Müller SC 28.19 pro, SC 88.X0 pro, SC 98.X0 pro User guide

Instruction Manual (Site 1/2)
ON OFF
P
Time switch (weekly or yearly program)
Connection diagram
Yearly time switch
4. Menu overview 5. Symbol legend
6. Key function
1. To access the Enter- mode (program, adjust ments, options) from t he automatic-mode.
2. To revert to the beginning of the current (sub-) menu.
1. To adjust the flashi ng digit.
2. To scroll through a choice
1. Automatic-mode: To swit ch the channel ON or OFF until the ne xt programming step occu rs.
2. Automatic-mode: A push lon ger than 3 sec. = Permanent switching st atus (7).
1. To activate the time switch when operated without power supply.
2. To confirm the selection o r the entered data.
7. Handling advice 8. Channel ON OFF / Permanent P 9. Programming menu
The time switch is programm able without external power supply
after pressing the To revert one step or one level back while in the Enter-Mode press
.
After completion of a (sub-) me nu confirming end will return the
device into the autom atic-mode. With the choice changes from end to continue. By
confirming
continue the time switch r eturns to the beginnin g of
the current (sub-) menu. When confirming end before completion, the time switch returns
to the automatic-mode without saving the entered data.
10. Standard weekly program 11. Example for the programming of STANDARD switching times (ON and OFF)
70mm (1 channel - 4 channels)
Weekly or yearly time switch
-button.
GB
1 channel = Connection A 2 channels = Connection A,B 3 channels = Connection A,B,C 4 channels = Connection A,B,C,D
Directory
1. Safety instructions
2. Initial operation
3. DCF (Installation DCF-receiver)
4. Menu overview
5. Symbol legend
6. Key function
7. Handling advice
8. Channel
9. Programming menu
10. Standard weekly program
11. Example of a standard weekly switching time
12. Cycle
13. Cycle options
2. Initial operation 3. DCF (Installation of the DCF-antenna FU 20)
  
ON OFF
Channel
By pushing -buttons a manual switch of the channels take place. The resulting switching st atus is marked with the hand-symbol and remains until the next programming step occurs. (temporary over-ride)
Permanent switching st atus
By pressing the corresponding channel button more than 3 sec. the channel is permanently switched ON or OFF. The status remains until the next manual switching occurs (> 3 sec.). (permanent over-ride)
/ Permanent
The time switch is delivered in sleep-mode, the display is switched off. Press -button for 1 second. The current date and time is already programmed and European daylight savings tim e is activated. Select the desired language by pressing -buttons and confirm it by pressing . (Remark: By pressing you move one step backwards
from the current position)
If required, date, time and daylight savings time mode can be adjusted also by pressing -buttons and a subsequent confirmation with .
P
for
14. Pulse
15. Priority of the switching programs
16. Special program entry
17. Special program activation
18. Extra switching time
19. Permanentprogram
20. External Input
21. Switchoff warning
22. Channel keys
23. Additional adjustments
24. Program modify
25. Data-key
I
Z
W
e
F
X D
*within yearly time switches
A. If you want to program a standard weekly switching time (
B. For regular switching times choose C. Within this level you activate the days of the week (1…7) on which the switching time should happen.
With
D. Adjustment of the time: Hours E. Verify the entered switchi ng time: If the flashing summ ary of the programming st ep is correct, verify
off with . After verification you have the choice between edit/delete and end with .
or
F. If you want to proceed with programmi ng, confirm
To leave the programming menu confirm
Information: You can easil y transfer switching tim es from one channel to the oth er if you use the copy function.
SC 28.19 pro / SC 88.X0 pro / SC 98.X0 pro 172 419 pro / 179 4X0 pro / 179 6X0 pro
1. Safety instructions
!
The installation and assem bly of electrical equipme nt must be only carried out only by a skilled Person! Otherwise fire danger or danger of an electric shock exists!
!
Connect the supply voltage/frequency as stated on the product label!
!
Warranty void if housing opened by unauthorised person!
!
The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if external influences exceed certain limits!
The time switch can process the DCF sign al. The antenna FU 20 is not included in delivery of the time switch.
