boiler the Building Regulations, Building Standards Underuking Byelaws and IEE Detailed recommendations 8S5440:2:1989
Note:
Gas
in
accordance
and
4. The In A plug-in with A A A not casc
of
that
DELIYERY
unit
addition a
external control systems
all
from
lit Vertex flue
pump
and by-pass
rcquire adjusung and
extension
REQUIREMENTS
must be installed in accordance
Wiring Regulations.
in the following British
stated
are
B55449:1:1977
and
(Installation
Safety
with
the above
safety to
is
delivered
965 mm
progr:rmmer
tie
ensure
in
inside kit kit
is available
kit is
which increases
that
packagcs (
two
(38
in)
kit is
also available to
is
available
available allows the
.
and Use)
regulations.
'Jre
law
I
fiuc
extcnsion
shown
which
which
allows the boiler !o
which
combined cold
the
boiler
with:
Regulations 198^l:
Failure
is
comnlied
cased
the
)
is avarlable.
fit inside
in
system
the
enables
posiitions
heieht
The Gas (Scotland)
to
to 861
Safety
Regulations, Local Building
Standards:
It is
install
applnnces
wit}t.
boiler and
the boiler casing. This
wiring
the
the
feed
(2)
Under no circumstances should more
diagrams supplied
flue/terminal
connecrcd to
be
pump
in
a
vent
and
mm.
(lnstallation
85689l :1988, B56798: 1987,
law
the
conectly could lead
fludterminal
the
assembly to
readily
to be connected directly to the
and Use)
gas
that all
programmer
vertical
a
accessible
Regulations 1984
Regulauons,
appliances
prosecution.
to
assembly type A, B,
simplifies
with
the boiler.
fitted
be
flue
from inside
system.
position,
includes
and the current
Model
855!16:1990, BS5440:l:1990,
installed
are
than
boiler.
by competent
It is in
C, D or E as
two
extension
wiring
and
the building.
in
a
built
The kit includes
local Water
and
your
own
required.
kits
is
suiuble
by-pass
which
issue
of:
persons,
interest,
be used.
for
use
does
an outer
5. The natural Apollo30Si: The in Thc
6. ELECTRICITY SUPPLY210V - 50FIz and Fuse least All wiring
The In Earth
7. The If level with as stated Apollo If the and the door
SUPPLY
GAS
gas
requirements
l.l m3/h(37 ft3lh) Apollo40Si: l.4m3lh(51ft3/h)
meter
house.
thc
complete
shuttered socket outlet
the
0.75
appliance
evenl. of an
the
Continuity, Short
AIR
room in
the boiler
and one at
the
30 Si: 99 cm2
boiler
supply
and
installation
via
fused
a
supply
mm2
external to
SUPPLY
which
is installed in
same room
below. The frec
is insulled in
for
A. The minimum requirement
at
3
(24
x
0.2
must
be earthed.
electrical
the
low
level,
or
movemenL
air
pipes
must
must be
double
(both
mm)
the
boiler
fault
Circuit,
boiler
a cupboard or
either dircct
must
be on
area of each
(
15
inz)
cupboard or compartment
a
follows:
are as
be capable of delivering
gas
for
tested
pole
switch
complying
(code
designation HO5
shall
comply
inslallation
after
Polanty
is insnlled
compartment,
to
same
the
vent
Apollo 40
anC
soundness and
with
contact separation of
a
with
the
with
of
ResisLancc
not
docs
the outside air or to a roorn. Both high level
rcquire
wall
to outside air. Both the high level
may
be
133
Si:
quantity
this
purged
requircments
power
for the
VV-F
or HO5
latest IEE Wiring
the
the
appliance,
Eanh.
to
purpose provided
a
permanent
halved
cm2
with
air
ventilation
if
the
(20
inz) Apollo
a door, allow
gas
of
described in 85689l.
as
least 3 mm in
at
BSl363)
of
supply
cable
VVH2-F)
Regulations,
preliminary
vents
are
at
Apollo50Si: 1.8
in
addition
adjacent
is
it
that
specified in table 16
as
and any local
elecnical systems checks must
vent.
air
required in
and
and low
provided
is
50
Si: I 65 cm2
least
100 mm
mt/h(62ft3/h)
the
to
demand
poles
both
to the
should
0re cupboard or compartrncnt,
low level
directly from
clearance between
or
boiler.
PVC
a
be
regulations
air
level vent
(25
in2)
from
any other
preferably
sheathed
856500:1984.
of
vents
must
must each have a free
outside.
the
appliances
fused
a
be carried out i.e.
front
3
flexible
which
apply.
one at high
communicate
of the
pin plug
cord at
area
boiler
FLUESYSTEM
E. Five
telescopic The flue Sizp A:
B: 17l
Siire Sizr C:
Siz.c D: 362 - 652 mm Sze Unless The following RearflueA=C+83 mm(3%in) Where A = required flue If Note: The maximum
274 - 478 mm
E: 582 - lW2 mm
otherwise
greater
A is
Poge 4
flue/terminal
lengths
123
are:
-
175 mm
-275mm(GA -
specified
method
than
-
(43A
7
lUAin)
-
(|Glr
l8% in)
-
(l4t/e
251/t in)
-
(23
the C
should be
length, B
1092
mm
allowable
asscmblies
n)
43
in)
size used
(43
flue length is3022
available and a fixed length,
are
flue/terminal will
to
determine the
=
inside wall
in) one or two
be
required
flue
Side
to
extension
A
side
of boiler and C
(119
mm
965 mm
supplied
=
kits
in).
with
the boiler.
flue/terminal assembly.
