Namco Controls Namur Sensor Application Information

S
ions
NAMUR Sensors
PWR
Ch 1
O/P
FAIL
Ch 2
NAMUR refers to the standards committee of measurement and control of the chemical industry of Europe. Namco sensors comply with DIN 19234 and therefore are compatible with the NAMUR requirements.
NAMUR sensors are typically used for hazardous location sensing in areas
Connector Circuit Housing Housing Shielded Unshielded
Type Description Material Length Model No. Model No.
6.5mm Diameter NAMUR 5-25 VDC Smooth
6.6' Cable Analog Metal 30mm ET112-00310 1mm N/A 1KHz N/A
8mm Diameter NAMUR 5-25 VDC
6.6' Cable Analog Metal 30mm ET112-10310 1mm N/A 1KHz N/A
12mm Diameter NAMUR 5-25 VDC
6.6' Cable Analog Metal 30mm ET112-20310 ET112-21310 2mm 4mm N/A 800Hz 400Hz N/A
6.6' Cable Analog Plastic 30mm ET212-20310 ET212-21310 2mm 4mm N/A 800Hz 400Hz N/A
18mm Diameter NAMUR 5-25 VDC
6.6' Cable Analog Metal 30mm ET112-30310 ET112-31310 5mm 8mm N/A 500Hz 200Hz N/A
6.6' Cable Analog Plastic 30mm ET212-30310 ET212-31310 5mm 8mm N/A 500Hz 200Hz N/A
30mm Diameter NAMUR 5-25 VDC
6.6' Cable Analog Metal 40mm (Sh) ET112-40310 ET112-41310 10mm 15mm N/A 300Hz 250Hz N/A
6.6' Cable Analog Plastic 40mm ET212-40310 ET212-41310 10mm 15mm N/A 300Hz 250Hz N/A
Small Rectangular NAMUR 5-25 VDC
pecial Application Solut
6.6' Cable Analog Plastic 12x26x40mm ET912-10310 ET912-11310 2mm 4mm N/A 800Hz 400Hz N/A
42mm (UnSh)
that require extremely compact sensors. Namur Sensors are not stand-alone sensors unless your control system input is capable of determining current change. Unlike most other sensors, the Namur Sensor uses very low voltage as a source and changes the current passed through as a function of how close the
Sensing
Range
Shielded Unshielded
target is to the sensing coil. Namur sensors are used with either stand-alone amplifiers or Namur specific PLC input cards. When used in a hazardous location, an appropriate barrier is required.
Maximum
Maximum
Load
Current
Switching Frequency
Shielded Unshielded
Short
Circuit
Protected
Please consult factory for other versions.
Protected by the
Lifetime Replacement Program
142
Namco • 2013 West Meeting Street • Lancaster, SC 29720 • 1-803-286-8491 • FAX: 1-800-678-6263
ions
Common Sensor Characteristics
(-)
(+)
1.20" (30.0)
Metal Shielded
Plastic Shielded & Unshielded
0.90" (22.0) Metal
Unshielded
NAMUR DC SENSORS
Shielded Sensing Range 6.5mm: 1mm
8mm: 1mm 12mm: 2mm 18mm: 5mm 30mm: 10mm Sm. Rec.: 2mm
Unshielded Sensing Range 8mm: 2mm
12mm: 4mm 18mm: 8mm 30mm: 15mm Sm. Rec.: 4mm
Shielded Standard Target 6.5mm: 8x8x1 (mm) (mild steel) 8mm: 8x8x1
12mm: 12x12x1 18mm: 18x18x1 30mm: 30x30x1 Sm. Rec.: 12x12x1
Unshielded Standard Target 8mm: 8x8x1 (mm) (mild steel) 12mm: 12x12x1
18mm: 24x24x1 30mm: 45x45x1
Sm. Rec.: 16x16x1 Repeatability 2% Hysteresis 3-8% (typ.); 15% (max.) Temperature Drift (Max.) ±15% Ambient Temperature Range -13˚F to +158˚F Current Consumption N/A NEMA Rating 1, 3, 4, 6, 13 LED Indicator N/A Metal Housings Chromed Brass Plastic Housings Ultradur® Shipping Weight 6.5mm: 8 oz.
8mm: 8 oz.
