Napoleon B30NTR Installation Manual

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
SAFETY BARRIER
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED TO CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS FIREPLACES.
B30NTR-1 / B30NTRE-1
FOR INDOOR USE ONLY
NATURAL GAS MODEL
EN
FR PG 71
SAFETY INFORMATION
!
WARNING
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a certifi ed kit is used.
B30PTR-1 / B30PTRE-1
PROPANE GAS MODEL
!
DANGER
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
Phone (705)721-1212 • Fax (705)720-9081 • www.napoleonfi replaces.com • hearth@napoleonproducts.com
$10.00
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
1.28G
W415-1768 / 06.12.17
2
EN
TABLE OF CONTENTS
NOTE: The camera icon indicates video tutorials are available as additional reference, visit http://www.napoleonfireplaces.com/category/product-support/support-centre/
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
3.0 VENTING 9
4.0 INSTALLATION 26
5.0 FRAMING 36
6.0 FINISHING 46
7.0 WIRING DIAGRAM 51
8.0 OPERATION (ELECTRONIC) 52
9.0 OPERATION (MILLIVOLT) 53
10.0 ADJUSTMENT 54
11.0 MAINTENANCE 56
12.0 REPLACEMENTS 59
13.0 ACCESSORIES 63
14.0 TROUBLESHOOTING (ELECTRONIC) 64
15.0 TROUBLESHOOTING (MILLIVOLT) 66
16.0 WARRANTY 69
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 6
2.3 GENERAL INFORMATION 7
2.4 RATING PLATE INFORMATION 8
3.1 VENTING LENGTHS AND COMPONENTS 10
3.2 TYPICAL VENT INSTALLATION 11
3.3 SPECIAL VENT INSTALLATIONS 13
3.3.1 PERISCOPE TERMINATION 13
3.3.2 CORNER TERMINATION 13
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES 14
3.5 VENTING APPLICATION FLOW CHART 15
3.6 DEFINITIONS 16
3.7 ELBOW VENT LENGTH VALUES 16
3.8 TOP EXIT HORIZONTAL TERMINATION 17
3.9 REAR EXIT HORIZONTAL TERMINATION 19
3.10 TOP AND REAR EXIT VERTICAL TERMINATION 21
3.11 REAR EXIT 23
3.12 REAR EXIT SHIELD (FOR REAR VENT ONLY) 24
3.13 TOP EXIT 25
4.1 WALL AND CEILING PROTECTION 26
4.1.1 HORIZONTAL INSTALLATION 27
4.1.2 VERTICAL INSTALLATION 27
4.2 USING FLEXIBLE VENT COMPONENTS 28
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 28
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 29
4.2.3 APPLIANCE VENT CONNECTION 30
4.3 USING RIGID VENT COMPONENTS 30
4.3.1 HORIZONTAL AIR TERMINAL INSTALLATION 30
4.3.2 VERTICAL AIR TERMINAL INSTALLATION 31
4.3.3 RESTRICTING VERTICAL VENTS 32
4.4 VERTICAL THROUGH EXISTING CHIMNEY 33
4.5 MOBILE HOME INSTALLATION 34
4.6 GAS INSTALLATION 35
4.7 OPTIONAL WALL SWITCH 35
5.1 MINIMUM FRAMING DIMENSIONS 37
5.2 MINIMUM ENCLOSURE CLEARANCES 39
5.3 NON-COMBUSTIBLE FACING MATERIAL 43
5.4 ALCOVE CLEARANCES 43
5.5 RECESSED INSTALLATION 44
5.6 MINIMUM MANTEL CLEARANCES 45
6.1 SAFETY SCREEN / DOOR REMOVAL AND INSTALLATION 46
6.2 FRONT HOOD INSTALLATION 47
6.3 LOG PLACEMENT 48
6.4 CHARCOAL EMBERS 49
6.5 LOGO PLACEMENT 49
6.6 BATTERY BACK-UP INSTALLATION 50
10.1 PILOT BURNER ADJUSTMENT 54
10.2 VENTURI ADJUSTMENT 54
10.3 FLAME CHARACTERISTICS 55
10.4 OPTIONAL ANTI CONDENSATION SWITCH (MODELS B30NTRE-1 AND B30PTRE-1 ONLY) 55
11.1 ANNUAL MAINTENANCE 57
11.2 DOOR GLASS REPLACEMENT 58
11.3 CARE OF GLASS 58
12.1 OVERVIEW 60
12.2 ELECTRONIC VALVE TRAIN ASSEMBLY 61
12.3 MILLIVOLT VALVE TRAIN ASSEMBLY 62
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
W415-1768 / 06.12.17
1.0 INSTALLATION OVERVIEW
“INSTALLATION”.
3
See the section “MINIMUM ENCLOSURE CLEARANCES” for drywall (or other combus­tible material).
See the section “MINIMUM MANTEL CLEARANCES”.
See the section “MINIMUM FRAMING DIMENSIONS”.
EN
See the section “VENTING” and
See the section “FRAMING”.
Side
Wall
See the section “RATING PLATE INFORMATION”.
SAFETY BARRIER
Batteries must be disposed of according to the local laws and regulations. Some batteries may be recycled, and may be accepted for disposal at your local recycling center. Check with your municipality for recycling instructions.
W415-1768 / 06.12.17
4
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and
!
WARNING
2.0 INTRODUCTION
EN
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND ARE PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fi re or injury.
Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot
surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These
screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the appliance.
