Myson Apollo 30Si, Apollo 40Si, Apollo 50Si Installation And Servicing Instructions

Page 1
lWYSOnr
HEATIh'G
4UC3r24
-01
Apollo
30Si,40Si and
for.
the
wall mounted
G.C. Appliance No's.
Apollo Apollo 40Si 41 494 Apollo
30Si 50Si
gas
41 494 41 494
37 38 39
boilers
Read
FOR
instructions
these
Leave
IMPORTANT
USE WITH NATURAL
thoroughly
instructions
these
adjacent to the
GAS ONLY.
before working
gas
on the boiler.
meter.
Page 2
LIST OF CONTENTS
Section
I 2 3 4 5 6 7 8 9
l0 ll t2 t3 l4 l5 l6 t7 l8 19
20 2r
22 23
u
Subject Page Introduction
Technical Creneral Delivery
Gas Electricity Air
Flue
Boiler location Important installation noles Boiler dimensions
Water system schematics 6
Sealed
Instnllation Commissioning 12 Boiler controls 13 Final Annual Lighting Replacement Wiring diagrams Fault Exploded view Short
data 3
requirements
supply
supply
supply 4
syslem
position
and
system requirements
procedure
parts
of
guide
parts
handing
assembly and
servicing 14
instructions
finding
list
spare
water and
of
over the
instqllation
gas
connections
3
4 4 4 4
4 5 5 6
7 8
13
15
15 20 23 U 25
you
If
have
model,
boiler Address for return:
Adminisration
Spare Curzon Components Earlsway
Team Valley Trading Estate Gateshead, NEII OSA
Page 2
any
your
Tyne
reason
!o compliain of any shortage
name,
address and any
ldanager
Ltd.
Wear
and
of
information
components listed in Figs
which may help
us avoid further
5 or 6, supply a list
error.
of the
item(s)
concerned,
Page 3
1. INTRODUCTION These fanned
Apollo
The
models
All The boilers THEY MUST NOT
2. TECHNICAL DATA
For
boiler model see
the bottom of tle
draught
boilers are nmge
Apollo Apollo40 Si: Apollo 50 Si: I1.7 to
are
are
room-sealed wall mounted
Si: 4.4
30
factory
designed
s€t to the
BE
lighting instruction
inner case
rated
at the
kW
8.8
to
kW
ll.7
8.8 to
14.7
maximum outpuL
for
use only
CONNECTED
just
on
above
borlers are
following
(15
(30
kW
fully
TO A DIRECT CYLINDER.
label
the control box
outputs:
000 to 30 000
000 to40 000
(40
to 50 000
000
pumped
inside the bottom cover or the
for Btu/h)
Btu/h)
vented
open
(visible
use on
Btu/h)
after removing the bottom
natural
or sealed
data
gas
only,
watcr
plate
and are
systems
on the
cover).
suitable for
with an
inner
case. For serial
rear
or side
indirect hot water
No.
exit flue.
cylinder.
see tag on
Boiler Burner
type Burner injector Pilot
injector
Pilot flame
gap
Spark
lgnition
Weight Lifting weight
water Max. Design Maximum Minimum
'
Head loss
Height
(empty)
content
flow
temperature
temperature
static
static
width
Depth
Clearance
required
for ServrCrng
Flue
terminalsize
Water
I Too 50 mm /2 in't I
, Fronl | 3fn mm r 1 13,. Inl
I
connections
Gas connection
(installing)
rise
head
head
Bottom
Sides
Aoollo
&ay A82,1013M o.
Furiqas 179500-018
30 Si
bray AEzz+ucr+M
Furigas 175-50G032
40
Aoollo
Si
Apollo
50 Si
Eray 482401
Furioas 1 75-500-01 7
4M or
Bray 16/800 Bray 2811000 Bray 16/1400
Honeywell 4500-41
35 to
08-005
40
3.0 to
lntermittent
.3 kg
27
21.8 kg
gal)
(0.08
litre
0.36
150 mm
(15
0.38 m
|
in) 0.54
100
Compression
(6
mm
fittings
in)
dia. x
above the
lire
0.€ g20c
goc
m
30.5
m
711 mm
mm
340
mm
300
mm
90
mm
5
mm
65
deep
to accept
RpV"
marked
mm long
4.0
mm
oilot
(60
lb)
(48
lb)
gal)
(0.1
(100
ft)
(28
in) (13% (113/
(3'r'z
in)
p'.In)
(4
in
point
in) in)
dia.
copper tube to
highest
QlYzinl
22 mm
424
56/
in
the system
tn
x 2'/z
0.50 lite
0.71
d*9\
852871
(0.11
(28
m
gal)
in)
'
Head loss
litres/h
910
given
(3.3
is
applicable only
gal/min)
for
the
when the flow
40
Apollo
Boiler OuFut
kw
Apollo
30 Si
40
Apollo
Apollo 50
Si
Si
4.4 15
8.8 30 000
8.8 30 000
11.7 40
11.7 40
14.7
Si
and
NOMINAL
Btu/h
50 000
through
1 146 litres/h
the
(4.2
BOILER
kw
000
000
000
5.8
11.0
11.4
14.7
14.9
18.3
boiler
gal/min)
RATINGS
Input
litreVh (2.5
is
690
for
the
Apollo
Btu/h mbar
19
600
37 500
39 000 50 000 50 900 62 500
gal/min)
50
Burner
4.1
14.9
10.0
16.5
9.0
12.2
for
Si.
setting
pressure
the
in wo
6.0
4.4
6.6
3.6
4.9
Apollo
't.6
30 Si,
Page
3
Page 4
3.
GENERAL
The
boiler the Building Regulations, Building Standards Underuking Byelaws and IEE Detailed recommendations 8S5440:2:1989
Note:
Gas
in
accordance
and
4. The In A plug-in with A A A not casc
of
that
DELIYERY
unit
addition a
external control systems
all
from
lit Vertex flue
pump
and by-pass
rcquire adjusung and
extension
REQUIREMENTS
must be installed in accordance
Wiring Regulations.
in the following British
stated
are
B55449:1:1977
and
(Installation
Safety
with
the above
safety to
is
delivered
965 mm
progr:rmmer
tie
ensure
in
inside kit kit
is available
kit is
which increases
that
packagcs (
two
(38
in)
kit is
also available to
is
available
available allows the
.
and Use)
regulations.
'Jre
law
I
fiuc
extcnsion
shown
which
which
allows the boiler !o
which
combined cold
the
boiler
with:
Regulations 198^l:
Failure
is
comnlied
cased
the
)
is avarlable.
fit inside
in
system
the
enables
posiitions
heieht
The Gas (Scotland)
to
to 861
Safety
Regulations, Local Building
Standards:
It is
install
applnnces
wit}t.
boiler and
the boiler casing. This
wiring
the
the
feed
(2)
Under no circumstances should more
diagrams supplied
flue/terminal
connecrcd to
be
pump
in
a
vent
and
mm.
(lnstallation
85689l :1988, B56798: 1987,
law
the
conectly could lead
fludterminal
the
assembly to
readily
to be connected directly to the
and Use)
gas
that all
programmer
vertical
a
accessible
Regulations 1984
Regulauons,
appliances
prosecution.
to
assembly type A, B,
simplifies
with
the boiler.
fitted
be
flue
from inside
system.
position,
includes
and the current
Model
855!16:1990, BS5440:l:1990,
installed
are
than
boiler.
by competent
It is in
C, D or E as
two
extension
wiring
and
the building.
in
a
built
The kit includes
local Water
and
your
own
required.
kits
is
suiuble
by-pass
which
issue
of:
persons,
interest,
be used.
for
use
does
an outer
5. The natural Apollo30Si: The in Thc
6. ELECTRICITY SUPPLY 210V - 50FIz and Fuse least All wiring
The In Earth
7. The If level with as stated Apollo If the and the door
SUPPLY
GAS
gas
requirements
l.l m3/h(37 ft3lh) Apollo40Si: l.4m3lh(51ft3/h)
meter
house.
thc
complete
shuttered socket outlet
the
0.75
appliance
evenl. of an
the
Continuity, Short
AIR
room in
the boiler
and one at
the
30 Si: 99 cm2
boiler
supply
and
installation
via
fused
a
supply
mm2
external to
SUPPLY
which
is installed in
same room
below. The frec
is insulled in
for
A. The minimum requirement
at
3
(24
x
0.2
must
be earthed.
electrical
the
low
level,
or
movemenL
air
pipes
must
must be
double
(both
mm)
the
boiler
fault
Circuit,
boiler
a cupboard or
either dircct
must
be on
area of each
(
15
inz)
cupboard or compartment
a
follows:
are as
be capable of delivering
gas
for
tested
pole
switch
complying
(code
designation HO5
shall
comply
inslallation
after
Polanty
is insnlled
compartment,
to
same
the
vent
Apollo 40
anC
soundness and
with
contact separation of
a
with
the
with
of
ResisLancc
not
docs
the outside air or to a roorn. Both high level
rcquire
wall
to outside air. Both the high level
may
be
133
Si:
quantity
this
purged
requircments
power
for the
VV-F
or HO5
latest IEE Wiring
the
the
appliance,
Eanh.
to
purpose provided
a
permanent
halved
cm2
with
air
ventilation
if
the
(20
inz) Apollo
a door, allow
gas
of
described in 85689l.
as
least 3 mm in
at
BSl363)
of
supply
cable
VVH2-F)
Regulations,
preliminary
vents
are
at
Apollo50Si: 1.8
in
addition
adjacent
is
it
that
specified in table 16
as
and any local
elecnical systems checks must
vent.
air
required in
and
and low
provided
is
50
Si: I 65 cm2
least
100 mm
mt/h(62ft3/h)
the
to
demand
poles
both
to the
should
0re cupboard or compartrncnt,
low level
directly from
clearance between
or
boiler.
PVC
a
be
regulations
air
level vent
(25
in2)
from
any other
preferably
sheathed
856500:1984.
of
vents
must
must each have a free
outside.
the
appliances
fused
a
be carried out i.e.
front
3
flexible
which
apply.
one at high
communicate
of the
pin plug
cord at
area
boiler
FLUESYSTEM
E. Five
telescopic The flue Sizp A:
B: 17l
Siire Sizr C:
Siz.c D: 362 - 652 mm Sze Unless The following RearflueA=C+83 mm(3%in) Where A = required flue If Note: The maximum
274 - 478 mm
E: 582 - lW2 mm
otherwise
greater
A is
Poge 4
flue/terminal
lengths
123
are:
-
175 mm
-275mm(GA -
specified
method
than
-
(43A
7
lUAin)
-
(|Glr
l8% in)
-
(l4t/e
251/t in)
-
(23
the C
should be
length, B
1092
mm
allowable
asscmblies
n)
43
in)
size used
(43
flue length is3022
available and a fixed length,
are
flue/terminal will
to
determine the
=
inside wall
in) one or two
be
required
flue
Side
to
extension
A
side
of boiler and C
(119
mm
965 mm
supplied
=
kits
in).
with
the boiler.
flue/terminal assembly.
