Myson KICKSPACE 500 DUO Instructions Manual

Page 1
Part Number: 1370070
Product code and serial number location
COMPLETE HEATING SOLUTIONS
01.10.17 ISSUE 2
KICKSPACE®500 DUO
INSTALLATION & OPERATING MANUAL
PLEASE LEAVE THIS MANUAL WITH THE END USER
Page 2
03
KICKSPACE
®
500 DUO
®
500 DUO, a fused
®
500 DUO
Children of less than 3 years should be kept away from the unit unless continuously supervised.
Children aged from 3 years and less than 8 years shall only switch on / off the appliance provided that it has been placed or installed in its normal operating position and they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Children aged from 3 years and less than 8 years shall not plug in, clean the appliance or perform user maintenance.
1.0
2.0
3.0
®
500 DUO models must be earthed.
®
500 DUO MUST NOT be installed in a bathroom or other similar high
2.0 Installation
l Before proceeding with the installation, the heating system
design must be considered and the unit correctly sized to meet the heat loss requirements of the room.
l Before proceeding with the installation, unpack the carton
contents and check against the checklist below:
1. KICKSPACE
®
unit.
2. Flexible hoses including isolating valves (1 pair).
3. Instruction manual.
4. Warranty card.
5. Grille.
6. Screw fixing kit (with grille).
l This MYSON KICKSPACE
®
fan convector is designed for installation in the cavity beneath kitchen cupboards on the vacant floor space, or other similar locations.
l For KICKSPACE
®
500 DUO a minimum of 25mm clear
headroom is required above the top of the KICKSPACE
®
when
fitted.
l The unit should be mounted on a clean and level floor area
under the cupboard base.
l KICKSPACE
®
500 DUO floor mounting (see Fig. 1a) - The
KICKSPACE
®
is normally fitted directly onto the floor and the
base of the unit is fitted with four mounting feet.
l KICKSPACE
®
500 DUO plinth mounting (see Fig. 1b) -
• As an alternative to floor mounting the unit may be fitted
into the plinth.
• A suitable support must be securely fitted to the floor.
• The top of the support must be level with the lower edge of
the cut-out when fitted.
l Decide the position of the KICKSPACE
®
, mark out and cut the
plinth to the dimensions using table on page 6.
l Complete connection to the central heating system according
to Section 3, Water Connection.
l Position the KICKSPACE
®
under the cupboard in the required
location, with the front edge just behind the line of the plinth.
l Replace the plinth and bring the KICKSPACE
®
forward into the opening so the front edge projects approximately 10mm through the plinth.
l KICKSPACE
®
DUO is fitted with a transit cover to protect the electric element and to minimise risk of electric shock prior to the grille being fitted. The cover must only be removed with the electrical supply switched off immediately prior to fitting of the grille.
l Align the grille and secure it to the unit with two screws
supplied (use the shorter screws). (See Fig. 2).
l Secure the unit/grille to the plinth with two screws supplied
(use the longer screws). (See Fig. 2).
l Complete the electrical installation, switch on and test the
KICKSPACE
®
(see Fig. 3).
l When installed in a kitchen consideration should be given to
storage of perishable goods in the cupboard above.
l No rear access to the unit shall be available after installation.
3.0 Water Connection
l The KICKSPACE®should only be used on closed circulation,
two pipe, pump assisted central heating systems.
l For optimum fan convector heating performance the system
must be capable of providing sufficient hot water through the heat exchanger. This means that:
1. The minimum pipe size from boiler to fan convector must be at least 15mm. Microbore pipe MUST NOT be used.
2. Where the unit is fitted on to a system with other emitters a separate circuit for the fan convector should be considered to provide adequate water flow.
3. The system water temperature on the return of the KICKSPACE
®
must be above 43°C for the fan to switch on.
4. This unit is NOT suitable for one-pipe systems.
5. Optimum performance will require effective balancing of
the whole system.
6. This unit must not be used to replace a radiator in an existing system unless an adequate flow of water can be guaranteed.
l Connect valve ends of the flexible pipes to the KICKSPACE
®
.
Note: The direction of the arrows on the valves are not significant in this application (see Fig. 4).
l Open valves fully, check pipe connections for leaks and vent
the heat exchanger. A vent screw is provided to vent the heat exchanger.
Pipework must be positioned correctly to ensure flexible hoses are not kinked when installed (see Figs. 5a & 5b). Only use the hose sets supplied with this unit. Do not use old or alternative hose sets.
CAUTION: Some parts of this product can become very hot and cause burns. Particular attention has to be given where children and vulnerable people are present.
Page 3
0504
2
cord.
l If the supply cord to KICKSPACE
®
500 DUO is damaged, it must be replaced by the manufacturer, its service agent or similar qualified persons in order to avoid a hazard.
