Myron L CTCIITD User Manual

CTCII
Water Quality Instrumentation
Accuracy • Reliability • Simplicity
CONDUCTIVITY/TDS
Chemical Treatment Controller
(Cooling Tower Controller)
Operation
Manual
14 JANUARY 05
INSTALLATION • OPERATION • MAINTENANCE
Monitor/controller: CTCIID, & CTCIITD
ACCURACY • RELIABILITY • SIMPLICITY
ELECTRONIC CALIBRATION (CIRCUIT ONLY) -
CTCII MAIN CIRCUIT BOARD
Figure V.A.1
115/230 VAC SELECT SWITCH
100mA Slow Blow (T.10A) 115 & 230 VAC (V~)
Wickman Fuse 5 Amp (#3741500041 or equiv) 115 VAC(V~)
SCALE SELECT
ELECTRONIC CALIBRATION
MAIN CALIBRATION CONTROL
DISPLAY CALIBRATION CONTROL (FACTORY SET)
OPTIONAL LIMIT TIMER CONTROL MODULE
OPTIONAL 4-20 mA OUTPUT MODULE
DIS
CAL
TDS COND
EC
CTCII
DISPLAY
TRANSFORMER
Yel
CAP CAP
C4AM
LTM
HYST
Flow Switch Jumper ­Remove if flow switch installed.
SWITCH
FUSE
RELAY RELAY
BLEED FEED
FEED PUMP
BLEED VALVE
POWER
FLOW SWITCH
SENSOR 0-10VDC
FS BK WTRD GN NU R- R+PWR C GDPWR C GDPWR C GD
SET POINT HYSTERESIS RIGHT INC LEFT DEC
a. Set Point Control Calibration
1. Ensure power is OFF.
2. Using a standard slot screwdriver remove the four (4) screws on the clear cover and remove cover.
3. The front panel is held in place with hook & loop strips on each side. By carefully lifting at the slot on the top, the front panel will pull toward you. Do not pull more than about 8 inches/20CM.
DO NOT pull on control knob(s).
4. Rotate the front panel down so that the back side is facing you. The Circuit Board is mounted to the back of the front panel.
5. Turn power ON.
Caution: When handling CB, DO NOT touch component side.
Electrical shock may occur.
6. Press and hold the EC switch.
7. Rotate Set Point control from “0” toward EC. At EC the relay should click, and the LED should change from RED to GREEN. If not, set Set Point control to EC and adjust the CALibration control. Models with 3 1/2 digit LCD. The display should indicate 2.50. If not, adjust the DISplay calibration control.
8. Turn power OFF.
9. Re-install front panel and cover as described in
USING STANDARD SOLUTIONS - Section V.B.2.
The BEST method of verifying and recalibrating your CTCII
“REASSEMBLY”.
10. To operate, turn power ON.
b. 0-10VDC Recorder Output Calibration
Chemical Treatment Controller is with NIST traceable Standard Solution (available from the Myron L Company). Because it includes the sensor, the entire system is calibrated.
See section V.B.1.
See Section V.B.1.
The following procedure describes the easiest method for standard solution calibration. We recommended using Myron L 442-3000 Standard Solution or equivalent. This standard solution will calibrate either Conductivity µS (at 3900 µS) or TDS ppm (at 3000 ppm).
1. Rinse thoroughly, and ll a clean glass beaker with standard solution.
2. Place sensor in beaker of standard solution. The level of standard solution must be high enough to cover at least 1/2” above the electrodes.
3. Slowly shake the sensor to remove air bubbles from the electrodes.
4. Allow 5-10 minutes for temperature to equilibrate. For the quickest and the best results, both the sensor and solution should be at the same temperature.
5. Turn power ON.
6. Rotated the Set Point control to 3900 for Conductivity models or 3000 for TDS models. The relay should click and the LED will change from GREEN to RED. If the set point is different, adjust CALibration control on the main circuit board until the reading matches the solution. Models with display (standard 3 1/2 digit). The display should match the value of the standard solution, 3900 µS (displayed as 3.90) or 3000 ppm (displayed as 3.00). If the reading is different, adjust DISplay calibration control on the main circuit board until the reading matches the solution.
7. After adjustment, turn power OFF.
8. Re-install front panel and cover as described below in “REASSEMBLY”.
9. To operate, turn power ON.
TRANSFER STANDARD METHOD - See Section V.B.3.
CTCII
CHEMICAL TREATMENT CONTROLLER
(COOLING TOWER CONTROLLER)
QUICK REFERENCE GUIDE!
If you read nothing else in this manual please read this Quick Reference Guide.