B +
C+ 127
may be
mm
=
finished
used.
(5
(38
in)
wall
in),
extension
thickness.
kil
Page 5
BOILER
9. The boiler The
boiler
The
boiler
25 mm
than 25 mm If
rhe boiler
for
Gas Gas or The boiler Regulations and, of the troiler Wherea room-sealed appliance mains Where give
detailed
A
cupboard cupboard compartment The
boiler for installation any adjacent The
boiler allows the The minimum acceptable
LOCATIONis not suitable musr be
is
suitable
(l
in)
to
(l
in)
annular
is to be
Installation
from Myson
may
be
in
Scotland,
in a room
electricity
the
should be so situated
installation
guidance
or compartment
or compargnent
design
requires
must
be
passage
free
for external
mounted on a
for installation to a
combustible
Further
space. installed in a timber in Timber
Framed Housing"
Heating.
installed
in
any
the electrical
containing
is installed in a room containing abath
boiler
of the
on this aspecl
used to
may
including
airing
only the clearances
kitchen units or
installed so that the
of air across
spacings
table:
installation.
flat wall which
combustible
material.
A metal sleeve should bc
guidance
framed building
room, although
provisions
or shower.
a bath
it
that
cannot be touched
will
in an unusual
be
enclose the boiler
be used
provided
cupboard
stated
fitments may have to be
flue
terminal
it
at all ttmes.
from
terminal to obstructions, corners
the
is
sufficiently
wall e.g.
given
is
reference
particular
of the
in BS5440:l:1990, sub-clauses 3.3 and
it
robust
woo<l
be fitted
should
DM2. If in
attention
Building
by a
position,
must
be designed
it is modified for the
that
installations are
given
in the technical data,
is
exposed to
take the
to
cladding,
installed
provided
surround the airlt'lue tube
to
in accordance with the British Gas
advicc
doubt
is drawn to thc
Standards
applicable
or shower, any person
special
using
procedures
and constructed
purpose.
in 856798 and
page
3, after
installation. If it is felt
removed.
the external air.
ventilation
and
weight of the boiler.
that the airlflue tube
assembly
assembly to
is not closer
provide
4.2.5.
-
"Cuide
British
of
IEE Wiring
installation
the
must
be sought
rcquirements
in
Scotland
publication
from
the
local
of the current
with respect
region
to
electrical switch or appliance control, utilising
the bath or shower.
may be
B55546
necessary
specifically
Details
of essential
and should be complied
for
It is important that the
openings are
856798
and
pupose.
this
features
extra space
that
position
specificd
855546
and
An existing
of cupboard/
with.
is required
of the terminal
in
following
the
a
Termlnal Directly Below Below eaves Above adjacent From vertical soil From inlernal or From a surlace From Vertically
Horizontally Adjac€nt From
*
If
rhe rerminal
shield of ar **
If
the terminal
a suitable
A
type
r555.
35
guard
The
IMPORTANT
I().
The Apollo is to be used
l.
{Jnly
2.
posltlon
below an openable
gutters,
soil
or a balcony
ground
pipes
external corn€rs
lacino the lerminal
a lerminal
lacing the terminal
lrom a terminal
trom a lerminal on
to an op€ning
an opening
in a car
is fitted
least 750
mm
is fiaed
terminal
protective
Kl
guard
must be securely
INSTALLATION
pumps producing
head
high
30 Si,910litreJh
pump
3. Connect
the
4. Mains electricity It is important that the
5. For open
6.
vented
schematics.
7. A and
system
by-pass
return
pipes adjust as described Tbe
8.
9.
system wiring
When
commissioning,
air vent or any other
pipes75 mm
level
pipes
pipes
or balcony
or drain
window,
or drain
on the same
lhe same wall
window
pod
i.e. door
within
(30 less must
guard
850
in) in length
than
be
is availble
fitted to the
(34
mm
(6.6
2 m
provided
from Tower Flue
wall
NOTES
only on
fully
at
(33
gaVmin)
in the
and the
polarity
systems is
essential.
least 1.5 m
and at
in
the commissioning
for
pipe
flow
pump
must
of the
a combined
The by-pass should
away
must be completed
the system
must be
ventilation opening
wall
or window into the
plastic
in)
of a
should be
ft)
and
fitted to the underside of
a balcony, above
above
fitted.
and centrally
pumped
least
Apollo 40
the
as shovrn
systems,
3.35 in
m
house
painted gutter/pipe
or
Components
located over the
with
and
(ll
f0 head
1146litresih
Sior
water
the
system schematics.
ground
Ltd. at:
flue
an
flow rate
at a
(4.2
450 mm
or
gutter/pipe
the
or
above a
Vale Rise, Tonbridge, Kent TN9 1TB, Tcl: 0732
terminal.