The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
Under no circumstances should this appliance be modifi ed.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance
and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes
containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures
on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic components.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be
installed.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
The millivolt version of this appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
3.1E
W415-1768 / 06.12.17
34 5/8"
879mm
18 5/16"
465mm
7 3/16"
182mm
1 13/16"
46mm
GAS
INLET
B30 ILLUSTRATED
B35 ILLUSTRATED
5"
127mm
11 13/16"
299mm
8"
203mm
35"
890mm
11 5/16"
288mm
762mm
SAFETY BARRIER
2.1 DIMENSIONS
5
7"
12 3/4"
324mm
4"
178mm
24 3/16"
102mm
614mm
8 5/8"
136mm
GAS
30"
INLET
EN
879mm
34 5/8"
170mm
6 11/16"
14"
355mm
46mm
1 13/16"
SAFETY BARRIER
W415-1768 / 06.12.17
6
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER
conform with local codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for example in Massachusetts State:
The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or ANSI Z223.1 and NFPA 54 in the United States.
As long as the required clearance to combustibles is maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
WARNING
2.2 GENERAL INSTRUCTIONS
EN
!
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUATE VENTILATION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48 INCHES
(121.9cm) FROM THE FRONT FACE OF THE APPLIANCE.
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THE APPLIANCE MUST NOT BE OPERATED AT TEMPERATURES BELOW FREEZING (32°F / 0°C).
ALLOW THE APPLIANCE TO WARM TO ABOVE FREEZING PRIOR TO OPERATION.
to
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of Massachusetts. The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas log. The appliance off valve must be a “T” handle gas cock. The fl exible connector must not be longer than 3 feet (91.4cm). A Carbon Monoxide detector is required in all rooms containing gas fi red appliances. The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
We suggest that our gas hearth products be installed
www.ncertied.org
and serviced by professionals who are certied in the U.S. by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
W415-1768 / 06.12.17
4.1C
2.3 GENERAL INFORMATION
7
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
RATES AND EFFICIENCIES
B30-1
NG P
Altitude (FT) 0-4,500 0-4,500 Max. Input (BTU/HR) 15,000 15,000
Min. Inlet Gas Supply Pressure 4.5" (11mb) w.c. 11" (27mb) w.c. Max. Inlet Gas Supply Pressure 13" (32mb) w.c. 13" (32mb) w.c.
Manifold Pressure (Under Flow Conditions)
B30-1 MODEL DESIGNATIONS
B30NTR-1 B30NTRE-1 B30PTR-1 B30PTRE-1
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home installation.
3.5" (9mb) w.c. 10" (25mb) w.c.
FUEL TYPE OPERATING SYSTEM
NATURAL MILLIVOLT
NATURAL ELECTRONIC IGNITION PROPANE MILLIVOLT PROPANE ELECTRONIC IGNITION
EN
No external electricity (110 volts or 24 volts) is required for the gas millivolt system operation.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
W415-1768 / 06.12.17
EN
C
SAMPLE
8
2.4 RATING PLATE INFORMATION
DIRECT VENT GAS FIREPLACE. SUITABLE FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
W565-0154. FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
9700539 (WSL) 4001657 (NGZ) 4001658 (NAC) 4001659 (WUSA)
B30NTR CB30NTR MODEL CB30PTR B30PTR
15,000 BTU/h INPUT / ALIMENTATION 15,000 BTU/h 10,000 BTU/h REDUCED INPUT / ALIMENTATION REDUITE 11,500 BTU/h
PRESSION AU COLLECTEUR: 3.5" (9 MB) D'UNE COLONNE D'EAU PRESSION AU COLLECTEUR: 10" (25MB) D'UNE COLONNE D'EAU MINIMUM SUPPLY PRESSURE: 4.5" (11MB) WATER COLUMN MINIMUM SUPPLY PRESSURE: 11" (27MB) WATER COLUMN PRESSION D'ALIMENTATION MINIMALE: 4.5" (11MB) D'UNE COLONNE D'EAU PRESSION D'ALIMENTATION MINIMALE: 11" (27MB) D'UNE COLONNE D'EAU MAXIMUM SUPPLY PRESSURE: 7.0" (17MB) WATER COLUMN MAXIMUM SUPPLY PRESSURE: 13" (32MB) WATER COLUMN PRESSION D'ALIMENTATION MAXIMALE: 7.0" (17MB) D'UNE COLONNE D'EAU PRESSION D'ALIMENTATION MAXIMALE: 13" (32MB) D'UNE COLONNE D'EAU P4: 44% P4: 44%
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING:
ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD. DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE. MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS / DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES: TOP/ DESSUS 0 RECESSED DEPTH / PROFONDEUR D'ENCASTRE 14 ½" FLOOR / PLANCHER 0 VENT SIDES / COTES DE L'EVENT 1" SIDES / COTES 0 VENT TOP / EVENT SUPERIEUR 3" BACK / ARRIERE 0 VENT BOTTOM / EVENT INFERIEUR 1" MANTEL / MANTEAU 12" * * MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES.
THIS FIREPLACE USES AND REQUIRES A FAST ACTING THERMOCOUPLE. REPLACE
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS. REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR LES LONGUEURS D'EVACUATION MINIMALE ET MAXIMALE.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
MANIFOLD PRESSURE: 3.5" (9MB) WATER COLUMN MANIFOLD PRESSURE: 10" (25MB) WATER COLUMN
FOYER À GAZ VENTILÉ DIRECT. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER,
UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME
FOR USE WITH BARRIER
B30NTRE CB30NTRE CB30PTRE B30PTRE
0-4500FT (0-1370m) ALTITUDE / ELEVATION 0-4500FT (0-1370m)
RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.
UNE UTILISER AVEC BARRIÈRE W565-0154. SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE MANUEL D'INSTALLATION
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET APPAREIL. UTILISER AVEC LES PORTES VITREES HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT: CE FOYER UTILISE ET REQUIERT UN THERMOCOUPLE À ACTION RAPIDE.