PLEASE READ and COMPREHEND ALL WARNINGS, CAUTIONS and ADVISEMENTS CONTAINED WITHIN THIS MANUAL.
Failure to comply is beyond the responsibility of the Myron L Company.
WARNING: ALL CONTROLLERS ARE FACTORY SET TO OPERATE ON 115 VAC. BEFORE APPLYING POWER ENSURE THE INPUT POWER “115/230 VAC” SELECTION IS CORRECT FOR YOUR REQUIREMENTS. FAILURE TO DO SO IS BEYOND THE RESPONSIBILITY OF THE MYRON L COMPANY. See section II.D.1. and gure II.E.1.
WARNING: ENSURE POWER IS OFF WHILE INSTALLING ELECTRICAL EQUIPMENT. IF MONITOR/CONTROLLER IS INSTALLED, ENSURE THE POWER IS OFF BEFORE SERVICING. FAILURE TO DO SO COULD CAUSE DAMAGE TO THE INSTRUMENT, AND COULD BE HARMFUL OR FATAL TO PERSONNEL. ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR SERVICE ELECTRICAL EQUIPMENT.
CAUTIONS: Before installation, ensure you have the correct model (with options), AND it is scaled for your application. See sections I.A. & I.B. Do you have the correct sensor? See section I.E. Mounting requirements. What is needed? See section II.B.
The following will give the installer and user a quick overview. See the sections listed for details.
REMOVING FRONT PANEL
1. Using a Phillips Head screwdriver remove the four (4) screws on the clear cover.
2. Remove clear cover.
3. The front panel is held in place with hook & loop strips on each side. By carefully lifting at the slot on the top, the front panel will pull toward you. Do not pull more than about 8 inches/20CM.
DO NOT pull on control knob(s).
4. Rotate the front panel down so that the back side is facing you. The Main Circuit Board is mounted to the back of the front panel.
REASSEMBLY
1. Carefully reinstall the front panel.
2. Reinstall the clear cover.
3. Reinstall the four (4) screws and tighten.
4. If desired, install corner covers.
5. To operate, turn power ON.
INTRODUCTION - Section I.
This section covers the specications of your new CTCII Chemical Treatment Controller including sensor information.
INSTALLATION - Section II.
This section covers how to install your new CTCII Chemical Treatment Controller; mechanically and electrically.
OPTIONS & ACCESSORIES - Section III.
This section covers the specications, installation, set up, and operation of each option.
OPERATING PROCEDURES - Section IV.
This section covers a brief description of different models and their features; how they work, and how to set them up for your particular use.
QUICK CHECK-OUT PROCEDURE -
See Section IV.B.1. It is assumed that the Controller power is ON, that it is connected to an appropriate sensor, and that the sensor is immersed in water within the range that the Controller will be required to operate, and the clear lid is removed from the Controller.
1. Rotate the large Set Point Control knob on the front panel through its entire range.
2. Verify that the set point indicator light changes from RED to GREEN and visa versa.
3. Verify that the relay clicks, and controls the bleed valve and/or chemical feed pump.
4. Adjust the set point control to the desired set point value.
5. Re-install clear cover.
HYSTERESIS (DEAD BAND) ADJUSTMENT -
See Section IV.B.3.
PRIMARY COMPONENT IDENTIFICATION -
Section V.A.
Review the gure on the following page to familiarize yourself with the Main circuit board assembly. The diagram shows the Limit Timer and the optional 4-20 mA Output module installed.
QUICK CALIBRATION - Section V.B.
WARNING: When performing calibration procedures, the technician must take extreme care to avoid contacting the circuitry other than the CALibration control. Failure to do so could result in damage to the equipment, property and/or personal injury.
