If you read nothing else in this
manual please read this
Quick Reference Guide.
PLEASE READ and COMPREHEND ALL
WARNINGS, CAUTIONS and ADVISEMENTS
CONTAINED WITHIN THIS MANUAL.
Failure to comply is beyond the responsibility of
the Myron L Company.
WARNING: ALL MONITOR/CONTROLLERS ARE
FACTORY SET TO OPERATE ON 115 VAC. BEFORE
APPLYING POWER ENSURE THE INPUT POWER
“115/230 VAC” SELECTION IS CORRECT FOR YOUR
REQUIREMENTS. FAILURE TO DO SO IS BEYOND
THE RESPONSIBILITY OF THE MYRON L COMPANY.
See section II.E.2. and figure II.E.1.
WARNING: ENSURE POWER IS OFF WHILE
INSTALLING ELECTRICAL EQUIPMENT. IF
MONITOR/ CONTROLLER IS INSTALLED, ENSURE
THE POWER IS OFF BEFORE SERVICING. FAILURE
TO DO SO COULD CAUSE DAMAGE TO THE
INSTRUMENT, AND COULD BE HARMFUL OR FATAL
TO PERSONNEL. ONLY QUALIFIED PERSONNEL
SHOULD INSTALL OR SERVICE ELECTRICAL
EQUIPMENT.
WARNING: THE DISPLAY WILL BE IRREPARABLY
DAMAGED IF THE DISPLAY HARNESS IS INSTALLED
UPSIDE-DOWN OR MISALIGNED. THE HARNESS
MUST BE INSTALLED AS SHOWN IN FIGURE II.E.5.
CAUTIONS:
Before installation, ensure you have the correct
model (with options), AND it is ranged for your
application. See sections I.A., I.B. & I.G.
Do you have the correct sensor? See section I.E.
Mounting requirements. What is needed? See
section II.B.
The following will give the installer and user a quick
overview. See the sections listed for details.
REMOVING FRONT PANEL
NOTE: When opening instrument, remove front cover with care;
a ribbon cable connects the front panel and main board.
1. Ensure power is OFF.
2. Remove the two (2) screws on the front panel.
3. Carefully wiggle the front panel and pull gently toward
you. Do not pull more than about 8 inches/20CM or you
could damage the wiring harness.
REASSEMBLY
1.Carefully reinstall the front panel, bottom first.
Ensure no wires have been pinched between enclosure
and front panel.
2.Reinstall the two (2) screws and tighten.
3.To operate, turn power ON.
INTRODUCTION - Section I.
This section covers the specifications of your new
AQUASWITCH including sensor information.
INSTALLATION - Section II.
This section covers how to install your new AQUASWITCH;
mechanically and electrically.
OPTIONS & ACCESSORIES - Section III.
This section covers the specifications, installation, set up, and
operation of each option.
QUICK LOCATOR
-4A/4AO MODULE (4-20mA), see section III.A.
-PA/PAO (Piezo Alarm), see section III.B.
-TP/TPO (Temperature Module, see section III.C.
RA (Remote Alarm), see section III.D.
OPERATING PROCEDURES - Section IV.
This section covers a brief description of the models and their
features; how they work, and how to set them up for your
particular use.
QUICK SET POINT CONVERSION (SPC) /
REVERSING SET POINT - See Section IV.B.1.
Resistivity AQUASWITCH II‘s are configured to trigger the
alarm relay as the resistivity reading decreases.
Conductivity/TDS AQUASWITCH II’s are configured to trigger
the alarm relay as the conductivity/TDS reading increases.
To reverse:
1. Locate the jumper block for the alarm to be configured.
See figure V.A.1.
2.Remove and rotate the jumpers 1/4 turn and reinstall
them on their posts.
QUICK CHECK-OUT PROCEDURE -
See Section IV.C.
It is assumed that the AQUASWITCH power is ON, that it is
connected to an appropriate Sensor, and that the Sensor is
immersed in water within the range that the AQUASWITCH II
will be required to control; and the front panel is removed.
1. Make a note of the reading on the display.
2. While pressing the Calibration/Full Scale Test Switch (FS
SW), verify that the front panel display is indicating a full
scale reading. If not, see Calibration, section V.C.