Disconnect power supply voltag e
Connect the antenna as indicated by the connection diagram
Connect supply voltage
Antenna symbol (LCD) flashes for approx. 3 minutes
Reception is not possible if se vere interference is pres ent (Permanent flashing of the symbol / The osci llating crystal is us ed as time base) Defective wire between antenna and time switch (No antenna symbol visible / The oscillating crystal is used as time base)
Channel is switched ON
Channel is switched OFF
For the current date t he “holiday program” / “permanent by date ” is activated
Standard programming step
Current state is based on a manual over-ride. The stat e will be cancelled with the n ext programming step
Current state is based o n a manual over-ride. The state is permanent until terminated man ually
Days of the week Monday, Tuesday, ... Sunday; The underscores indicate if the program is active for the days above
Current state is based on a switching time with pulse f unction
Current state is based o n a switching time with cycle function
Weekday function: Switching time is entered by date but is shifted for future years in respect of the weekday (E.g. Tuesday this year... Tuesday next year).
Is displayed if the cor responding channel i s activated by the ext ernal input.
Element within sub-menu “program delete”
Switching function / switching time with Easter function: The switching function takes into account the yearly shift of Easter holiday for future years and changes the date of the switching program accordingly.
1x-Function active: The switching time will be executed only once.
DCF: The time switch receives the signal for the DCF -77 time standard
The time switch is locked; to unlock the device the PIN has to be entered
on or off with -buttons and confirm with .
you activate “yes” or deactivate “no” the corresponding date. Confirm each day with .
and . Minutes and .
end.
on, off) confirm Standard with .
next switching with .
on
**The cycle function will only be available if it is activated (point 13)
12. Cycle 13. Cycle options
Standard weekly program:
Program -> new program -> channel A/B/C/D -> Standard ->
Special (weekly) program (to be activated by date for the yearly function):
Program -> new program -> channel A/B/C/D -> Special-program -> SP-entry -> program-number ->
For the cycle function it is pos sibile to enter a periodic swit ching time. The time switch a cts as a recycling timer and switches between pulse (ON) and pause (OFF). The max. value for pulse and pause is 9:59:59 h:mm:ss.
If you haven’t defined and activated a cycle, the cycle function will not be available as switching time. Therefore you have to activate and defin e at least one of the four cy cles within menu Options and sub-menu Cycle (point 13). The cycle switching time will be terminated by another switching time (on, off, pulse) or by another cycle switching time.
14. Pulse 15. Priorities of the switching programs
Standard weekly program:
Program -> new program -> channel A/B/C/D -> Standard ->
Special (weekly) program (to be activated by date for the yearly function):
Program -> new program -> channel A/B/C/D -> Special-program -> SP-entry -> program-number ->
The pulse function provides you the opportunity of programming a switching time with a defined duration. As soon as the pulse-duration ha s expired the time switch switch es OFF automatically (the duration of the pulse is up to 59:59 mm:ss).
Options -> Cycle -> Cycle 1 - 4 ->
You have the possibility to define 4 different Cycles. For these purposes choose menu Options and sub-menu Cycle. The different cycles can be activated, defi ned or deactivated (the m ax. value for pulse or pause is 9:59: 59 h:mm:ss):
Choose menu Options and sub-menu Cycle and confirm with .
Select with -button s one out of the 4 cycles (Cycle 1 – Cycle 4 ) and confirm with .
Activate the cycle by changin g No to Yes with -buttons and subsequent confirming with .
Define duration of the pulse „on -time“ ( -> …).
Define duration of the pause „off time“ ( -> …).
Confirm End with .
The cycle is now offered wit hin the programming m enu. Further applications of the cycle function in combination with: External Input function and/or Channel keys function.
Standard switching times, Special programs, Extra switching times and Permanent by date are executed according to their corresponding priority (by channel and date) All switching programs except Extra switching times, suspend all ot her switching programs wit h lower priority:
highest priority Ö manual over-ride Permanent (3 sec. push) × Ö Permanent by date × Ö Extra switching tim e (yearly time switch)
× Ö Special program 10 by date (yearly time switch)
× Ö Special program ... by date (yearly time switch)
× Ö Special program 01 by date (yearly time switch)
lowest priority Ö Standard weekly program
BA SC2819-SC88-SC98-pro MP; DE, GB - 22476 - 2008.05-03
Instruction Manual (Site 2/2)
Time switch (weekly or yearly program)
16.Special program Entry (within yearly time switches)
** The cycle function will only be offered if it is activated (point 13)
17. Special program activation by date (within yearly time switches)
18. Extra switching time (within yearly time switches) 19. Permanent program
Program -> new program -> channel A/B/C/D -> Extra switching time ->
These programming steps are singl e switching times by date. Extra swit ching times do not disable switching p rograms with lower priority.