60
80
100
120
0
1000
2000
3000
4000
5000
40
20
0
MICROSIEMENS / CM
CTCII
EC
MINUTES
CTCII Basic Model
1
60
80
100
120
0
1000
2000
3000
4000
5000
40
20
0
MICROSIEMENS / CM
CTCII
EC
MINUTES
CTCII w/ 3 1/2 Digit LCD
2
60
80
100
120
0
1000
2000
3000
4000
5000
40
20
0
MICROSIEMENS / CM
CTCII
EC
MINUTES
CTCII w/ Feed Pump Limit Timer
3
60
80
100
120
0
1000
2000
3000
4000
5000
40
20
0
MICROSIEMENS / CM
CTCII
EC
MINUTES
CTCII w/ 3 1/2 Digit LCD Feed Pump Limit Timer
4
TABLE OF CONTENTS
SECTION PAGE
CTC Series II ILLUSTRATIONS (CTCII, CTCIID, CTCIIT & CTCIITD)......................................................................1-4
I. INTRODUCTION .................................................................................................................................................................. 7
A. SCOPE................................................................................................................................................................... 7
1. Functional Descriptions ........................................................................................................................... 7
2. Applications.............................................................................................................................................. 7
B. SPECIFICATIONS.................................................................................................................................................. 7
C. OPTIONAL FEATURES..........................................................................................................................................8
D. ACCESSORIES...................................................................................................................................................... 8
E. SENSORS .............................................................................................................................................................. 9
1. Conductivity/TDS ..................................................................................................................................... 9
2. Sensor Specications ..............................................................................................................................9
F. ORDER INFORMATION......................................................................................................................................... 9
1. How to order a CTCII controller .............................................................................................................. 9
2. How to order Sensors .............................................................................................................................. 9
II. INSTALLATION ....................................................................................................................................................................10
A. GENERAL............................................................................................................................................................... 10
B. MECHANICAL INSTALLATION .............................................................................................................................. 10
1. Surface Mounting..................................................................................................................................... 10
C. SENSOR INSERTION / DIP MOUNT ASSEMBLIES ............................................................................................. 11
1. CSAR Insertion Mode Assembly.............................................................................................................. 11
2. CS51R Alternate Dip Sensor Assembly ................................................................................................... 11
D. ELECTRICAL INSTALLATION................................................................................................................................ 11
1. 115/230 VAC Conversion......................................................................................................................... 11
2. Connecting the Sensor Cable.................................................................................................................. 12
a. Modication for US Pharmaceutical 25 (No Temperature Compensation) ......................................... 12
3. Flow Switch.............................................................................................................................................. 12
E. 0-10 VDC OUTPUT ................................................................................................................................................ 13
1. Connection............................................................................................................................................... 13
2. Voltage Divider......................................................................................................................................... 13
F. RESCALE............................................................................................................................................................... 14
III. OPTIONS & ACCESSORIES INSTALLATION.................................................................................................................... 15
A. -LTM (LIMIT TIMER MODULE) ............................................................................................................................. 15
1. Description............................................................................................................................................... 15
2. Installation................................................................................................................................................ 15
a. Hysteresis.......................................................................................................................................................... 15
B. -C4A MODULE (4-20mA OPTION) ........................................................................................................................ 15
1. Description............................................................................................................................................... 15
2. Installation................................................................................................................................................ 16
3. Recalibration............................................................................................................................................ 17
IV. OPERATING PROCEDURES .............................................................................................................................................. 18
A. FRONT PANEL INDICATORS & CONTROLS ....................................................................................................... 18
1. Red LED Indicator ................................................................................................................................... 18
2. Green LED Indicator ................................................................................................................................ 18
3. Set Point Control...................................................................................................................................... 18
4. Digital Display Models.............................................................................................................................. 18
5. Limit Timer Models................................................................................................................................... 18
B. SETUP PROCEDURES......................................................................................................................................... 19
1. Check-Out Procedure .............................................................................................................................. 19
2. Set Point Adjustment ............................................................................................................................... 19
3. Hysteresis (Dead Band) Adjustment........................................................................................................ 19
4. Feed Pump Limit Timer............................................................................................................................ 19
V. COMPONENT IDENTIFICATION, CALIBRATION AND PREVENTIVE CARE...................................................................20
A. PRIMARY COMPONENT IDENTIFICATION ......................................................................................................... 20
B. CALIBRATION PROCEDURES - MAIN CIRCUIT BOARD.................................................................................... 21
1. Electronic Calibration (Circuit Only)......................................................................................................... 21
2. Calibration Using Standard Solution........................................................................................................ 21
3. Transfer Standard Method....................................................................................................................... 22
C. PREVENTIVE CARE.............................................................................................................................................. 22
5
TABLE OF CONTENTS Continued
SECTION PAGE
VI. OPTIONS & ACCESSORIES............................................................................................................................................... 23
A. OPTIONS ORDERED WITH CTCII....................................................................................................................... 23
B. OPTIONS & ACCESSORIES ORDERED SEPARATELY ......................................................................................23
C. STANDARD SOLUTIONS...................................................................................................................................... 24
VII. REPLACEMENT PARTS ..................................................................................................................................................... 25
VIII. WARRANTY......................................................................................................................................................................... 26
IX. GLOSSARY.......................................................................................................................................................................... 27
X. NOTES ................................................................................................................................................................................. 28
XI. ADDENDUM......................................................................................................................................................................... 29
A. CONDUCTIVITY, TDS AND TEMPERATURE RELATIONSHIPS.......................................................................... 29
6
I. INTRODUCTION
Thank you for selecting one of the Myron L Company’s latest Chemical Treatment Controllers. The CTCII is based on input from ‘you’ - our customers, time proven designs, and many years of instrumentation experience. Since 1957, the Myron L Company has been providing customers with quality products at an affordable price by designing and producing products that are Accurate, Reliable, and Simple to use. Quality you have come to rely and depend on. As you read through this operation manual you will see the CTCII is truly designed to be user friendly and simple to install. The CTCII is packaged as a complete set ready to install which includes the sensor, input power cord (115VAC) and two (2) output connectors (115VAC) in a fully waterproof enclosure.
