammable vapors and liquids.
• If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it
serviced. Keep burner and control compartment clean.
• Under no circumstances should this appliance be modifi ed.
• Do not allow wind or fans to blow directly into the appliance. Avoid any drafts that alter burner fl ame
patterns.
2
W415-1768 / B / 08.10.18
before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.
• If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it serviced. Keep burner and control compartment clean.
• Under no circumstances should this appliance be modified.
• Do not allow wind or fans to blow directly into the appliance. Avoid any drafts that alter burner flame
patterns.
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
!
WARNING
!
WARNING
WARNING
!
WARNING:
Electric
This product can expose you to chemicals including lead and lead compounds,
Gas, Wood
which are known to the State of California to cause cancer, and chemicals including BBP and DEHP, which are known to the State of California to cause birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
!
AVERTISSEMENT:
Ce produit peut vous exposer à des substances chimiques incluant le
plomb et les composés de plomb qui, selon l’État de Californie, causeraient le cancer, et des substances chimiques incluant le BBP et DEHP qui, selon d’État de Californie, causeraient des malformations congénitales ou autres dangers pour la reproduction. Pour de plus amples renseignements, visitez le www.P65Warnings.ca.gov.
!
ADVERTENICA:
Este producto puede exponerlo a productos químicos, entre ellos, plomoy compuestos con plomo, que el Estado de California reconoce como causantes de cáncer, y productos químicos, entre ellos, bencilbutilftalato (BBP, por sus siglas en inglés) y di(2-etilhex-il) ftalato (DEHP, por sus siglas en inglés), que el Estado de California reconoce como caus-antes de malformaciones congénitas u otros daños para la reproducción. Para obtener más información, visite www.P65Warnings.ca.gov.
• Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this
appliance.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning
appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has
been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person, if equipped.
• Do not strike or slam shut the appliance glass door, if equipped.
• Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As
with all plastic bags, these are not toys and should be kept away from children and infants.
• Carbon or soot should not occur in a vent free appliance as it can distribute into the living area of your
home. If you notice any signs of carbon or soot, immediately turn off your appliance and arrange to have
it serviced by a qualifi ed technician before operating it again.
• If equipped, the screen must be in place (closed) when the appliance is in operation.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating
to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of
the exhaust escaping through these openings can also cause the surrounding combustible materials to
overheat and catch fi re.
• Carbon monoxide poisoning may lead to death; early signs of carbon monoxide poisoning resemble the
fl u, with headache, dizziness and/or nausea. If you have these signs, the appliance may not be working
properly. Get fresh air at once! Have appliance serviced. Some people; pregnant women, persons with
heart or lung disease, anemia, those under the infl uence of alcohol, those at high altitudes are more
affected by carbon monoxide than others. Failure to keep the primary air opening(s) of the burner(s) clean
may result in sooting and property damage.
• As with any combustion appliance, we recommend having your appliance regularly inspected and
serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and
your family against Carbon Monoxide (not applicable for outdoor appliances).
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the
appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting,
discolouration or damage to decorations, a T.V. or other electronic components.
• For appliances equipped with a safety barrier; if the barrier becomes damaged, the barrier
shall be replaced with the manufacturer’s barrier for this appliance.
• Installation and repair should be done by a qualifi ed service person. It is imperative that control
• For outdoor products only: this appliance must not be installed indoors or within any structure that
• If applicable, the millivolt version of this appliance uses and requires a fast acting thermocouple. Replace
compartments, burners and circulating air passageways of the appliance be kept clean.
prevents or inhibits the exhaust gases from dissipating in the outside atmosphere.
only with a fast acting thermocouple supplied by Wolf Steel Ltd.
!
WARNING:
which are known to the State of California to cause cancer, and chemicals including carbon
monoxide, which are known to the State of California to cause birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
Add California Prop 65 warning
This product can expose you to chemicals including lead and lead compounds,
safety information
EN
!
FIRE RISK HAZARD / DELAYED IGNITION
High supply pressure will damage the valve / controls.
Disconnect the appliance main gas valve/control
from the supply piping when pressure testing that
system at pressures in excess of 1/2 psi (3.5 kPa).
Isolate the appliance with it’s shut off valve during
any pressure testing of the supply piping at
pressures equal to or less than 1/2 psi (3.5 kPa).
!