Adjust the switching f unction (AT on, AT off, AT cycle, AT pulse) and the date on which the extra switching time will be executed. The following options are additionally availa ble for the Extra swit ching time:
Without special function: The switching time will be applied each year fixed to the entered date.
With weekday function: The switchi ng date takes into acc ount the yearly shift of the weekday of the mo nth.
(E.g.: The switching date is always the sec ond Saturday in Febru ary for the current an d the following years )
With 1xFunction: The switching time will be applied only once.
20. External Input (within 70 mm time switches) 21. Switchoff warning
Options -> Input->
The external input can be connected to a switched contact such as a push-button or light switch. Therefore you can activate and de-activate functions from a remote location or automatically from a control system:
Connection external inputs:
Connect the voltage/frequ ency as stated on the product la bel! External input 1: A switch or pushbutton can be connected to EXT 1: Terminal 6 (Voltage EXT 1 = Supply v oltage of the time switch) External input 2: A potential free switch or pushbutton can be connected to EXT 2: Terminals 13 u. 14 (potential free = 0V)
Functional options of the „external input“:
Within menu Options and submenu Input you have to define if a switch or a push-button-signal will be applied to the external input. Furthermore you can choose the channel(s) which react to the e xternal signal:
Using the -buttons select if you are connecting a pushbutton or a switch and confirm by pressing .
Select the channel(s) which will be controlled by the external signal with the buttons (channel … yes) and confirm by pressing . Channels which should not
be controlled by the extern al signal remain deactivat ed, confirm channel … no then press to confirm
Define a response function within menu Options and submenu Channel-keys. This function will be performed by the output channel when the external input is activated! The pre-defined (default) setting is the standard ‘Change function’ which changes the switching status from ON to OFF and vice versa.
22. Channel keys
Options -> channel-keys ->
Within the Options menu you will find submenu channel-keys. Here you have the opportunity to assign different response functions to the output channels.
These response functions will only be carried out when using the channel-keys of the ti me switch (manual over-ride) or optionally when activating the channel with the external input. Thus, a programmed switching time will be executed as usual, independent of the settings within this channel-key-menu.
The correlation betwe en the channel-keys and the channels is as f ollows:
channel A => channel key A (push-button “A” of the device) / channel B => channel key B …
GB
SC 28.19 pro / SC 88.X0 pro / SC 98.X0 pro 172 419 pro / 179 4X0 pro / 179 6X0 pro
The yearly function of the switch is realised by special (weekly) programs which can be called up by date. Up to 10 special (weekly) programs can be entered (Program-Number 01 –> Program-Number 10).
Execution of the Special program only after activation by date (SP activation see point 17).
Some rules for the programming of Special programs
Define the program number in which the new step will be an element before a new switching step is entered.
(Program-number 01 Program-number 10) The number of switching times which ca n be programmed in each special program is onl y limited by the total number
of free memory locations: (SP on, SP off, SP cycle, SP pulse) The dates of the year during which the special program should be applied can be entered within the activation menu
(point 17) Each special program can be activated as often as there are memory locations are available (point 17)
During the activation dates of special programs only switching steps of the special program with highest priority will
be executed. Remaining special and standard programs are disabled. Please note the priorities of the different switching programs (point 15)
Information: You can easily transfer switching times from one channel to the other if you use the copy function.
A special program will only be executed if it is activated (and if it has the highest priority of all active switching programs (point 15) ). Special programs can be activat ed as often as free memory locations a re available. You can choose th e special program (Program-Number), the dates for activation (Start-
date until End-date) and additionally following options:
Without special function: Special program will be applied each year fixed to the entered
dates
With Easter function: The time switch takes into account the yearly shift for Easter holiday for
the following years and corrects the activation dates. (For programs relative to Easter, Pentecost Carnival, Ascension,...)