B +
C+ 127
may be
mm
=
finished
used.
(5
(38
in)
wall
in),
extension
thickness.
kil
Page 5
BOILER
9. The boiler The
boiler
The
boiler
25 mm
than 25 mm If
rhe boiler
for
Gas Gas or The boiler Regulations and, of the troiler Wherea room-sealed appliance mains Where give
detailed
A
cupboard cupboard compartment The
boiler for installation any adjacent The
boiler allows the The minimum acceptable
LOCATION is not suitable musr be
is
suitable
(l
in)
to
(l
in)
annular
is to be
Installation
from Myson
may
be
in
Scotland,
in a room
electricity
the
should be so situated
installation
guidance
or compartment
or compargnent
design
requires
must
be
passage
free
for external
mounted on a
for installation to a
combustible
Further
space. installed in a timber in Timber
Framed Housing"
Heating.
installed
in
any
the electrical
containing
is installed in a room containing abath
boiler
of the
on this aspecl
used to
may
including
airing
only the clearances
kitchen units or
installed so that the
of air across
spacings
table:
installation.
flat wall which
combustible
material.
A metal sleeve should bc
guidance
framed building
room, although
provisions
or shower.
a bath
it
that
cannot be touched
will
in an unusual
be
enclose the boiler
be used
provided
cupboard
stated
fitments may have to be
flue
terminal
it
at all ttmes.
from
terminal to obstructions, corners
the
is
sufficiently
wall e.g.
given
is
reference
particular
of the
in BS5440:l:1990, sub-clauses 3.3 and
it
robust
woo<l
be fitted
should
DM2. If in
attention
Building
by a
position,
must
be designed
it is modified for the
that
installations are
given
in the technical data,
is
exposed to
take the
to
cladding,
installed
provided
surround the airlt'lue tube
to
in accordance with the British Gas
advicc
doubt
is drawn to thc
Standards
applicable
or shower, any person
special
using
procedures
and constructed
purpose.
in 856798 and
page
3, after
installation. If it is felt
removed.
the external air.
ventilation
and
weight of the boiler.
that the airlflue tube
assembly
assembly to
is not closer
provide
4.2.5.
-
"Cuide
British
of
IEE Wiring
installation
the
must
be sought
rcquirements
in
Scotland
publication
from
the
local
of the current
with respect
region
to
electrical switch or appliance control, utilising
the bath or shower.
may be
B55546
necessary
specifically
Details
of essential
and should be complied
for
It is important that the
openings are
856798
and
pupose.
this
features
extra space
that
position
specificd
855546
and
An existing
of cupboard/
with.
is required
of the terminal
in
following
the
a
Termlnal Directly Below Below eaves Above adjacent From vertical soil From inlernal or From a surlace From Vertically
Horizontally Adjac€nt From
*
If
rhe rerminal
shield of ar **
If
the terminal
a suitable
A
type
r555.
35
guard
The
IMPORTANT
I().
The Apollo is to be used
l.
{Jnly
2.
posltlon
below an openable
gutters,
soil
or a balcony
ground
pipes
external corn€rs
lacino the lerminal
a lerminal
lacing the terminal
lrom a terminal
trom a lerminal on
to an op€ning
an opening
in a car
is fitted
least 750
mm
is fiaed
terminal
protective
Kl
guard
must be securely
INSTALLATION
pumps producing
head
high
30 Si,910litreJh
pump
3. Connect
the
4. Mains electricity It is important that the
5. For open
6.
vented
schematics.
7. A and
system
by-pass
return
pipes adjust as described Tbe
8.
9.
system wiring
When
commissioning,
air vent or any other
pipes 75 mm
level
pipes
pipes
or balcony
or drain
window,
or drain
on the same
lhe same wall
window
pod
i.e. door
within
(30 less must
guard
850
in) in length
than
be
is availble
fitted to the
(34
mm
(6.6
2 m
provided
from Tower Flue
wall
NOTES
only on
fully
at
(33
gaVmin)
in the
and the
polarity
systems is
essential.
least 1.5 m
and at
in
the commissioning
for
pipe
flow
pump
must
of the
a combined
The by-pass should
away
must be completed
the system
must be
ventilation opening
wall
or window into the
plastic
in)
of a
should be
ft)
and
fitted to the underside of
a balcony, above
above
fitted.
and centrally
pumped
least
Apollo 40
the
as shovrn
systems,
3.35 in
m
house
painted gutter/pipe
or
Components
located over the
with
and
(ll
f0 head
1146litresih
Sior
water
the
system schematics.
ground
Ltd. at:
flue
an
flow rate
at a
(4.2
450 mm
or
gutter/pipe
the
or
above a
Vale Rise, Tonbridge, Kent TN9 1TB, Tcl: 0732
terminal.
indirect
cylinder.
of 690
gaVmin)
always be connected to the boiler to allow the
mains
supply
or close coupled
from
the boiler. Install
is
correct and that the boiler
feed
be of 15 mm
vent must
and
pipe
and
the by-pass as shown
be connected as sho*r
must
be
instructions.
in
accordance
vented
with
and the
the diagrams supplied
pump
running
before the main
Minimum spacing
300 mm
(12
(3
mm
(8
(12
(3
(1
(24
200 mm
300
75 mm
25 mm
600 mm 1200 mm 1500 mm
300 mm
150
(12
mm
1200 mm
(18
in)
of
painted
or
flat roof
Refer
litres/h
for
is
as short
with
which
to
to the
(25
Apollo 50 Si
the
pump
overrun to
adequately earthed.
possible
as
in
water
the
the boiler.
burner
in)
rn)
in; in) in)
in)
in)
(48
in)
(60
in)
in)
(6
in)
(48
in)
painted
an aluminium
eaves,
surface.
people
havc
manufacturers
gaVmin)
for
must
function.
in
water system
the
across the
system schematics
is lit.
then
access
instrucLions.
Apollo
the
be used.
22 mm flow
and
Page
5
Page 6
10. The
system must
heating.
11.
Where
12. In
areas with hard
instructions for
13.
The inner
the
Apollo
casc
of
flushed
be
replaces
an older
twice;
initially
boiler in
cold with
an existing
or aggressive wet€r we recommend
details of
the boiler
use.
should not
be removed
the
system,
that
during
pump
removed make
Fernox CP3
installation.
and all
valves
open,
and then
sure the cylinder is indirect.
inhibitor
should be
used. See commissioning
after the
first
T1. BOILER DIMENSIONS Refer Overall
Clearances
See Water connections
12.
a. Fully The
Some water b. Length
The these
F,g.
to
1.
cased dimensions: Height: Width: Depth:
7ll mm 340 300
required for Top: Bottom:
Front
Sides:
section 9
connections:
50
90 mm 300 mm
mm
5
for installation
Compression
to accept 22mm
WATER
SYSTEM
pumped
open vented
combined cold feed
authorities
wet
of
and
distance
pipes
between the
should be as
mm mm
servicin
mm
SCHEMATICS
vent
and
require
vents for
dry
cold feed
close to
AND POSITION
g:
clearances.
fittings
copper tubing
are
to BS287l.
system with
must
rise
from
a stop cock
and
the boiler
close
vent
as
in the
coupled
connection
practicable.
WATER
OF
supplied
combined
the boiler.
feed,
cold
cold
to
for flow
feed
cold
in
which
-
feed
the
system must
AND GAS
CONNECTIONS
and return
-
vent
and
case a separate vent
Fig.
see
3. not
s€e
be
22 nn Relurn.
Fig.2.
more
.
145
must
than
zJo
-
be
connected as
150
mm. The
22 mm
-^ Flow
Fig.I
-bE-
shown.
point
of connection
of
The
by-pass
pipe
each
side between it Always The
ensure that
flow
through 910 litres/h Ensure that
Fit
one
more
or
Optronal Zone Valves
Optrona
.3
va
Fig.2
the
valve
pump
balancing
the boiler must not
(3.3
gaVmin)
pump
the
is
draining taps
pos
See 8S5449
clause
t
on
ve
should
and the
for
boiler.
has
sufficient
Apollo
the
accessible
(BS2879)
I
Alternative arrangement
i
cold feed is
I
l
24
be
of a type that is non-adjustable
static head.
be
allowed
40
Si or l146 litres/h
for
servicing.
to enable
vent
It
valved
Check the
fall
ao
below 690 litreVh
Isolating
the
valves
water
(4.2
system
A - length
-
length
B
-
150
C
by the householder
pump
manufacturers
(2.5
ga[min)
gaVmin)
must
to be
for
positioned
be
fully
drained.
the Apollo
of dry venl ol water filled
mD
min
minimum
for
as close ro
vent
HEATII{G
Bu,n
5C 40
3C 000 20 000
.0
Fig.
3
and musr have
head.
the Apouo
50 Si
while
pump
rhe
30 rhe burner
T
2CDmm
I
LOAD
000
000
000
least 1.5
ar
Si,
possible.
as
VENT
(mm)
A
4n 3(n z&
140
50
m
is
alight
LENGTH
(mm)
330
m m no no
of 22 mm
Page
6
Page 7
13. SEALED SYSTEM
Refer a. b.
c. d. A diaphragm
Frg. 4.
to The installation must A safety between creating A
must of Hot Water"
valve
set to operat€ at 3 bar
the
ahazard
pressure gauge
be chosen tro
valve
safety
to occupants or cause damage !o electrical components and
covering at
type
expansion
suit
connection. Further
published
Sizing table:
REQUTREMENTS
comply
with
and the boiler.
least
vessel,
volume
the
requirements
the
(45
lbf/in2)
The
range 0 m 4
the
to BS48
water in
of
shall be
valve
14,
the system and the
details can be obtained from
British
by
Gas and
BS7074:1.
of
should
bar
shall
be
"Material
856798
fitted in
(0
and
the
positioned
be
lbf6nz;
!o
60
connected
charge
and
BS5449:1.
pipe
flow
on
a discharge
shall be
point
a
at
pressure
Installation
Maximum
close !o the
water
boiler.
pipe fitted
wiring.
fitted
in
the system.
in the return
must
pipe
not be less
Specification
temperature
There must
prcvent
[o
to
close
than the
the
static
for Domestic
is
82oC t
not
be
any
boiler.
head
Central
3oC.
valves
any
discharge
The vessel
point
at the
Heating
and
NiEogen
Air or
Pre-pressurisation
Expansion vessel volume
=
A
The hot water
e. f. Water lost
volume
System
from the
system on the
provided
g.