REMPLACEZ UNIQUEMENT AVEC UN THERMOCOUPLE À ACTION RAPIDE DE WOLF STEEL LTÉE. N’AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT. THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM. L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A NAPOLEON. REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. IL EST IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR ASSURE LE MAINTIEN DU SYSTEME DE PRISE D'AIR. DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPPAREIL DE CHAUFFAGE. ELECTRICAL RATING / CLASSIFICATION: 115V 0.82AMP, 60HZ OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: EP35
SERIAL NUMBER/NO. DE SERIE:
B30
POUR
W385-1951 / C
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
A barrier designed to reduce the risk of burns from the hot viewing glass, is provided with the appliance and shall be installed.
W415-1768 / 06.12.17
3.0 VENTING
WARNING
9
!
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 4” (102mm) EXHAUST / 7” (178mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling. The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for 400°F (204°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.1F
EN
W415-1768 / 06.12.17
10
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
3.1 VENTING LENGTHS AND COMPONENTS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab
EN
venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting components. A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
VENT MANUFACTURER
Duravent W175-0053 Wolf Steel www.duravent.com
Amerivent 4DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 4DT-AAN Selkirk www.selkirkcorp.com
SuperSeal 4DNA Metal-Fab www.mtlfab.com
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature sealant Mill Pac. High temperature sealant must be ordered separately.
STARTER ADAPTER PART NUMBER
SUPPLIER WEBSITE
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following termination kits: wall terminal kit GD-222, GD-222R, or 1/12 to 7/12 pitch roof terminal kit GD-110, 8/12 to 12/12 roof terminal kit GD-111, fl at roof terminal kit GD-112 or periscope kit GD-201 (for wall penetration below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD-220 or the 10 foot (3.1m) vent kit GD-330.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.
must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
8.1C
W415-1768 / 06.12.17
3.2 TYPICAL VENT INSTALLATION
11
EN
16" (40.6CM)
MINIMUM
8" (203MM)
MINIMUM
24" (61CM)
MAXIMUM
40 FT (12M)
MAXIMUM
3 FT (1M)
MINIMUM
TOP VENT
W415-1768 / 06.12.17
EN
12
16" (40.6CM)
MINIMUM
20"
(50.8CM)
MAX
24 3/16" (61.4CM)
MINIMUM PLUS
RISE *
40 FT (12M)
MAXIMUM
3 FT (1M)
MINIMUM
24 3/16"
(61.4CM)
REAR VENT
* See "VENTING" section
W415-1768 / 06.12.17
3.3 SPECIAL VENT INSTALLATIONS
30”
MINIMUM
12” MINIMUM
TOP EXIT INSTALLATION
REAR EXIT INSTALLATION
30”
MINIMUM
12”
MINIMUM
MAXIMUM 10FT VENT LENGTH
6” (152mm) RISE MINIMUM
20” (50.8cm)
REAR EXIT INSTALLATION
12” MINIMUM
13
3.3.1 PERISCOPE TERMINATION
30" (76.2CM)
MINIMUM
12" (30.5CM)
MINIMUM
TO GRADE
EN
12" (30.5CM)
MINIMUM
TO GRADE
30" (76.2CM)
MINIMUM
34 5/8"
(87.9CM)
9.4B
3.3.2 CORNER TERMINATION
The maximum vent length for a corner installation is 20" (50.8cm) of horizontal run, in addition to the 45° offset. In this case zero rise is acceptable. When using rigid venting, it is required to maintain a 6" (152mm) rise. When using flexible venting, see illustrations below.
MAXIMUM
6” (152mm) RISE MINIMUM
FLEXIBLE VENTING RIGID VENTING
W415-1768 / 06.12.17
14
3.4 MINIMUM AIR TERMINAL LOCATION CLEARANCES
EN
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
Q
= 3 feet
MIN
(0.9m)
R
= 2 x
MAX
Q
ACTUAL
R
MAX
INSTALLATIONS
CANADA U.S.A.
12” (30.5cm) 12” (30.5cm) Clearance above grade, veranda porch, deck or balcony.
A
Δ
12” (30.5cm)
B
12” (30.5cm)* 12” (30.5cm) * Clearance to permanently closed windows.
C
D
E
F
G
H
I
J
K
L
M
18”
(45.7cm)**
12” (30.5cm)** 12” (30.5cm)** Clearance to unventilated soffi t.
0” (0mm) 0” (0mm) Clearance to an outside corner wall.
0” (0mm)*** 0” (0mm)***
2” (51mm)*** 2” (51mm)*** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
3’(0.9m) 3’(0.9m)****
3’ (0.9m) 3’ (0.9m)**** Clearance to a service regulator vent outlet.
12” (30.5cm) 9” (229mm) Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet.
7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
9” (229mm) Clearance to windows or doors that open.
18”
(45.7cm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ (0.6m) from the center line of the terminal.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maxi­mum vertical distance of 15’ (4.6m).
≤ 15 feet
(4.6m)
16” (40.6cm) 16” (40.6cm) Clearance above the roof.
N
2’ (0.6m)†* 2’ (0.6m) †* Clearance from an adjacent wall including neighbouring buildings.
O
P
Q
R
12” (30.5cm) 12” (30.5cm) Clearance under a covered balcony
S
Δ The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
W415-1768 / 06.12.17
8’ (2.4m) 8’ (2.4m)
3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
6’ (1.8m) 6’ (1.8m)
Roof must be non-combustible without openings.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.