3. Press and hold the "SET POINT" switch on the front
panel. Using a tweaker or a small screwdriver, adjust the
Set Point trimmer adjustment screw on the circuit board
to sweep the display from zero to full scale. (A digital
display may be blank at the full scale end. This is
normal.) Listen for the alarm relay to click on and off as
the alarm set point moves past the water reading.
4. Adjust the alarm to the desired set point value. Release
the "SET POINT" switch.
Continued
QUICK SET POINT ADJUSTMENT -
See Section IV.B.2.
The set point setting is based upon the user's particular water
purity specifications or requirements.
1. While pressing the "SET POINT" switch, turn the Set
Point #1 adjustment screw (see figure V.A.1) until the
desired set point value is indicated on the display.
HYSTERESIS (DEAD BAND) ADJUSTMENT -
See Section IV.B.3.
ELECTRONIC CALIBRATION (CIRCUIT ONLY) -
See Section V.D.1.
Full Scale Calibration V.D.1.a.
1. Press and hold the Full Scale Test switch. The display
should indicate Full Scale for the particular range
selected, i.e. 0-20 MΩ should indicate 20. If not, set to
Full Scale with the CALibration control.
2. Turn power OFF.
3. Re-install front panel as described in “REASSEMBLY”.
4. To operate, turn power ON.
PRIMARY COMPONENT IDENTIFICATION -
Section V.A.
Review the figure below to familiarize yourself with the different
circuit boards and component locations. The diagram has the
second alarm/control module option installed.
“PURGE CYCLE” CALIBRATION PROCEDURE
Section V.B.
“ALARM RESET” MODE CHANGE PROCEDURE
Section V.C.
QUICK CALIBRATION - Section V.D.
WARNING: When performing calibration procedures,
the technician must take extreme care to avoid
contacting the circuitry other than the CALibration
control. Failure to do so could result in damage to
the equipment, property and/or personal injury.
The following assumes the front panel has been
removed and the power is ON.
AQUASWITCH II
AQUASWITCH II MAIN MONITOR/CONTROLLER BOARD
BK WT RD GN NU R- R+
RANGE
MODULE
3S
}
UP
-11
0-20mΩ
751 756
752 757
753 758
754 759
MYRON L
COMPANY
TRANSFORMER
115/
230
FUSE*
CALIBRATION
CONTROL
CAL
PWR C GD NC NO CM
HYS1SP1FS SW
SPC
INC
DIS
DEC
REMOVE TO
INSTALL
SECOND
RELAY
AQUASWITCH II DIGITAL DISPLAY
DISPLAY
DISPLAY CONNECTOR
DISPLAY
HARNESS
DISPLAY
HARNESS
CONNECTOR
DISPLAY
CALIBRATION
CONTROL
4-20
CONNECTOR
E
N
C
L
O
S
U
R
E
F
R
O
N
T
P
RED
A
N
TO MONITOR/
CONTROLLER
E
CIRCUIT BOARD
DISPLAY
CONNECTOR
LLOW
SET POINT
SWITCH
GREEN
10VDC Calibration - See Section V.D.1.b.
USING STANDARD SOLUTIONS - See Section V.D.2.
The BEST method of verifying and recalibrating your
conductivity/TDS AQUASWITCH II is with NIST traceable
Standard Solution (available from the Myron L Company).
Because it includes the sensor, the entire system is recalibrated.
NOTE: Since standard solution calibrations are NOT practicable
with resistivity models, another means of verification or
calibration of resistivity models is to use the transfer standard
method, using a hand-held or portable instrument capable of
resistivity measurements, such as the Myron L Ultrameter™. See
section V.C.4 for description.
Thank you for selecting one of the Myron L Company’s newest
AQUASWITCH Monitor/controllers. The new AQUASWITCH™
series is based on input from ‘you’ - our customers, time proven
designs, and many years of instrumentation experience.
Since 1957, the Myron L Company has been providing customers
with quality products at an affordable price by designing and
producing products that are Accurate, Reliable, Simple to use.
Quality you have come to rely and depend on.
As you read through this operation manual you will see the new
AQUASWITCH is truly designed to be user friendly with simple
to install options, and easy re-rangeability as conditions or
applications change. This manual is actually more complex than
the AQUASWITCH, but must be to address all the variables.
A. SCOPE
This operation manual provides the user with the necessary
information to install, operate and maintain the
Myron L Company's latest AQUASWITCH Resistivity &
Conductivity/TDS Controllers.