The mains
system may be filled from the mains
pre-pressurisation
by
pressure, provided perrnanent part i) iD iii)
valve
a stop a test cock.
anti-vacuum valve
an
iv) a non-return valve
h. Fill
the system until
Refer
to
the
commissioning Examine for leaks the required
value.
prsssure
cfiarge
pressure (bar)
(lifes)
(litres)
cylinder shall
either be the
system shall be
return
side
of the cylinder or
that
of fre system and
complying
to tle
of a typ€ approved by the Narional
of an approved
pressure gauge
the
instructions, light
then turn off
The
by-pass
at ieast 1
between it and
Exoansron Vessel
(bar)
indirect
replaced
the syste.
of
via
procedure
this
fitted
in the order stated:
requiremenLs
type.
registers 1.5
boiler. Drain the
the
balancing valve
5rn of
22mm
the boiler.
0.5 1.0
None
A x 0.07 Ax0.120 A x
coil type
from
a make-up
radiators.
Lemporary hose
a
is
Where
accepuble
BSl0l0:2.
of
(22lbflinz).
bar
boiler and
the
system
must have
pipe
each side
Pressure Gauge
1.0
cylinder fitted
or a
vessel
non-return valve,
and
access to a make-up
connection
to
the
Water
from
local water
Council.
a draw-off tap
Examine for
allow the
while it is
l5mm
Balancrng
valve
-
systern
hot. Refill,
still
with
authority. The following
Optional Zone Valve
None 1.5
0.088
immersion
an
A x 0.160
calorifier.
mounted higher
vessel
would
be difficult,
supplied
leaks
reach
to
and
ils
vent
and adjust
whcre
rectify
maximum working
than the top
make-up
from
a service
pipe
fittings should form
neccssary.
temperature.
the
cold
pressure
fill
the
of
can be
under
to
a
Fig.4
Optronal 3-position valve
Page 7
Page 8
INSTALLATION
14.
14.1 Unpack the boiler
Note:
Do
not
stand the
PROCEDUR.E
-
Fig.5.
see
boiler on
its
end as
valve.
Do not
bottom
off the
case
discard the
cover
fixing
from
found.
pulling
the boiler.
the the
l. Carefully unpack
items
the
are
2. Carefully slide off Remove the outer case by slackening the
3.
firmly
and
4. Keep the outer case, bottom cover and place
IF REAR TO
SECTION
PROCEED
14.2 Prepare the
L Decide upon the
template supplied
not
so as
to damage them
EXIT FLUE IS TO
l42.IFSIDEEXITFLT.IE
TO
SECTION
(rear
wall
position
with
flue).
of the
the boiler.
before fitting.
BE
USED
14A.
boiler
The
using the
overall
clearances.
you
2. When Make sure
3.
4. Mark Remove
5. Reposition the template on the
6.
7. Make a the Remove
8. way
have
decided on the
that the
position
the
the template
note
of the
fl ue/terminal
the template and
(studs
up
at the bottom). Secrrre the
position
the hole for the flue.
of
finished wall
assembly.
(do
position
of the flue terminal
not
discard
i0
wall, mark,
thickness,
position
wall mounting
the
it will damage
packing
boiler.
the
the
until
botlom fixing screw
pins.
panels
infrll
in
a safe
CONTINUE ON
IS TO BEUSED
wall mounting
size
of the template
of the boiler
tape
will meet
cut the I 15 mm
and
drill and
this
plug
the
is
very important
plate
mounting
plate
o
gas
all
t!
plate
mountrng
is
size
the
the
template
the requirements
in) diameter hole in the wall for
@th
hve fixing holes
and
cenrally over the hole
the wall with
of the boiler
to the wall, ensuring it is level
given
to accept
is required for
four
21h" lg. No.12 woodscrews
No 8 x
cover
Flnd these
parls
in the
pack.
Fis.5
plus
minimum
the
and the correct
in
section
9. flue/terminal
the
215" lg. No.12 woodscrews.
section
in
the wall,
14.5 when ensuring
adjusting
it is level and
T??TTT??
12 19
scraaa
8 off
6@
nuts
M6
2 off
side, top and bottom
way
up.
assembly.
the length of
right
the
(not
supplied).
14.3
Secure the boiler
Note: The
L Lift
inner
boiler into
the
the boiler
2.
the
Secure woodscrew
case
wall
to the
bottom
(not
does not
position
of the
supplied)
wall
to the
need
and
mounting
boiler
via
plugged.
Remove
3. not to damage
4.
Connect the unions
Refit the flue diverter facing to the rear.
5.
14.4 Unpack the
Carefully packing
until all the
14.5 Adjust
(rear
flue).
l.
Using
flue/terminal
the
mm
83 terminal flange !o the
1
Note:
2. Drill through mm drill No.8 x l0lg. Note: When to damage the
3. Seal
the
terminal
flue
the
the
system
(see
water system
diverter
from the
gasket
flow
and
return
schematics, section
flue/terminal assembly - see
unpack
the
the measurement
(3V
Ensure
and
flue/terminal
the
items
length of
found.
are
flue/terminal
the
noted in
the
of
in
holes,
that
OUTER air the
assembly so
+ finished wall
in)
end
the
that
the
seams
three
pilot
secure the two nrbes ogether using the three
supplied with the flue/terminal
screws
drilling through the outer air tube
inner flue
centre
joint
with the tape
tube
with
assembly.
(rear
flue).
to be removed during
locate
plate
with
wall wildl.
to the
the hole
top of
pipes
the
holes
two
M6 nuts
two
a2th"
previously
the boiler
to the top
compression
l2).
Fig.6.
assembly.
Do
not
assembly
section
thickness,
14.2
it
is:
from
tube as
air tubes are
outer
in Fig. 7, with a 2.8
shown
adjust the
the
shown
assembly.
take
care
drill.
the
supplied
with
the
installatron
in the top
supplied
lg. No.l2
drilled and
care
taking
Fig.
see
length
of the
the
of
discard
-
back
in Fig.
inline.
not
flue/
of the chassis over
with
the boiler.
Clamping
ring 2
gggg
M4 ' 16 19
7
F+
screws
I roll
oi sealing
o
'O'ring
Seal
this
wtth
tape
supplied
Finished
wall thickness
fte studs
off
4
tape
Flue./lerminal
Flnd there
loint
Keeo seams
on the
off
parts
wall
llll
AAAg
x
1"
No. 8 screws 4 of{
ass€mbl!
in lhe
Fig.6
notes
Prlot
In lrne
*
83
mounting
lg
sra nress
pack.
t3 off)
(3%
mm
---
plate.
Outer
Outer seaftng
AAJ
No
lO lg
8'
3 of{
in)
Secure
plate
wall
plate
screws
Page I
Fig. 7
Page 9
14.6
Fit
the
Note:
If the
need
not be used.
1. Fit
2. Fit
the outer
the section. From
3.
outside
wall. Ensure
4. Push into
the
the
tube slides
into
slides
that the
Check Push fully home
flue/terminal
wall
is to be
plate
wall
'O'
ring in
position
the building
that the
flue/terminal
flue
diverter
INTO
the
the
diverter.
'O'
ring
until
ess€mbly - s€e Fig. t
good
made
over
up o
flue/terminal
the
over the
the
outer
insert the flue/terminal
slots in
the
end
of the terminal are
assembly lowards the boiler
on
top of the
inner
is
on the boiler'side of the flared section.
the flared
boiler,
of the
tube
end of the ouler
(rear
flue).
terminal,
the
assembly.
air tube
against
assembly into the
and
ensuring that the
diverter and the outer
tube
outer wall
the flared
vertical.
engage
the tube
inner flue
air
in
is
contact with
plate
tube
the
flue
diverter.
Fig.
t
14.7
Connect
l. Fit
that the the flared
2.
Secure the clamping the Tighten
3.
4. Proceed
14.E
Prepare the wall - see Fig. 10
l.
Decide upon with minimum side,
the two
flat
the flue
halves
part
to the boiler - see Fig.
of the
side is
against the
of the air
ring
threaded
holes in
the screws to seal
lo section 14.14.
position
the
the boiler. The overall
top and the longest flue/terminal the
2. Tape way
3.
Continue the
4.
Tape in
5. Make sure that
in Mark
6.
of the white
side
wall
the
mounting
up.
line,
the red
wall.
side
side flue template,
the
Lhe corner and that
posirion
the
section
9.
positions
the
of the
case to the OUTSIDE
clamping
wall mounting
tube.
flue diverter
to the
the clamping
flue
the
(side
of the boiler
size
bottom
clearances.
assembly and
template to the
on
the template,
supplied
the line
just
drawn
of the
four wall
ring
ring).
assembly.
of
flue
mounring
(rear
9
over the air
flue).
tube
plate,
using the
flue).
the wall mounting
using
the template is
Note
that
965 mm
two
wall is 2895
of the
wall,
ensuring it
horizontally
with
the boiler,
lines
up
across
with
terminal n ill meet
plate
fixing screw.
7. Drillandplugthefivefixingholes!oaccept2th" position
8.
Cut
of the hole in the
ll5
the
mm
(4rh
wall for
side
in)
diameter hole in
the
lg. No.l2
flue/terminal
the side
assembly.
9. Make a the
side
important
10.
Remove the
botrom).
at the
note of the white case
and are
finished
of tle
required in
templates
Secure
and
the mounting
wall thickness
shown on
as
section
place
the wall mounting
plate
and the
distance
the template. These
14.10 when
adjusting the
plate
!o
the wall with four 21h" lg. No.l2 woodscre*
as shown in Fig.
recessed
the
and
four M4
screws
template
of
size
the
(38
the boiler
maximum
in) flue
extensions) from
distance
mm
is level the
and the correct
wall until
to the side wall so
red
the
line
on
tie requiremcns
fixing scre
*s
and the lo*er
*mdscre*s.
asse mbly.
wall for
rhe
from
the side
measurements
length
position
in
Ensure
9.
side against
supplied
(use
supplied
plus
the
(using
(114
in).
itreaches
it is
that
the template.
given
\{ark
r}r
flueAcrmrnal
*all
to
ver)'
are
of
flue/termrnal
tlre
on tlre wall
ensuring rr rs le
,!?'
asse
(
nor
s
Fig.9
'.u.r'r€
Fig. I0
mbly.
vel
and the
supplied).
right way
up
(studs
14.9
Secure the boiler to the
Note:
I . Lift
2.
inner
The
the boiler into
the
boiler to
the bouom
Secure
case does
the
plugged.
3. Remove the flue
4.
Connect
5. Refit
6.
Unpack
the
system
flue
the
diverter
the flue/terminal
wall
not
need
position
and
wall mounting
the
of
boiler to
flow
facing
from
return
and
left or right as determined
diverter
assembly as described in
(side
flue).
be removed
to
locate
the wo
plate
with
wall
the
top
the
of the boiler
pipes
during insnllation.
holes
in
the top
nvo M6 nuts
with
lg. No.12 woodscrew
a2l5"
taking care
to the
top compression
section
of fte chassis over the
supplied with the
not
to damage
unions
by the flue
direction.
