NAMUR refers to the standards
committee of measurement and control
of the chemical industry of Europe.
Namco sensors comply with DIN 19234
and therefore are compatible with the
NAMUR requirements.
NAMUR sensors are typically used
for hazardous location sensing in areas
that require extremely compact sensors.
Namur Sensors are not stand-alone
sensors unless your control system input
is capable of determining current
change. Unlike most other sensors, the
Namur Sensor uses very low voltage as a
source and changes the current passed
through as a function of how close the
Sensing
Range
Shielded Unshielded
target is to the sensing coil. Namur
sensors are used with either stand-alone
amplifiers or Namur specific PLC input
cards. When used in a hazardous
location, an appropriate barrier is
required.
Maximum
Maximum
Load
Current
Switching
Frequency
ShieldedUnshielded
Short
Circuit
Protected
Please consult factory for other versions.
Protected by the
Lifetime Replacement Program
142
Namco • 2013 West Meeting Street • Lancaster, SC 29720 • 1-803-286-8491 • FAX: 1-800-678-6263
Shielded Standard Target6.5mm: 8x8x1
(mm) (mild steel) 8mm: 8x8x1
12mm: 12x12x1
18mm: 18x18x1
30mm: 30x30x1
Sm. Rec.: 12x12x1
Unshielded Standard Target 8mm: 8x8x1
(mm) (mild steel)12mm: 12x12x1
18mm: 24x24x1
30mm: 45x45x1
Sm. Rec.: 16x16x1
Repeatability2%
Hysteresis3-8% (typ.); 15% (max.)
Temperature Drift (Max.)±15%
Ambient Temperature Range-13˚F to +158˚F
Current ConsumptionN/A
NEMA Rating1, 3, 4, 6, 13
LED IndicatorN/A
Metal HousingsChromed Brass
Plastic HousingsUltradur®
Shipping Weight6.5mm: 8 oz.
8mm: 8 oz.
12mm: 8 oz.
18mm: 8 oz.
30mm: 10 oz.
34mm: 11 oz.
Flat Pack: 5 oz.
(Add 5 oz. for Cable model)
Dimensional Drawings
6.5mm DIAMETER SENSOR
8mm DIAMETER SENSOR
12mm DIAMETER SENSOR
18mm DIAMETER SENSOR
30mm DIAMETER SENSOR
1.57" (40.0)
Metal Shielded
Plastic Shielded & Unshielded
NAMUR
1.18"
(30.0)
1.20" (30.0)
Shielded
1.18" (30.0)
Metal Shielded
Plastic Shielded & Unshielded
0.91" (23.0)
Metal Unshielded
1.18" (30.0)
Metal Unshielded
Special Application Solut
Circuit Drawings
SENSOR WIRING DIAGRAM
1.65"
(42.0)
Small Rectangular SENSOR
1.57"
(40.0)
0.47"
(12.0)
2013 West Meeting Street • Lancaster, SC 29720
LED
1.02"
(26.0)
1-803-286-8491 • FAX: 1-800-678-6263
www.namcocontrols.com
For technical assistance, call 1-800-NAMTECH
143
S
ions
Intrinsically
Hazardous Location
Safe
Sensor Systems
For use in:
Class I - Groups A, B, C, & D
Class II - Groups E, F, & G
The EE931 Hazardous Location
sensor system is excellent for sensing of
position in paint spray booths, belt slip
on conveyors, or anywhere that explosion
proof switches are normally used. Since
the EE931 system is intrinsically safe, no
special housings are required to contain
any potential flame. Intrinsic Safety is
obtained by design of the product such
that extremely limited energy is available
in the hazardous location. For this
reason, these Namco sensors must only
be used with the Namco control module.
It is possible, however, to use the Namco
control module with either the Namco
sensors listed in this section or a
standard limit switch. (Limit switches
must be of the gold contact type due to
the low current and voltage supplied by
the control module.)
Sensors
Namco offers a variety of intrinsically
safe sensors for use in Class I, Groups A,
B, C, and D and Class II, Groups E, F, and
G hazardous locations. These EE931-
pecial Application Solut
series sensors must be used ONLY in
conjunction with Namco’s EE931-series
control modules. The hazardous location
sensors are completely encapsulated and
contain a transistor oscillator circuit.
Variations in oscillator amplitude caused
CONTROL MODULES
BARRIER
Hazardous
Hazardous
Hazardous
HAZARDOUS
AREA
An intrinsically safe proximity sensor system consists of a sensor, which is mounted in the
hazardous area, and a control module, which is mounted in the safe area.
by metallic objects passing in front of the sensor face
produce activation of the control module output.
Twenty feet of 18AWG oil resistant cable is provided
with tubular sensors, although up to 1000 feet can be
obtained for applications where the hazardous area is a
considerable distance away from the safe area control
panel. Sensors providing up to one inch of sensing range
are available.