12.1E
3.5 VENTING APPLICATION FLOW CHART
15
Horizontal Termination
Vertical rise is equal
to or greater than the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
TOP EXIT
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
REAR EXIT
Vertical Termination
Vertical rise is equal
to or greater than the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
EN
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.3A
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
3.5 times the
vertical rise equal to
or greater than the
horizontal run
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Vertical rise is less than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.2A
W415-1768 / 06.12.17
EN
For the following symbols used in the venting calculations and examples are: > - greater than > < - less than < H H H V
0.03 0.5 12.7 15° 0.45 6.0 152.4 30° 0.9 11.0 279.4 45° 1.35 16.0 406.4 90°* 2.7 32.0 812.8
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
16
3.6 DEFINITIONS
- equal to or greater than
- equal to or less than
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
T
- combined horizontal vent lengths in feet
R
- offset factor: .03 (total degrees of offset - 90°*) in feet
O
- combined vertical vent lengths in feet
T
3.7 ELBOW VENT LENGTH VALUES
FEET INCHES MILLIMETERS
14.1
15.1A
W415-1768 / 06.12.17
3.8 TOP EXIT HORIZONTAL TERMINATION
0
2.5
(0.8)5(1.5)
7.5
(2.3)
10
(3.1)
12.5 (3.8)15(4.6)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
17.5 (5.3)20(6.1)
39 (11.9)
REQUIRED
VERTICAL
RISE IN FEET
(METERS)VT
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
7.5
(2.3)
10
(3.1)
12.5 (3.8)15(4.6)
17.5
(5.3)20(6.1)
FEET (METERS) H
T
17
(HT) < (VT)
Simple venting confi guration (only one 90° elbow)
REQUIRED
40 (12.2)
39 (11.9)
30 (9.1)
See graph to determine the required vertical
for the required horizontal run HT.
rise V
T
VERTICAL
RISE IN FEET
20 (6.1)
(METERS)VT
10 (3.1)
0
2.5
(0.8)5(1.5)
7.5
(2.3)
(3.1)
10
12.5 (3.8)15(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
The shaded area within the lines represents
acceptable values for H
T
For vent confi gurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet (12.2m)
and V
17.5 (5.3)20(6.1)
T
EN
Example: V1 = 3 FT (0.9m)
V2 = 8 FT (2.4m) VT = V1 + V2= 3 FT (0.9m ) + 8 FT (2.4m) = 11 FT (3.4m) H1 = 2.5 FT (0.8m) H2 = 2 FT (0.6m) HR = H1 + H2 = 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m) HO = .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT (1.7m) HT = HR + HO = 4.5 FT (1.4m) + 5.4 FT (1.6m) = 9.9 FT (3m) HT + VT = 9.9 FT (3m) + 11 FT (3.4m) = 20.9 FT (6.4m)
Formula 1: HT < V
T
9.9 FT (3m) < 11 FT (3.4m) Formula 2: HT + VT < 40 FT (12.2m)
20.9 FT (6.4m) < 40 FT (12.2m) Since both formulas are met, this vent confi guration is acceptable.
90°
V
1
16.1B
90°
90°
H
2
V
2
H
1
W415-1768 / 06.12.17
18
(HT) > (VT)
Simple venting configuration
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1:
H H H
Formula 2:
H H H
See graph to determine the required vertical rise VT for the required horizontal run HT.
EN
(only one 90° elbow)
REQUIRED
VERTICAL
RISE IN INCHES
(CENTIMETERS) V
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT
The shaded area within the lines represents acceptable values for H
< 4.2 V
H
Formula 2: HT + V
T
T
< 24.75 feet (7.5m)
T
Example:
= VT = 6 FT (1.8m)
V
1
= 3 FT (0.9m)
H
1
H
= 5 FT (1.5m)
2
= H
+ H
H
R
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7FT (0.8m)
O
= H
T
+ V
T
= 3FT (0.9m) + 5FT (1.5m) = 8FT (2.4m)
1
2
+ H
= 8FT (2.4m) + 2.7FT (0.8m) = 10.7FT (3.3m)
R
O
= 10.7FT (3.3m) + 6FT (1.8m) = 16.7FT (5.1m)
T
150 (381)
147 (373)
100 (254)
T
57 (145)
50 (127)
8 (20.3)
0
(1.5)
2
(0.6)
90°
V
1
5
10
(3.1)
12.5 (3.8)
(4.6)
15
20 (6.1)
19.5 (5.9)
and VT
T
H
1
H
2
90°
Formula 1: H
4.2 VT = 4.2FT (1.3m) x 6FT (1.8m) = 25.2FT (7.7m)
16.7 FT (5.1m) < 24.75 FT (7.5m)
Since both formulas are met, this vent configuration is acceptable.
< 4.2 V
T
+ V
H
T
T
< 24.75 FT (7.5m)
T
90°
Example:
= 4 FT (1.2m)
V
1
V
= 1.5 FT (0.5m)
2
= V
+ V
V
T
H
= 2 FT (0.6m)
1
= 1 FT (0.3m)
H
2
= 1 FT (0.3m)
H
3
H
= 1.5 FT (0.5m)
4
= H
H
R
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT (2.5m)
O
= H
T
+ V
T
Formula 1: H
4.2 VT = 4.2 FT (1.3m) x 5.5 FT (1.7m) = 23.1 FT (7m)
= 4 FT (1.2m) + 1.5 FT (0.5m) = 5.5 FT (1.7m)
1
2
+ H2 + H
1
+ H
R
= 13.6 FT (4.2m) + 5.5 FT (1.7m) = 19.1 FT (5.8m)
T
+ H4 = 2FT (0.6m) + 1FT (0.3m) + 1FT (0.3m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
3
= 5.5 FT (1.7m) + 8.1 FT (2.5m) = 13.6 FT (4.2m)
O
< 4.2 V
T
T
V
1
13.6 FT (4.2m) < 23.1 FT (7m)
Formula 2: HT + V
19.1 FT (5.8m) < 24.75 FT (7.5m)
< 24.75 FT (7.5m)
T
Since both formulas are met, this vent configuration is acceptable.