®
500 DUO models must be earthed.
KICKSPACE®500 DUOKICKSPACE
KICKSPACE®may have poor performance/cycle if a low water temperature/flow rate is supplied, please refer to your installer as this could be from the following:
• Unit incorrectly sized for heat loss of room
• Lack of flow to KICKSPACE
®
from heating system
• Pipe sizes/pump sized incorrectly
• System incorrectly balanced
Fan not working in
heating mode
Possible Causes
Unit switched off
Room thermostat not calling for heat
Unit not switched on at fused spur
Fuse blown at fused spur
Unit isolating valves shut
Water temperature of
KICKSPACE
®
below 43°C
Problem Remedy
Turn on
Turn up room thermostat
Switch on at spur
Replace fuse
Open valves
Ensure boiler, pump and other central
heating equipment is working correctly,
if not contact your installer
Note: Operation of fan can be checked by
switching to summer setting
If the fan convector is still faulty after checking the above, call your installer.
Once installed this fan convector becomes an integral part of a complete heating system that includes boiler, pump, other emitters such as radiators and fan convectors, and a number of heating controls, dependent on system complexity. An apparent
problem with this unit may be the result of system controls being incorrectly set and can be solved easily without calling out your installer. Before calling your installer, please carry out the checks listed below.
6.0 Troubleshooting
7.0 Appendix
Model
ΔT20 ΔT30 ΔT40 ΔT50 ΔT60 ΔT20 ΔT30 ΔT40 ΔT50 ΔT60
500 DUO
Normal 393 566 733 896 1056 1340 1930 2501 3057 3603
Boost 447 683 923 1166 1412 1524 2331 3150 3980 4817
Heat Output (Watts) Heat Output (Btu/h)
Heating Performance Data
Temperature Difference (°C)
Fan
Speed
Sound Levels
Heat outputs tested in accordance with BS 4856 Part 1.
Flow Rate: 340 ltr/h (75 gal/h).
Flow Rate Correction Factors: 455 ltr/h (100 gal/h) multiply output by 1.03. 227 ltr/h (50 gal/h) multiply output by 0.96. 113 ltr/h (25 gal/h) multiply output by 0.85. Test Pressure 20 bar Maximum Working Pressure 10 bar Rated Power in Electric Mode 1025W
Model
Sound Pressures at 2.5m (dBA)
500 DUO 25.7 38.1
Normal Boost
Weight, Water Content and Motor Power
Model
Motor
Power (W)
Water
Content (l)
Unit Weight
(kg)
500 DUO 25 0.26 4.3
Approximate Hydraulic Resistance
Litres/h
mm wg
788 488 231
82
kPa
7.7
4.8
2.3
0.8
455 340 227 113
500 DUO
Sound levels tested in accordance with EN 23741.
WARNING: DO NOT cover the unit or obstruct the grille as this could give risk of fire.
®
Heating mode – Electric
The KICKSPACE®500 DUO incorporates a 1 kW electric heating element to provide heating when the central heating is not in operation. The electric element is controlled independently but cannot be used simultaneously with the central heating.
• Set the fan only/off/heating switch to heating
• Set the system selector switch to position I
• Set the fan speed switch to position I
• The unit will now run on low fan speed
The element will not activate if the system water temperature on the return of the KICKSPACE
®
is above 40°C.
In electric mode at low speed the air temperature will feel warmer than at high speed.
Fan Only Mode
If required, the KICKSPACE®can be used in summer for air circulation without heat.
• Set the fan only/off/heating switch to fan only
• Adjust fan speed to required setting
4.0
5.0
6.07.0
Page 4
0706
KICKSPACE
®
500 DUOKICKSPACE
7.0 Appendix (continued...)7.0 Appendix (continued...)
A
300
400
WALL
250
100
WALL
Fig. 5a Left hand view - suggestion only Fig. 5b Right hand view - suggestion only
®
500 DUO
496
129
322
25
67
93
View on arrow
Cable Entries
Top view
Mains Cable
Cable Entry
FRONT GRILLE
Fig. 2 Front view of unit
B
A
B
Isolating valves
Flexible pipes
Fig. 4
Unit Securing Screws
Grille Securing Screws
Heating Switch
(Fan Only/Off/Heating)
System Selector
Switch
(Electric/Central
Heating)
Fan Speed Switch
(Normal/Boost)
Lo
Hi
N
L
M
Y
bl
bl
y
y
r
r
br
br
bl
bl
w
w
w
br
gy
br
gy
br
gy
br
br
br
gy
g/y
br
gy
w
L H
w
Heating Switch
System Switch
Electric Element
VIEW SWITCHES FROM FRONT
Thermal Cut-Out
Fan Switch
Colour code: br-Brown, bl-Blue r-Red, y-Yellow w-White, gy-Grey g/y-Green/Yellow
Fig. 6 Wiring diagram
Fig. 3
7.0