Section I. Descriptions, Applications, Specifications.
Section II. Installation; mounting, wiring and set up.
Section III. Options and Accessory installation procedures.
Section IV. Operating procedures.
Section V. Identifies their primary components and provides the
user with easy-to-use calibration and preventive care
procedures.
Section VI. Options & Accessories List.
Section VII. Replacement Components.
Section VIII. Warranty information.
Section IX. Glossary, definitions.
Section X. Notes.
Section XI. Addendum.
1. FUNCTIONAL DESCRIPTIONS
Both models have water & corrosion resistant IP64/NEMA 3
housings suitable for panel, bench or surface mounting.
The AQUASWITCH I is packaged within a compact 6.0" x 4.8"
(152mm x 122mm) housing. The AQUASWITCH II is packaged
within a 6.0" x 10.8" (152mm x 274mm) housing.
The AQUASWITCH I does not monitor water quality itself, but
should be used with any reliable resistivity or conductivity/TDS
controller such as the Myron L Company’s 750 Series II
Resistivity or Conductivity/TDS Monitor/controllers.
The AQUASWITCH II is an integrated unit requiring no other
Monitor/controller.
NOTE: All specifications for the AQUASWITCH I also apply to
AQUASWITCH II unless otherwise indicated. Bright green/red
LEDs indicate HIGH/LOW set point readings. All AQUASWITCHII’s feature a heavy-duty 10 amp output relay, operating on either
increasing or decreasing readings. May use the optional 4-20mA
output for PLC or SCADA operations.
2. APPLICATIONS
Conductivity/TDS
Reverse Osmosis
Process Control
Seawater Desalinization
Food Processing
Plating
Power Plants
Laboratories
Printing
Are just a few of the applications
Resistivity
Deionization (DI) and Distillation Ultrapure Water
Treatment Systems
Electronics
Pharmaceutical
Laboratories
Food Processing
Plating
Power Plants
Are just a few of the applications
B. SPECIFICATIONS
1. GENERAL ASI & ASII
INPUT POWER:
115/230 VAC ±15%, 50/60 Hz (User selectable)
overvoltage category II
100 mA Maximum Current
Double Insulated (with circuit board ground for OEM operation)
Fuse - 100mA Slow Blow (T.10A) for both 115 & 230 VAC (V~)
User replaceable
Humidity - 20-90% non-condensing
Max. Altitude -
40,000 ft/12,000 meters non-operating
10,000 ft/3000 meters operating
Pollution degree 2
24 VAC or 24 VDC Option available on Special Order
Overvoltage category II (24 VAC)
250 mA Maximum Current
Double Insulated (with circuit board ground for OEM operation)
Fuse - 250mA Slow Blow (T.25A) User replaceable
AQUASWITCHI:
Provides automatic switching from exhausted to fresh Dl banks;
push-button override for immediate bank change-over; adjustable
purge timer for “FAILSAFE” operation; front panel LED displays
provide continual status of both Dl banks; and an alarm is
automatically activated as each bank is depleted.
AQUASWITCH II:
AQUASWITCH II combines the operating features of the
AQUASWITCH I with the additional features of a
Monitor/controller. These include: a 3 1/2 digit Liquid Crystal
Display and a front panel accessible “SET POINT CHECK” switch.
(Set point setting is internal to discourage unauthorized
adjustments).
AMBIENT TEMPERATURE RANGE
32°F ( 0°C) to 131°F (55°C)
OUTPUT POWER:
24 VAC (Standard if ordered with Myron L valves)
115 VAC (Standard if ordered without Myron L valves)
230 VAC (Optional)
MAXIMUM LOAD PER VALVE OUTPUT:
200 milliamps;
(5 watts for a 24 V valve)
(25 watts for a 115 V valve)
(50 watts for a 230 V valve)
4
AMBIENT TEMPERATURE RANGE:
32°F (0°C) to 140°F (60°C)
HOUSING CONSTRUCTION
Fully gasketed heavy-duty ABS for splashproof and corrosion
-PC115 VAC Powercord (8 ft. with USA plug and strain
relief) - NOT for use with 230 VAC.