Cylindicator® sensor versions are provided with 50 feet
of cable. For longer cable lengths, consult factory.
Tubular Sensors (See “Sensing Range” opposite page)
Sensing Range
Model
No.
EE931-562000.20"0.25"0.40"3/4"-202 Cond.
EE931-765000.37"0.25"0.57"M30 x 1.52 Cond.
EE931-751001.00"0.50"2.50"M30 x 1.52 Cond.
Namco • 2013 West Meeting Street • Lancaster, SC 29720 • 1-803-286-8491 • FAX: 1-800-678-6263
“A”“B”
Sensing FieldSide
(5.0)(6.3)(10.1)18 AWG SVO
(9.5)(6.3)(14.6)18 AWG SVO
(25.4)(12.7)(63.5)18 AWG SVO
“C”Cable
Mtg. Clear.Thread(20')
ions
Dimensional Drawings
90˚ ROTATABLE
CYLINDICATOR
®
SENSOR
1.09"
(27.7)
Dimensional Drawings
TUBULAR SENSOR – 3/4-20 THREAD
17mm SMOOTH BARREL
Model No.
1.38"
EE931-56200
2 COND/
18 AWG
SVO OR
SJO
BLACK (COMMON)
WHITE (+VDC)
1.25"
(28.6)
1/2-14 NPT
1.00" HEX
(25.4)
Side ViewTop View
0.59"
(15.0)
(2) 1/4-20 X 1 1/4"
SOC HD CAP
SCREWS
SUPPLIED
0.50"
(12.7)
(35.0)
3.30"
(83.8)
2.43"
(61.7)
SLOT FOR #10 SCREWS
3/4-20 UNEF
0.88"
(22.4)
1.51"
(38.4)
1.75"
(44.4)
PROBE
LENGTH
(SEE CHART)
Sensor Mounting
Sensors may be installed with mounting bracket furnished in
any position provided the sensor face is kept free of electrically
conductive material. See below for maximum sensing range and
pattern of minimum mounting distances from other conductive
materials for the EE931-series sensors.
See the Cylindicator section in this book for application
information on Cylindicator sensors.
Factors influencing sensing range are temperature, target size,
target material, and speed. For best all-around performance, use
“slide-by” actuation as opposed to “head-on” actuation. Target
should present as much surface area to the sensor face as practical.
Sensing of non-ferrous metals may reduce sensing range by as
much as 50%, depending on the type of material. Since the sensing
range of each sensor is fixed, no control module adjustment is
required. The target should be placed as close to the sensor face as
possible. Namco recommends setting the target at one-half the
“maximum” sensing range or closer for best system operation.
Sensing Range
"B"
LABEL
"B"
NOMINAL
SENSING
RANGE
PATTERN
OF MINIMUM
MOUNTING
CLEARANCE
ACTUAL
SENSING
RANGE
"A"
"C"
0.80"
(20.3)
0.40"
0.16"
(10.1)
(4.0)
1.00"
(25.4)
TUBULAR SENSOR – M 30x1.5
FULL THREAD
Model No.
EE931-76500
2C/18 AWG
SVO OR SJO
1.63"
(41.3)
WHITE
(+VDC)
(COMMON)
0.20" WIDE X 1.00" LONG SLOT
1.65"
(41.9)
FEMALE ENTRY
BLACK
2 HOLES
1.16"
(29.4)
LABEL
1/2-14 NPT
1.50"
(38.1)
3.54"
(89.9)
TUBULAR SENSOR – M 30x 1.5 THREAD
1" SMOOTH BARREL
Model No.
EE931-75100
0.03"
2 COND/18AWG
SVO OR SJO
CABLE
(0.76)
0.78"
(19.8)
1.16"
(29.4)
1.65"
(41.9)
0.20" (5.08) WIDE X 1.00" (25.4) LONG SLOT
1.50"
(38.1)
2 HOLES
3.78"
(96.0)
1-7/16" ACROSS
BLACK (COMMON)
WHITE (+VDC)
LABEL
Continued on
next page.
➟
2013 West Meeting Street • Lancaster, SC 29720
1-803-286-8491 • FAX: 1-800-678-6263
0.67"
(17.0)
LABEL
0.68"
(17.2)
0.36"
(9.1)
1.09"
(27.7)
X
1.5 THREAD
M30
0.78"
(19.8)
1.44"
(36.6)
ACROSS
FLATS
2.20"
(55.9)
1.00"
(25.4)
M30 X 1.5 THREAD
(36.6) FLATS
1.625"
(41.3)
www.namcocontrols.com
Special Application Solut
For technical assistance, call 1-800-NAMTECH
145
S
ions
Intrinsically
Hazardous Location
Safe
Sensor Systems
Control Modules
The EE931-series control modules
are designed to be mounted in the safe
area. These modules provide limited
energy to Namco’s line of hazardous
location sensors described on the
previous pages. The control modules are
housed in high impact Lexan® enclosures and are equipped with eight screw
terminals (#8 stud size) for ease of
installation. The EE931-02103 module
provides an electro-mechanical relay
output (One Form C), while the EE93102303 unit has a photo-darlington (open
collector) output for higher speed
requirements. The outputs become
energized when a metallic target is
present in front of the associated sensor.
