Installation, Operating, Maintenance
and After Sales Manual.
®
WHISPA III
5000, 9000 & 12000 RCU
heatingthroughinnovation.
Product Serial Number:
Installation Date:
Part Number: 1371056
01.06.2009 ISSUE 1
Issue 1
Tested to UL & CSA Standards
Contents
1.0General Information03
2.0Heating System Design03
3.0Selection and Sizing for Heating03
4.0Location03
5.0Preparation04
6.0Electrical Connection05
7.0Water Connection06
8.0Technical Data08
9.0Operating Instructions09
10.0Troubleshooting10
11.0Maintenance11
1.0 General Information
WHISPA III
®
5000, 9000 & 12000 RCU
03
G This MYSON WHISPA III®recessed commercial unit (RCU) is
designed for recessed wall applications where the use of
surface mounted units would not be appropriate. All units
have a one piece low profile front cover.
G WHISPA III
®
RCU fan convectors are designed to be used with
mono-flo Tees from a series loop, on a two pipe system, or as
a stand alone zone.
G WHISPA III
®
RCU fan convectors are available in three sizes,
and before proceeding with the installation the heating
system design must be considered and the unit correctly
selected to meet the heat loss requirement of the room.
G WHISPA III
®
RCU fan convectors are supplied with a fan speed
selector switch mounted on the front of the unit.
G WHISPA III
®
RCU fan convectors are supplied with built in
½" compression shut off valves for both the supply and
return.
G WHISPA III
®
RCU fan convectors are supplied with high
volume purge valve - air vents.
2.0 Heating System Design
The WHISPA III
mono-flo or venturi Tees, on a two pipe system or as a stand
alone zone.
For optimum fan convector performance the system must be
capable of providing sufficient hot water through the heat
exchanger. This means that:
1. Care must be taken in sizing both the pump and piping.
The minimum pipe size from the boiler to the fan convector
must be 1/2" copper tube.
2. Where the WHISPA III
emitters, mono-flo Tees or diverter Tees should be used to
provide adequate water flow.
®
RCU can be fitted on a series loop with
®
RCU is fitted on to a system with other
G WHISPA III
®
RCU fan convectors are supplied with an integral
combi - zone control and flow control valve, with a factory
fitted insert set to give 1 GPM. The flow rate through the unit
will not exceed this value, however, other inserts of 2 GPM or
3 GPM can be fitted by the installer to give higher flow rates.
G A low limit thermostat prevents the fan from operating if the
water temperature in the unit is below 110°F
G WHISPA III
®
RCU fan convectors are not designed for use with
steam.
G A 24V room thermostat, On – Off or set back type, can be
wired to this unit to give room temperature control.
G A time control can be wired to WHISPA III RCU fan convectors
to provide occasional coil purging flow through the coil if
considered necessary.
G All waterways are of copper. No lead brazing materials are
used to assemble this unit.
3. The system water must be above 110°F for fan to switch on,
and best results the mean water temperature should not be
below 140°F.
4. Optimum performance will require effective balancing of the
whole system.
5. The WHISPA III
®
RCU should not be used to replace a
radiator in an existing system unless an adequate flow of
water can be guaranteed through the unit.
6. The loop must be pumped. WHISPA III®RCU fan convectors
are not suitable for gravity circulation systems.
1.0
2.0
3.04.0
3.0 Selection and Sizing for Heating
G Heat output performance figures for the three sizes of
WHISPA III
Data section of this manual.
G Since WHISPA III
speed control, it is important to size the unit to match the
calculated heat loss requirements of the room with the unit
operating at the low fan speed (I).
®
RCU fan convectors are given in the Technical
®
RCU fan convectors are supplied with fan
4.0 Location
G The WHISPA III®RCU fan convector is designed for recessed
wall applications.
G WHISPA III
2" x 4" stud wall framing, with 5/16" thick cover
extending beyond the wall surface once installed.
®
RCU fan convectors are designed for normal
G The higher fan speed can then be used for more rapid
heating from cold in extreme conditions.
G When establishing the temperature difference, i.e. entering
water to room temperature, allowance should be made for
temperature drop in the system. It is the water temperature
at the fan convector that dictates the output.
G The size of the opening required to be cut for installation is
shown in Fig 1.
04
WHISPA III
®
5000, 9000 & 12000 RCU
5.0 Preparation
Before proceeding with the installation, unpack the carton
contents and check against the checklist below:
1. WHISPA III
2. Instruction manual.
3. Front cover.
4. Screw fixing kit.
G The WHISPA III
piping and wiring connections are made within the cabinet of
the unit itself. The installer should inspect the unit and note
that the ½" piping should enter on the lower right corner of
the unit and the 110V AC wiring for the unit enters on the
lower left hand corner of the unit, see Fig 2.