-24VA24 VAC isolated power supply (special order)
-24VD24 VDC isolated power supply (special order)
-PTSPanel mounted Full Scale Test Switch ((ASII special order)
D.ACCESSORIES (ordered separately)
4AO4-20 mA Isolated output
PAO70 db Piezo Electric Alarm ONLY (ASII)
35BLO 3 1/2 digit backlit LCD (ASII)
PCO115 VAC Powercord (8 ft. with USA plug and strain
0-10 VDC @ 5mA max. (linear); standard on all models
OUTPUT IMPEDANCE
100Ω ±5%
SENSOR INPUT
Resistivity — 1 CS10 sensor
Conductivity/TDS — 1 CS51LC sensor up to 0-10
1 CS51 sensor above 0-10
CONTROL FUNCTION
Models ASIIC & ASIIR:
Single set point alarm/control continuously adjustable
5
E. SENSORS
All sensors feature integral thermistor style temperature sensors
to ensure accurate, rapid and reliable automatic temperature
compensation.
1. CONDUCTIVITY/TDS
AQUASWITCHII Conductivity/TDS Monitor/controllers use the
CS51LC or CS51 Series sensor depending on range. The 1.0 cell
constant CS51 model is recommended for ranges of 0-10 through
100 µS/ppm. Its compact size allows mounting in a standard 3/4"
tee. The sturdy polypropylene bushing is modular for easy,
inexpensive replacement. Other models available by special
order.
CS51LC sensor has a cell constant of 0.1 and is used for
conductivity/TDS values of 0-1 to 0-5 µS/ppm.
2. RESISTIVITY
AQUASWITCHII Resistivity Monitor/controllers use the CS10
sensor. It has a cell constant of 0.05 and is used for ultra pure
water applications. Other models available by special order.
Special order High Temperature, High Pressure sensors; and Low
Cost, Low Temperature, Low Pressure sensors are available.
For detailed descriptions of these and other sensors, see Sensor
Selection Guide and specific sensor data sheets available from
your local distributor, the Myron L Company, or on line at
www.myronl.com.
3. SENSOR SPECIFICATIONS
STANDARD MODELS — 316 Stainless SteelCONSTANT
CS10:For ALL Resistivity ranges0.05
CS51 LC: For ranges 0-5 µS/ppm & below 0.1
CS51:For ranges between 0-10 & 0- 100 µS/ppm1.0
See Range Selection Guide, Page 8.
SPECIAL ORDER MODELS — 316 Stainless Steel
CS40Resistivity/Conductivity/TDS
Valve Insertable 100PSI@150°C
(1.0, 0.1 & 0.05)
CS40HTAbove High Temperature Model 250PSI@205°C
CS41Cond/TDS High Temperature Model 100PSI@150°C
CS41HTCond/TDS High Temperature Model 250PSI@205°C
CS50Conductivity/TDS 100PSI@95°C (1.0 & 0.1)
CSALow Cost Conductivity/TDS - NO Temperature
Compensation 75PSI@60°C (1.0)
CSATCLow Cost Conductivity/TDS - with Temperature
Compensation 75PSI@60°C (1.0)
4. SENSOR OPTIONS
-TTitanium - in place of Stainless Steel
-2525’ Shielded Cable
-100100’ Shielded Cable
-PV 1/2" PVDF fitting for CS10 & CS51 ONLY
{replaces polypropylene}
-HPSS 1/2" 316 STAINLESS STEEL fitting
for CS10 & CS51 ONLY (replaces
polypropylene).
-STFSanitec Fitting for CS10, CS51 & CS51LC. 1/2”
thru 4”. State size, i.e. STF-1/2.
Special Order Options
-WTVWet-Tap Valve for CS40 (0.1 & 1.0 only)
-JBJunction Box - Class I, Group D, Div. S,
Explosion proof, Weather proof, Aluminum. For
CS40 ONLY.
TEMPERATURE COMPENSATION
Automatic to 25°C, between 32-212°F (0-100°C)
except high temperature models - up to 205°C.
PRESSURE/TEMPERATURE LIMITS
CS10 & CS51 - 100 psi (689.6 kPa) at 212°F (100°C)
For higher limits, see specifications below.
*CS51LC conductivity sensor (0. 1 constant) required for these ranges.
Conductivity/TDS AQUASWITCH II Controllers require a sensor with a cell constant of 1.0. The Model CS51 is the
most commonly selected sensor due to its ease of use and low cost.
Resistivity AQUASWITCH II Controllers require a sensor with a cell constant of 0.05. The Model CS10 is the most
common selected due to its ease of use and low cost.