12mm: 8 oz.
18mm: 8 oz.
30mm: 10 oz.
34mm: 11 oz.
Flat Pack: 5 oz.
(Add 5 oz. for Cable model)
Dimensional Drawings
6.5mm DIAMETER SENSOR
8mm DIAMETER SENSOR
12mm DIAMETER SENSOR
18mm DIAMETER SENSOR
30mm DIAMETER SENSOR
1.57" (40.0)
Metal Shielded
Plastic Shielded & Unshielded
NAMUR
1.18"
(30.0)
1.20" (30.0) Shielded
1.18" (30.0)
Metal Shielded
Plastic Shielded & Unshielded
0.91" (23.0)
Metal Unshielded
1.18" (30.0)
Metal Unshielded
Special Application Solut
Circuit Drawings
SENSOR WIRING DIAGRAM
1.65"
(42.0)
Small Rectangular SENSOR
1.57"
(40.0)
0.47"
(12.0)
2013 West Meeting Street • Lancaster, SC 29720
LED
1.02"
(26.0)
1-803-286-8491 • FAX: 1-800-678-6263
www.namcocontrols.com
For technical assistance, call 1-800-NAMTECH
143
S
ions
Intrinsically
Safe
Sensor Systems
For use in: Class I - Groups A, B, C, & D Class II - Groups E, F, & G
The EE931 Hazardous Location sensor system is excellent for sensing of position in paint spray booths, belt slip on conveyors, or anywhere that explosion proof switches are normally used. Since the EE931 system is intrinsically safe, no special housings are required to contain any potential flame. Intrinsic Safety is obtained by design of the product such that extremely limited energy is available in the hazardous location. For this reason, these Namco sensors must only be used with the Namco control module. It is possible, however, to use the Namco control module with either the Namco sensors listed in this section or a standard limit switch. (Limit switches must be of the gold contact type due to the low current and voltage supplied by the control module.)
Sensors
Namco offers a variety of intrinsically safe sensors for use in Class I, Groups A, B, C, and D and Class II, Groups E, F, and G hazardous locations. These EE931-
pecial Application Solut
series sensors must be used ONLY in conjunction with Namco’s EE931-series control modules. The hazardous location sensors are completely encapsulated and contain a transistor oscillator circuit. Variations in oscillator amplitude caused
CONTROL MODULES
BARRIER
Hazardous
Hazardous
Hazardous
HAZARDOUS
AREA
An intrinsically safe proximity sensor system consists of a sensor, which is mounted in the hazardous area, and a control module, which is mounted in the safe area.
by metallic objects passing in front of the sensor face produce activation of the control module output.
Twenty feet of 18AWG oil resistant cable is provided with tubular sensors, although up to 1000 feet can be obtained for applications where the hazardous area is a considerable distance away from the safe area control panel. Sensors providing up to one inch of sensing range are available.
Cylindicator® sensor versions are provided with 50 feet of cable. For longer cable lengths, consult factory.
SAFE AREA
Protected by the
Lifetime Replacement Program
Cylindicator® Sensors
Model Probe
No. Length
EE931-30101 0.950 EE931-30401 1.025 EE931-31301 1.250 EE931-38701 2.062 EE931-37801 2.875 EE931-39001 3.775
144
Tubular Sensors (See “Sensing Range” opposite page)
Sensing Range
Model
No.
EE931-56200 0.20" 0.25" 0.40" 3/4"-20 2 Cond.
EE931-76500 0.37" 0.25" 0.57" M30 x 1.5 2 Cond.
EE931-75100 1.00" 0.50" 2.50" M30 x 1.5 2 Cond.
Namco • 2013 West Meeting Street • Lancaster, SC 29720 • 1-803-286-8491 • FAX: 1-800-678-6263
“A” “B”
Sensing Field Side
(5.0) (6.3) (10.1) 18 AWG SVO
(9.5) (6.3) (14.6) 18 AWG SVO
(25.4) (12.7) (63.5) 18 AWG SVO
“C” Cable
Mtg. Clear. Thread (20')
ions
Dimensional Drawings
90˚ ROTATABLE CYLINDICATOR
®
SENSOR
1.09" (27.7)
Dimensional Drawings
TUBULAR SENSOR – 3/4-20 THREAD 17mm SMOOTH BARREL
Model No.