W415-1768 / B / 08.10.18
3
EN
table of contents
1.0 general information 5
1.1 rates and efficiencies 5
1.2 rating plate information 7
1.3 dimensions 8
2.0 venting requirements 9
2.1 typical vent installation 10
2.2 special vent installations 12
2.2.1 periscope termination 12
2.2.2 corner termination 12
2.3 minimum air terminal location
clearances 13
2.4 venting application flow chart 14
2.5 definitions 14
2.6 elbow vent length values 15
2.7 top exit horizontal termination 15
2.8 rear exit horizontal termination 17
2.9 top and rear exit vertical termination 19
2.10 rear exit 21
2.11 rear exit shield (for rear vent only) 21
2.12 top exit 22
3.0 rough framing 23
3.1 minimum framing dimensions 24
3.2 minimum enclosure clearances 25
4.0 venting installation 30
4.1 horizontal installation 31
4.2 vertical installation 31
4.3 using either flexible or rigid vent
components 32
4.3.1 horizontal air terminal installation 32
4.3.2 vertical air terminal installation 33
4.3.3 appliance vent connection 33
4.3.4 horizontal air terminal installation 34
4.3.5 vertical air terminal installation 35
4.4 vertical through existing chimney 36
4.4.1 restricting vertical vents 37
5.0 electrical information 38
5.1 battery back-up installation 39
5.2 optional wall switch 40
6.0 gas installation 40
7.0 operation (electronic) 41
8.0 operation (millivolt) 42
9.1 minimum framing dimensions 43
9.0 finish framing 43
10.0 finishing 44
10.1 safety barrier / door removal and
installation 44
10.2 front hood installation 45
10.3 non-combustible facing material 46
10.4 alcove clearances 47
10.5 minimum mantel clearances 47
10.6 recessed installation 48
10.7 log placement 49
10.8 charcoal embers 50
10.9 logo placement 50
11.0 adjustments 51
11.1 pilot burner adjustment 51
11.2 venturi adjustment 51
11.3 flame characteristics 52
11.4 optional anti condensation switch
(models B30NTRE-1 and B30PTRE-1
only) 52
12.0 maintenance 53
12.1 annual maintenance 54
12.2 door glass replacement 55
12.3 care of glass 55
13.0 replacement parts 56
13.1 overview 57
13.2 electronic valve train assembly 58
13.3 millivolt valve train assembly 59
14.0 accessories 60
15.0 troubleshooting (electronic) 61
16.0 troubleshooting (millivolt) 64
17.0 warranty 66
4
note:
The information throughout this manual is believed to be correct at the time of printing. Wolf Steel
Ltd. reserves the right to change or modify any information within this manual at any time without
notice. Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1768 / B / 08.10.18
Installer: please fill out the following information
Customer:
Address:
Date of Installation:
Location of the appliance
Installer:
Dealer/Distributor contact number:
Serial #:
Model:
standard checklist
EN
Natural Gas:B30NTR-1
B30NTRE-1
Propane:B30PTR-1
B30PTRE-1
1.0 general information
When the appliance is installed at elevations above 4,500ft (1372m), and in the absence of specific recommendations
from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each
additional 1,000ft (305m). Expansion / contraction noises during heating up and cooling down cycles are normal
and are to be expected. Change in flame appearance from “HI” to “LO” is more evident in natural gas than in
propane.
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is certified for mobile
home installation.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified kit is used.
note:
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the
appliance and must be installed.
The protective wrap on plated parts is best removed when the assembly is at room temperature but this can be
improved if the assembly is warmed, using a hair dryer or similar heat source.
This appliance is a decorative product. It is not a source of heat and not intended to burn solid fuel.
Batteries must be disposed of according to the local laws and regulations. Some batteries may be
recycled, and may be accepted for disposal at your local recycling center. Check with your
municipality for recycling instructions.
1.1 rates and efficiencies
Altitude (FT)0-4,5000-4,500
Max. Input (BTU/HR)15,00015,000
Min. Inlet Gas Supply Pressure4.5" (11mb) w.c.11" (27mb) w.c.
Max. Inlet Gas Supply Pressure13" (32mb) w.c.13" (32mb) w.c.
Manifold Pressure (Under Flow
Conditions)
Natural GasPropane
3.5" (9mb) w.c.10" (25mb) w.c.
W415-1768 / B / 08.10.18
5
EN
roof joist. If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood fl ooring, the
general information
WARNING
!
• Always light the pilot whether for the first time or if the gas supply has run out, with the glass door opened
or removed.
• Provide adequate clearance for servicing and operating the appliance.
• Provide adequate ventilation.
• Never obstruct the front opening of the appliance.
• Objects placed in front of the appliance must be kept a minimum of 48” (121.9cm) from the front face of
the appliance.
• Surfaces around and especially above the appliance can become hot. Avoid contact when appliance is
operating.
• Fire risk. Explosion hazard.
• High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test
pressures above 1/2 PISG (35mb). Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 PISG (35mb).
• Use only Wolf Steel approved optional accessories and replacement parts with this appliance using nonlisted accessories (blowers, doors, louvres, trims, gas components, venting components, etc.) could result
in a safety hazard and will void the warranty and certification.
• The appliance must not be operated at temperatures below freezing (32ºF/0ºC). Allow the appliance to
warm to above freezing prior to operation.
THIS GAS APPLIANCE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local
codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for
example in the state of Massachusetts:
• This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of
Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas
log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 36 inches (0.9m).
• A carbon monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed
combustion product.
The installation must conform with local codes or, in absence of local
codes, the National Gas and Propane Installation Code CSA B149.1
in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54
in the United States. Suitable for mobile home installation if installed
in accordance with the current standard CAN/CSA Z240MH Series,
for gas equipped mobile homes, in Canada or ANSI Z223.1 and
NFPA 54 in the United States.