indirect
cylinder.
of 690
gaVmin)
always be connected to the boiler to allow the
mains
supply
or close coupled
from
the boiler. Install
is
correct and that the boiler
feed
be of 15 mm
vent must
and
pipe
and
the by-pass as shown
be connected as sho*r
must
be
instructions.
in
accordance
vented
with
and the
the diagrams supplied
pump
running
before the main
Minimum spacing
300 mm
(12
(3
mm
(8
(12
(3
(1
(24
200 mm
300
75 mm
25 mm
600 mm 1200 mm 1500 mm
300 mm
150
(12
mm
1200 mm
(18
in)
of
painted
or
flat roof
Refer
litres/h
for
is
as short
with
which
to
to the
(25
Apollo 50 Si
the
pump
overrun to
adequately earthed.
possible
as
in
water
the
the boiler.
burner
in)
rn)
in;in)in)
in)
in)
(48
in)
(60
in)
in)
(6
in)
(48
in)
painted
an aluminium
eaves,
surface.
people
havc
manufacturers
gaVmin)
for
must
function.
in
water system
the
across the
system schematics
is lit.
then
access
instrucLions.
Apollo
the
be used.
22 mm flow
and
Page
5
Page 6
10. The
system must
heating.
11.
Where
12. In
areas with hard
instructions for
13.
The inner
the
Apollo
casc
of
flushed
be
replaces
an older
twice;
initially
boiler in
cold with
an existing
or aggressive wet€r we recommend
details of
the boiler
use.
should not
be removed
the
system,
that
during
pump
removed make
Fernox CP3
installation.
and all
valves
open,
and then
sure the cylinder is indirect.
inhibitor
should be
used. See commissioning
after the
first
T1. BOILER DIMENSIONS Refer Overall
Clearances
See Water connections
12.
a. Fully The
Some water b. Length
The these
F,g.
to
1.
cased dimensions:Height: Width: Depth:
7ll mm340 300
required for Top:Bottom:
Front
Sides:
section 9
connections:
50
90 mm300 mm
mm
5
for installation
Compression
to accept 22mm
WATER
SYSTEM
pumped
open vented
combined cold feed
authorities
wet
of
and
distance
pipes
between the
should be as
mmmm
servicin
mm
SCHEMATICS
vent
and
require
vents for
dry
cold feed
close to
AND POSITION
g:
clearances.
fittings
copper tubing
are
to BS287l.
system with
must
rise
from
a stop cock
and
the boiler
close
vent
as
in the
coupled
connection
practicable.
WATER
OF
supplied
combined
the boiler.
feed,
cold
cold
to
for flow
feed
cold
in
which
-
feed
the
system must
AND GAS
CONNECTIONS
and return
-
vent
and
case a separate vent
Fig.
see
3.not
s€e
be
22 nn Relurn.
Fig.2.
more
.
145
must
than
zJo
-
be
connected as
150
mm. The
22 mm
-^ Flow
Fig.I
-bE-
shown.
point
of connection
of
The
by-pass
pipe
each
side between it Always The
ensure that
flow
through 910 litres/h Ensure that
Fit
one
more
or
OptronalZoneValves
Optrona
.3
va
Fig.2
the
valve
pump
balancing
the boiler must not
(3.3
gaVmin)
pump
the
is
draining taps
pos
See 8S5449
clause
t
on
ve
should
and the
for
boiler.
has
sufficient
Apollo
the
accessible
(BS2879)
I
Alternative arrangement
i
cold feed is
I
l
24
be
of a type that is non-adjustable
static head.
be
allowed
40
Si or l146 litres/h
for
servicing.
to enable
vent
It
valved
Check the
fall
ao
below 690 litreVh
Isolating
the
valves
water
(4.2
system
A - length
-
length
B
-
150
C
by the householder
pump
manufacturers
(2.5
ga[min)
gaVmin)
must
to be
for
positioned
be
fully
drained.
the Apollo
of dry venlol water filled
mD
min
minimum
for
as close ro
vent
HEATII{G
Bu,n
5C 40
3C 00020 000
.0
Fig.
3
and musr have
head.
the Apouo
50 Si
while
pump
rhe
30 rhe burner
T
2CDmm
I
LOAD
000
000
000
least 1.5
ar
Si,
possible.
as
VENT
(mm)
A
4n3(nz&
140
50
m
is
alight
LENGTH
(mm)
330
mmnono
of 22 mm
Page
6
Page 7
13. SEALED SYSTEM
Refer a. b.
c. d. A diaphragm
Frg. 4.
to The installation must A safety between creating A
must of Hot Water"
valve
set to operat€ at 3 bar
the
ahazard
pressure gauge
be chosen tro
valve
safety
to occupants or cause damage !o electrical components and
covering at
type
expansion
suit
connection. Further
published
Sizing table:
REQUTREMENTS
comply
with
and the boiler.
least
vessel,
volume
the
requirements
the
(45
lbf/in2)
The
range 0 m 4
the
to BS48
water in
of
shall be
valve
14,
the system and the
details can be obtained from
British
by
Gas and
BS7074:1.