1.38"
EE931-56200
2 COND/ 18 AWG SVO OR
SJO
BLACK (COMMON)
WHITE (+VDC)
1.25"
(28.6)
1/2-14 NPT
1.00" HEX (25.4)
Side ViewTop View
0.59"
(15.0)
(2) 1/4-20 X 1 1/4" SOC HD CAP SCREWS SUPPLIED
0.50" (12.7)
(35.0)
3.30"
(83.8)
2.43" (61.7)
SLOT FOR #10 SCREWS
3/4-20 UNEF
0.88"
(22.4)
1.51"
(38.4)
1.75" (44.4)
PROBE
LENGTH
(SEE CHART)
Sensor Mounting
Sensors may be installed with mounting bracket furnished in any position provided the sensor face is kept free of electrically conductive material. See below for maximum sensing range and pattern of minimum mounting distances from other conductive materials for the EE931-series sensors.
See the Cylindicator section in this book for application information on Cylindicator sensors.
Factors influencing sensing range are temperature, target size, target material, and speed. For best all-around performance, use “slide-by” actuation as opposed to “head-on” actuation. Target should present as much surface area to the sensor face as practical. Sensing of non-ferrous metals may reduce sensing range by as much as 50%, depending on the type of material. Since the sensing range of each sensor is fixed, no control module adjustment is required. The target should be placed as close to the sensor face as possible. Namco recommends setting the target at one-half the “maximum” sensing range or closer for best system operation.
Sensing Range
"B"
LABEL
"B"
NOMINAL SENSING RANGE
PATTERN OF MINIMUM MOUNTING CLEARANCE
ACTUAL SENSING RANGE
"A"
"C"
0.80"
(20.3)
0.40"
0.16"
(10.1)
(4.0)
1.00"
(25.4)
TUBULAR SENSOR – M 30x1.5 FULL THREAD
Model No. EE931-76500
2C/18 AWG
SVO OR SJO
1.63"
(41.3)
WHITE (+VDC)
(COMMON)
0.20" WIDE X 1.00" LONG SLOT
1.65"
(41.9)
FEMALE ENTRY
BLACK
2 HOLES
1.16" (29.4)
LABEL
1/2-14 NPT
1.50"
(38.1)
3.54"
(89.9)
TUBULAR SENSOR – M 30x 1.5 THREAD 1" SMOOTH BARREL
Model No. EE931-75100
0.03"
2 COND/18AWG
SVO OR SJO
CABLE
(0.76)
0.78"
(19.8)
1.16" (29.4)
1.65"
(41.9)
0.20" (5.08) WIDE X 1.00" (25.4) LONG SLOT
1.50"
(38.1)
2 HOLES
3.78"
(96.0)
1-7/16" ACROSS
BLACK (COMMON) WHITE (+VDC)
LABEL
Continued on
next page.
2013 West Meeting Street • Lancaster, SC 29720
1-803-286-8491 • FAX: 1-800-678-6263
0.67"
(17.0)
LABEL
0.68"
(17.2)
0.36" (9.1)
1.09"
(27.7)
X
1.5 THREAD
M30
0.78"
(19.8)
1.44"
(36.6)
ACROSS
FLATS
2.20"
(55.9)
1.00" (25.4)
M30 X 1.5 THREAD
(36.6) FLATS
1.625" (41.3)
www.namcocontrols.com
Special Application Solut
For technical assistance, call 1-800-NAMTECH
145
S
ions
Intrinsically
Safe
Sensor Systems
Control Modules
The EE931-series control modules are designed to be mounted in the safe area. These modules provide limited energy to Namco’s line of hazardous location sensors described on the previous pages. The control modules are housed in high impact Lexan® enclo­sures and are equipped with eight screw terminals (#8 stud size) for ease of installation. The EE931-02103 module provides an electro-mechanical relay output (One Form C), while the EE931­02303 unit has a photo-darlington (open collector) output for higher speed requirements. The outputs become energized when a metallic target is present in front of the associated sensor.