14.4.
boiler.
(not
(se€
water
studs on the
supplied)
gaskcr-
the
i'ia
system schematics,
wall
mounting
rlre hole
plate.
previously
drilled
section l2).
Page
Secure
and
9
Page 10
14.10 Adjust the length
l.
Using
length of the
127 mm
the end
to Where A between Note:
2. Drill
2.8 No.8 x l0lg. Note: to damage ihe
3. Seal the cenre
m@surements noted in
the
flue/terminal assembly so
(5
in) + A + B,
the
of
OUTER
is
finished wall
the
the side wall and the side of the
Ensure that the seams
through the three
mm
drill and
secure the
screws sup'plied
When drilling through the outer air tube take care not
inner
joint
flue/terminal
the
of
from
the back
air tube as shown
thickness and
in the
pilot
holes,
tubes
two
with
flue tube
with
with
the tape
assembly - see
that
14.8, it is:
adjust the
section
of the terminal flange
in
Fig. I l.
B is
the distance
white
case.
outer air tubes are
in Fig. I l, with
shown
together using the three
fluelterminal
the
assernbly.
the drill.
supplied
with
the flue/terminal
inline.
Fig. 11
a
(side
flue).
Seal thrs;oint wrlh supplied
+--
Finished
assembly.
tape
Keep
seams
wall thickness
Fig.11
Pilor
,
rn lrne
+8+
holes
127 mm
(3
off)
(5
tn)
l4.ll Flue
The flue
be
to A maximum
extension - see
extension
extended by 965
of two flue
l. If the flue
extension to assembly. Ensure
terminal
fis INSIDE
the outer aL
kit
allows the standard
mm
extension
extension kit
the
swaged end
thatthe
the
tube fits
OVER the air tube of
Fig. 12 (38
is
(side
in).
may be used,
used, connect the
of
the sondard
innerflue
inner flue
tubeof
tube of the extension and
Push fully home. Note:
Ensure that the seams
2. Drill three equally
spaced
in
the outer
holes
using a and the extension tube sleeve. Serure the two Note:
When drilling through the outer air tube take care
Seal the
3.
4.
Adjust the OVERALL
Fit
14.12
Note:
plate
l. Fit
2. Fit
the flue/terminal
If
the
need not
the outer
'O'
the
with the tape
lrints
wall
is to be made
be us€d.
wall
ring in
length
pssembly -
plate
over the
position
supplied
as described
good
up to the
flue/terminal
over
the outer air tube
section.
From
3.
4.
outside the building
wall. Ensure
that
the slos
Push the flue/terminal assembly towards the
into
tube flue tube tube slides Push
the flue slides INTO
into
the
fully home
diverter
until the
insert
in
on top of the
inner
the
diverter.
flared
the
the end of the terminal
tube
Check that the
end of the
flue).
flue/terminal
if required.
plain
flue/terminal
the standafiflue/
the extension.
air tubes
mm
2.8
drill
&bes
with
s€€
flue extension.
the
in
section
13
(side
Fig.
terminal, tlre outer
assembly.
flue/terminal
boiler and engage the
ensuring
boiler,
of the
diverter
'O'
ring is on the
outer tube
assembly
end of
the
inline.
are
position
in the
together using
not
to
14.10.
Secure and
flue).
against
assembly
the flared
vertical.
are
that the
into
inner
and the outer
is in
contact
this
Seal with
shown
the three
damage
loint
tape supplied..
Extension Keeps
seams
Fig.
in Fig. 12,
through
No.8 x l0lg. screws
inner
the
seal
the
flue
joins.
tube
in line
12
with
wall
the
air
boiler side of the flared section.
with
the flue
diverter.
Standard assemblv
both the standard
flueltermrnal
fluelterminal
supplied with the flue extension.
tlre drill.
14.13
Connect
the
flue
to
the
boiler - see
Fig. 14
(side
flue).
l. FitthetwohalvesoftheclampingringovertheairtubeasshowninFig.14.Ensure
that the flared
2.
Secure the clamping
flat
part
the threaded Tighten
3.
4. Make
Page
the screws
good
I0
is
facing
side
of the air tube.
ring
in
holes
the
the clamping ring).
to
seal
gap
on
the
away
the flue
to
the flue inside
from the
boiler, and the
diverter using the
assembly.
wall
around the
recessed
four M4
flue
tube.
is
side
against the
screws supplied
(use
Fig.14
Page 11
Fit the outer sealing
14.14 l. Make
good
the outside Note: The outer sealing terminal.
2. Place
the outer sealing fixing holes. Remove the
3.
sealing
plate woodscrews. Note: The terminal
should
terminal.
4. Remove any covering terminal terminal
and secure to the
assembly).
-
plate
wall
plate
plate
and drill and
be
Fig. 15.
see
around the
flue duct
need not be used
over
covered
terminal and
the
plug
the
before drilling
from the terminal.
with four I " lg. No.8 screws
wall
if
wall
the
mark the
fixing holes,
prevent
lo
Position
the
is
good
made
position
of
up
the
to
four
suitable for I " lg. No.8
entering the
debris
plate
with
over
the
the
flue/
sealing
(supplied
the
14.15
Connect Connect a 15 Do not
14.16
Connect Note: A
mm
turn the
permanent
l. Remove the
2.
Slacken two screws wires,
brown to
3. Keep
the wiring centre
cable clamp, power
supply cable.
When
Note:
out of
slips
pump
4. The
lead
wiring centre, and
programmer
If
5.
a
Do
not switch
on the electricity
gas
the
the
supply
gas
supply to the
gas
supply on at
power
live
and
securing the
screw
in the cable clamp below the
L
and blue to N on
tighten
then
connecting
the
cable clamp
and any
connected
is not fitted,
-
see
F
supply
pump
the
in
the open
cable clamp screws.
the
power
the
the
external controls
16.
Fig.
service
this
cock.
stage.
I6
cabh - see
must
be connected to
front
of the
the
terminal
position,
supply cable, ensure that the
live
neutral wires become taut before the
and
wiring should be
to the terminal block. See
remove link HW
supply at
this
Fig. 17.
the
boiler.
wiring
centre and carefully
take
block and up
wiring
centre.
excess
Check that
Feed the
green
slack
the
and
in
the
wiring
length of
passed
through one or both of the
wiring
diagram
to ON and connect a switched
stage.
iL
lower
power
supply cable under the
yellow
to the earthing screw
power
supply cable between the terminal block and the
will open and
centre
earth wire is such,
the
earth wire.
page
20. live to
lr
Fis. I7
close
that
bushes,
terminal ON.
Fig. l5
clamp and
(
f
).
wiihout sraining
freely
po*,er
if
the
provided
at
the
connect
supply
cable
rear
of the
the
the
14.17 Remove l. With the
2.
Unscrew
remove the
If
3.
the
facia
Fit
14.18
1.
With the
2.
Connect
3. Close the
the inner case wiring the four
inner
programmer
panel
at this
programmer
the
wiring
programmer
the
wiring
14.19 Complete the l. Thoroughly
2. With the
flush the
pump
in readiness for commissioning.
centre open slide out
inner case
fixing
screws, two at the top,
case.
kit is
not
to be
fitted
stage.
kit.
lowered,
centre
centre
and
6-pin
secure
engage
plug
in
installation.
whole
system
fitted, fill, vent
and check
the facia
close the
panel
wiring
programmer
the
the
on
centre and secure
to the 6-pin socket on
position
witlr
with
water without
cold
for water
fixing
the
soundness,
of the connol box.
side
one
above the
fixing into
wiring
the
screw.
pump
the
rectifying
gas
in
the slot
centre,
posirion.
in
where
valve
and one
position
in
the conrol
push
fully home
Ensure
necessary.
to
with the
bor
all
left
the
fixing
push
and
until the
valves
*
of thc
inng
scre* . Do
fully
latch
engages.
are open.
centre, and
not
replace the
home.
Page
II
Page 12
15. COMMISSIONING for
See section
1. Test for
a. b. Remove the
c. Loosen the
2. Check the With the a. Set the b. Switch
c.
3. Check the a. b. Remove the two screws securing c. Disconnect and d. e.
f. g. h. Test
4. a. Apply a suitrble
b.
5. Check the After a.
b.
c. Set the boiler thermostat switch
d.
Note: The
the Replace
6. Replace
7. Replace a.
b. Ensure that the c. If
16
gas
soundness
With the boiler service cock closed
pipework
inlet
gas
in
accordance
ignition
gas
supply
programme
on the electricity supply and set
fan
will start
the ignition
ignition
the
the boiler thermostat switch
Set
pilot
Ensure that
Set the Checkthatthepilotflame(35to40mmlong)envelopstheelecrodeandextendsl0mmpastit.Adjustifnecessary(clockwise to reduce the flame). Test the Set Replace the
of the Set the A connections
Set the connect Set the Turn the adjusting screw Note: The
thermostat suitable Check the correct boiler
If of the control box.
sufficiently to If
boiler
pilot
the boiler thermostat switch
main
the
gas
valve
boiler
or
second
main
main
the
boiler thermostat switch to O.
pressure gauge.
a
boiler
boiler
switch to
leak
that
the
pilot
thermostat requires heaL
boiler
gas
the
gas
the
inner
the
programmer
a
programmer
a
programmer
a
controls.
boiler
purge
and
connection
securing the
screw
pressure
inlet
with 85689l. Retighten the test
sequence
isolated
switch
purge
after a
and
will
sparks sparks
flame and
the boiler
thermostat
supply connections
pilot burner
thermostat
so after
for
burner
burner
thermostat switch
detecting
arrow on fte data
burner
valve
valve
inner
form
also
will
continue
test
thermostat
isolate
one
switch to
Note: The
shield
and
supply leak detecting fluid manifold.
switch
pilot
the
gas
soundness.
setting
has
been
clockwise to decrease the
is factory
HIGH
fluid. Set the
rating.
is
tumed
cover
cover,
case
is fiued
is fitted replrce is
open
case seal
a seal.
not
fitted
the supply
(the
cock
boiler
o the
gas
test
check
CONT, if a
to
period
heard. The
be
the
of the
pilot to
secure
gas
for
to HIGH. The
is lit
pressure
alight
to HIGH and if necessary the maximum
set to
to
light
to
off every time the
ensuring that the
the wiring
is intact
open rhe
service cock
valve
point
screw one nrrn.
the ignition sequence as follows:
the boiler
of about
until either the electricity supply to
O to terminate the
pilot
supply for
switch is
pilot
the
(black
leads
HIGH. The
throttle is factory set
gas
at
the
O and
with
two soundness to the
the main
for l0 minutes:
Remove
O, disconnect the
main burner
the
boiler
plate
(positioned
centre, disconnect the
around
and reconnect
wiring
is
cover and
point
programmer
l0
ignition
set !o O.
shield
or
unit
valve
reconnect
screws.
main
burner
unit
gas
solenoid
input See Technical
thermostat swirch
cable
the
cenEe,
when
closed
for soundness
lift off
Ensure
screw and test
is
fitted and
thermostat switch
seconds a click
sparks
continue
ignition
gas
soundness
lift
and
white)
and
the burner setting
main
clamp is located correctly in
boiler chassis
the
off the
from
go
will
pilot
main
tlte
manifold
go
will
will
seuing
pressure gauge
test for
and
on the front
burner is off. The ignition
programmer
replrce
the operating slot
in
accordance
cover.
the
gas
the
the
through
fully
assembly
gas
through open
adjust
pressure.