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing
of that system at test pressures in excess of 1/2 psig (35 mb).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (35 mb). When installed
with a blower or fan, the junction box must be electrically connected and grounded in accordance with local codes. In the
absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI / NFPA 70 National
Electric Code in the United States. In the case where the blower is equipped with a power cord, it must be connected into a
properly grounded receptacle. The grounding prong must not be removed from the cord plug.
The following does not apply to inserts; as long as the required clearance to combustibles is maintained, the most desirable
and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat
created. The location of windows, doors and, the traffi c fl ow in the room where the appliance is to be located should be
considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
appliance shall be installed on a metal or wood panel extending the full width and depth, unless otherwise tested.
6
W415-1768 / B / 08.10.18
1.2 rating plate information
SAMPLE
To convert from one gas to another, consult your Authorized dealer/distributor.
Certified to Canadian and American National Standards: CSA 2.22-2016 / ANSI Z21.50-2016 for Vented Decorative Gas Appliances
Certifié selon les normes Nationales Canadiennes et Américaines: CSA 2.22-2016 / ANSI Z21.50-2016 pour les Appareils à gaz décoratif à évacuation
Direct vent, vented gas fireplace. Approved for bedroom, bathroom and bed-sitting room installation. Suitable for mobile home installation, if installed in accordance with the current
standard CAN / CSA Z240MH Series gas equipped mobile homes in Canada, or, in the United States, the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part
3280. When this US Standard is not applicable, use the Standard for Fire Safety Criteria for Manufactured Home Installations, Sites and Communities, ANSI / NFPA 501A. This appliance
must be installed in accordance with local codes, if any; if none, follow the current ANSI Z223.1 or CSA B149. For use with barrier W565-0154. Follow installation instructions.
Foyer à gaz ventilé. Homologué pour installation dans une chambre à coucher, une salle de bain et un studio. Approprié pour installation dans une maison mobile si son installation
conforme aux exigences de la norme CAN / CSA Z240MH Séries de maisons mobile équipées au gaz en vigueur au Canada, ou, aux États-Unis selon la norme 24 CFR, Part 3280,
Manufactured Home Construction and Safety Standard. Dans le cas ou cette norme d’États-Unis n’est pas pertinentes, utiliser la norme NFPA 501A, Fire Safety Criteria for Manufactured
Home Installations, Sites and Communities. Installer l’appareil selon les codes ou règlements locaux ou, en l’absence de tels règlements, selon les codes d’installation ANSI Z223.1 ou
CSA B149 en vigueur. Utiliser uniquement avec l’écran W565-0154. Suivre les instructions d’installation.
Altitude
Input
Reduced Input
P4
Manifold Pressure: 3.5” w.c. (NG)
Minimum Supply Pressure: 4.5” w.c. (NG)
Maximum Supply Pressure: 7”* w.c. (NG)
Pression au Collecteur: 3,5” d’une colonne d’eau (GN)
Pression d’Alimentation Min.: 4,5” d’une colonne d’eau (GN)
Pression d’Alimentation Max.: 7”* d’une colonne d’eau (GN)
*Maximum inlet pressure not to exceed 13”.
Minimum clearance to combustible materials:
Sides & back: per standoff spacers for framing and finishing
materials. For non-combustible framing and finishing materials,
see installation manual.
Top 0”
Floor 0”
Sides 0”
Back 0”
WARNING:
fast-acting thermocouple. Replace only with a fast-acting
thermocouple supplied by Wolf Steel Ltd.
WOLF STEEL LTD. 24 Napoleon Road, Barrie, ON, L4M 0G8 Canada
**Maximum horizontal extension: 2”. See installation manual
for greater extensions, minimum vent lengths and maximum
vent lengths.
MODEL / MODÈLE
0-4500ft (0-1370m)
15,000 BTU/h
10,000 BTU/h
51.7%
Élévation
Alimentation
Alimentation Réduite
Manifold Pressure: 10” w.c. (P)
Minimum Supply Pressure: 11” w.c. (P)
Maximum Supply Pressure: 13”* w.c. (P)
Pression au Collecteur: 10” d’une colonne d’eau (P)
Pression d’Alimentation Min.: 11” d’une colonne d’eau (P)
Pression d’Alimentation Max.: 13” d’une colonne d’eau (P)
*Pression d’alimentation maximale ne devait pas dépasser 13”.
Dégagements minimaux des matériaux combustibles:
Côtés et arrière: selon les espaceurs de dégagements pour les
matériaux d’ossature selon le manuel du propriétaire pour les
Dessus du conduit d’évent 3”
Côtés et dessous du conduit d’évent 1”
Tablette 12”**
Profondeur d’encastré 14 1/2”
AVERTISSEMENT:
thermocouple à action rapide. Remplacez uniquement avec
un thermocouple à action rapide de Wolf Steel Ltée.