Control Module Mounting:
The EE931-series control module
should be panel mounted in the safe area where it will be protected from
physical damage, dirt, and vibration. The location should be established within the limits of the sensor cable. The unit can be mounted vertically or horizontally using two No. 8 screws. When mounting with only two screws, it is imperative to use
the two mounting holes provided with brass eyelet inserts. This method
provides an additional ground path for the electronic circuit contained in the module. The ambient temperature range should be from -40°F to +158°F. The physical construction of the control module housing insures a separation of at least two inches between intrinsically safe terminals (5 and 6) and non­intrinsically safe terminals (7 thru 12).
It is important when installing the sensor cable to the control unit terminals (5 and
6) to maintain this minimum spacing of two inches. A separate wiring duct is required to insure that the intrinsically safe sensor cable does not become intermingled with non-intrinsically safe wiring due to vibration. A separate conductor MUST be wired from Terminal 9 to earth ground to insure intrinsic safety of the system. Terminal 8 is for the neutral side of AC line. Terminal 7 is hot side of AC line and MUST be wired accordingly or intrinsic safety is voided.
Namco advises that the Instrument Society of America Specification RP12.6, which gives the recommended practice for installation of intrinsically safe systems, be followed when using the EE931-series control modules and sensors.
pecial Application Solut
146
Namco • 2013 West Meeting Street • Lancaster, SC 29720 • 1-803-286-8491 • FAX: 1-800-678-6263
ions
Dimensional Drawing
123456
4.00"
(101.6)
3.25"
(82.5)
#8 - 32 X 5/16"
SCREWS (8)
OUTPUT
INDICAT OR
0.73"
(18.5)
PRIMARY MOUNTING HOLES (WITH BRASS EYELETS)
LABEL
1.06"
(27.0)
3.00"
(76.2)
1.16"
(29.3)
CONTROL
MODULE
0.82" (20.9)
0.27" (6.8)
0.37" TYP (9.5)
7 8 9 10 11 12
0.38" TYP (9.6)
3.25"
(82.5)
0.37" TYP (9.5)
4.00"
(101.6)
Circuit Drawings
RELAY OUTPUT PHOTO-DARLINGTON
OUTPUT
+
BLK
LOAD #1
WHT
CONTROL MODULE
MENTOR, OHIO 44060
INPUT
115VAC
50/60 HZ
2.5 VA
LINE NEUT.
CONTROL MODULE
MENTOR, OHIO 44060
INPUT
115VAC
50/60 HZ
2.5 VA
LINE NEUT.
TO HAZARDOUS LOCATION
INTRINSICALLY SAFE
®
EE931-02103
RATING
SPOT SWITCH
ONLY ONE POLARITY STD DUTY
120 VAC
OR SA RESISTIVE
GRND.
@ 120 VAC
SENSOR #1
OUTPUT STATUS
+
EE931-02103 NON-HAZARDOUS LOCATION CONTROL UNIT FOR EE931-SERIES SENSORS USED IN CLASS I GROUPS. A. B. C AND D; CLASS II. GROUPS E. F. AND G HAZARDOUS LOCATIONS.
RELAY OUTPUT
TO HAZARDOUS LOCATION
INTRINSICALLY SAFE
®
EE931-02303
RATING
RATING
24Vceo
MAX.
50 mA MAX.
GRND.
SENSOR #1
OUTPUT STATUS
+
EE931-02303 NON-HAZARDOUS LOCATION CONTROL UNIT FOR EE931-SERIES SENSORS USED IN CLASS I GROUPS. A. B. C AND D; CLASS II. GROUPS E. F. AND G HAZARDOUS LOCATIONS.
OUTPUT - PHOTO-DARLINGTON
LOAD #1
+
BLK
WHT
Common Control Module Characteristics
INTRINSICALLY SAFE CONTROL MODULE
EE931-02103 EE931-02303
Output Electro-Mechanical Photo-Darlington
Speed (Hz) 3 1400 Supply Voltage 120 VAC Sensor Input Namco EE931-Series only Ambient
Temperature Case Material Lexan
SPDT Relay 50mA max. Rated 5A Resist. @ 24 VAC One form C Open Collector
-40˚F to +158˚F
Special Application Solut
2013 West Meeting Street • Lancaster, SC 29720
1-803-286-8491 • FAX: 1-800-678-6263
www.namcocontrols.com
For technical assistance, call 1-800-NAMTECH
147