of
should
bar
shall
be
"Material
856798
fitted in
(0
and
the
positioned
be
lbf6nz;
!o
60
connected
charge
and
BS5449:1.
pipe
flow
on
a discharge
shall be
point
a
at
pressure
Installation
Maximum
close !o the
water
boiler.
pipe fitted
wiring.
fitted
in
the system.
in the return
must
pipe
not be less
Specification
temperature
There must
prcvent
[o
to
close
than the
the
static
for Domestic
is
82oC t
not
be
any
boiler.
head
Central
3oC.
valves
any
discharge
The vessel
point
at the
Heating
and
NiEogen
Air or
Pre-pressurisation
Expansion vessel volume
=
A
The hot water
e. f. Water lost
volume
System
from the
system on the
provided
g.
The mains
system may be filled from the mains
pre-pressurisation
by
pressure, provided perrnanent part i) iD iii)
valve
a stop a test cock.
anti-vacuum valve
an
iv) a non-return valve
h. Fill
the system until
Refer
to
the
commissioning Examine for leaks the required
value.
prsssure
cfiarge
pressure (bar)
(lifes)
(litres)
cylinder shall
either be the
system shall be
return
side
of the cylinder or
that
of fre system and
complying
to tle
of a typ€ approved by the Narional
of an approved
pressure gauge
the
instructions, light
then turn off
The
by-pass
at ieast 1
between it and
ExoansronVessel
(bar)
indirect
replaced
the syste.
of
via
procedure
this
fitted
in the order stated:
requiremenLs
type.
registers 1.5
boiler. Drain the
the
balancing valve
5rn of
22mm
the boiler.
0.51.0
None
A x 0.07Ax0.120A x
coil type
from
a make-up
radiators.
Lemporary hose
a
is
Where
accepuble
BSl0l0:2.
of
(22lbflinz).
bar
boiler and
the
system
must have
pipe
each side
Pressure Gauge
1.0
cylinder fitted
or a
vessel
non-return valve,
and
access to a make-up
connection
to
the
Water
from
local water
Council.
a draw-off tap
Examine for
allow the
while it is
l5mm
Balancrng
valve
-
systern
hot. Refill,
still
with
authority. The following
OptionalZoneValve
None1.5
0.088
immersion
an
A x 0.160
calorifier.
mounted higher
vessel
would
be difficult,
supplied
leaks
reach
to
and
ils
vent
and adjust
whcre
rectify
maximum working
than the top
make-up
from
a service
pipe
fittings should form
neccssary.
temperature.
the
cold
pressure
fill
the
of
can be
under
to
a
Fig.4
Optronal3-positionvalve
Page 7
Page 8
INSTALLATION
14.
14.1 Unpack the boiler
Note:
Do
not
stand the
PROCEDUR.E
-
Fig.5.
see
boiler on
its
end as
valve.
Do not
bottom
off the
case
discard the
cover
fixing
from
found.
pulling
the boiler.
the the
l. Carefully unpack
items
the
are
2. Carefully slide off Remove the outer case by slackening the
3.
firmly
and
4. Keep the outer case, bottom cover and place
IF REAR TO
SECTION
PROCEED
14.2 Prepare the
L Decide upon the
template supplied
not
so as
to damage them
EXIT FLUE IS TO
l42.IFSIDEEXITFLT.IE
TO
SECTION
(rear
wall
position
with
flue).
of the
the boiler.
before fitting.
BE
USED
14A.
boiler
The
using the
overall
clearances.
you
2. When Make sure
3.
4. Mark Remove
5. Reposition the template on the
6.
7. Make a the Remove
8. way
have
decided on the
that the
position
the
the template
note
of the
fl ue/terminal
the template and
(studs
up
at the bottom). Secrrre the
position
the hole for the flue.
of
finished wall
assembly.
(do
position
of the flue terminal
not
discard
i0
wall, mark,
thickness,
position
wall mounting
the
it will damage
packing
boiler.
the
the
until
botlom fixing screw
pins.
panels
infrll
in
a safe
CONTINUE ON
IS TO BEUSED
wall mounting
size
of the template
of the boiler
tape
will meet
cut the I 15 mm
and
drill and
this
plug
the
is
very important
plate
mounting
plate
o
gas
all
t!
plate
mountrng
is
size
the
the
template
the requirements
in) diameter hole in the wall for
@th
hve fixing holes
and
cenrally over the hole
the wall with
of the boiler
to the wall, ensuring it is level
given
to accept
is required for
four
21h" lg. No.12 woodscrews
No 8 x
cover
Flnd these
parls
in the
pack.
Fis.5
plus
minimum
the
and the correct
in
section
9.flue/terminal
the
215" lg. No.12 woodscrews.
section
in
the wall,
14.5 when ensuring
adjusting
it is level and
T??TTT??
12 19
scraaa
8 off
6@
nuts
M6
2 off
side, top and bottom
way
up.
assembly.
the length of
right
the
(not
supplied).