**L’extension horizontale maximale: 2”. Référez au manuel d’installation
pour des extensions plus grandes, les longueurs d’évacuation minimaux et
matériaux de finition.
Dessus 0”
Plancher 0”
Côtés 0”
Cet appareil utilise et requiert un
Arrière 0”
maximum.
general information
Insert testing agency
logo
VENTED DECORATIVE GAS APPLIANCE: NOT A SOURCE OF
HEAT, NOT INTENDED FOR USE AS A HEATING APPLIANCE,
NOT FOR USE WITH SOLID FUEL.
APPAREIL À GAZ DÉCORATIF À ÉVACUATION: N’EST PAS
UNE SOURCE DE CHALEUR; N’EST PAS DESTINÉ À ÈTRE
UTILISÉ COMME UN APPAREIL DE CHAUFFAGE; NE
P4
CONVIENT PAS AUX COMBUSTIBLES SOLIDES.
FOR USE WITH GLASS DOORS CERTIFIED WITH THIS APPLIANCE ONLY.
POUR UTILISATION UNIQUEMENT AVEC LES PORTES EN VERRE
CERTIFIÉES AVEC L’APPAREIL.
WARNING: Do not add any material to the appliance which will come in contact with the
flames, other than that supplied by the manufacturer with the appliance.
AVERTISSEMENT: N’ajoutez pas à cet appareil aucun matériau devant entretien
contact avec les flammes autre que celui qui est fourni avec cet appareil par le fabricant.
The appliance must be vented using the appropriate Napoleon vent kits. See installation
manual for venting specifications. Proper reinstallation and resealing is necessary after servicing
the vent-air intake system.
L’appareil doit être ventilé à l’aide de l’ensemble d’évacuation propre à Napoleon. Référez au
manuel d’installation pour les spécifications d’évacuation. Il est nécessaire de bien réinstaller et
resceller l’évacuation après avoir executer l’entretien du système de prise d’air.
Optional fan kit: AUB
Ensemble de ventilateur facultatif: AUB
Electrical rating: 115V, 60HZ. Less than 12 amperes.
Spécifications électriques: 115V, 60HZ. Moins de 12 ampère.
Serial Number / N° de Série:
REFERENCE# 161746
B30
W385-1951 / E
EN
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
note:
The rating plate must remain with the appliance at all times. It must not be removed.
1.3 mobile home installation
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home
Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas
indicated on the rating plate.
This mobile/manufactured home listed appliance comes factory equipped with a means to secure the appliance. Built
in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the base.
Use appropriate fasteners, inserted through the holes in the base to secure. For free standing products contact your
local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must
be fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and
the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting the
appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible
for use with other gases, unless a certifi ed kit is used.
Conversion Kits
This appliance is fi eld convertible between Natural Gas (NG) and Propane (P).
W415-1768 / B / 08.10.18
7
EN
762mm
general information
1.4 dimensions
SAFETY BARRIER
34 5/8"
879mm
1 13/16"
46mm
355mm
GAS
INLET
30"
14"
170mm
136mm
8 5/8"
6 11/16"
24 3/16"
614mm
324mm
12 3/4"
8
W415-1768 / B / 08.10.18
102mm
4"
178mm
7"
2.0 venting requirements
WARNING
venting requirements
!
• Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
• The vent system must be supported every 3’(0.9m) for both vertical and horizontal runs. Use support ring assembly W0100067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both vertical and
horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air gap to the outer
pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this
gap is maintained. These spaces must not be removed.
This appliance uses a 4” (102mm) exhaust / 7” (178mm) air intake vent pipe system. Refer to the section applicable
to your installation.
For safe and proper operation of the appliance, follow the venting instructions exactly. Deviation from the minimum vertical
vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes
(5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through
unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize
condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for
400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.
note:
If for any reason the vent air intake system is disassembled, re-install per the instructions provided for the initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate
constructions such as a chimney as part of the vent system is not permitted.
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components.
Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles
and air terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Simpson Dura-Vent,
Selkirk Direct Temp, American Metal Amerivent and Metal-Fab, follow the installation procedure provided with the venting
components or on the website for your venting supplier.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high
temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all
other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed
using the black high temperature sealant Mill Pac. High temperature sealant must be ordered separately.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following ter-
This template must be used in conjunction with templates 7.1.1 or 7.1.2, depending on
mination kits: wall terminal kit GD-222, GD-222R, or 1/12 to 7/12 pitch roof terminal kit GD-110, 8/12 to 12/12 roof terminal
kit GD-111, fl at roof terminal kit GD-112 or periscope kit GD-201 (for wall penetration below grade). With fl exible venting, in
termination shape (i.e. round, or round and square). See appropriate templates folder.
conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD-220 or the 10 foot (3.1m) vent kit GD-330.
For stoves only: wall terminal kit GD-175 (venting included).