Control Module Mounting:
The EE931-series control module
should be panel mounted in the safe
area where it will be protected from
physical damage, dirt, and vibration. The
location should be established within the
limits of the sensor cable. The unit can be
mounted vertically or horizontally using
two No. 8 screws. When mounting with
only two screws, it is imperative to use
the two mounting holes provided with
brass eyelet inserts. This method
provides an additional ground path for
the electronic circuit contained in the
module. The ambient temperature range
should be from -40°F to +158°F. The
physical construction of the control
module housing insures a separation of
at least two inches between intrinsically
safe terminals (5 and 6) and nonintrinsically safe terminals (7 thru 12).
It is important when installing the sensor
cable to the control unit terminals (5 and
6) to maintain this minimum spacing of
two inches. A separate wiring duct is
required to insure that the intrinsically
safe sensor cable does not become
intermingled with non-intrinsically safe
wiring due to vibration. A separate
conductor MUST be wired from Terminal
9 to earth ground to insure intrinsic
safety of the system. Terminal 8 is for
the neutral side of AC line. Terminal 7 is
hot side of AC line and MUST be wired
accordingly or intrinsic safety is voided.
Namco advises that the Instrument
Society of America Specification RP12.6,
which gives the recommended practice
for installation of intrinsically safe
systems, be followed when using the
EE931-series control modules and
sensors.
pecial Application Solut
146
Namco • 2013 West Meeting Street • Lancaster, SC 29720 • 1-803-286-8491 • FAX: 1-800-678-6263
ions
Dimensional Drawing
123456
4.00"
(101.6)
3.25"
(82.5)
#8 - 32 X 5/16"
SCREWS (8)
OUTPUT
INDICAT OR
0.73"
(18.5)
PRIMARY
MOUNTING
HOLES (WITH
BRASS
EYELETS)
LABEL
1.06"
(27.0)
3.00"
(76.2)
1.16"
(29.3)
CONTROL
MODULE
0.82"
(20.9)
0.27"
(6.8)
0.37" TYP
(9.5)
789 10 11 12
0.38" TYP
(9.6)
3.25"
(82.5)
0.37" TYP
(9.5)
4.00"
(101.6)
Circuit Drawings
RELAY OUTPUTPHOTO-DARLINGTON
OUTPUT
+
—
BLK
LOAD #1
WHT
CONTROL MODULE
MENTOR, OHIO 44060
INPUT
115VAC
50/60 HZ
2.5 VA
LINENEUT.
CONTROL MODULE
MENTOR, OHIO 44060
INPUT
115VAC
50/60 HZ
2.5 VA
LINENEUT.
TO HAZARDOUS LOCATION
INTRINSICALLY SAFE
®
EE931-02103
RATING
SPOT SWITCH
ONLY ONE
POLARITY
STD DUTY
120 VAC
OR SA RESISTIVE
GRND.
@ 120 VAC
SENSOR #1
OUTPUT
STATUS
+
EE931-02103 NON-HAZARDOUS
LOCATION CONTROL UNIT FOR
EE931-SERIES SENSORS USED IN
CLASS I GROUPS. A. B. C AND D;
CLASS II. GROUPS E. F. AND G
HAZARDOUS LOCATIONS.
RELAY OUTPUT
TO HAZARDOUS LOCATION
INTRINSICALLY SAFE
®
EE931-02303
RATING
RATING
24Vceo
MAX.
50 mA MAX.
GRND.
SENSOR #1
OUTPUT
STATUS
+
EE931-02303 NON-HAZARDOUS
LOCATION CONTROL UNIT FOR
EE931-SERIES SENSORS USED IN
CLASS I GROUPS. A. B. C AND D;
CLASS II. GROUPS E. F. AND G
HAZARDOUS LOCATIONS.
OUTPUT - PHOTO-DARLINGTON
LOAD #1
+
—
BLK
WHT
Common Control Module Characteristics
INTRINSICALLY SAFE CONTROL MODULE
EE931-02103EE931-02303
OutputElectro-MechanicalPhoto-Darlington
Speed (Hz)31400
Supply Voltage120 VAC
Sensor InputNamco EE931-Series only
Ambient
Temperature
Case MaterialLexan
SPDT Relay50mA max.
Rated 5A Resist.@ 24 VAC
One form COpen Collector
-40˚F to +158˚F
Special Application Solut
2013 West Meeting Street • Lancaster, SC 29720
1-803-286-8491 • FAX: 1-800-678-6263
www.namcocontrols.com
For technical assistance, call 1-800-NAMTECH