MyMeters MM-SDM630-2C User Manual

MM-SDM630-2C
Multi-Channel DIN Rail Smart Energy Meter
DIN RAIL SMART METER FOR SINGLE AND THREE PHASE ELECTRICAL SYSTEMS
USER MANUAL V4.1
1. Introduction
This meter can be congured to work with a wide range
of CTs, giving the unit a wide range of operation. Built-in interfaces provide pulse and RS485 Modbus RTU outputs.
Conguration is password protected.
1.1 Unit Characteristics
The Unit can measure and display electronic information of multi-channels:
• L-N voltage and THD% (total harmonic distortion) of all phases
• Line Frequency
• Currents, Current demands and current THD% of all phases
• Power, maximum power demand and power factor
• Active energy imported and exported
• Reactive energy imported and exported
The unit has password-protected set-up screens for:
• Changing password
• Supply system selection 1phase2wire, 3phase 4wires
• CT Ratio (1 to9999 )
• PT ratio (1 to 9999)
• Demand Interval time
• Reset for demand measurements
• Pulse output duration
A pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer.
1.2 Current Transformer Primary Current
The unit can be congured to operate with CT ratio between
Primary Current and Secondary Current. The secondar y CT has two options: 1A / 5A
1.3 RS485 Serial - Modbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the Unit Set-up screens are provided for setting up the RS485 port.
1.4 Pulse Output
This provides 2 pulse outputs referring the energy consump-
tion of two circuits. Both pulse outputs are congurable.
The pulse width for active energy can be set from the Set-up menu.
2. Start Up Screens
The rst screen lights all
display segments and can be used as a display check.
The second screen
indicates the rmware
installed in the unit and its build number.
Next the unit performs a self-test and indicates if the test passes.
After a short delay, the screen will display active energy measurements.
3. Measurements
The MM-SDM630-2C measures all important electrical parameters, which is shown on the LCD display and approach­able via RS485. On the front panel there are four sensitive buttons and four LED indicators. The buttons operate as follows:
Selects the Voltage and Current display screens In Set-up Mode, this is the “Left” or “Back” button.
Select the Frequency and Power factor display screens In Set-up Mode, this is the “Up” button.
Select the Power display screens In Set-up Mode, this is the “Down” button.
Select the Energy display screens In Set-up mode, this is the “Enter” or “Right” button.
The default display after the meter is power on, the LCD show “C1” circuit information.The way to shift “C1” circuit information to “C2” circuit information is by pressing the “Down” button .
If the meter are showing “C2”, and the user want to shift it to be “C1” circuit, then he shall keep pressing the “UP” button .
(Circuit 1)
(Circuit 2)
3.1 Voltage and Current
Each successive pressing of the button selects a new range:
Phase to neutral voltages
Current on each phase
Phase to neutral voltage THD%
Current THD% for each phase
3.2 Frequency and Power Factor and Demand
Each successive pressing of the button selects a new range:
3.3 Power
Each successive pressing of the button selects a new range:
Frequency Power factor (total)
Power factor of each phase
Max. Power demand
Max. Current demand
Instantaneous active power (kW)
Instantaneous reactive power (kVAr)
Instantaneous Volt-amps (KVA)
Total kW, kVAr, kVA
Total active energy in kWh
C1-L1 kwh
C1-L2 kwh
Imported active energy in kWh
Exported active energy in kWh
Total reactive energy in kVAh
C1-L1 kVarh
C1-L2 kVarh
C1-L3 kVarh
Imported reactive energy in kVArh
Exported reactive energy in kVArh
4. Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before processing. If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
4.1 Set-up Menu Structure
Change password nnnn 4-digit number-default ‘1000’
CT Set the value of the CT ratio nnnn 4-digit number 0001~9999.v
PT set the value of PT Ratio nnnn 4-digit number 0001~9999.
DIT Demand Integration Time This is the period in minutes over which the current and power readings are integrated for maximum demand mea­surement. Options are: 5 , 10, 15, 30 and 60minutes.
4.2 Set-up Entry Methods
Some menu items, such as password and CT, require a four-digit number entry while others, such as supply system, require selection from a number of menu options.
4.2.1 Menu Option Selection
5) Having completed a parameter setting, press to return to a higher menu level. The SET indicator will be removed and you will be able to use the and buttons for further menu selection.
6) On completion of all setting-up, press repeatedly until the measurement screen is restored.
4.2.2 Number Entry Procedure
When Setting up the unit , some screens require the entering of a number. In par ticular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right.The procedure is as follows:
1)The current digit to be set ashes and is set using the
and buttons.
2) Press to conrm each digit setting. The SET
indicator appears after the last digit has been set.
3) After setting the last digit, press to exit the num­ber setting routine. The SET indicator will be removed.
4.3 Change Password
Use and to choose the change password option.
Press to enter the change password routine. The new password screen
will appear with the rst digit ashing.
Use and to set
the rst digit and press to conrm your
selection. The next digit
will ash.
Repeat the procedure for the remaining three digits
After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be removed.
4.4 DIT Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for maximum demand mea­surement.The options are: 5, 10,15 30,60 minutes.