With 1xfunction: Special program will be applied only once.
Information: You can easil y transfer switching tim es from one channel to the oth er if you use the copy function.
Program -> new program -> channel A/B/C/D -> permanent ->
The permanent by date program (holiday program) is a permanently on or off status of the channel for the programmed dates. The number of switching times is only limited by the total number of free memory locations. Adjust channel, switching function and the duration by date. The following options are additionally available for the permanent by date program:
Without special function: The program will be applied each year fixed to the entered dates.
With Easter function: The time switch takes into account the yearly shift for Easter holiday for
following years and corrects the activation dates. (For programs relative to Easter, Pentecost Carnival, Ascension,...).
With 1xfunction: The Program will be applied only once.
Options -> Switchoff warning ->
Within menu Options and submenu Switch off warning the early warning switch off function can be activated and deactivated:
Warning No: The function remains inactive.
Warning Yes: The function is activated and the switch off is signalled in
advance (For illuminati on purposes the warni ng is signalled by th e flashing of the light according DIN 18015-2 = warning to avoid sudden darkness). An activated warning affects all chan nels and all OFF switching times
Overview „channel-keys“ functions:
If you have assigned a specific response function to a channel, this switching function will occur if you push the channel-button on the front pl ate of the time switch (or if the exte rnal input for this channel is activated a nd a signal is appli ed to the input). For e ach channel one ou t of the following func tions can be defined:
Change function (default setting): By pressing the channel key (or optionally using the external input) the switching status changes from ON to OFF or
OFF to ON. This corresponds to a standard manual over-ride of the channel. Timer function: By pressing the channel key (or optionally using the external input) the Timer starts and the corresponding channel switches ON. After
the expiry of the Tim er-time the channel sw itches OFF. If the channel receives another signal before the expiry of time the time switch reacts as follows:
After pressing the channel-button = Timer stop s and the channel switches OFF.Signal on the external input = Timer restarts/ Staircas e lighting timer -> Resettable.
Cycle 1 – 4: By pressing the channel key (or optionally using the external input) the cycle function starts. Attention: This function is only available if
the cycle is activated and defined in advance within menu Options and submenu Cycle.
Perm on: By pressing the channel key (or optionally using the external input) the channel switches permanently ON. This status remains active until the
channel key of the device is pre ssed again.
Perm off: By pressing the channel key (or optionally using the ext ernal input) the channel switches permanently OFF. This status r emains active until th e
channel key of the device is pre ssed again.
The Change function, Timer function and Cycle functions will be overridden by the regular switching program or by a manual over-ride!!!
** The cycle function will only be offered if it is activated (point 13)
23. Additional adjustments 24. Program modify
Menu Main menu Application
Program query
Program copy
Program delete
Date-Time Summertime Language
Factory Defaults
Counter
PIN-Code
Reset-Function
Adjustment Adjustment Adjustment
Adjustment
Press all front keys for 2 seconds. The time switch is reset. The values for date and time will be deleted and have to be re-entered. The switching program has not been deleted!
To query the programming steps and remaining memory locations
Program
Copy from one channel to another. Memory of the channel won’t be overwritten; the copied swit ching steps appear additi onally.
Program
!
Permanent by date function is not copied!
Deletion of switching time( s). The program for all channel s, single channels and single programming steps within on channel can be
Program
deleted. Adjustment of date and time Adjustment of the dayli ght saving time mode ( ON/OFF) Choice of languages
Reset to the state of delivery.
!
Date, time and switching program will be lost!
Displays the hour counter and pulse counter for each channel and
Options
the time switch itself.
The time switch can be locked with a 4-digit PIN-Code. The code can be adjusted, activated and deactivated. If you have forgotten
Options
the Code please call c ustomer service.
Program -> Program modify ->
Within Program modify each single switching time can be modified.
25. Data-key
With a Data-key following activities are possible:
Save data: Writes the data fr om the time switch into the m emory of the Data-key.
Program timeswitch: Writes the data located inside th e Key into the memory.
Key function: The time switch will solely apply programming steps from the Data-key. The
switching program of the time switch is suppressed.
Key readout: To query the switching program of the Data-key.
BA SC2819-SC88-SC98-pro MP; DE, GB - 22476 - 2008.05-03
Loading...