OPERATION AND MAINTENANCE MANUAL FOR CALMOUNT® AND MULTICAL® BRAND CAPACITORS
Calmount® and Multical® Brand Capacitor Series Indication Lights
AMBER LIGHT (A)
The amber light on the KIM series will illuminate in either of the following circumstances:
Blown fuse – middle phase (L2)
Loss of capacitance in a capacitor cell detected by CelTel® brand indicator
RED LIGHTS (R)
A red light will illuminate when a fuse blows. Each red fuse light is wired in parallel to its fuse. The left-most light (L1) will illuminate if
the left fuse blows and the right-most light (L3) will illuminate if the right fuse blows.
SITUATIONS WHEN FUSE MAY BLOW
In general, overcurrent is the cause for any fuse failure. The amount and duration of the overcurrent may determine which of the
following is the actual cause:
Shorted Cell
Capacitor cells normally fail open; however, it may be possible for a cell to short. Use capacitance meter to check.
Starter or contactor bad contact pickup
If a set of contacts bounces, the capacitor starts to charge, allowing it to receive a new voltage before it is completely
discharged. This may cause a spike that can overload the fast-acting fuse.
Jogging motors
The capacitor could be charged to peak of the sine wave and then receive a new charge. This may cause a spike and overload
the fuse. In this case, the fuse should be removed from the capacitor when checking a machine or checking motor rotation.
Adjustable Speed drive (ASD) in system
Any ASD, whether VFD or DC drive, will generate harmonic currents that the capacitor will attract in addition to the normal 60
Hz current. This additional current can then overload the fuse to the point of failure.
Other capacitors
Adding new capacitors to a system that already has capacitors or adding a large unit to a system might put the system
resonance point at or near a harmonic frequency. In this case, even a small harmonic current can excite very high circulating
currents that can overload either the capacitor or switchgear fuse.
Welding
Excessive welding in a facility may cause many voltage spikes and ringing transients that are at many different frequencies
above 60 Hz. The spikes typically are short-lived but can accumulate with multiple welders. These higher-frequency currents
and spikes are attracted by the capacitor and cause the fuse to overload.
Induction heating and other nonlinear loads
Harmonics are generated with induction heating and by rectifiers in a plating process or large UPS systems. Here again, the
additional harmonic currents are attracted by the capacitor and may overload the fuse.
Fuse lights come on when energized
Consult factory.
MAINTENANCE ON CAPACITORS MUST BE DONE BY QUALIFIED PERSONNEL
Field evaluation of capacitors is called for on a routine maintenance basis. There are no moving parts to wear out; however, on rare
occasions failures do occur. If the application is severe due to high voltages, harmonics, switching surges or vibration, a more frequent
check is warranted. This is to ensure that the capacitor equipment is operating properly. Capacitor cells are of low losses; they operate
barely warm. If the capacitor cell case is cold, check for blown fuses, open switches, or other losses of power. Bulging cases or puffed-up
covers are a good indication of capacitor cell failure. Before simply replacing a fuse on the capacitor, check for bulging c ases or puffed-
up covers. These are often signs of failed capacitor cells.
If the top is not distorted, test each capacitor cell from terminal to terminal with a capacitance meter. If the capacitor c ell’s pressure-
actuating device has opened, no microfarad reading will be present. This means that the capacitor cell is opened and should be
replaced. If a capacitance meter is not available, use a clamp-on amp meter. Re-fuse where necessary and then energize the capacitor.
A clamp-on meter will indicate if the capacitor cell’s currents are balanced in each phase and drawing the correct amperage per phase. If
this is not the case, then the capacitor cell might have to be replaced. To determine how much amperage is correct for your capacitor
cell, see the ratings below.
Standard Ratings
240 VAC, 3 Phase, 60 Hertz = 2.41 amps per kVAr per phase
480 VAC, 3 Phase, 60 Hertz = 1.20 amps per kVAr per phase
600 VAC, 3 Phase, 60 Hertz = 0.96 amps per kVAr per phase
All Available Ratings
Example: 10 kVAr at 480V, 3 Phase, 60 Hertz
10 kVAr x 1.2 = 12 amps per phase