For optimum flame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not
be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20
feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Starter Adapter Part Number SupplierWebsite
Horizontal runs may have a 0” rise per foot or 0mm rise per meter however for optimum performance it is recommended
that all horizontal runs have a minimum 1/4” rise per foot or 21mm rise per meter using fl exible venting. For safe and proper
operation of the appliance, follow the venting instructions exactly.
W415-1768 / B / 08.10.18
9
!
WARNING
• Risk of fire. Maintain specified air space clearances to vent pipe and appliance.
• The vent system must be supported every 3’(0.9m) for both vertical and horizontal runs. Use support ring assembly W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air gap to the outer pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this gap is maintained. These spaces must not be removed.
This appliance uses a 4” (102mm) exhaust / 7” (178mm) air intake vent pipe system. Refer to the section applicable to your installation.
For safe and proper operation of the appliance, follow the venting instructions exactly. Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for 400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance flue collar which must be sealed using the black high temperature sealant Mill Pac. High temperature sealant must be ordered separately.
For optimum flame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.
Rigid and flexible venting systems must not be combined. Different venting manufacturer components must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using flexible venting.
Horizontal runs may have a 0” rise per foot or 0mm rise per meter however for optimum performance it is recommended that all horizontal runs have a minimum 1/4” rise per foot or 21mm rise per meter using flexible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab, follow the installation procedure provided with the venting components or on the website for your venting supplier. A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
note:
If for any reason the vent air intake system is disassembled, re-install per the instructions provided for the initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
This template must be used in conjunction with templates 7.1.1 or 7.1.2, depending on termination shape (i.e. round, or round and square). See appropriate templates folder.
EN
venting requirements
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings
and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” (31.8mm) air gap
all around between the inner liner and outer liner is required for safe operation.
This appliance is certified for use with a power vent kit. Contact your local authorized dealer for more
If approved for use with a power vent kit, state: “This appliance is certified for use with a
information.
power vent kit. Contact your local authorized dealer for more information.”
2.1 typical vent installation
16" (40.6cm)
minimum
40ft (12m)
8" (203mm)
minimum
24" (61cm)
maximum
Maximum
3ft (1m)
minimum
34 5/8"
(86cm)
10
W415-1768 / B / 08.10.18
TOP VENT
venting requirements
16" (40.6cm)
minimum
EN
20"
(50.8cm)
Max.
40 ft (12m)
Maximum
3 ft (1m)
minimum
24 3/16" (61.4cm)
minimum plus rise *
24 3/16"
(61.4cm)
REAR VENT
* See "venting" section
W415-1768 / B / 08.10.18
11
EN
30”
MINIMUM
12” MINIMUM
TOP EXIT INSTALLATION
REAR EXIT INSTALLATION
30”
MINIMUM
12” MINIMUM
MAXIMUM 10FT VENT LENGTH
6” (152mm)RISE MINIMUM
20” (50.8cm)
REAR EXIT INSTALLATION
12” MINIMUM
venting requirements
2.2 special vent installations
2.2.1 periscope termination
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when
fi nal grading is completed, the bottom air slot is located a minimum 12” (305mm) above grade. The maximum
allowable vent length (including both rise and run) is 10’ (3m) for a fi replace and 8’ (2m) for a stove. An insulation
sleeve is illustrated in the top vent image below, use only when supplied with the appliance.
(The insulation sleeve is not required with a stove appliance)
12" (30.5cm)
minimum
to grade
30" (76.2cm)
minimum
2.2.2 corner termination
The maximum vent length for a corner installation is 20" (50.8cm) of horizontal run, in addition to the 45° offset.
In this case zero rise is acceptable. When using rigid venting, it is required to maintain a 6" (152mm) rise. When
using flexible venting, see illustrations below.
30" (76.2cm)
minimum
34 5/8"
(87.9CM)
TOP VENTREAR VENT
12" (30.5cm)
minimum
to grade
12
W415-1768 / B / 08.10.18
6” (152mm)
MAXIMUM
RISE MINIMUM
Flexible VentingRigid Venting
2.3 minimum air terminal location clearances
Covered balcony applications ††*
venting requirements
Q
S
R
P
G
EN
Q
= 3 feet
MIN
(0.9m)
INSTALLATIONS
CANADAU.S.A.
12” (30.5cm)12” (30.5cm)Clearance above grade, veranda porch, deck or balcony.
A
18”
Δ
9” (229mm) ΔClearance to windows or doors that open.
18”
(45.7cm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ (0.6m)
from the center line of the terminal.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum
vertical distance of 15’ (4.6m).
12” (30.5cm)
B
12” (30.5cm)*12” (30.5cm)*Clearance to permanently closed windows.
C
D
(45.7cm)**
12” (30.5cm)**12” (30.5cm)**Clearance to unventilated soffi t.
E
0” (0mm)0” (0mm)Clearance to an outside corner wall.
F
0” (0mm)***0” (0mm)***
G
2” (51mm)***2” (51mm)***Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
H
K
L
M
3’(0.9m)3’(0.9m)****
3’ (0.9m)3’ (0.9m)****Clearance to a service regulator vent outlet.