14.3
Secure the boiler
Note: The
L Lift
inner
boiler into
the
the boiler
2.
the
Secure woodscrew
case
wall
to the
bottom
(not
does not
position
of the
supplied)
wall
to the
need
and
mounting
boiler
via
plugged.
Remove
3. not to damage
4.
Connect the unions
Refit the flue diverter facing to the rear.
5.
14.4 Unpack the
Carefully packing
until all the
14.5 Adjust
(rear
flue).
l.
Using
flue/terminal
the
mm
83 terminal flange !o the
1
Note:
2. Drill through mm drill No.8 x l0lg. Note: When to damage the
3. Seal
the
terminal
flue
the
the
system
(see
water system
diverter
from the
gasket
flow
and
return
schematics, section
flue/terminal assembly - see
unpack
the
the measurement
(3V
Ensure
and
flue/terminal
the
items
length of
found.
are
flue/terminal
the
noted in
the
of
in
holes,
that
OUTER air the
assembly so
+ finished wall
in)
end
the
that
the
seams
three
pilot
secure the two nrbes ogether using the three
supplied with the flue/terminal
screws
drilling through the outer air tube
inner flue
centre
joint
with the tape
tube
with
assembly.
(rear
flue).
to be removed during
locate
plate
with
wall wildl.
to the
the hole
top of
pipes
the
holes
two
M6 nuts
two
a2th"
previously
the boiler
to the top
compression
l2).
Fig.6.
assembly.
Do
not
assembly
section
thickness,
14.2
it
is:
from
tube as
air tubes are
outer
in Fig. 7, with a 2.8
shown
adjust the
the
shown
assembly.
take
care
drill.
the
supplied
with
the
installatron
in the top
supplied
lg. No.l2
drilled and
care
taking
Fig.
see
length
of the
the
of
discard
-
back
in Fig.
inline.
not
flue/
of the chassis over
with
the boiler.
Clamping
ring 2
gggg
M4 ' 16 19
7
F+
screws
I roll
oi sealing
o
'O'ring
Seal
this
wtth
tape
supplied
Finished
wall thickness
fte studs
off
4
tape
Flue./lerminal
Flnd there
loint
Keeo seams
on the
off
parts
wall
llll
AAAg
x
1"
No. 8 screws 4 of{
ass€mbl!
in lhe
Fig.6
notes
Prlot
In lrne
*
83
mounting
lg
sra nress
pack.
t3 off)
(3%
mm
---
plate.
Outer
Outer seaftng
AAJ
No
lO lg
8'
3 of{
in)
Secure
plate
wall
plate
screws
Page I
Fig. 7
Page 9
14.6
Fit
the
Note:
If the
need
not be used.
1. Fit
2. Fit
the outer
the section.From
3.
outside
wall. Ensure
4. Push into
the
the
tube slides
into
slides
that the
Check Push fully home
flue/terminal
wall
is to be
plate
wall
'O'
ring in
position
the building
that the
flue/terminal
flue
diverter
INTO
the
the
diverter.
'O'
ring
until
ess€mbly - s€e Fig. t
good
made
over
up o
flue/terminal
the
over the
the
outer
insert the flue/terminal
slots in
the
end
of the terminal are
assembly lowards the boiler
on
top of the
inner
is
on the boiler'side of the flared section.
the flared
boiler,
of the
tube
end of the ouler
(rear
flue).
terminal,
the
assembly.
air tube
against
assembly into the
and
ensuring that the
diverter and the outer
tube
outer wall
the flared
vertical.
engage
the tube
inner flue
air
in
is
contact with
plate
tube
the
flue
diverter.
Fig.
t
14.7
Connect
l. Fit
that the the flared
2.
Secure the clamping the Tighten
3.
4. Proceed
14.E
Prepare the wall - see Fig. 10
l.
Decide upon with minimum side,
the two
flat
the flue
halves
part
to the boiler - see Fig.
of the
side is
against the
of the air
ring
threaded
holes in
the screws to seal
lo section 14.14.
position
the
the boiler. The overall
top and the longest flue/terminal the
2. Tape way
3.
Continue the
4.
Tape in
5. Make sure that
in Mark
6.
of the white
side
wall
the
mounting
up.
line,
the red
wall.
side
side flue template,
the
Lhe corner and that
posirion
the
section
9.
positions
the
of the
case to the OUTSIDE
clamping
wall mounting
tube.
flue diverter
to the
the clamping
flue
the
(side
of the boiler
size
bottom
clearances.
assembly and
template to the
on
the template,
supplied
the line
just
drawn
of the
four wall
ring
ring).
assembly.
of
flue
mounring
(rear
9
over the air
flue).
tube
plate,
using the
flue).
the wall mounting
using
the template is
Note
that
965 mm
two
wall is 2895
of the
wall,
ensuring it
horizontally
with
the boiler,
lines
up
across
with
terminal n ill meet
plate
fixing screw.
7. Drillandplugthefivefixingholes!oaccept2th" position
8.
Cut
of the hole in the
ll5
the
mm
(4rh
wall for
side
in)
diameter hole in
the
lg. No.l2
flue/terminal
the side
assembly.
9. Make a the
side
important
10.