H
1
90°
90°
16.16
90°
H
V
2
H
H
2
3
4
W415-1768 / 06.12.17
3.9 REAR EXIT HORIZONTAL TERMINATION
(HT) < (VT)
19
Simple venting configuration
(only two 90° elbows)
See graph to determine the required vertical rise V
horizontal run H
40 (12.2)
38.3 (11.7)
REQUIRED
30 (9.1)
VERTICAL
RISE IN
20 (6.1)
FEET
(METERS) V
T
1.6 (0.5)
10 (3.1)
0
2.5
(0.8)5 (1.5)
1.6
(0.5)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable values for H
and HT
For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: H Formula 2: HT + V
Example:
= 9 FT (2.7m)
V
1
V
= 6 FT (1.8m)
2
= V
V
T
1
= 3 FT (0.9m)
H
1
H
= 2 FT (0.6m)
2
= 1.5 FT (0.5m)
H
3
H
= H
R
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT (2.5m)
H
O
= H
H
T
H
+ V
T
T
Formula 1: H
14.6 FT (4.5m) < 15 FT (4.6m) Formula 2: HT + V
29.6 FT (9m) < 40 FT (12.2m)
< V
T
T
< 40 feet (12.2m)
T
+ V
= 9FT (2.7m) + 6FT (1.8m) = 15FT (4.6m)
2
+ H2 + H
1
+ H
R
= 14.6FT (4.5m) + 15FT (4.6m) = 29.6 FT (9m)
= 3FT (0.9m) + 2FT (0.6m) + 1.5FT (0.5m) = 6.5FT (2m)
3
= 6.5FT (2m) + 8.1FT (2.5m) = 14.6FT (4.5m)
O
< V
T
T
< 40 FT (12.2m)
T
H
1
Since both formulas are met, this vent configuration is acceptable.
7.5
(2.3)
(6.1)
T
EN
20
T
for the required
.
T
(3.1)
T
10
12.5
15
(4.6)
17.5 (5.3)
(3.8)
90°
H
3
V
2
90°
H
2
V
1
90°
90°
16.3A
W415-1768 / 06.12.17
EN
(HT) > (VT)
20
Simple venting configuration
(only two 90° elbows)
See graph to determine the required vertical rise V
150(3810)
147 (3733.8
required horizontal run H
.
T
for the
T
REQUIRED
VERTICAL RISE IN
100 (2540)
INCHES
(MILLIMETERS)V
T
66
(1676.4)
50 (1270)
12
(304.8)
0
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: H Formula 2: HT + V
< 3.5V
T
T
< 24.75 feet (7.5m)
T
Example:
= 4 FT (1.2m)
V
1
V
= 1.5 FT (0.5m)
2
= V
+ V
V
T
= 2 FT (0.6m)
H
1
H
= 1 FT (0.3m)
2
= 1 FT (0.3m)
H
3
H
= 1.5 FT (0.5m)
4
= H1+ H2+H3+H4= 2FT(0.6m) + 1FT(0.3m) + 1FT(0.3m) + 1.5FT(0.5m) = 5.5 FT(1.7m)
H
R
= .03 (four 90° elbows + one 45° elbow - 90°)
H
O
= .03 (90 + 90 + 90 + 90 + 45 - 90) = 9.45 FT (2.9m)
H
= H
T
H
+ V
T
Formula 1: H
3.5VT = 3.5FT (1.1m) x 5.5FT (1.7m) = 19.25FT (5.9m)
= 4FT (1.2m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
1
2
+ H
= 5.5FT (1.7m) + 9.45FT (2.9m) = 14.95FT (4.6m)
R
O
= 14.95FT (4.6m) + 5.5FT (1.7m) = 20.45FT (6.2m)
T
< 3.5V
T
T
14.95 FT (4.6m) < 19.25 FT (5.9m)
Formula 2: HT + V
20.45 FT (6.2m) < 24.75 FT (7.5m)
< 24.75 FT (7.5m)
T
Since both formulas are met, this vent configuration is acceptable.
2.5
(0.8)5 (1.5)
1
(0.3)
(1.1)
values for H
7.5
10
12.5
15
17.5
(2.3)
(3.1)
(3.8)
3.5
and HT
T
(4.6)
(5.3)
19.25 (5.9)
(6.1)
20
T
90°
H
3
V
2
90°
H
2
V
1
H
1
90°
90°
W415-1768 / 06.12.17
16.3_2B
3.10 TOP AND REAR EXIT VERTICAL TERMINATION
for the
(HT) < (VT)
Simple venting configurations.
REQUIRED
VERTICAL RISE
IN FEET
(METERS)V
See graph to determine the required vertical rise V
T
40 (12.2)
30 (9.1)
20 (6.1)
required horizontal run HT.