!o O
the
supply
gas
for
check
!o HIGH.
will be heard
until the
is switched off
sequence.
shield.
gas
main
the ignition
open.
for
solenoid
joint
the chassis
at
the
automatic ignition sequence
and
gas
of
programmer
and
main
tlre
pressure
the
burner sening
Data,
and soundness around the
to
turn the boiler off.
the inner
replace
replace
then
panel
facia
is
vertical),
with 85689l.
is
on and open the boiler service cock to
soundness.
that all system controls are calling
The
automatic
indicating
pilot
is lit.
or the
solenoid on the
sequence but only the
gas
soundness
lead.
and
burner will light. Test
point
test
pressure
page
3, for the boiler ratings and
replace
qrse
the
pressure
the
at the bottom
sequence is
the cover, and secure
plug
and socket
inner
the wiring centre.
replace
then
pressure
ignition sequence
that the
gas
As
the
boiler
gas
using a suitable leak detecting
gas
the
screw
on the to
test
pressure
s€cure
case,
the
test
gas
start thermoslat switch
valve
give
right hand
automatically
and
winng
solenoid
supply is not
valve.
pilot
and chassis
and the
the
burner
gas
valve manifold
the heat
point
screw. Set the
point
test
with
slide
tle
with
four
centre.
gas
the
supply and
heat
for will
start.
has
opened,
yet
turned
is
set to O.
will light-
connections
pilot
will light.
and manifold
input
required.
pressures.
setting
screw
using
corner)
is
against
activated when
its
screw.
programmer
screws. Tighten
purge
fluid.
boiler
The
on
and
a
out
Page
12
Page 13
t.
Final
When
a.
hot When
b.
boilers
water
system
the system
in order
inhibitor is
an
and
check and addition of
has
been tested,
complete
to
the flushing
added to the
should be used
this is required. The system should be drained and quantity
4Vtpins and c. After the By-pass valve
9. Fully
a.
balance tle
b. Adjust the
the
of
CP3
system
close the
by-pass
by-pass.
for the system
radiattr
a 9
has
been
adjustment
by-pass
system
using
valve
volume.
system about6%
filled,
valve
and
pump
necessary
as
inhibitor
ensure the boiler
process.
system,
in
accordance
Fernox Manufacturing Co. Ltd.
guide
As a
pints.
vent
then
and
make a final
and
open
radiator
give
to
is
off
Soiler
with flushed
instructions. Where
their
out, ensuring that all
radiator
a 3
check
it
full
one
valves
a temperature
turn.
give
to
rise of 9oC across
thermostat
switch
recommend
the
radiators
will on average
system
for water soundness.
Light
an
the boiler
loC
l
temperature
with
the
se
t to O), drain the
Fernox
boiler is used
are
drained.
require
about 2%
heating
the
drop
across the
CP3
on an
circuit
water while it is still
for
with
use
old system,
copper tube special
When filling add
pints,
radiator
a 6
only in operation and
individual
radiators.
the
care
correct
system
boiler flow and return, i.e. measured before
BOILER
16.
Refer to
CONTROLS
Fig. 18.
(inner
case,
/
bas servrce cock
gas
valve
cover and
Pilot
burner
pressure
Inlet
point pressure
lest
Prlot
Burner selting
adlustlng screw
facia
throtlle
panel
removed)
Eurner setttng Boiler pressure
polnt sw{tch
test
Thermostat
Fis.18
17. FINAL ASSEMBLY AND
l Before fitting
panels, in
2. Lift the case If
3.
if
side exit
the case side and
outer cas€
the
in
programmer
a
switches to
4. Hand
5.
6.
7.
the User Advise rem
ain
the
in g i
AdvisetheUserthatforcontinuedefficientandsafeoperationoftheboileritisimportantthatadequateservicingiscarriedout
least
at Leave a.
b. c.
once a
permanent
a
Name and
Date
of
A wiring
out€r case, the
the
flue has been
s@ure with four of the N0.8 x 12
into
position
by retightening the bottom
is fitted, set the
the required settings. See User
instructions to the user and
User
of
the
noperati ve
year
by a card auached to the boiler
address of
installation.
diagram
of
HANDING
inhll
used
position
over
clock
precautions
frost
during
qualified
installer.
circuit-
the
OVER
panel(s)
fit
one of the
the
boiler
to the conect time
necessary
condi
l.ions.
service engineer or the
THE INSTALLATION
must
and
fixing
fitted
be
panels
to
lg.
screws supplied
push
back to engage the
screw.
(do
instructions.
instruct in
prevent
to
safe
the
damage to
local
giving:
to
the
side
of the
the side opposite the
with
fixing
not rotate
the dial anti-clockwise) and the
If
case.
rear exit flue
flue. To fit
the boiler.
pins
on
an
the chassis side
operation of the boiler and controls.
the system and to the building
Region.
Gas
has
panel, place
infill
in
been used,
it
into
the
case.
programme
tle event
of
fit
the two
position
in
Secure
and selector
the system
Page
13
Page 14
{\\T AL
IIt.
Ti
r.oSUre conrinued
rrrt!-n
als.
should be registered The following aspects of the boiler and
l. Run
switches
2.
Check the
If it is necessary
L Remove
2. Remove the
Examine the main
3.
4.
If a sufficiently large When refitting
5.
SER\-ICTNG
of
the appliance,
will
depend upon the
frequency
The
adequate.
efficient operation
of servicing
It is
the
law
that any service
personnel.
installation
the boiler and check the operation of
programmer.
and
installation
to dismantle the boiler the
the combustion
combustion chamber
injector
inner
the
flue terminal
of the
fan
and ensure
front
orifice and ensure
pilot
flame
cannot be achieved
case check that the
following
that it is
and check if the burner or heat exchanger requires
it is recommended that
particular
work must
be carried out by a competent
should be examined, and
its
controls, observe the
and ensure
it is not
checks should be
clean and
it
is clear and undamaged.
free
examine
seal is in
good
condition and ensure that
Instellstisn
obstructed.
of debris. Check the
the
On completion of the service run the boiler and ensure that it operates The
boiler data
plate WARNING: Before supply. Slide off the bottom cover and turn off the IMPORTANT: Always
positioned
is commencing
gas
for
test
inner
on the
work
case at the bottom
set the boiler thermostat
gas
supply
right hand
switch to O.
gas
the
at
soundness after completing any servicing of
checks of controls.
it is
conditions and
rectified
picture
flame
made.
pilot
injector orifice
satisfactorily.
corner.
Allow
service
cock. gas
checked and
person
nec€ssary.
as
cleaned as
usage
but
such
as
and ensure that the boiler
impellor for freedom
necessary
general
in
British
Gas or other Corgi
responds
rotation.
of
cleaning.
to ensure
it
compresses
the boiler to cool and
it is
clear and undamaged.
satisfrctorily.
isolate
carrying components and carry
regular
at
per
once
year
to any
the electricity
functional
out
18.1
Dismantling
I .
Slacken
Place
case. Remove
2.
wiring
centre and
3. If a
programmer
centre and
programmer
If
a
4.
Unscrew the four gas
valve
-
Fig. 19.
see
the screw securing
the case safely aside to avoid
the one screw,
lower
is fitted,
slide
out the
is not fitted,
inner
and one o the
case.
Disconnect
5.
tle two
wires from is not importanl Remove
6. assembly to with impellor from
7,
Remove the two
8. Slacken the Remove
9.
10.
Undo the securing nut and lead from the
I l. Remove
12.
Remove the clamping bracket
13.
Undo the tubing
14.
Carefully
15. From
16.
Carefully
17.
Cover the exposed
the three hex. hd. screws
the fan housing
the
hex. hd.
nuts
the
two
four
burner
securing
screws and
air
the screw secunng the
nuts
and
remove
and
underneath the base of the chassis
the
pilot
move
gas way
the bottom of the outer case and
possible
the
above
the
unplug the
boiler therrnostat switch, securing the
wiring
centre.
programmer plug
programmer.
slide out the
fixing
case
left
of the
the
and carefully
screws,
wiring
fan motor,
and
facia
two at the top, one above the
centre, and
the
washers
securing the fan
withdraw
fan housing.
screws securing
the flue hood
wing
nut
secunng Ore combustion
remove
the electrode, see Fig. 19, from
flue hood
the
to the combusrion
guide.
disconnect
reuin
the
gas valve
*
hich pilot
cover
retains
the
pilot
the
injector,
supply,
see
remove
supply to one side and lift
in
the base of the chassis.
pull
off the
damage.
from
the
wiring
panel.
remove
polarity
of these
the
inner
wires
motor
motor
the
complete
cover and
remove
the
chamber.
the
front
pilot
both the
and
pilot
lift
off the cover.
supply
and electrode
Fig. 19, from
see
chamber
Fig. 19.
the two
pozi
screws securing the
out the burner assembly. Take
cover. cover
assembly.
lead
at the bottom left hand
pilot
withdraw
and
Remove
assembly and
manifold.
burner
not
care
to
Fig. 19
the
lose
the burner
4.omm
3.O to
the
cover.
grommet
corner
gas
valve.
on the
elecEode
of the chassis.
'O'
flange
ring.
lE.2
Cleaning the boiler.
Brush
L
deposits
2. Examine the fan impellor and
the
from
heat
exchanger
the boiler base.
from
above and
carefully clean
3. Turn the burner upside down and tap
4.
Clean the
5. Unscrew the wire.
To
clean or
pilot
injector from
Clean the
replace
burner and spark
the burner
pilot
the
pilot
injector in
a similar manner.
filter
in the
electrode
Page 14
below using a suitable brush. Brush
if necessary.
gently
manifold,
gas
remove
to
with a fine wire
any debris.
brush if necessary.
clean by blowing through or washing. Do NOT
valve
refer
to section 20. I l.
back to
front NOT
sideways. Remove
any
clear the injector with
fallen
pin
a
or
Page 15
18.3 Reassemble L Replace
Remove
2. Check that the
3.
4. Replace Replace the
5. Replace
6. gap
Replace
7 .
the clamp. Replace
8. nuL Fully
9.