I
12” (30.5cm)9” (229mm)Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
J
6’ (1.8m)3’ (0.9m) †Clearance to a mechanical air supply inlet.
7’ (2.1m) ‡7’ (2.1m) ****Clearance above a paved sidewalk or paved driveway located on public property.
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
note:
Wall terminals are for illustration purposes only. Size and
shapes may vary.
R
= 2 x
MAX
Q
ACTUAL
R
MAX
≤ 15 feet
(4.6m)
16” (40.6cm)16” (40.6cm)Clearance above the roof.
N
2’ (0.6m)†*2’ (0.6m) †*Clearance from an adjacent wall including neighbouring buildings.
O
8’ (2.4m)8’ (2.4m)
P
3’ (0.9m)3’ (0.9m)See chart for wider wall dimensions.
Q
6’ (1.8m)6’ (1.8m)
R
12” (30.5cm)12” (30.5cm)Clearance under a covered balcony
S
ΔThe terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18 inches clearance from an inside corner.
****This is a recommended distance. For additional requirements, check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements, check local codes.
††*Permitted only if the balcony is fully open on a minimum of one side.
Roof must be non-combustible without openings.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening
between the terminal and the open side of the structure.
note:
Clearances are to be in accordance with local
installation codes and the requirements of the gas
supplier. In their absence, clearances are to be as
listed above and are based on national codes.
W415-1768 / B / 08.10.18
13
EN
For the following symbols used in the venting calculations and examples are:
> - greater than
>
< - less than
<
H
H
H
V
- combined vertical vent lengths in feet
venting requirements
2.4 venting application flow chart
TOP EXIT
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
Horizontal Termination
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
REAR EXIT
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
Vertical Termination
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
3 times the vertical
rise equal to or
greater than the
horizontal run
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
3.5 times the
vertical rise equal to
or greater than the
horizontal run
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
2.5 definitions
- equal to or greater than
- equal to or less than
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
14
T
- combined horizontal vent lengths in feet
R
- offset factor: .03 (total degrees of offset - 90°*) in feet
• Failure to create a seal to the firebox with the exhaust collar assembly will cause the appliance to function
improperly and can cause injury or property damage.
EN
A.Remove the safety barrier and glass front, refer to "safety
barrier & door removal/installation" section.
B.Remove the contents from the firebox and set aside, you will
need the exhaust flue collar from the top of the log carton.
C.To ease assembly, remove the four hex head screws
securing the deflector from inside the top front of the firebox,
refer to Figure 1.
D.Place the gasket (provided) over the 4" (102mm) flue collar
assembly and bend along perforation.
E.From inside the firebox, insert the 4" (102mm) flue collar through the back
of the firebox. Install the rear exit shield onto the 4" (102mm) flue collar, see
"rear exit shield" section for installation instructions.
F.Secure the flue collar assembly, gasket and rear exit shield using the four hex
head 3/8" thread cutting screws, refer to Figure 2.
note:
Do not overtighten. The gasket needs only to be
snug against the firebox.
G.Reattach the deflector using the four screws and
install the log set, glass door and safety barrier.
H.Install the 7" collar assembly, complete with
gasket, onto the rear panel around the 4"
(101.6mm) collar with the screws provided (FIG
3).
Fig. 1
Fig. 2
Fig. 3
GASKET
INTAKE COLLAR
ASSEMBLY
2.11 rear exit shield (for rear vent only)
A.Remove the safety barrier assembly and door from the appliance, refer to the “safety barrier & door removal / installation” section of the manual for detailed instructions.
B.Loosen the two screws, that secure the exhaust plate, and slide the shield in place by sliding its slotted openings behind the screwheads,
tighten the two previously loosened
screws. Refer to the illustration .
C.Reinstall the door and safety barrier assembly on the appliance, see to
the “safety barrier & door removal / installation” section.
note:
This shield is used to block the view
through the venting to the outdoors.
W415-1768 / B / 08.10.18
21
EN
INTAKE COLLAR
ASSEMBLY
GASKET
OUTER COVER
INNER
D
E
E
OUTER
DEFLECTOR
venting requirements
2.12 top exit
WARNING
!
• Failure to install the cover plate and gasket will cause the appliance to function improperly and can cause
injury or property damage.
This appliance is factory shipped as a rear vent model equipped with a #50 burner orifice. This orifice
size is suitable for rear vent installations with 0" vertical rise only. For top exit applications, the main
burner orifice should be changed to the #49 burner orifice (supplied) for natural gas. For propane
models, the appliance is converted to a #58 burner orifice for rear vent applications or a #57 burner
orifice for top vent applications.
A.Remove the safety screen and glass front, refer to " SAFETY
SCREEN / DOOR REMOVAL AND INSTALLATION" section.
B.Remove the contents from the firebox and set aside, you will
need the exhaust collar from the top of the log carton.
C.To ease assembly, remove the four hex head screws securing
the deflector from inside the top front of the firebox.
D.Remove the single screw from the outer cover on the
back of the appliance.