From the set-up menu, use and buttons to select the dIT option. The screen will show the currently selected integra­tion time.
Press to enter the selection routine. The current time interval
will ash.
Use and buttons to select the time required.
Press to conrm
selection. SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.
4.5 CT
The CT option sets the current ratio (1~9999) and secondary current (CT2 1A/5A) of the current transformer (CT) that wires to the meter.
From the Set-up menu, use and buttons to select the CT option. The screen will show the current CT primary current value.
C1.CT2 -> Circuit 1
C2.CT2 -> Circuit 2
There are four LED indicators on the front panel , namely C1, C2, Pulse1 and Pulse2. The unit can measures and displays data of two three phase circuits: C1 circuit and C2 circuit. If C1 LED shows, that means the reading on the LCD are for C1 circuit. While C2 is there, it means the measurements on the LCD are for C2 circuit.
Each successive pressing of the button selects a new range:
3.4 Energy Measurements
C1-L3 kwh
1) Use the and buttons to select the required item from the menu shown in section 4.1. Selection does not roll over between bottom and top of list.
2) Press to conrm your selection
3) If an item ashes, then it can be adjusted by the and
buttons. If not, there maybe a further layer.
4) Having selected an option from the current layer, press
to conrm your selection. The SET indicator will
appear.
Secondary CT setting
Press to enter the CT secondary current selection routine. 5A/1A
Set CT Ratio Value
Press to enter the CT Ratio. The range is from 0001~9999.
Example: if set the ratio to be 100, that means the primary current is secondary current x100.
4.6 PT
The PT option sets the secondary voltage (PT2 100~500V) of the Voltage transformer (PT) that wires to the meter and the PT ratio between PT1 to PT2. The default value is 400V for Secondary PT (L-L), and the ratio between PT1 and PT2 is 1.
Secondary PT setting
The setting method is same as Primary voltage setting PT1. Max PT2 value is 500V
Set PT Ratio Value
Press to enter the PT Ratio. The range is from 0001~9999.
From the Set-up menu, use and buttons to select the PT option. The screen will show the voltage PT secondary voltage value.
Press to exit the system selection routine and return to the menu. SET will disappear and you will be returned to the main Set-up Menu.
4.7 Pulse Output
This option allows you to congure the pulse output. The
output can be set to provide 2 pulses, Pulse 1 is lock to C1, and Pulse 2 is lock to C2. The setting will be effective for both pulse outputs. Use this section to set up the pulse output (Units: kWh, kVarh)
From the Set-up menu, use and buttons to select the Pulse output option.
Press to enter the selection routine. The unit
symbol will ash.
Use and buttons to choose kWh or kVArh.
On completion of entry procedure, press to conrm
the setting and press to return to the main set up menu.
4.7.1 Pulse Rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per 0.01/0.1/1/10/100/1000kWh/KVArh.
(It shows 1 impulse = 10kWh/kVArh)
Press to enter the selection routine. The cur-
rent setting will ash. Use
and and buttons to choose pulse rate.
From the Set-up menu, use and buttons to select the Pulse Rate option.
On completion of the entry procedure, press to
conrm the setting and press to return to the main
set up menu.
4.7.2 Pulse Duration
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100 or 60ms.
(It shows pulse width of 200ms)
From the Set-up menu, use and buttons to select the Pulse width option.
Press to enter the se­lection routine. The current
setting will ash.
200/100/60ms
Use and buttons to choose pulse width.
On completion of the entry procedure, press to
conrm the setting and press to return to the main
set up menu.
4.8 Communication
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus RTU, parameters are selected from Front panel.
From the Set-up menu, use and buttons to select the Address ID.
Press to enter the selection routine. The current setting will be
ashing.
Use and buttons to choose Modbus Address (001 to 247).
On completion of the entry procedure, press button
to conrm the setting and press button to return to
the main set-up menu.
4.8.2 Baud Rate
From the Set-up menu, use and buttons to select the Baud rate option.
Press to enter the selection routine. The
current setting will ash.
Use and buttons to choose Baud rate 2.4k, 4.8k, 9.6k, 19.2k,
38.4k.
On completion of the entry procedure, press to
conrm the setting and press to return to the main
set-up menu.
4.8.3 Parity
From the Set-up menu, use and buttons to select the Parity option.
Press to enter the selection routine. The
current setting will ash.
Use and buttons to choose Parity (EVEN / ODD / NONE). Default is NONE.
On completion of the entry procedure, press to
conrm the setting and press to return to the main
set-up menu.
4.8.4 Stop Bits
From the Set-up menu, use and buttons to select the Stop Bit option.
Press to enter the selection routine. The
current setting will ash.
Use and buttons to choose Stop Bit (2 or 1).
On completion of the entry procedure, press to
conrm the setting and press to return to the main
set-up menu.
5. Specications
5.1 Measured Parameters
The unit can monitor and display the following parameters of a single phase, 3-phase 4-wire supply.
5.1.1 Voltage and Current
Phase to neutral voltages 100 to 289V a.c.
Voltages between phases 173 to 500V a.c.