10. Replace the flue I l. Replace
12. lf Refertothecommissioninginstructions,sectionl5.Lightthepilotandchecktheflame,testthepilotandmainburnersupplies
13. for
14. Lift in If
15. switches to
16. Replace
19. LIGHTING INSTRUCTIONS See section With the
l Turn
2.
Set the
3. Set
of The Note: The the
4.
If programme
the burner
the the the spark
is 3.0 to
the clamping bracket the combustion chamber
tighten the
the
programmer
a
gas
soundness, check the
outJer
the
position
programmer
a
the bottom cover.
16 for
gas
supply on, electricity
on the
programme
boiler thermostat switch to
the
l0
about
pilot
will
thermostat requires
boiler
programmer
a
boiler.
the
injector
protective
'O'
ring is in
assembly
burner pilot
injector
electrode.
4.0 mm,
nuts
hood
fan motor
is fitted,
into
case
by retightening the
is fitted,
previous
their
boiler controls.
gas
seconds a
pilot
and selcctor
electricity
and
switch to CONT, if a
light and after a
burner
is fitted,
using a small amount of
covering
and
Ensure
Fig.
see
securing the
cover
impellor
and
temporarily
position
set the
sett"ings.
will
click
is
turned off every time the
ensure that the
s*'itche s
gas
from the
position
and
reconnect
-
and securc
main
heat
in the
secure
that the
19. bottom
bottom
supply
supplies to the boiler.
be
second
left hand
front
ensuring that
flue
assembly and
reconnect it
burner setting
the boi-ler and
over
fixing
to the correct time
clock
off
HIGH. heard
or
s€t
are
way
burner
with two
pilot
the
grommet
hood.
with
two screws
screw.
the
and
programmer The automatic
indicating
the
sc'
clock
to their
jointing
in the base of the chassis.
flange.
screws
supply
on the elecrode
corner of
the
reconnect
to the
pressure
push
boiler
that
gas
main
main
is
set
previous
compound.
previously
to the
the
chassis.
burner stud
previously
the
wiring
and
back
to engage the
(do
not
thermostat switch set to
is fitted
ignition
the start
solenoid
burner
to the
correct
scttings.
removed.
pilot
assembly
Enswe that
locates in
removed.
fan wires
centre.
replace
rotate
and check that all system
sequence
gas
solenoid
will
is
off.
time
Note: The
lead is htted
the
(the
gas
the
fixing
dial anti-clockwise)
the
will
has
and the
open
The ignition
(do
40
gas
and
to the bumer air
pilot
the
bracket. Secure
polarity
valve
cover
pins
O:
The fan will start
start.
opened, the
main
sequence is automatically
not
rotate
Si injr:ctor
valve.
supply and electrode
of
the
and
on
the chassis side
controls are calling
burner
the dial
uses a
guide.
with four screws
wires
is not
inner
case.
programme
the
and
and after a
ignition
sparks
will light.
anti-clockwise)
sealing washer.
Check that the spark
lead
are
behind
one wing
and
important).
into
case.
the
and
selector
for heat.
purge
will
also be heard.
activated when
and
that
Secure
period
the
20. REPLACEIIIENT WARNING: supply. Slide IMPORTANT: checks of controls.
20.1 To replace Remove
l.
2. Disconnect Withdra* tlre
3. chassis).
4.
Undo Insert a new
5.
chassis), Ensure mounting box. Replace any
6. Remove
7 .
in
Fig.
Replace
8. Replace
9.
10. Refer
Before
off
fre outer and
the securing
through
that the
the two screws securing the
19. the the
to the lightrng
commencing
bottom
the
Al*a; s test for
spark
the
tlre electrode
electrode
nut
electrode and
the side of
large
winng
pilot
shield
inner
case,
OF PARTS
*ork
se t
the boiler thermostat switch to
cover and
electrode - see
inner
lead from
lead through the
remove
and
secure with
grommet
connectors removed from the
and
programmer
instructions,
turn off
gas
soundness after completing
Fig.
cases as described
ignition
the
the electrode
nut.
the
is fitted to
secure
board mounting
circuit
pilot
with
facia
or
section
gas
the
19.
circuit
Pass the
burner
the
shield.
screws.
two
panel
19. Light
in
circuit board.
board
Lift
supply
section
from
circuit
18.1,
mounting
pilot
the
elecrode
box and connect guide
air
board
off the
,wiring
the boiler
Allow
O.
gas
at
the
any
lead
pilot
centre
service
exchange
paras
See section
box and the clamping bracket
assembly.
behind the clamping bracket
and the small
replace
and
shield
and outer case.
replace
and
cock. gas
of
carrying
4.
I
o
20.6.
it
to the
circuit board.
grommet
the
circuit
and check that the
bottom
the
the boiler to cool
components and carry out
(bouom
(bottom
is
fitted in
board mounting
spark
cover.
the side of
gap
isolate
and
left hand
left hand
plate.
is
3.0 to
the electricity
functional
corner
corner of the
circuit
the
4.0 mm
as
the
of
board
shown
Page
15
Page 16
l0.l To replece the
I R-,.mov€ the
l. Remove the screw securing
Remove
3.
4.
Undo the tubing
5. Remove the Fit a new injecor and
6. Replace
7 .
the clamp. Refer
8. replace Replace the outer case.
9.
10. Refer
the clamping bracket
the the
to
the
to the
pilot injector
outer
pilot
clamping commissioning
gas
lighting instructions,
inner
and
nuts
and disconnect
injector from
reconnect
bracket - bottom
valve
cover, inner
-
Fig. 19.
see
cases as described
gas
the
instructions,
valve cover
which recains
pilot
the
pilot
the
the
assembly,
pilot
left hand
section
programmer
case,
section
supply.
19.
the
Light the
in
section
lift off
and pilot
supply and electrode
supply,
see
see Fig. 19.
corner of the chassis.
15. Light or facia
boiler
paras
18.1, the cover.
Fig. 19, from both
pilot
the
panel
replace
and
4.
I to
lead
the
Ensure that the
and
check the
wiring
and
the bottom
the botmm left hand
at
pilot
assembly and
pilot
supply
flame,
test the
centre.
cover.
corner of the chassis.
gas
valve.
and electrode
pilot
supply
for
lead
gas
are
behind
soundness,
20.3 To l. Remove the outer
2. Remove
3.
4.
5. Undo the tubing
6. Remove the
7.
8.
9. Fit a new
10. Remove the I l. Replace the
12. Refer
13.
14. Refer
20.4 To Note:
L Remove
2. Remove the
3.
4.
5.
6.
replace
the screw securing the Remove Undo the securing
Remove Remove the remaining screw
spark
the clamp. replace
Replace
Remove the burner Using a
Ifaprogrammerisfitted,temporarilyreconnectittothewiringcentre.Refertothecommissioninginstructions,section the case,
Replace the
the clamping bracket which
the
gap
the
to
the
the the lighting insrucdons, section 19. Light
to
replace
The
burner
the outer
injector. Note: The 40
new
pilot
and
prognrmmer
pilot
the
pilot two screws
pilot
is
3.0 uppermost
clamping bracket - boaom commissioning
gas
outer
the burner.
burner
pilot
'O'
check
outer
burner - see
inner
and
nut
nuts
injector
burner and secure
4.0 mm
to
valve
case.
fitted may be either Furigas
and inner
as
assembly and
ring in the burner
the
or facia
case and
cases as described
gas
and remove the elecrode
and disconnect
from
the
securing the
securing the
with two screws. Replace
shown in
as
screw
securing the
instructions,
cover, inner
described
flame,
case,
cases as described
in
main
injector
Si
test the
panel and wiring
bottom
Fig.l9.
in
section
valve
cover
and
retains
pilot
the
pilot
assembly, see
pilot
Fig. 19.
left
section
programmer
section
bumer
uses a
manifold flange fit
pilot
cover.
pilot
the
from
supply, see
shield and pilot
burner and
pilot
burner and
hand
corner
15.
Light the
the boiler
(silver)
in
section
paras
18.1, injector
and main burner supplies
centre.
and
sealing washer.
paras
18.1,
lift
off the cover.
supply and elecrode lead
pilot
the
Fig. 19,
Fig. 19.
lift
off
the
remove
tlre
replace
the
of
chassis.
pilot
or facia
or Bray
panel
and replace
18.1,
8
17,
to
fit to
the
tlre burner and
I o 4.
assembly.
from
both the
pilot
shield.
pilot
the
pilot
injector,
pilot
the
Ensure
and check
wiring
and
the bottom
(blue)
either
paras
I
4.
to
new
burner. Use a small
reassemble
gas
for
the bottom left hand
at
pilot
assembly and
burner.
pilot
supply
and spark
shield
securing
that the
may
soundness
pilot
the flame, test the
centre.
be
used as a
as described in section 18.3,
it
with
supply and electrode
pilot
cover.
replacement
amount of
replace
and
corner
gas
valve.
electrode.
two screws.
lead
for
supply
for
jointing
gas
compound
valve
cover, inner
of
the chassis.
Check that the
are behind
gas
soundness,
the other.
paras
2
to 9.
l5.Light
on
the
20.5 To replace Three
thermostats are
paint,
brown
I . Remove the
2. Disconnect
3. Unscrew the
4.
Ensure Reconnect
5. device, a brown and page Replace
6.
7
Refer
.
the the
8. Replace
that the
20. the
to the
boiler
'Lo'
thermostat the bottom
the
the two
the two
off and on
Page 16
'Hi'
the
'Lo'
outer and
fixing
mounting
inner
lighting instructions,
'Lo'
or
mounted on the right hand
thermostat
wires from
screws and
wires. The
yellow
qrse,
when
switches the
cover.
thermostats.
with white
inner cases as
the thermostal remove
plate
is
clean,
polarity
wire
to
programmer
section 19.
the boiler thermostat switch
boiler
described
the
fit
of
these
'Hi'
the
facia
or
off and on.
(flow)
pipe
from
the
paint
and
in section
thermostal the new
wires is not important. Ensure
thermostat and a white
panel
Light
overheat
the
18.
thermostat
wiring
is
centre
set to
,
the boiler and allow it to heat
cut-off device
paras
I
,
and secure in
and and
HIGH.
heat
exchanger.
4.
I
o
position. that
yellow
wire
outer
case.
Set the boiler thermosrar switch to
The'Hi'
grey
with
to the
grey 'Lo'
the two
up. Check
thermostat
paint.
*
irt's
rmostat.
the
rhar the
go
'Hi'
is marked
to
overheat cut-off
the
wiring diagram
See
thermostat switches
LOW
and check that
with
Page 17
'see
To replace
20.6 ignition
The behind
Remove
l.
wiring
2. If
centre the From underneath
3. screw
and
disengage
circuit
facia
the
the screw
centre.
programmer
a
slide
and
panel.
facia
securing
carefully
the
4. Disconnect wiring
two Carefully
5. with a Reassemble
6. Refer to
7. To replace
20,7
Ensure
l. Remove
18.1,
Remove the
2.
the Disconnect
3. terminal not (pilot) (main)
4. Remove in section Remove
5. side sure Remove
6. Disconnect
7. Remove
8. Withdraw
9.