21
T
EN
3 (0.9)
10 (3.1)
0
5
(1.5)
10
(3.1)
15
(4.6)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
(METERS) H
T
The shaded area within the lines represents acceptable
values for H
and HT
T
For vent configurations requiring one or more 90° elbows (top exit) or one or more 90° elbows (rear exit), the following formulas apply:
Formula 1: H Formula 2: HT + V
< V
T
T
< 40 feet (12.2m)
T
Example:
= 5 FT (1.5m)
V
1
V
= 6 FT (1.8m)
2
= 10 FT (3.1m)
V
3
V
= V
+ V2 + V
T
1
= 8 FT (2.4m)
H
1
H
= 2.5 FT (0.8m)
2
= H1+ H2 = 8FT (2.4m) + 2.5FT (0.8m) = 10.5FT (3.2m)
H
R
= .03 (four 90° elbows - 90°)
H
O
= .03 (360° - 90°) = 8.1 FT (2.5m)
H
= H
+ H
T
R
H
+ V
= 18.6FT (5.7m) + 21FT (6.4m) = 39.6FT (12.1m)
T
T
= 5FT (1.5m) + 6FT (1.8m) + 10FT (3.1m) = 21 FT (6.4m)
3
= 10.5FT (3.2m) + 8.1FT (2.5m) = 18.6FT (5.7m)
O
20
(6.1)
Formula 1: H
18.6 FT (5.7m) < 21 FT (6.4m) Formula 2: HT + V
39.6FT (12.1m) < 40 FT (12.2m)
< 3.5V
T
< 40 FT (12.2m)
T
T
Since both formulas are met, this vent configuration is acceptable.
18.2A
W415-1768 / 06.12.17
EN
(HT) > (VT)
22
Simple venting configurations.
REQUIRED
VERTICAL
RISE IN
FEET
(METERS)V
See graph to determine the required vertical rise V
T
20
(6.1)
.
(7.6)
19 (5.8)
3 (0.9)
T
20 (6.1)
10 (3.1)
required horizontal run H
5
0
(1.5)
10
(3.1)
15
(4.6)
for the
T
25
30
(9.1)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H
The shaded area within the lines represents acceptable
values for H
and HT
T
For vent configurations requiring more than two 90° elbows (top exit) or one 90° elbow (rear exit), the following formulas apply:
Formula 1: H Formula 2: HT + V
< 3 V
T
T
< 40 feet (12.2m)
T
Example:
= 2 FT (0.6m)
V
1
V
= 1 FT (0.3m)
2
= 1.5 FT (0.5m)
V
3
= V
V H H H H
= .03 (360° - 90°) = 8.1 FT (2.5m)
H H
Formula 1: H
3.5 V
16.1FT (4.9m) < 13.5 FT (4.1m)
+ V2 + V3 = 2FT (0.6m) + 1FT (0.3m) + 1.5FT (0.5m) = 4.5 FT (1.4m)
T
1
= 6 FT (1.8m)
1
= 2 FT (0.6m)
2
= H
+ H
R
= .03 (four 90° elbows - 90°)
O
= H
T
+ V
T
= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
1
2
+ H
= 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m)
R
O
= 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6FT (6.3m)
T
< 3.5 V
T
T
= 3FT (0.9m) x 4.5FT (1.4m) = 13.5 FT (4.1m)
T
90°
90°
V
V
1
H
1
V
H
2
2
90°
3
90°
Since this formula is not met, this vent configuration is unacceptable. Formula 2: HT + V
16.1FT (4.9m) < 13.5 (4.1m)
< 40 FT (12.2m)
T
Since only formula 2 is met, this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas.
18.2_2B
T
W415-1768 / 06.12.17
Example:
V
WARNING
FAILURE TO CREATE A SEAL TO THE FIREBOX WITH THE EXHAUST COLLAR ASSEMBLY WILL CAUSE
DEFLECTOR
= 1.5 FT (0.5m)
1
= 5 FT (1.5m)
V
2
= V
V H H H H H = .03 (270° + 45° - 90°) = 6.75 FT (2.1m) H H
+ V2 = 1.5FT (0.5m)+ 5FT (1.5m) = 6.5 FT (2m)
T
1
= 1 FT (0.3m)
1
= 1 FT (0.3m)
2
= 10.75 FT (3.3m)
3
= H
+ H2 + H3 = 1FT (0.3m) + 1FT (0.3m) + 10.75FT (3.3m) = 12.75FT (3.9m)
R
1
= .03 (three 90° elbows + one 45° elbow - 90°)
O
= H
+ H
T
T
+ V
= 12.75FT (3.9m) + 6.75FT (2.1m) = 19.5 FT (5.9m)
R
O
= 19.5FT (5.9m) + 6.5FT (2m) = 26 FT (7.9m)
T
Formula 1:
< 3 V
H
T
3 V
19.5FT (5.9m) = 19.5FT (5.9m)
T
= 3FT (0.9m) x 6.5FT (2m) = 19.5FT (5.9m)
T
Formula 2: HT + V 26 FT (7.9m) < 40 FT (12.2m)
< 40 FT (12.2m)
T
Since both formulas are met, this vent configuration is acceptable.
3.11 REAR EXIT
23
EN
V
2
90°
H
1
H
2
45°
V
1
H
3
90°
90°
18.2_3B
!
THE APPLIANCE TO FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE.
A. Remove the safety screen and glass front, refer
to " SAFETY SCREEN / DOOR REMOVAL AND INSTALLATION" section.
B. Remove the contents from the firebox and set aside, you
will need the exhaust flue collar from the top of the log carton.
C. To ease assembly, remove the four hex head screws
securing the deflector from inside the top front of the firebox, refer to Figure 1.
D. Place the gasket (provided) over the 4" (102mm) flue collar assembly and
bend along perforation.
E. From inside the firebox, insert the 4" (102mm) flue collar through the back
of the firebox. Install the rear exit shield onto the 4" (102mm) flue collar, see "REAR EXIT SHIELD" section for installation instructions.
F. Secure the flue collar assembly, gasket and rear exit shield using the four
hex head 3/8" thread cutting screws, refer to Figure 2. NOTE: Do not
overtighten. The gasket needs only to be snug against the firebox.
G. Reattach the deflector using the four screws and install the log set, glass
door and safety screen.