NOTE: UNLESS ppm/NaCl is specified with order, TDS/ppm type conductivity instruments will be calibrated to the
Myron L "442™" Natural Water standard. For NaCl ppm/ppt add the letter "N" after the number, i.e. -114N.
8
II.INSTALLATION
A.GENERAL
This section provides the recommended procedures for properly
installing the AQUASWITCH I Controller, or AQUASWITCHII Monitor/controller, Valve(s), and Sensor. Figure II.A.1 gives
an overview of the entire system. Alternate configurations on
page 39.
rotated or mounted upside down so that the cutouts are
on the opposite side.
4.AQUASWITCH II
For best results, position your Monitor/controller and
sensor as close as possible to the point(s) being
controlled. The AQUASWITCH II Resistivity &
Conductivity/TDS Monitor/controllers are not designed to
operate with a sensor cable length that exceeds 100' (30
meters).
AQUASWITCH II
SOURCE
WATER
MONITOR/CONTROLLER
MEGOHMS - CM
AQUASWITCH II
BANK A
DIDIDI
DIDIDI
BANK B
BANK A
PILOT VALVE
NC
NC
BANK B
PILOT VALVE
BLEED
PILOT VALVE
(NC)
WASTE WATER
750II
WASTE
WATER
AQUASWITCH I/II SYSTEMS DIAGRAM
(SEE PAGE 39 FOR ALTERNATIVE CONFIGURATIONS)
AQUASWITCH I
AQUASWITCH I
RESISTIVITY
SENSOR
PROCESS
WATER
OPTIONAL
PROCESS
PILOT VALVE
(NO)
VAC
ALARM
RELAY
Figure II.A.1.
CAUTION - READ FOLLOWING CAREFULLY
!
WARNING: THE MYRON L COMPANY RECOMMENDS
THAT ALL MOUNTING AND ELECTRICAL
INSTALLATIONS BE PERFORMED BY QUALIFIED
PERSONNEL ONLY. FAILURE TO DO SO COULD
CAUSE DAMAGE TO INSTRUMENT, AND COULD BE
HARMFUL OR FATAL TO PERSONNEL.
B.MECHANICAL INSTALLATION
All AQUASWITCH electronics are packaged inside
drip/weather-proof housings. The physical dimensions of the
housing is suitable for panel, bench or surface mounting.
There are four basic guidelines to consider when selecting a
mounting location:
1.Select a site that limits the AQUASWITCH‘s exposure
to excessive moisture and corrosive fumes.
2.If at all possible, mount the AQUASWITCH at eye level
for viewing convenience.
3.AQUASWITCH I
If needed, the AQUASWITCH I enclosure may be
1. SURFACE MOUNTING WITH SMP
NOTE: A Surface Mounting Plate (AQUASWITCH I - #SMP50)
or (AQUASWITCH II - #SMP60) may be required when access
to the back side of the mounting site is impractical or if the
AQUASWITCH must be mounted on a solid wall. Both SMP’s
come with the proper hardware to mount the AQUASWITCH to
the SMP, however, the installer must provide the four (4)
additional screws/bolts to mount the SMP to the wall or fixture.
Their type and size is to be determined by the user.
1. Select your mounting location. Mark and drill the four (4)
required mounting holes. For hole locations, use the SMP
as a template.
2. Drill the corner holes in the SMP according to the size of
the screws or bolts selected.
3. Attach and securely fasten the SMP to the Monitor using
the 1/4" X 20 X 3/8" screws provided.
4. Mount the SMP to the prepared site using the selected
screws or bolts.
2. SURFACE MOUNTING WITHOUT SMP
NOTE: Surface mounting will require two (2) 1/4 " X 20 screws of
a length equal to the thickness of the mounting site plus 3/8"
9
1. Select mounting site location. Mark and drill the required
mounting holes. For hole drilling locations, see figure
II.B.1.
2. Insert the 1/4" X 20 screws into the holes from the side
opposite the mounting site.
3. Hold the Monitor in place while starting and tightening the
mounting screws.
AQUASWITCH I
4.80
(122)
Face Plate Gasket
Panel Gasket
0.88 DIA
(22)
1.13 DIA
(29)
3. PANEL MOUNTING
A panel mounting fastening kit is provided with all
AQUASWITCH’s. Panel mounting will require the use of the
fastening kit's two (2) 4-40 mounting screws/nuts or two (2) #4 x
1/2" sheet metal screws. See figures II.B.1 & II.B.2. for panel
cutout dimensions.