10.
Using to the of the
Do
remove the
new
the
the
that
the
paras
cover.
from the
importantbut
solenoid
solenoid).
tlre
20.6.
the one
wiring
of the
the
that
the the
the
new
boiler
chassis.
replace the
not
ignition
the
panel
board
circuit
is
programmer.
or
securing
is fitted, unplug
programmer.
out the
ignition
the
back.
it at the
lower the
rear
wiring connector
the
connectors
mounting
fixing.
from the
circuit
one.
in reverse order. lighting
the gas
outer
I
to
screw
the
instructions,
gas
valve
suPPlY
and
4. securing
push-on
is
inner
gas valve.
red and blue
the
white
the
and
wiring
See
ignition
'tag;
the
,O'
in reverse
circuit
securing
screw
anO
centre
rear of
at the
pilor
3
bracket
supply
socket screws
mm
clamping eight
gas valve and discard
in
rings
the
order.
gas valve cover
board
positioned on the
front of the
the
programmer
the
programmer
If a
mounting
board
circuit
Remove
board
'see
tfte two
plate
from
rear of
from
section
Fig.2l.
withdrawing
front,
the
the circuit
the
19. Light
off.
described
as
cases
gas valve cover and
the
unscrew
terminals
board
wittrOraw
and
polarity
(The
must
wires
wires to the
blrck
and
diagram,
page20.
mounting
mountingplatebox
the
ne box.
located
the box
is
which retains
the
both
from
securing
'O'
the
service
cock and
Ensure that
this stage.
at
the
ll. Ifaprogrammerisf,itted,temporarilyreconnectittothewiringcentre.Refertothecommissioninginstruclions,section
pitoi
ttre
burner
the
12. Replace
anO
setring
the
theflame,iestthepilotsupply
check
pressure, replace the
outer
case and
bottom
cover.
gas
20.
Fig.
of the
side
wiring
plug
screws
elecnode
the
board,
mounting
in section
tle
of these
go
the
o
plate
as described
The screw
in
the
pilot
the
gas valve
the
in
rings
manifold
burner
pilot
supply
connections
valve
cover,
wiring
and
centre
from the
fitted, slide
is not
plate
slacken
securing
it
it fonvards
lead
Fig'
see
pillan
and
boiler and
the
lift off
earth
wires is
inlet
outlet
the
to
is
accessible
on
out
cut
and electrode
supply
pilot
and
gas valve
service
the
flanges
and electrode
and
inner
centre
Mounting oox
plate
lower the
wiring
out
one
the
front
the
at
and
to
the
slightly
20'
replace
replace
- from
the
assembly.
(four
cock
side
the
to
and
of
Take care
(both
lead
the bottom
beneath the
lead
service
burner
'O'
are
the box.
wiring centre
the
at
cock
manifold
rings are
behind
cover.
bottom
not to lose
and
the same the clamp
Fig.20
Fig.21
Note: When
before
hand corner
left
pilot injector,
the
to the burner
four
flanges.
size)
in
the
gas valve inletandoutletconnections
programmer
case,
or
facia
panel and
Fan,
refitting the box
replacing
the
manifold)'
reassemble
bottom
forgas
wiring
left
soundness, check
centre.
pressure
@@
make
fixing screw'
chassis.
of the
Fig. l9'
see
valve
new
the
hand
corner
l5.Light
replace
To
20.E Remove
l.
2. Remove Unscrew
3.
4.
Screw
Replace
5. Ifaprogrammerisfitted,temporarilyreconnectittothewiringcentre.Refertothecommissioninginsfictions,sectionl5.Light
6.
boiler,
the
facia
or Replace
7.
the burner
outer and
the the burner assembly
injector
tlre
replacement
in a
burner assembly
the
test the
panel
and
outer case and
the
injector.
inner cases
from
injector
pilot
and
wiring
centre.
as described
as described
manifold.
the
using
as described
burner supplies
main
botlom
cover'
in
section
a small
in
section
in
section
18.1,
amount
18.3, gas
for
paras I
18.1, paras
jointing
of
paras 2
soundness
4.
to
U'
8 to
compound.
9'
to
replace the
and
Note: The
gas valve
40 Si
inlcctor use
inner
cover,
s a sealing
progfammer
case,
Page
washer.
17
Page 18
20.9
To replace
l.
Remove
2.
Disconnect the valve.
go
must (main)
3.
Carefully
(fhe polarity
solenoid).
gas
a screw
the
push-on
to the inlet
prise
out the
solenoid and its mounting
4.
Position
the
new
solenoid
order.
5. Refer bottom
20.10
To replace
pump
The above
the wiring
l.
Remove
2.
Remove
3. Remove next
to
with
thermostaL
4.
Disconnect
lighting
to the
cover.
overrun
the
outer and
ignition
the
one
the
wiring
the
the
the
thermostat is
centre.
screw
centre underneath
three wires
brackeL
5. Fit
6. Connect
7. Refer
new
the
thermostat
the three wires
n the
lighting cover. Allow
8. run for
the boiler to
15 minutes.
5 to
the
-
gas
Fig. 22.
see
valve
cover and
valve
solenoid
securing
terminals and unscrew
of these wires is not important
(pilot)
solenoid
See wiring
retaining
bracket,
into
instructions,
pump
oyerrun
inner
control box as
securing the
and the white
diagram,
page20.
clip from
seeFig.22.
the mounting
section
thermostat
situated at
cases
described in
as
described
pump
behind the solenoid
bracketand
19. Light
tbe
overrun thermostat mounting
tlre chassis.
remove
and
to the mounting
to the
instructions,
heat
up
fully
thermostat,
then
the
two
bracket
see
section 19. Light
switch it
lift
the
off
the
terminal
earth
but the red
and blue wires
and black wires
and
reassemble
the boiler
-
see Fig.
bottom right
section
in
section 20.6.
and replace
23. hand
18.1,
Carefully withdraw
screws
securing the thermostat
and secure with
Fig.
23 and reassemble
the
boiler
and
off at the
programmer
cover.
lift
gas
the
outlet
off the
from
to the
in reverse
the
corner of the
4.
I
to
bracket situated
the
bracket
two screws.
in reverse
replace
or
extemal
chassis
complete
the
to
order.
the
bottom
conrrols and
Yellow
lead
check
Mounting
Fig.22
(2)
Fig.23
that the
bracket
overrun
thermostat
pump
continues
Brown
(3)
lead
ro
20.11 To replace Note: It is injector Ensure l.
Remove
2.
Remove
extremely unlikely
pilot
and
that the
the the
24. Discard
3.
Carefully
4.
Replace
remove
the
pilot
the
supply are
gas
supply
gas
valve
five
screws securing
gasker
the
ttre
rear
cover screws. Replace
5. cover or the Turn
6. using
7. Refer
gas
for
8. If
programmer
a
9. Apply
instructions,
10.
Refer
wiring
and
gas
valve
the
inner
and
gas
on
the a suitable to the
supply
leak
detecting
commissioning
soundness.
is fitted
suitable leak
a
section
l9
to the commissioning instructions,
centre.
11. Replace the outer case
20.l2To replace L Remove the
2.
Unplug the
3. Slide out
4.
Slide the
5. Connect
the new
the
6. Refer m the
7.
Set
Replace
8.
programmer
the
the bottom
programmer (if
the
screw
securing
programmer
programmer
progmmmer programmer lighting
instructions, section
clock o the correct time
cover.
-
filter
as described in
pilot
using a
in reverse
that the
clear
is
off.
filter,
see Fig. 24.
pilot
and
the
section 20.7.
rear
the
see Fig.24
gasket
new
order
section 20.7,
to
outer cases.
and test the
servibe cock to
fluid.
instructions,
temporarily reconnect it
detecting fluid
around
and light the main
and
bottom cover.
fitted).
front
the
plug
from
inlo the
plug
from
of the
wiring
the
the control
control box, and
wiring
to the
filter *ill
filter is
cover
become
still suspect
plate
and
and replace with
and secure
by evenly
but do
gas
valvejoint
section 15. Light
to the wiring
gas
the
burner.
section l5
wiring
valve
Test
the
and
cenuc
replace
centre.
box.
push
centre,
close the
19. Light and
the boiler
switches to
the
blocked. If
proceed
carefully
remove
a new one.
tightening the five
not
replace
for
pilot
the
nrre.
ce
rear co','er
gas valve
the
carefully
and
fully home.
wiring
and check
their
the
follows:
as
it,
see Fig.
gas
the
gas
soundness
and check
and $c'
rL-ar
cover
las
gas valve
lower
iL
cenre and
the controls.
previous
pilot
valve
flame
tre
valve
and
rcsr ric
outlet
connection. Refer
and outlet conneclion
cover,
inner case,
secure in
posiuon
prcgrammer
with
settings.
I-ig.24
pilot
for
supply
gas
connections
to
the
soundness.
facia
or
the fixing screw.
lighting
panet
Page
I8
Page 19
To replace
20.13 The
l. Remove the outer
2.
3. Remove the
4.
5.
6. Reconnect the 7 . Refer to
8.
flow
air
Carefully
screws to
these
a
Using
washers
fibre
Reconnect the
Replace
the air
pressure
disconnect the
screws securing the
two
insulate
pressure
new
are used.
wires
flexible
lighting instructions, section
the
the bottom cover.
pressure
flow
switch
and inner
is
flexible
the
switch
to the
tube and
pressure
switch.
situated at
cases as
tube
pressure
pressure
(supplied
switch from the
switch.
reassemble
the top
described
from
with mounting bracket) secure the mounting
19. Light
right hand
in
section
pressure
the
mountirig
switch
flue
wiring
See
in
reverse ordcr.
the boiler
corner of the chassis to
paras
18.1,
switch and
hood.
diagram
and check
I
to
disconnect
bracket to the
page
20. that the
4. the three
flue hood. Note: There
pressure
right
the
wires
bracket to the
switch
allows
the fan.
of
noting their
,
are two
flue hood. Ensure
position.
fibre washers
main burner to light.
the
on
that the two
2A,MTo replace the
l. Remove
2. Reassemble in reverse ordcr using the Refer to the
3. on and off
4. Replace
20.15
l. Remove the outer and
2. Remove the bumer as dcscribed Remove the two
3.
4. Remove
chamber
5. Slide
6. Slide
7. Fit a
Reassemble in
8.
of Ifaprogrammerisfitted,temporarilyreconnectittotlewiringcentre.Refertothecommissioninginstructions,section l5.Light
9.
the boiler,
10. or
10. Replace the outer
20.16
Ensure that the system
care
Take and its connecting
L Remove the outer and
2. Remove the burner as described in
Remove
3.