Fig. 1
Fig. 2
W415-1768 / 06.12.17
24
3.12 REAR EXIT SHIELD (FOR REAR VENT ONLY)
A. Remove the safety barrier assembly and door from the appliance, refer to the “SAFETY SCREEN &
EN
DOOR REMOVAL / INSTALLATION” section of the manual for detailed instructions.
B. Loosen the two screws, that secure the exhaust plate, and slide the shield in place by sliding its slotted openings behind the screwheads, tighten the two previously loosened screws. Refer to the illustration below.
C. Reinstall the door and safety barrier assembly on the appliance, refer to the “SAFETY SCREEN & DOOR REMOVAL / INSTALLATION” section of the manual for detailed instructions.
NOTE: THIS SHIELD IS USED TO BLOCK THE VIEW THROUGH THE VENTING TO THE OUTDOORS.
W415-1768 / 06.12.17
3.13 TOP EXIT
INTAKE COLLAR
ASSEMBLY
GASKET
OUTER COVER
INNER
D
E
E
WARNING
DEFLECTOR
25
!
FAILURE TO INSTALL THE COVER PLATE AND GASKET WILL CAUSE THE APPLIANCE TO
FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE.
NOTE: This appliance has been factory shipped as a rear vent.
A. Remove the safety screen and glass front, refer to " SAFETY SCREEN / DOOR REMOVAL AND
INSTALLATION" section.
B. Remove the contents from the firebox and set aside,
you will need the exhaust collar from the top of the log carton.
C. To ease assembly, remove the four hex head screws
securing the deflector from inside the top front of the firebox.
D. Remove the single screw from the outer cover on the
back of the appliance.
E. Remove the four screws on the 7" (178mm) intake
collar assembly; set the intake collar and gasket aside. Careful not to damage gasket.
F. Remove the single screw from the outer cover with
knockout intact, on the top of the appliance and set aside.
G. Remove the inner cover plate and gasket by removing
the four screws. Reinstall the inner cover plate and gasket onto the back of the appliance.
H. Take the outer cover (with knockout intact) and secure
onto the back of the appliance.
I. Remove and discard the 1 1/2" thick batt of insulation
from the top opening.
J. Place the 7" (178mm) intake collar
and gasket onto the top of the appliance and secure with the four screws.
K. Reinstall the outer cover (without
knock out) over the 7" (178mm) exhaust collar assembly and secure.
L. From inside the firebox, install the 4"
(102mm) exhaust collar up through the top of the firebox and secure with the the four hex head 3/8" thread cutting screws. NOTE: Do not overtighten. The gasket needs only to be snug against the
firebox.
M. Reattach the top deflector, log set, glass door and safety screen.
F
I
GASKET
INTAKE COLLAR
OUTER COVER
(with knockout)
E
ASSEMBLY
OUTER COVER
COVERPLATE
G
EXHAUST FLUE COLLAR
EN
E
D
GASKET
W415-1768 / 06.12.17
26
WARNING
WARNING
(NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR WHICH MUST
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, A MINIMUM OF 3 SCREWS MUST ALSO
4.0 INSTALLATION
EN
!
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE, ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
EXACTLY.
ALL EXHAUST AND INTAKE VENT PIPE JOINTS MUST BE SEALED USING RED RTV HIGH TEMP
SILICONE SEALANT (W573-0002) (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC (W573-0007)
BE SEALED USING MILL PAC.
BE USED TO ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2D
4.1 WALL AND CEILING PROTECTION
!
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
70.1
W415-1768 / 06.12.17
4.1.1 HORIZONTAL INSTALLATION
CAULKING
VENT
PIPE
COLLAR
fi restop.
WARNING
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
This application occurs when venting through an exterior wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall as illustrated to accommodate the fi restop assembly. Dry fi t the fi restop assembly before proceeding to ensure the brackets on the rear surface fi t to the inside surface of the horizontal framing.
The vent shield must be installed to the full depth of the combustible wall. The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2" (216mm) thick.
reduced side clearances or move the shield for reduced top clearances.
A. Apply a bead of caulking (not supplied) around the corner edge of the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your manual baggie).
NOTE : Do not fi ll the air space
between the fi restop spacer and the exterior wall with any type of insulating material (i.e., spray foam).
B. Once the vent pipe is installed in its fi nal position, apply red
NOTE: Bend the tabs for
RTV silicone sealant (W573-0002) (not supplied) between the pipe and the
!
CAULKING
FIRESTOP
SPACER
CAULKING
27
EN
VENT
SHIELD
DETERMINE THE CORRECT HEIGHT
FINISHING MATERIAL
4.1.2 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for various roof pitches are available from your authorized dealer / distributor. See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1" (25mm) clearance between the vent pipe and any combustible material. Try to center the vent pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings. A vent pipe shield will prevent any materials such as insulation, from fi lling up the 1" (25mm) air space around the pipe. Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the
Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished ceiling), and secure over the opening in the ceiling. A fi restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a fi restop spacer over the vent shield to restrict cold air from being drawn into the room or around the fi replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply Mill Pac sealant (W573-0007) (not supplied) or red RTV silicone (W573-0002) (not supplied) between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1" (25mm) air space around the pipe.
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
VENT
PIPE
SHIELD
21.1B
W415-1768 / 06.12.17
28
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high temperature
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
WARNING
A. Stretch the inner fl ex pipe to the required length taking into account
B.
C.
D.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its return fl ange.
HI-TEMP
SEALANT
ADD FASTENER TYPE
4.2 USING FLEXIBLE VENT COMPONENTS
EN
!
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
For safe and proper operation of the appliance, follow the venting instructions exactly.