Dimensions of opening to be cut in wall
®
RCU.
®
RCU fan convector is designed so that the
141/2"
241/2"
G Prepare the opening in the wall to accept the unit as shown
in Fig. 1. Depending on the wall framing layout, the 9,000 and
12,000 models may require re-framing of the opening to
ensure proper support.
G Do not fit the unit at this stage.
195/16"
241/2"
5000 RCU
241/2"
Fig. 1
Note: All models require a depth of at least 3½".
9000 RCU
313/4"
12000 RCU
6.0 Electrical Connection
Line
(Supply) Ground
Neutral
T1T2
Ground
Actu
TrAcT
WARNING: This appliance must be grounded.
WHISPA III
®
5000, 9000 & 12000 RCU
05
G The electrical installation must comply with local or national
wiring regulations.
G A hole is provided at the lower left hand corner of the unit
for a BX or Romex connector.
G Make electrical connection to the terminal block:
Black Lead – Hot 110V 60Hz
White lead – Neutral
Green – Ground
Do not energize the electrical supply until the remaining stages of the installation have been completed.
5.0
Fig. 2
6.0
06
C
B
A
WHISPA III
®
5000, 9000 & 12000 RCU
7.0 Water Connection
G This unit is supplied with ½" compression isolating valves.
Bring ½ " copper tubing to the unit and make the
compression joints. Connect the supply to the left hand
isolating valve. This is necessary to allow proper venting and
purging of the fan convector.
G The WHISPA III
regulator set at 1 GPM maximum. If another pre-set
maximum flowrate is required then the insert can be changed
at this stage. Unscrew the insert cap on the flow control valve.
Remove the insert and replace with the alternative. Replace
cap and tighten.
G Many installers are now beginning to use flexible heat tubing
to make these connections. Ensure prior to use that the
tubing selected is appropriate for the water temperature to
be supplied.
®
RCU fan convector is fitted with a flow
G Once the connections to the heating loop are complete, the
unit must be vented using the air purge valve. Fit a length of
hose to the purge valve so that any water from the heating
circuit escaping during the venting process can be directed
to waste, see Fig 3. Open the air purge valve by loosening
the screw.
G Open the left hand valve at the bottom of the unit and purge
the unit for 1-2 minutes. Close the LH valve and then open
the RH valve. Switch on the supply to the unit and energise
the flow control valve by switching on the room thermostat.
Purge the air from the unit, then close the RH valve and switch
off the room thermostat. Close the purge valve, disconnect
the hose and open both valves.
G When the operation of the unit has been tested, align and
secure the front cover (eight screws), see Fig 4.
Dimensions (in)
ModelABC
5000143/16135/8103/8
7000191/8171/8151/16
9000315/8291/4271/8
Note: dimensions in inches.
Fig. 3
7.0 Water Connection (continued...)
Front cover
fixing screws
WHISPA III
®
5000, 9000 & 12000 RCU
07
Fig. 4
7.0
08
WHISPA III
®
5000, 9000 & 12000 RCU
8.0 Technical Data
Heating Performance Data
Model
5000 RCU
9000 RCU
12000 RCU
Fan Setting
High (II)
Low (I)
High (II)
Low (I)
High (II)
Low (I)
High (II)
Low (I)
High (II)
Low (I)
High (II)
Low (I)
Flowrate
(gpm)
3
1
3
1
3
1
Heat Output (Btu/h)
Entering Water Temperature (°F), Entering Air Temperature (65°F)
110120130140150160170180190200
2040251629973480396744574949544359396437
1749209624372773310434323756407843974713
1795221426373063349139224355479052265664
1539184421442440273230203306358938694147
375946295504638572718160905399491084811750
3266391645565185580764227031763482338827
33084073484456196398718179678755954610340
2874344640094563511056526187671872457767
436954376524762387399866110031214913307 14472
3019373344545180591166497389813688879640
384547855740670976908682968210692 1170912734
2657328439184558520258516504716078198482
Maximum inlet water temperature 200°F
Heat outputs tested in accordance with BS 4856 Part 1
Electrical supply: 110V 60Hz
Max working pressure: 145psi
Water connections:
1
"
Sweat
/
2
Approximate Hydraulic Resistance through Units
g/min
34.906.8913.1
10.751.071.4
5000900012000
ft wg
Weight, Water Content and Motor Power
Model
50002559.5
90004011.514.2
120006218.919
Motor
Power (W)
Water
Content (fl oz)
Unit Weight
(lbs)
Fig. 5 Wiring diagram
9.0 Operating Instructions
WHISPA III
®
5000, 9000 & 12000 RCU
09
WHISPA III®RCU fan convectors are controlled by the switch on
the front of the unit.