Remove the
botrom).
at the
note of the white case
and are
finished
of tle
required in
templates
Secure
and
the mounting
wall thickness
shown on
as
section
place
the wall mounting
plate
and the
distance
the template. These
14.10 when
adjusting the
plate
!o
the wall with four 21h" lg. No.l2 woodscre*
as shown in Fig.
recessed
the
and
four M4
screws
template
of
size
the
(38
the boiler
maximum
in) flue
extensions) from
distance
mm
is level the
and the correct
wall until
to the side wall so
red
the
line
on
tie requiremcns
fixing scre
*s
and the lo*er
*mdscre*s.
asse mbly.
wall for
rhe
from
the side
measurements
length
position
in
Ensure
9.
side against
supplied
(use
supplied
plus
the
(using
(114
in).
itreaches
it is
that
the template.
given
\{ark
r}r
flueAcrmrnal
*all
to
ver)'
are
of
flue/termrnal
tlre
on tlre wall
ensuring rr rs le
,!?'
asse
(
nor
s
Fig.9
'.u.r'r€
Fig. I0
mbly.
vel
and the
supplied).
right way
up
(studs
14.9
Secure the boiler to the
Note:
I . Lift
2.
inner
The
the boiler into
the
boiler to
the bouom
Secure
case does
the
plugged.
3. Remove the flue
4.
Connect
5. Refit
6.
Unpack
the
system
flue
the
diverter
the flue/terminal
wall
not
need
position
and
wall mounting
the
of
boiler to
flow
facing
from
return
and
left or right as determined
diverter
assembly as described in
(side
flue).
be removed
to
locate
the wo
plate
with
wall
the
top
the
of the boiler
pipes
during insnllation.
holes
in
the top
nvo M6 nuts
with
lg. No.12 woodscrew
a2l5"
taking care
to the
top compression
section
of fte chassis over the
supplied with the
not
to damage
unions
by the flue
direction.
14.4.
boiler.
(not
(se€
water
studs on the
supplied)
gaskcr-
the
i'ia
system schematics,
wall
mounting
rlre hole
plate.
previously
drilled
section l2).
Page
Secure
and
9
Page 10
14.10 Adjust the length
l.
Using
length of the
127 mm
the end
to Where A between Note:
2. Drill
2.8 No.8 x l0lg. Note: to damage ihe
3. Seal the cenre
m@surements noted in
the
flue/terminal assembly so
(5
in) + A + B,
the
of
OUTER
is
finished wall
the
the side wall and the side of the
Ensure that the seams
through the three
mm
drill and
secure the
screws sup'plied
When drilling through the outer air tube take care not
inner
joint
flue/terminal
the
of
from
the back
air tube as shown
thickness and
in the
pilot
holes,
tubes
two
with
flue tube
with
with
the tape
assembly - see
that
14.8, it is:
adjust the
section
of the terminal flange
in
Fig. I l.
B is
the distance
white
case.
outer air tubes are
in Fig. I l, with
shown
together using the three
fluelterminal
the
assernbly.
the drill.
supplied
with
the flue/terminal
inline.
Fig. 11
a
(side
flue).
Seal thrs;ointwrlh supplied
+--
Finished
assembly.
tape
Keep
seams
wall thickness
Fig.11
Pilor
,
rn lrne
+8+
holes
127 mm
(3
off)
(5
tn)
l4.ll Flue
The flue
be
to A maximum
extension - see
extension
extended by 965
of two flue
l. If the flue
extension to assembly. Ensure
terminal
fis INSIDE
the outer aL
kit
allows the standard
mm
extension
extension kit
the
swaged end
thatthe
the
tube fits
OVER the air tube of
Fig. 12 (38
is
(side
in).
may be used,
used, connect the
of
the sondard
innerflue
inner flue
tubeof
tube of the extension and
Push fully home.Note:
Ensure that the seams
2. Drill three equally
spaced
in
the outer
holes
using a and the extension tube sleeve. Serure the two Note:
When drilling through the outer air tube take care
Seal the
3.
4.
Adjust the OVERALL
Fit
14.12
Note:
plate
l. Fit
2. Fit
the flue/terminal
If
the
need not
the outer
'O'
the
with the tape
lrints
wall
is to be made
be us€d.
wall
ring in
length
pssembly -
plate
over the
position
supplied
as described
good
up to the
flue/terminal
over
the outer air tube
section.
From
3.
4.
outside the building
wall. Ensure
that
the slos
Push the flue/terminal assembly towards the
into
tube flue tube tube slides Push
the flue slides INTO
into
the
fully home
diverter
until the
insert
in
on top of the
inner
the
diverter.
flared
the
the end of the terminal
tube
Check that the
end of the
flue).
flue/terminal
if required.
plain
flue/terminal
the standafiflue/
the extension.
air tubes
mm
2.8
drill
&bes
with
s€€
flue extension.
the
in
section
13
(side
Fig.
terminal, tlre outer
assembly.
flue/terminal
boiler and engage the
ensuring
boiler,
of the
diverter
'O'
ring is on the
outer tube
assembly
end of
the
inline.
are
position
in the
together using
not
to
14.10.