Elbow
Spacers
“Wolf Steel Approved Venting” or “E2” as identifi ed by the stamp on the fl ex pipes.
red RTV silicone W573-0002 (not supplied) or the high temperature sealant W573­0007 Mill Pac (not supplied). However, the high temperature sealant W573-0007 Mill Pac (not supplied) must be used on the joint connecting the inner fl ex pipe and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
22.1C
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION
the additional length needed for the fi nished wall surface. Apply a heavy bead of the Mill Pac sealant (W573-0007) (not supplied) to the inner sleeve of the air terminal. Slip the vent pipe a minimum of 2” (50.8mm) over the inner sleeve of the air terminal and secure with a minimum of 3 screws.
Using the outer fl ex pipe, slide over the outer
combustion air sleeve of the air terminal and secure with a minimum of 3 screws. Seal using red RTV silicone (W573-0002) (not supplied).
Insert the vent pipes through the fi restop maintaining the
required clearance to combustibles. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).
If more vent pipe needs to be used to reach the fi replace,
couple them together as illustrated. The vent system must be supported approximately every 3 feet (0.9m) for both vertical and horizontal runs. Use non-combustible strapping to maintain the minimum clearance to combustibles.
SCREWS
(SUPPLIED)
HI-TEMP
SEALANT
OUTER
FLEX PIPE
CAULKING
INNER FLEX
PIPE
2" (50.8mm) OVERLAP
HIGH TEMPERATURE
INNER FLEX PIPE
OUTER FLEX PIPE
SEALANT
SCREWS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE
W415-1768 / 06.12.17
23.1D
4.2.2 VERTICAL AIR TERMINAL INSTALLATION
A.
B.
C.
D.
E.
F.
G.
H.
WARNING
29
!
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
NOTE : Fastening hardware provided with appropriate roof terminal and liner kits.
Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case the
venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
Stretch the inner fl ex pipe to the required length. Slip the inner
fl ex pipe a minimum of 2” (51mm) over the inner pipe of the air terminal connector and secure with a minimum of
3 screws. Seal using a heavy bead of Mill Pac sealant (W573-0007) (not supplied).
Repeat using the outer fl ex pipe, using a heavy bead of red
RTV silicone (W573-0002) (not supplied) and a minimum of 3 screws.
Thread the air terminal connector / vent pipe assembly
down through the roof. The air terminal must be positioned vertically and plumb. Attach the air terminal connector to the roof support, ensuring that the top of the air terminal is 16” (40.6cm) above the highest point that it penetrates the roof.
Remove nails from the shingles, above and to the sides of the air
terminal connector. Place the fl ashing over the air terminal connector leaving a min. 3/4” (19mm) of the air terminal connector showing above the top of the fl ashing. Slide the fl ashing underneath the sides and upper edge of the shingles. Ensure that the air terminal connector is properly centered within the fl ashing, giving a 3/4” (19mm) margin all around. Fasten to the roof. Do not nail through the lower portion of the fl ashing. Make weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the fl ashing with roofi ng material.
Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal. Secure with 3 screws.
Apply a heavy bead of weatherproof caulking 2” (51mm)
above the fl ashing. Install the storm collar around the air terminal and slide down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved.
If more vent pipe needs to be used to reach the appliance see
“HORIZONTAL AIR TERMINAL INSTALLATION” section.
ROOF SUPPORT
AIR
TERMINAL
CONNECTOR
2” (51mm)
INNER PIPE
MILL PAC SEALANT
(W572-0007)
INNER FLEX PIPE
OUTER FLEX PIPE
AIR INLET BASE
CAULKING
STORM COLLAR
24.1D
FLASHING
WEATHER SEALANT
EN
W415-1768 / 06.12.17
30
A. Install the inner exhaust fl ue collar to the appliance. Secure
B.
The vent system must be supported approximately every 3 feet (0.9m) for both vertical and horizontal runs. Use Wolf Steel Ltd. support ring assembly or equivalent noncombustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs.
All inner exhaust and outer intake vent pipe joints may be sealed using either red high temperature silicone sealant (W573-0002) (not supplied) or black high temperature sealant W573-0007 Mill Pac (not supplied) with the exception of the appliance exhaust fl ue collar which must be sealed using Mill Pac.
A. Move the appliance into position. Measure the
B.
C.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of the return fl ange.
26.1A
WARNING
4.2.3 APPLIANCE VENT CONNECTION
EN
with a minimum of 3 #8 screws. Seal the joint and screw holes using Mill Pac sealant (W573-0007) (not supplied).
Install the outer fl ex pipe to the appliance. Attach and seal the joints using a red RTV silicone and a minimum of 3 #8 screws.
4.3 USING RIGID VENT COMPONENTS
4.3.1 HORIZONTAL AIR TERMINAL INSTALLATION
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
#8 X 1/2”
SELF
DRILLING
SCREWS
28.1D
25.1A
2” (50.8mm) OVERLAP
HIGH TEMP SEALANT
!
vent length required between terminal and appliance taking into account the additional length needed for the fi nished wall surface and any 1¼” (31.8mm) overlaps between venting components.
Apply high temperature sealant W573-0007 Mill Pac
(not supplied) to the outer edge of the inner exhaust fl ue collar of the appliance. Attach the fi rst inner rigid pipe component and secure using a minimum of 3 self tapping screws. Repeat using the outer rigid pipe.
Insert the vent pipes through the fi restop maintaining the required clearance to combustibles. Holding
the air terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).
#10x2"
SCREWS
CAULKING
OUTER RIGID PIPE
INNER RIGID
PIPE
SELF DRILLING
1" (25.4mm)
OVERLAP
HI-TEMP
SEALANT
#8x1/2"
SCREWS
W415-1768 / 06.12.17