E.Remove the four screws on the 7" (178mm) intake collar
assembly; set the intake collar and gasket aside. Careful
not to damage gasket.
F.Remove the single screw from the outer cover with
knockout intact, on the top of the appliance and set aside.
G.Remove the inner cover plate and gasket by removing the
four screws. Reinstall the inner cover plate and gasket
onto the back of the appliance.
H.Take the outer cover (with knockout intact) and secure
onto the back of the appliance.
I.Remove and discard the 1 1/2" thick batt of insulation
from the top opening.
J.Place the 7" (178mm) intake collar and
gasket onto the top of the appliance
and secure with the four screws.
K.Reinstall the outer cover (without knock
out) over the 7" (178mm) exhaust collar
assembly and secure.
L.From inside the firebox, install the 4"
(102mm) exhaust collar up through the
top of the firebox and secure with the the four
hex head 3/8" thread cutting screws. NOTE:
Do not overtighten. The gasket needs only
to be snug against the firebox.
M.Reattach the top deflector, log set, glass door
and safety screen.
I
F
COVER
PLATE
(without
knockout)
GASKET
INTAKE COLLAR
EXHAUST FLUE COLLAR
E
E
ASSEMBLY
OUTER COVER
COVERPLATE
G
GASKET
D
22
W415-1768 / B / 08.10.18
3.0 rough framing
!
WARNING
note:
When using optional fi nishing accessories, the framing dimensions and fi nishing materials may differ from
what is outlined in the section below; refer to the leafl et instructions supplied in the accessory kit for specifi c
framing and fi nishing specifi cations.
• Risk of fi re!
• In order to avoid the possibility of exposed insulation or vapour barrier coming in contact with the appliance
body, it is recommended that the walls of the appliance enclosure be “fi nished” (i.e. drywall / sheetrock),
as you would fi nish any other outside wall of a home. This will ensure that clearance to combustibles is
maintained within the cavity.
• Do not notch the framing around the appliance stand offs. Failure to maintain air space clearance may cause
over heating and fi re. Prevent contact with sagging or loose insulation or framing and other combustible
materials. Block opening into the chase to prevent entry of blown-in insulation. Make sure insulation and
other materials are secured.
• When constructing the enclosure, allow for fi nishing material thickness to maintain clearances. Framing or
fi nishing material closer than the minimums listed must be constructed entirely of non-combustible materials.
Materials consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination
thereof are suitable. Materials that are reported as passing ASTM E136, standard test method for behaviour
of materials in a vertical tube furnace at 1382ºF (750ºC) and UL763 shall be considered non-combustible
materials.
• Minimum clearance to combusibles must be maintained or a serious fi re hazard could result.
• The appliance requires a minimum enclosure height. Measure from the appliance base.
• If steel stud framing kits with cement board are provided, or specifi ed in the installation instructions, they
must be installed.
• If specifi ed in the installation instruction, fi nishing must be done using a non-combustible board, ceramic tile,
marble, etc. Do NOT use wood or drywall. Any fi re rated drywall is not acceptable.
rough framing
EN
It is best to frame your appliance after it is positioned and the vent system is installed. Frame to local building
codes.
It is not necessary to install a hearth extension with this appliance.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the finished floor
materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower access
door and the installation of many decorative flashing accessories.
Combustible materials may be installed flush with the front of the appliance but must not cover any of the black
face-areas of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas.
W415-1768 / B / 08.10.18
23
EN
Do not put objects in front of the appliance
(minimum distance of 4 feet)
rough framing
3.1 minimum framing dimensions
SIDE WALL
2”
(51mm)
30 1/2”
(77.5cm)
14 1/2”
(36.8cm)
29 1/2”
(75cm)
30 1/2”
(77.5cm)
41 3/4”
(106
cm
)
* HORIZONTAL VENT SECTIONS: A minimum of 1" (25mm) at the bottom and sides and 3" (76mm) at the top
of the vent pipe on all horizontal runs to combustibles is required. Use firestop spacer W010-1777 (supplied).
NOTE: The minimum clearances from the top of the horizontal vent pipe to combustible materials may
be reduced from 3"(76mm) to 1"(25mm) in those installations with a minimum 38" (965mm) vertical
vent rise made immediately off the fireplace collar.
* VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. See "minimum enclosure clearances"
section. Use firestop spacer W500-0096 (not supplied).
24
W415-1768 / B / 08.10.18
3.2 minimum enclosure clearances
COMBUSTIBLE
NON-COMBUSTIBLE
TOP VENT
rough framing
EN
54"
[1372mm]
CEILING
(MIN)
50 1/2"
[1283mm]
15 5/8"
3" [76mm]
[403mm]
3" [76mm]
MINIMUM *
2"
[51mm]
BRICK
3" [76mm]
1"
[25mm]
42 5/8"
[1083mm]
0” (0MM) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
MINIMUM
14 1/2"
PLUS RISE*
[368mm]
1"
[25mm]
TOP EXIT ENCLOSURE
The appliance requires a minimum non-combustible enclosure height of 50 1/2" (1283mm). For temperature
requirements, the enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall
penetration.