A. SCOPE
This operation manual provides the user with the necessary information to install, operate and maintain your Myron L Company CTCII Chemical Treatment Controller. Section I. Provides Descriptions, Applications, Specications. Section II. Installation; mounting, wiring and set up. Section III. Options and Accessory installation procedures. Section IV. Operating procedures. Section V. Identies their primary components and provides the
user with easy-to-use calibration and preventive care
procedures. Section VI. Options & Accessories List. Section VII. Replacement Components. Section VIII. Warranty information. Section IX. Glossary, denitions. Section X. Notes. Section XI. Addendum.
1. FUNCTIONAL DESCRIPTIONS
All models feature a water proof & corrosion resistant IP65/NEMA 4X enclosure for bench or surface mounting. The CTCII is a compact 4.7” (120mm) x 6.3” (160mm).
Bright dual GREEN/RED LED indicates ON/OFF (above or below set point). All models feature TWO heavy-duty 10 amp output relays, operating on increasing concentrations.
All models include input power cord* (115 VAC powercord 8 ft. with USA 3 prong plug - NOT for use with 230 VAC), two (2) output power connectors, CSAR sensor, and appropriate strain reliefs.
LED. A 120 minute Limit Timer is provided to stop the feed pump from continuing to pump chemical(s) in to tower, tank or system. A bright YELLOW LED indicates when Limit Timer is on.
Model CTCIID Chemical Treatment Controller
0-5000 µS(µM) / ppm TDS 442™ Monitor/controller (value displayed as X.XX mS(mM) or ppt w/ standard LCD). Front panel is equipped with a “SET POINT” control, RED/GREEN indicator LED, and a 3 1/2 digit liquid crystal display (LCD)*.
Model CTCIITD Chemical Treatment Controller
0-5000 µS(µM) / ppm TDS 442™ Monitor/controller (value displayed as X.XX mS(mM) or ppt w/ standard LCD). Front panel is equipped with a “SET POINT” control, RED/GREEN indicator LED, and a 3 1/2 digit liquid crystal display (LCD)*. A 120 minute Limit Timer is provided to stop the feed pump from continuing to pump chemical(s) in to tower, tank or system. A bright YELLOW LED indicates when Limit Timer is on.
* A 35BL (3 1/2 digit) backlit, or a 45BL (4 1/2 digit) backlit display is available as an option for a full 0-5000 µS(µM) or ppm displayed value.
2. APPLICATIONS
Chemical Treatment Cooling Towers Process Control Wastewater Treatment Food Processing Plating Power Plants Laboratories Printing Boiler Agriculture/Aquaculture
Are just a few of the applications
B. SPECIFICATIONS
RANGE:
0-5000 µS(µM) or ppm TDS 442™ (user selectable)
DISPLAY:
Models CTCIID & CTCIITD:
1/2” (13mm) 3 1/2 digit LCD
Displayed value — 0-5.00 mS(mM) or ppt. NOTE: 3 1/2 digit LCD may be replaced with either a 3 1/2 or a 4 1/2 digit back lit LCD - available as options.
4 1/2 digit displayed value — 0-5000 µS(µM) or ppm.
The CS51R sensor for more demanding applications may be substituted at an additional cost.
For specic CTCII congurations, reference the following individual model descriptions.
*NOTE: for 230 VAC or other power requirements the plug must be cut off or removed and hard wired directly to the source or a local plug or adapter may be installed.
Model CTCII Chemical Treatment Controller
0-5000 µS(µM) / ppm TDS 442™ Controller. Front panel is equipped with a “SET POINT” control and RED/GREEN indicator LED.
Model CTCIIT Chemical Treatment Controller
0-5000 µS(µM) / ppm TDS 442™ Controller. Front panel is equipped with a “SET POINT” control and RED/GREEN indicator
ACCURACY
All Models: ± 2 % of Full Scale
SENSITIVITY
0.05% of span
STABILITY
0.05% of span
7
Loading...
+ 25 hidden pages