Secure and
flue).
against
assembly
the flared
vertical.
are
that the
into
inner
and the outer
is in
contact
this
Seal with
shown
the three
damage
loint
tape supplied..
Extension Keeps
seams
Fig.
in Fig. 12,
through
No.8 x l0lg. screws
inner
the
seal
the
flue
joins.
tube
in line
12
with
wall
the
air
boiler side of the flared section.
with
the flue
diverter.
Standard assemblv
both the standard
flueltermrnal
fluelterminal
supplied with the flue extension.
tlre drill.
14.13
Connect
the
flue
to
the
boiler - see
Fig. 14
(side
flue).
l. FitthetwohalvesoftheclampingringovertheairtubeasshowninFig.14.Ensure
that the flared
2.
Secure the clamping
flat
part
the threaded Tighten
3.
4. Make
Page
the screws
good
I0
is
facing
side
of the air tube.
ring
in
holes
the
the clamping ring).
to
seal
gap
on
the
away
the flue
to
the flue inside
from the
boiler, and the
diverter using the
assembly.
wall
around the
recessed
four M4
flue
tube.
is
side
against the
screws supplied
(use
Fig.14
Page 11
Fit the outer sealing
14.14 l. Make
good
the outside Note: The outer sealing terminal.
2. Place
the outer sealing fixing holes.Remove the
3.
sealing
plate woodscrews.Note: The terminal
should
terminal.
4. Remove any covering terminal terminal
and secure to the
assembly).
-
plate
wall
plate
plate
and drill and
be
Fig. 15.
see
around the
flue duct
need not be used
over
covered
terminal and
the
plug
the
before drilling
from the terminal.
with four I " lg. No.8 screws
wall
if
wall
the
mark the
fixing holes,
prevent
lo
Position
the
is
good
made
position
of
up
the
to
four
suitable for I " lg. No.8
entering the
debris
plate
with
over
the
the
flue/
sealing
(supplied
the
14.15
Connect Connect a 15 Do not
14.16
Connect Note: A
mm
turn the
permanent
l. Remove the
2.
Slacken two screws wires,
brown to
3. Keep
the wiring centre
cable clamp, power
supply cable.
When
Note:
out of
slips
pump
4. The
lead
wiring centre, and
programmer
If
5.
a
Do
not switch
on the electricity
gas
the
the
supply
gas
supply to the
gas
supply on at
power
live
and
securing the
screw
in the cable clamp below the
L
and blue to N on
tighten
then
connecting
the
cable clamp
and any
connected
is not fitted,
-
see
F
supply
pump
the
in
the open
cable clamp screws.
the
power
the
the
external controls
16.
Fig.
service
this
cock.
stage.
I6
cabh - see
must
be connected to
front
of the
the
terminal
position,
supply cable, ensure that the
live
neutral wires become taut before the
and
wiring should be
to the terminal block. See
remove link HW
supply at
this
Fig. 17.
the
boiler.
wiring
centre and carefully
take
block and up
wiring
centre.
excess
Check that
Feed the
green
slack
the
and
in
the
wiring
length of
passed
through one or both of the
wiring
diagram
to ON and connect a switched
stage.
iL
lower
power
supply cable under the
yellow
to the earthing screw
power
supply cable between the terminal block and the
will open and
centre
earth wire is such,
the
earth wire.
page
20.live to
lr
Fis. I7
close
that
bushes,
terminal ON.
Fig. l5
clamp and
(
f
).
wiihout sraining
freely
po*,er
if
the
provided
at
the
connect
supply
cable
rear
of the
the
the
14.17 Remove l. With the
2.
Unscrew
remove the
If
3.
the
facia
Fit
14.18
1.
With the
2.
Connect
3. Close the
the inner case wiring the four
inner
programmer
panel
at this
programmer
the
wiring
programmer
the
wiring
14.19 Complete the l. Thoroughly
2. With the
flush the
pump
in readiness for commissioning.
centre open slide out
inner case
fixing
screws, two at the top,
case.
kit is
not
to be
fitted
stage.
kit.
lowered,
centre
centre
and
6-pin
secure
engage
plug
in
installation.
whole
system
fitted, fill, vent
and check
the facia
close the
panel
wiring
programmer
the
the
on
centre and secure
to the 6-pin socket on
position
witlr
with
water without
cold
for water
fixing
the
soundness,
of the connol box.
side
one
above the
fixing into
wiring
the
screw.
pump
the
rectifying
gas
in
the slot
centre,
posirion.
in
where
valve
and one
position
in
the conrol
push
fully home
Ensure
necessary.
to
with the
bor
all
left
the
fixing
push
and
until the
valves
*
of thc
inng
scre* . Do
fully
latch
engages.
are open.
centre, and
not
replace the
home.
Page
II
Page 12
15. COMMISSIONINGfor
See section
1. Test for
a. b. Remove the
c. Loosen the
2. Check the With the a. Set the b. Switch
c.
3. Check the a. b. Remove the two screws securing c. Disconnect and d. e.
f. g. h. Test
4. a. Apply a suitrble
b.
5. Check the After a.
b.
c. Set the boiler thermostat switch
d.