1. Select your mounting location. Mark the appropriate
panel cutout and complete the necessary panel cut.
0.31 DIA, X2
(8)
0.53
(14)
0.13 RAD MAX, X4
(3)
3.96
(101)
6.00
(152)
AQUASWITCH I
6-32x3/8" x4
Face Plate Gasket
Panel Gasket
0.63 THK
3.89
(16)
(99)
AQUASWITCH II
10.81
(275)
0.50 DIA
(13)
0.5
(13)
Figure II.B.2
3.78
(96)
6.00
(152)
0.60 DIA
(15)
4.94
(126)
5.00
SURFACE
MOUNT
2.84
(72)
(127)
PANEL
CUTOUT
1.05
(27)
3.10
(79)
0.40
(10)
4.17
(106)
NOT TO SCALE
DIMENSIONS IN INCHES
(MILLIMETERS)
SURFACE AND PANEL MOUNTING DIAGRAMS
9.85
0.63 THK
(1.6)
5.00
(127)
0.50
(13)
0.75
(19)
5.00
(127)
3.75
(95)
3.77
(96)
0.31 DIA 2PL
(8)
SURFACE
MOUNT
(250)
0.113
(3)
2.54
(64)
0.11
(3)
2.00
(51)
AQUASWITCH II
0.50 DIA
(13)
9.85
(250)
Figure II.B.3
0.75
(19)
01.03 DIA 2 PL
(29)
0.68 DIA 2 PL
(22)
0.60 DIA
(15)
3.90
(99)
5.10
(129)
PANEL
CUTOUT
NOT TO SCALE
DIMENSIONS IN
INCHES
(MILLIMETERS)
DOUBLE INSULATED
SURFACE AND PANEL MOUNTING DIAGRAMS
9.92
(252)
10.19
(259)
0.12 RAD MAX 4PL
(3)
0.13 2PL
(3)
2.57
(65)
0.13
(3)
10
2. Carefully unfasten and separate the AQUASWITCH's
PILOT
VALVE
Figure II.D.2
!
front panel from its enclosure.
3. Disconnect all panel cable(s)/wires from the
AQUASWITCH's Control board.
4. Slide the enclosure through the panel cutout
until its flange contacts the panel.
5. Insert mounting screws through the flange
mounting holes and tightly secure.
6. Reconnect all panel cable(s)/wires and reinstall the front
panel.
C. SOLENOID VALVE INSTALLATION
There are many types of solenoid valves. The user must decide
which type is best suited for the specific application. The
following is an example installation of one type of valve,
1. Insert the pilot valve unit so that the systems’ INFLOW
source and OUTFLOW process piping connecting ends
are inserted into the valve as shown in figure II.C.1.
2. Repeat step until all appropriate pilot valve units have
been installed.
NOTE: The number of pilot valves used will be based upon the
user’s desired application.
24VAC
INTERCONNECTING
MANUAL OVERRIDE
ADJUSTABLE
FLOW CONTROL
OPERATES
NORMALLY
CLOSED
WIRES
OPERATES
NORMALLY
OPEN
SECURING NUT
FLANGE
CABLE
SS
WASHER
"T" FITTING
PLASTIC
WASHER
O-RING
THREADED FITTING
3/4" FNPT
OUT
IN
INSERTION MODE ASSEMBLY
Figure II.D.1.
2. IMMERSION OR DIP SENSOR ASSEMBLY
Use approved sealant, i.e. Teflon tape as required.
1. Verify that the Sensor’s Fitting assembly is properly
assembled as shown in figure II.D.2.
2. Insert and pull the Sensor’s cable through the extension
tube and then tightly attach extension tube to Sensor
assembly as shown in figure II.D.2.
PLASTIC
WASHER
O-RING
THREADED FITTING
3/4" FNPT
FLANGE
INFLOWOUTFLOW
OPTIONAL INFLOW
SOLENOID VALVE MOUNTING DIAGRAM
D.SENSOR INSERTION/IMMERSION MOUNTING
The SENSOR’s mounting orientation must provide a continuous
and adequate circulation flow to prevent the trapping of air
bubbles within the Sensor’s electrode area (CS10 shown in
figures II.D.1 & II.D.2). Failure to do so will result in conditions
that will prevent the Sensor from functioning properly.