* See "MINIMUM FRAMING DIMENSION" section for details on reducing vent pipe top clearances.
These parameters also apply to the illustrations found in the "MINIMUM ENCLOSURE CLEARANCES"
section.
W415-1768 / B / 08.10.18
25
EN
41 5/8"
[105.7cm]
rough framing
REAR VENT
For rear vent termination not exceeding 10" (254mm) of horizontal vent run.
NON-COMBUSTIBLE
41 5/8"
[105.7cm]
34 5/8"
[87.9cm]
7"
[178mm]
COMBUSTIBLE
BRICK
3"
[76mm]
1"
[25mm]
0” (0MM) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
24 3/16"
[61.4cm]
MINIMUM
PLUS RISE*
26
1"-10"
[25mm-254mm]
VENT RUN
REAR EXIT ENCLOSURE
The appliance requires a minimum enclosure height of 41 5/8" (1057mm). For temperature requirements, the
enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall
penetration.
* See "VENTING" section.
W415-1768 / B / 08.10.18
MAXIMUM REAR VENT CLEARANCES (EXAMPLE 1)
NON-COMBUSTIBLE
COMBUSTIBLE
11 1/2"
[292mm]
7"
rough framing
BRICK
0” (0MM) IF
3"
[76mm]
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
EN
41 5/8"
[178mm]
[105.7cm]
34 5/8"
[87.9cm]
1"
[25mm]
24 3/16"
24 1/8”
(61.4cm)
[61.3cm]
MINIMUM
PLUS RISE*
10"-20"
[254mm-508mm]
VENT RUN
REAR EXIT ENCLOSURE
The appliance requires a minimum enclosure height of 41 5/8" (1057mm). For temperature requirements, the
enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall
penetration.
W415-1768 / B / 08.10.18
27
EN
[178mm]
41 5/8"
[105,7cm]
34 5/8"
[87,9cm]
rough framing
MAXIMUM REAR VENT CLEARANCES (EXAMPLE 2)
7"
11 1/2"
[292mm]
3"
[76mm]
0” (0MM) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
41 5/8"
[178mm]
[105.7cm]
34 5/8"
[87.9cm]
COMBUSTIBLE
NON-COMBUSTIBLE
1"
[25mm]
BRICK
24 3/16"
24 1/8”
(61.4cm)
[61.3cm]
MINIMUM
PLUS RISE*
10"-20"
[254mm-508mm]
VENT RUN
REAR EXIT ENCLOSURE
The appliance requires a minimum enclosure height of 41 5/8" (1057mm). For temperature requirements, the
enclosure space around and above the appliance must be left unobstructed.
28
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall
penetration.
W415-1768 / B / 08.10.18
rough framing
note:
For heavier finishing materials such as marble, we recommend adding extra support to the frame. Ensure
there is adequate floor support for the appliance and finishing material.
Before framing your appliance, determine vent requirements before deciding the final location of the appliance.
After rough framing, place the appliance in its final position.
EN
RefMinimum rough framing dimensions
A
B
* Based on 1/2” finishing material thickness.
A
B
14 1/2”* (36.8cm)
30 1/2” (77.5cm)
W415-1768 / B / 08.10.18
29
4.0 venting installation
!
WARNING
EN
venting installation
• Ensure to unpack all loose materials from inside the fi rebox prior to connecting the gas and electrical supply
• If your appliance is supplied with a remote, ensure the remote receiver is in the “OFF” position prior
to connecting the gas and electrical supply to the appliance.
• For safe and proper operation of the appliance, follow the venting instructions exactly.
• The appliance exhaust fl ue collar must be sealed using Mill Pac. All exhaust and intake vent pipe joints
must be sealed using red RTV high temp silicone sealant (W573-0002) (not supplied) or black high temp Mill
Pac (W573-0007) (not supplied).
• If using pipe clamps to connect rigid vent components, a minimum of 3 screws must also be used to ensure
the connection cannot slip off.
• Do not clamp the fl exible vent pipe.
• Risk of fi re, explosion, or asphyxiation. Improper support of the entire venting system may allow vent to sag
and separate. Use vent run supports and connect vent sections per installation instructions.
• Risk of fi re, do not allow loose materials or insulation to touch the vent pipe. Remove insulation to allow for the
installation of the attic shield and to maintain clearances to combustibles.
• Do not fi ll the space between the vent pipe and enclosure with any type of material. Do not pack insulation
or combustibles between ceiling fi restops. Always maintain specifi ed clearances around venting and fi restop
systems. Install wall shields and fi restops as specifi ed. Failure to keep insulation or other materials away from
vent pipe may cause fi re.
For optimum performance, it is recommended that all horizontal runs have a minimum of 1/4" (6mm) rise
per foot using flexible venting. For safe and proper operation of the appliance, follow the venting instructions
exactly.
30
W415-1768 / B / 08.10.18
Loading...
+ 106 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.