Note: The
the Replace
6. Replace
7. Replace a.
b. Ensure that the c. If
16
gas
soundness
With the boiler service cock closed
pipework
inlet
gas
in
accordance
ignition
gas
supply
programme
on the electricity supply and set
fan
will start
the ignition
ignition
the
the boiler thermostat switch
Set
pilot
Ensure that
Set the Checkthatthepilotflame(35to40mmlong)envelopstheelecrodeandextendsl0mmpastit.Adjustifnecessary(clockwiseto reduce the flame). Test the Set Replace the
of the Set the A connections
Set the connect Set the Turn the adjusting screw Note: The
thermostat suitable Check the correct boiler
If of the control box.
sufficiently to If
boiler
pilot
the boiler thermostat switch
main
the
gas
valve
boiler
or
second
main
main
the
boiler thermostat switch to O.
pressure gauge.
a
boiler
boiler
switch to
leak
that
the
pilot
thermostat requires heaL
boiler
gas
the
gas
the
inner
the
programmer
a
programmer
a
programmer
a
controls.
boiler
purge
and
connection
securing the
screw
pressure
inlet
with 85689l. Retighten the test
sequence
isolated
switch
purge
after a
and
will
sparks sparks
flame and
the boiler
thermostat
supply connections
pilot burner
thermostat
so after
for
burner
burner
thermostat switch
detecting
arrow on fte data
burner
valve
valve
inner
form
also
will
continue
test
thermostat
isolate
one
switch to
Note: The
shield
and
supply leak detecting fluid manifold.
switch
pilot
the
gas
soundness.
setting
has
been
clockwise to decrease the
is factory
HIGH
fluid. Set the
rating.
is
tumed
cover
cover,
case
is fiued
is fitted replrce is
open
case seal
a seal.
not
fitted
the supply
(the
cock
boiler
o the
gas
test
check
CONT, if a
to
period
heard. The
be
the
of the
pilot to
secure
gas
for
to HIGH. The
is lit
pressure
alight
to HIGH and if necessary the maximum
set to
to
light
to
off every time the
ensuring that the
the wiring
is intact
open rhe
service cock
valve
point
screw one nrrn.
the ignition sequence as follows:
the boiler
of about
until either the electricity supply to
O to terminate the
pilot
supply for
switch is
pilot
the
(black
leads
HIGH. The
throttle is factory set
gas
at
the
O and
with
two soundnessto the
the main
for l0 minutes:
Remove
O, disconnect the
main burner
the
boiler
plate
(positioned
centre, disconnect the
around
and reconnect
wiring
is
cover and
point
programmer
l0
ignition
set !o O.
shield
or
unit
valve
reconnect
screws.
main
burner
unit
gas
solenoid
input See Technical
thermostat swirch
cable
the
cenEe,
when
closed
for soundness
lift off
Ensure
screw and test
is
fitted and
thermostat switch
seconds a click
sparks
continue
ignition
gas
soundness
lift
and
white)
and
the burner setting
main
clamp is located correctly in
boiler chassis
the
off the
from
go
will
pilot
main
tlte
manifold
go
will
will
seuing
pressure gauge
test for
and
on the front
burner is off. The ignition
programmer
replrce
the operating slot
in
accordance
cover.
the
gas
the
the
through
fully
assembly
gas
through open
adjust
pressure.
!o O
the
supply
gas
for
check
!o HIGH.
will be heard
until the
is switched off
sequence.
shield.
gas
main
the ignition
open.
for
solenoid
joint
the chassis
at
the
automatic ignition sequence
and
gas
of
programmer
and
main
tlre
pressure
the
burner sening
Data,
and soundness around the
to
turn the boiler off.
the inner
replace
replace
then
panel
facia
is
vertical),
with 85689l.
is
on and open the boiler service cock to
soundness.
that all system controls are calling
The
automatic
indicating
pilot
is lit.
or the
solenoid on the
sequence but only the
gas
soundness
lead.
and
burner will light. Test
point
test
pressure
page
3, for the boiler ratings and
replace
qrse
the
pressure
the
at the bottom
sequence is
the cover, and secure
plug
and socket
inner
the wiring centre.
replace
then
pressure
ignition sequence
that the
gas
As
the
boiler
gas
using a suitable leak detecting
gas
the
screw
on the to
test
pressure
s€cure
case,
the
test
gas
start thermoslat switch
valve
give
right hand
automatically
and
winng
solenoid
supply is not
valve.
pilot
and chassis
and the
the
burner
gas
valve manifold
the heat
point
screw. Set the
point
test
with
slide
tle
with
four
centre.
gas
the
supply and
heat
for will
start.
has
opened,
yet
turned
is
set to O.
will light-
connections
pilot
will light.
and manifold
input
required.
pressures.
setting
screw
using
corner)
is
against
activated when
its
screw.
programmer
screws. Tighten
purge
fluid.
boiler
The
on
and
a
out
Page
12
Page 13
t.
Final
When
a.
hot When
b.
boilers
water
system
the system
in order
inhibitor is
an
and
check and addition of
has
been tested,
complete
to
the flushing
added to the
should be used
this is required. The system should be drained and quantity