1. INSERTION MODE (in-line installation)
Use approved sealant, i.e. Teflon tape as required.
1.Verify that the Sensor’s Fitting assembly is properly
assembled as shown in figure II.D.1.
2.Insert the Sensor Fitting assembly into the "T" fitting with
electrode aligned as shown in figure II.D.1. and tightly
SENSOR TIP
COUPLING
3/4" NPT
CABLE
EXTENSION TUBE
IMMERSION OR DIP SENSOR ASSEMBLY
E.ELECTRICAL INSTALLATION
The AQUASWITCH I and AQUASWITCH II require the user
to follow separate electrical installation procedures. In addition,
based on the user’s solenoid voltage specifications, the user will
be required to connect Solenoid Power.
NOTE: All cable watertight restraints are user supplied.
WARNING !
11
A device to disconnect the AQUASWITCH from the
power supply is required. It is recommended that
this switch or circuit breaker be labeled as the
disconnection device for the AQUASWITCH.
1. AQUASWITCH I MAIN INPUT POWER
WARNING: All AQUASWITCH I’s are factory set for
115 VAC. Before starting, ensure the input power
“115/230” selection is correct for your requirements.
Failure to do so is beyond the responsibility of the
Myron L Company. See section II.E.3. and figure
II.E.1 and II.E.2.
NOTE: Some models may have either a 24 VAC or a
24 VDC input power requirement - check labels
carefully.
1. Verify that the main AC power source is turned "OFF" or
disconnected.
2. Using a standard slot screwdriver remove the two (2)
screws on the front panel.
3. Carefully wiggle the front panel to loosen the gasket and
pull gently toward you. Do not pull more than about 8
inches/20CM or you could damage the wiring harness.
4. Turn the front panel around so that the back side is
facing you and set aside for now.
5. Using the enclosure cutouts, install the proper wire and
watertight cable restraint (not provided) to comply with
local electrical codes.
6. Neatly connect wires to the AQUASWITCH I's
connectors*, as shown in figures II.E.1.
*CAUTION: The input power connectors require only a small
screwdriver, or a pen to push on the release levers†. The release
levers may be broken or damaged if not pushed straight toward
the circuit board. DO NOT push the release levers sideways.
† Early versions have screw terminals.
AQUASWITCH™
INPUT FROM
CONTROLLER
RELAY
ALARM
RELAY
{
SOLENOID
VALVE
OUTPUT
POWER
POWER BOARD
LOGIC
BOARD
CONNECTION
TRANSFORMER
NCNOCOM
GRDCAC
{
BK B
BK A
BLD
NO
COM
NC
BANK B
BANK A
BLEED
COM
ASI ELECTRICAL CONNECTION DIAGRAM
115/230
JUMPERS
LINE / +DC
(BLK)
NEUTRAL / -DC
(WHT)
WHT
BLK
COM
LINE
NEUTRAL
OR
115/230
SWITCH
FUSE*
}
FUSE
1/8 Amp
AGC 1/8
MAIN
INPUT
POWER
}
SOLENOID
INPUT
POWER
Figure II.E.1
2. AQUASWITCH II MAIN INPUT POWER
WARNING: All AQUASWITCH II’s are factory set for
115 VAC. Before starting, ensure the input power
“115/230” selection is correct for your requirements.
Failure to do so is beyond the responsibility of the
Myron L Company. See section II.E.3. and figure
II.E.2.