Ensure the electricity supply is switched on.
Heating Mode
The fan will only operate when
The central heating boiler is on
•
The pump is running
•
The system water temperature is greater than 110°F.
•
The room thermostat linked to the unit is switched on.
•
Ensure boiler is on, and set timer, boiler controls and room
thermostats as necessary.
G Set the fan speed switch to the LOW (I) position.
G The unit will now run on low fan speed. For satisfactory
operation the mean water temperature should not be below
140°F.
Operating Sequence
Power On
Timer On
Boiler On
Pump running
Select fan speed
Turn up room
thermostat
Solenoid valve
energises and valve
(1-2 seconds)
Temperature Control
The room thermostat setting should be adjusted to obtain the
desired temperature.
The fan speed can be set to boost by switching the fan speed
switch to II.
A low speed setting is recommended for normal operation with
the higher speeds for boost heating when required.
Low Limit Operation
The low limit thermostat fitted to the WHISPA III®RCU will
ensure that the fan stops after the heating system is switched
off and the water flow stops. If left in an operating position the
unit will automatically restart when the heating system is
reheated.
Off Position
Set the fan speed selector switch to the off position.
opens
Warm water flows
into coil. After 1-2
mins low limit stat
makes as coil
temperature rises
and fan starts.
Unit cycles on room
thermostat through
similar sequence
while heating is on.
8.09.0
10
WHISPA III
®
5000, 9000 & 12000 RCU
10.0 Troubleshooting
Once installed, this fan convector becomes an integral part of
the heating system that will also include boiler, pump, other
emitters such as radiators and fan convectors, and a number of
heating controls depending on system complexity. An apparent
ProblemRemedy
Possible Causes
Room thermostat not calling for heat
Unit not switched on at breaker panel
Breaker tripped at panel
Heating Mode -
No Fan
Heating Mode
Water temperature reaching unit
below 110°F
Low water temperature to unitTurn up boiler thermostat
poor heating
performance and/or
unit cycles on
Poor water flowVent air from heating system
low limit thermostat
problem with this unit may be the result of system controls being
incorrectly set, and can be solved easily without calling out your
installer or MYSON. Before calling out your installer or MYSON,
please carry out the checklist below.
Turn up room thermostat
Switch on breaker
Check all wiring, reset breaker
Check boiler -
Programmer ON
Boiler ON and set to high
Circulating pump running
Note: Operation of fan convector can be checked by
switching to summer setting
If the fan convector is still faulty after checking the above, call your installer or MYSON.
Common Installation Faults
For optimum performance, this unit must be correctly sized to
match the heat loss requirements of the space it is required to
Problem
Poor heating
performance
Unit incorrectly sized for heat loss of room
heat, and the heating system must be correctly designed to
provide adequate flow of hot water to the unit (see section 2). If
the recommendations in section 2 are not followed problems
may arise as detailed below.
Possible Causes
Boiler thermostat set too low
Lack of flow to fan convector Poor heating
performance
(unit may cycle on
low limit thermostat
System incorrectly balanced with unit starved of hot water flow
Pump set on low setting
Isolating valves not fully open
Pipe sizing to unit too small
Other Faults
ProblemRemedy
No flow through unit,
and fan not operating
Possible Causes
Solenoid valve not energised
Solenoid valve not opening
Check room thermostat set correctly and
functioning
Check transformer output 24V
Check 24V actuator
11.0 Maintenance
WHISPA III
®
5000, 9000 & 12000 RCU
11
Before undertaking any maintenance activity isolate the
electrical supply.
Maintenance should be restricted to occasional removal of dust
and lint around the front cover plate.
The unit should be serviced periodically by a competent person.
Spares List
Motor / Fan Assembly WHISPA III® 5000 RCU71000881
Motor / Fan Assembly WHISPA III®9000 RCU71000901
Motor / Fan Assembly WHISPA III
Switch, 3 way13000251
Low Limit Thermostat12600071
Cover plate Whispa III 5000 RCUTBA1
Cover plate Whispa III 9000 RCUTBA1
Cover plate Whispa III 12000 RCUTBA1
24V ActuatorTBA1
®
12000 RCUTBA1
This should involve internal cleaning of the heat exchanger using
a soft brush or vacuum cleaner, taking care not to damage the
fan or heat exchanger.
Part NumberDescriptionQuantity
TransformerTBA1
10.0
11.0
MYSON Inc. 948 Hercules Drive, Suite 5, Colchester, Vermont VT05446