4.
Remove the
5. Undo it
6. Reassemble
at
7. Fill and
Ifaprogrammerisfitted,temporarilyreconnectittothewiringcenue.Refertothecommissioninginstructions,secLron
8.
tle boiler, test the
or Replace
9.
the outer
the bottom cover.
To replace
the
to clear
out $e
the
out
panel,
ne*'
the chassrs.
panel
facia
To replace the heat
when
the the four screws
heat exchanger
littings
the
from
the
bouom left
the
vent
panel
facia
the
fan
motor and
inner
case,
lighting instructions, section 19. Light
respectrvely.
the combustion chamber
innc'r cases
nurs sccuring
four scrc*s
the
front rnsulation
side
tuo
lower
reverse
test
the
and
case
removing
pipes.
nuts securing
two
securing
pipes.
in
reverse order using a new
hand
the system.
pilot wiring
and
ourcr
case and bottom
(two
heat
exchanger
panels
edge
order.
pilot
and
wiring
centre.m cover.
and exchanger.
is
drained.
the
inner
(two
remove.
and
the
corner of the chassis.
and
centre.
impellor
case
and
as
in
section 18.1,
flue hood to
the
each side)
panel
and carefully
remove
and
first and
Ensure
main
burner
bottom
heat exchanger
cover.
cases
as
section 18.1,
the flue hood
each side) securing
inlet
and
main
burner supplies for
cover.
assembly.
the fan
new assembly.
insulation.
described
securing
remove.
and
the
push
back
that the
described in
pilot
supplies for
as
outlet
heat
motor
the boiler and check that the
in
section 18.1,
paras
the combustion chamber and disengage the tie
replace
panel
rear
into
supply and electrode
even
section
paras
ul the
fte combustion chamber. Carefully lower
pipes
exchanger. Ensure
impellor
and
to 17.
8
the combustion chamber
with a new
pulling
by
position.
gas
soundness and
with
the
18. I
17.
8 to
combustion chamber
to the heat exchanger
gas
soundness
assembly as
paras
forwards
in
Slide
paras
,
that the
drained
and
system
4.
I to
one.
new
two lead
are
replace
4.
I to
and disengage the tie rods.
and
pilot
replace
described in
fan
switches on and off
the
fo
chassis. Carefully
at the top then
panels.
side
behind the clamp
gas
the
there will
carefully
supply
lower
and electrode lead are
gas
the
section I 8.1
rods.
lifting
out
the bottom
at
valve
cover,
still be
valve
water in
the combustion chamber
heat
the
cover, inner case,
paras
,
the main
as
lower
inner
case,
the heat exchanger
exchanger ro
behrnd rhe
I to 6.
burner cycles
the combustion
left hand
corner
progmmmer
to
clear
disengage
clamp
l5.Light
programmer
Page
19
Page 20
WIRING
21. Illustrated wiring
a.
c0t0uR
ilOTE: lf
swilched live
Bemove link HW fined terminal
DIAGRAMS
diagram
v
c00E
-
b
blue
-
bk
black
br - brown
-
g
green
-
gy
grey
-
0
orange
Apollo
prog,ammer
to terminal
to
CH OFF
the
with Apollo
Fan
Motor
-
pk
pink
p - purple
-
Y
violet
r-red
w - white
y - yellow
-
g/y
green
is not
litted, remove
0l{.
Oil when
fitting erternal controls. lf an Apollo
is live
when HOT
programmer.
yellow
and
WATER
link
HW lo 0t{ and connecl a
is selected.
'Lo'Thermostat
programmer
is
'Hi
Overheat cut
Pump overrun Thermostat
Thermostat
gY
ofl devtce
br
l'
t
b,-,i
4
f..u'l ( lc
I >LVV
Ir
|
$t.a
MNI +
'
? NH
L
gv
6-waySocket for Apollo Programmer
'(
>
--
*l
lgnition
Crrcu,t
Board
Boiler
Terminal
Block
,,',{"
i
M",^,
Pumn
Earthin Stud
L't
.
-c
l,
{
{
L
L-\vL
i F
F HL
jarthrng
Screw
Twice
Once
Cont
3-way
Suppressor
High
o
Low
3-way
Apollo
Programmer
Switch
Switch
6-w plug
I
I I
I
Page 20
lr*
ott
I
Hw&cH
I
L-
3-r/ay Swrtch
Clock
I I
I
J
Page 21
Functional flow wiring
b.
Pump 0v!rrun Thermd,
diagram
*'ithout
programmer.
lli
Therm6tit
Lo Thermostal
3
I
=
Spark Ilarne
c(3)
electroder sensot
Pressure
Switch
L.I
Nc(1)
MN
L2
PN FN
N
cot
b
bk
br
g
gY
0
pk
ouR
-
blue
-
black
-
brown
-
gleen
-
grey
-
orange
-
pink
c00E
-
p
purple
v - violel
r-red
-
w
while
-
y
yellow
g/l green
and
yellow
\0'[
'a
programmer
rs not frtted,
hnk HW
to
0N to be removed
and
a switched live
connected
to lennrnai
-']^.
Page
2I
Page 22
c. Functiooal
flow wiring
Pump 0verrun Therm6t
diagram
l
with
Apollo programmer.
HW
oN
5s
Hr
Thermoslal
Cl6k
Thermostal
Lo
KEJ.-
a->-J
SWay Swrlch
CH OFF
N0TE:
Link
HW-0tl
,"r1
I
Stiark
=
I
anre
Pump
I
is removed
when
L3
c(3)
eleclrode
sensor
any exlernal
PL
Pressure
Swttch
controls
ML
I rlrl
lj'l
1_I{]]l
hoard
are
fitted
L1
MN
L2
PN
FN
N
.+l
>al
c0r.0uR
bk
b
blue
-
bk
black
-
br
brown
g
green
-
gy
orey
-
o
orange g/l
pk
pink
c00E
Pg
rr;
-D
\
-
p
-
v
r-red
w
Y
purple violet
white yellow green
Marns
and
N
yellow
Page
22
CF
C;;
r,',
SETECTOP
'
S//-'-
,
Page 23
22. FAULT
-= =
d>-
9:
c:--
i-:
--.
;i
tr--
-
-=
>-==
.=:-:
FTNDING GUIDE
=
I
!
ri
tE !-
it
--
t
ir
.E
|E =--* :l'
-
rI
-
ta
a;
It
:t
II
l!-
:it
!:t
I
it
=- - E
E1 = E
:e'
!!
-
+
E
E}
i-sF
i=1r
;
EE
t
6t
eE
E
E
Eo EE
.=-::
-=-=
-
^
::
--
-
-i
-
--
>-=
,:r ] I
-=
v
-:-
:-::::
a
=-:i
-=v
-v
,^ =
a"-=
--=-
d'o;
-=--
-:
(J!
c.r!
==
T=
L::
-
;:
-: > I
c
1>:
j.-x=
y!2.\
[:J-
e
:*
EE
-
-
r!
t! IE
rE
=*
TTE
a:
as!
EE
E6 :ii
e
v
!:i
:iE ;!I
=
.c9
ir
iE:
;5
Ege
:E
=--
IE
>.
-
t
-9
a t
I
€6
EE
E
.4T
:t;
errl
iII]
=El
!Ej
E
I
EF
a
;iE!g
EE
C2
E-
E
:=
-3
T
ii
l
!E!
4
E
-a
E
e
'a
-!
L9l l-l
lr
i'E
t
sEiEe
I
E
E: E;E
:a
EEcEEe
I
E
I
5
-*te
iiEis
E;9ET
iEi;,
E
,E
z
T
6
-E
=EE
f:i
iEE
!! a ;F-g
*
?-
--
!E
!t
!!
!l=;
:r
ar
E,
5rE
3
I
e I
t$
&
i
:;
t:
€l
E€
xi
€E
IE
6C
!
E
g;
.c
EI
5
!E
l
FE
l-
l:!
r;
I
a !
IIB
i
il tI
Page 23
Page 24
24.
SHORT
LIST
SPARE
PARTS
Ke1 No.
I l0 l3
2l 22 22 23 23 35 36 31
43
50 50 50 5l 5l 5l 52 53 55 56 6 72 76
ll5
r28 r29
o
52
GC
3327rr 377 000
323 342 323 323 323 323 344 395 880 382397 382373 384208 382
382
398
398329 323 386 532 381 377 M2 323 36r 386 359 31104,6 332 386 608
ee
ry
43
No.
405 343 406
422
423 316
468 702
756
2rl 12r
Description
Outer case Inspection Plastic door Combustion chamber Combustion chamber Combustion Combustion Combustion chamber Overheat
'Hi'thermostat 'Lo'thermostat
Pump overrun thermostat
Burner Burner - 40Si Burner Main injector, Main injector,Cat2S Main
Main injector washer Pilot burner Pilot injecor,56142A
Spark
Burner'O'ring Gas Gas
Ignition Fan
Air flow
l-ol
10
L-j
-
r=-1-
u
36
window
chamber chamber
cut-off device
-
30Si
-
50Si
Cat
injector,
electrode and
valve
valve'O'ring
assembly
Cat
PCB
pressure
76
'F]
,-l
L-l
-- Fr
assembly
insulation insulation insulation insulation insulation
16
size size
16
size
-
40Si
lead
switch
h{
dh
37
35
800 - 30Si
1000 1400
c
66
(sides) (front) (front) (rear) (rear)
-
40Si
-
50Si
V
@
-
30Si
-
40Si,
-
30Si
-
40Si,
w
13
72
@
129
50Si
50Si
o
o
il"rilH
115
Qty.
I I
2 2
1 I
I
I I I I
I I I I
I I I I
I I
I I I I
2
I I I
a8
q
53
Part No.
402A2r93 402A2476
402C3081
402Cr04 402C105 402Cr78 402Cr4r 402Cl8l
4025 1498
4025 l 14 4025 I l5 402S088
40252510
4025322r
402525
40253239
Q395A1003
45004108-005
402A2525
402S098
vR470081034
4m-mrc-7-32
40252240
l l
402S067 307S527
402Cs32
309S374 309S503
Page 25
Page 25
Eastern Avenue,
Telephone: 091
Team Valley
482
6699.
Myson
Trading Estato, Gateshead,
Heating
Tyne &
Telex: 53265 MYSEAS
Wear, NE11 0PG, England.
Telefax: 091
G.
482
6141.
m
v
BS5ZS8
SSSitEr
leafl€t ls
This bo disr€gard€d it Interests of
Allgoodssold are bo
obtain€d
acqrrat€
condnu€d lmproyernent.
on apdication.
at th€ date of
sp€cifications and/o( appoaran€s are chang€d
suq€cl toouroftlcial Conditions of Sal€, copyof
printing
butrylll be
supersed€d and should
JWCO990 D42
in
tr|€
which may
Loading...