MONITOR/CONTROLLER
MAIN CIRCUIT BOARD
MAIN
INPUT
POWER
FROM AS
POWER
BOARD
{
115/230
SWITCH
NEU-WHT
LINE-BLK
L N
FUSE
Figure II.E.2
(+)
(-)
NEU
GRN
RED
WHT
BLK
0-10VDC
}
OUTPUT
}
CONTROL
RELAY
AQUASWITCH™
*115/230VAC
FUSE
100mA
(T.10A) 5X20
Slow Blow/
Time Delay
*24VAC
FUSE
250mA
(T.25A) 5X20
SENSOR
ELECTRICAL CONNECTION DIAGRAM
Slow Blow/
Time Delay
GRN
ORN
WHT
ALARM
RELAY
AQUASWITCH II™
POWER BOARD
LOGIC
BOARD
CONNECTION
NO
COM
NC
{
{
BANK B
BANK A
BLEED
COM
SOLENOID
VALVE
OUTPUT
POWER
TRANSFORMER
NCNOCOM
BK B
BK A
GRDCAC
LINE / +DC
(BLK)
NEUTRAL / -DC
(WHT)
WHT
BLD
COM
115/230
JUMPERS
BLK
LINE
NEUTRAL
OR
115/230
SWITCH
FUSE*
}
SOLENOID
INPUT
}
POWER
FUSE
1/8 Amp
AGC 1/8
MAIN
INPUT
POWER
12
The following procedures are to be used to install the
AQUASWITCH II to 115 VAC main power source. For the
procedures to install the optional 230 VAC main power source, the
user must first complete the installation procedures in Section
II.E.3. Failure to do so could result in damage to equipment and/or
property.
NOTE: Both early and later models function exactly the same.
II.E.3.a. Early Model Power Boards with
Buss Wire JUMPERS
This requires extreme care as circuit board may be damaged if
improperly attempted.
1. Verify that the main power source is turned "OFF" or
disconnected.
2. Using a standard slot screwdriver remove the two (2)
screws on the front panel.
3. Carefully wiggle the front panel and pull gently toward
you. Do not pull more than about 8 inches/20CM or you
could damage the wiring harness.
4. Turn the front panel around so that the back side is
facing you and set aside for now.
5. Using the enclosure cutouts, install the proper wire and
watertight cable restraint (not provided) to comply with
local electrical codes.
6. Neatly connect wires to the AQUASWITCH II's
connectors*, as shown in figures II.E.2.
*CAUTION: The input power connectors require only a small
screwdriver, or a pen to push on the release levers†. The release
levers may be broken or damaged if not pushed straight toward
the circuit board. DO NOT push the release levers sideways.
† Early versions have screw terminals.
3. 115/230 VAC CONVERSION
Before turning power ON to the AQUASWITCH ensure the
proper input voltage has been selected. For the AQUASWITCHI, see figures II.E.1 & II.E.3. This is required in TWO locations on
the AQUASWITCH II, see figures II.E.2 & II.E.3. Failure to do
so will blow the fuse(s). It could, under some conditions, cause
injury and damage the instrument voiding the warranty.
On the early model AQUASWITCH Power Board the conversion
must be accomplished by desoldering and resoldering a buss wire
jumper as shown in figure II.E.3, (to desolder and resolder the
JUMPERS, the circuit board (CB) must be removed from the
enclosure), or may be accomplished as shown in figure II.E.4.
Later models have switches, see section II.E.3.b and figure
II.E.2.
1.Locate the jumpers below the transformer.
2.Cut jumpers in location as shown in figure II.E.4.
3.Carefully, bend leads toward each other (center) as
shown in figure II.E.4.
4.Solder the ends of the leads together.
Cut and carefully bend leads toward center
115 VAC
Solder ends together
230 VAC
JUMPERS LOCATED UNDER TRANSFORMER
EARLY MODEL POWER BOARD
115/230 VAC JUMPER CONVERSION
Figure II.E.4
II.E.3.b. Later Model Power Boards with SWITCH
1.Locate switch next to the fuse holder.
2.Using a screwdriver, turn switch to required voltage.
II.E.3.c. AQUASWITCH II Main Control Board
ALL AQUASWITCH II Main Control Boards have a switch. See
figure II.E.2.
115 VAC
230 VAC
JUMPERS LOCATED UNDER TRANSFORMER
EARLY MODEL POWER BOARD
115/230 VAC JUMPER CONVERSION
Figure II.E.3
1.Locate switch next to the fuse holder.
2.Using a screwdriver, turn switch to required voltage.
4. CONNECTING THE SENSOR CABLE
This section provides the procedure to properly wiring the sensor.
1.Place the SENSOR interface cable and user supplied
watertight cable restraint into the enclosure's
appropriate access hole.
2.Install the SENSOR cable wire to comply with local
electrical codes.
3.Follow the color code as marked. See figure II.E.2.
*CAUTION: The sensor connectors require only a small
screwdriver or a pen to push on the release levers. The release
levers may be broken or damaged if not pushed straight toward
the circuit board. DO NOT push the release levers sideways.
13
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.