Percentage total voltage harmonic distortion (THD%) for
each phase to N
Percentage voltage THD% between phases
Current on each phase – 1 to 9999A range, set by external
current transformer(s) (CTs)
Current THD% for each phase
5.1.2 Power Factor and Frequency and Max. Demand
Frequency in
Hz Instantaneous power
Power 0 to 3600 MW
Reactive Power 0 to 3600 MVAr
Volt-amps 0 to 3600 MVA
Maximum demanded power since last
Demand reset Power factor
Maximum neutral demand current, since the last Demand
reset
5.1.3 Energy Measurements
Imported active energy 0 to 9999999.9 kWh
Exported active energy 0 to 9999999.9 kWh
Imported reactive energy 0 to 9999999.9 kVArh
Exported reactive energy 0 to 9999999.9 kVArh
Total active energy 0 to 9999999.9 kWh
Total reactive energy 0 to 9999999.9 kVArh
5.2 Measured Inputs
Voltage inputs through 4-way xed connector with 2·5mm2
stranded wire capacity. Line frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2.5mm2 stranded wire capacity for connection of external CTs. Nominal rated input current 5A or 1A a.c. Rms.
5.3 Accuracy
Voltage 0.5% of range maximum Current 0.5% of nominal Frequency 0.2% of mid-frequency Power factor 1% of unity (0.01) Active power (W) ±1% of range maximum Reactive power (VAr) ±1% of range maximum Apparent power (VA) ±1% of range maximum Active energy (Wh) Class 1 IEC 62053-21 Reactive energy (VARh) ±1% of range maximum Total harmonic distortion 1% up to 31st harmonic
5.4 Power Supply
Two-way xed connector with 2.5mm2 stranded wire capacity.
The meter is powered from Phase L1. The user must make sure the meter Phase 1 has power on.
5.5 Interfaces for External Monitoring
Three interfaces are provided:
an RS485 communication channel that can be programmed
for Modbus RTU protocol.
an output indicating real-time measured energy.
(congurable)
an pulse output 3200imp/kWh (not congurable).
The Modbus conguration (Baud rate etc.) and the pulse
output assignments (kW/kVArh, import/export etc.) are
congured through the Set-up screens.
5.5.1 Pulse Output
The pulse output can be set to generate pulses to represent kWh or kVArh. Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh 1 = 1 kWh/kVArh 10 = 10 kWh/kVArh 100 = 100 kWh/kVArh 1000 = 1000 kWh/kVArh
Pulse width 200/100/60 ms.
5.5.2 RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication
parameters can be congured from the Set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400 Parity none/odd/even Stop bits 1 or 2 RS485 network address nnn – 3-digit number, 001 to 247
MyMeters.com Unit 4, 59 Beattie St, Kallangur QLD 4503 Australia Tel: 1300 METERS (1300 638 377) Email: info@mymeters.com web: www.mymeters.com
MID
7.3 Six Circuits Single Phase Two Wire
7.2 One Circuit Three Phase Four Wire + Three Circuits Single Phase Two Wire
7.1 Two Circuits Three Phase Four Wire
7. Installation
6. Dimensions
105mm
35mm
92mm
65mm
4.8.1 RS485 Address
(The range is from 001 to 247)
4.9 CLR
The meter provides a function to reset the maximum demand value of current and power.
From the Set-up menu, use and buttons to select the reset option.
Press to enter the selection routine. The dlt
will ash.
Press button to conrm the setting and press
to return to the main set up menu.
Modbus™ Word order Hi/Lo byte order is set automatically
to normal or reverse. It cannot be congured from the
set-up menu.
5.6 Reference Conditions of Inuence
Quantities
Inuence Quantities are variables that affect measurement errors to a minor degree. Accuracy is veried under nominal value (within the specied tolerance) of these conditions.
Ambient temperature 23°C ±1°C
Input waveform 50 or 60Hz ±2%
Input waveform Sinusoidal (distortion
factor < 0.005)
Magnetic eld of external origin Terrestrial ux
5.7 Environment
Operating temperature -25°C to +55°C*
Storage temperature -40°C to +70°C*
Relative humidity 0 to 90%, non-condensing
Altitude Up to 3000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-
2-6, 2g
Shock 30g in 3 planes
CT3
CT2
CT1
CT3
CT2
CT1
Circuit 1
Circuit 2
N L3 L2 L1
1a fast blow fuses
CT input for Circuit 1 CT input for Circuit 2
L32 L31 L22 L21 L12 L11 L32 L31 L22 L21 L12 L11
Voltage Input Pulse 1Pulse 2 RS485
N L3 L2 L1 - + - + B A
CT3
CT2
CT1
CT3
CT2
CT1
Circuit 1
Circuit 2
N L3 L2 L1
1a fast blow fuses
CT input for Circuit 1 CT input for Circuit 2
L32 L31 L22 L21 L12 L11 L32 L31 L22 L21 L12 L11
Voltage Input Pulse 1
Pulse 2
RS485
N L3 L2 L1 - + - + B A
CT3
CT2
CT1
CT3
CT2
CT1
Circuit 1
Circuit 2
N L1
1a fast blow fuses
CT input for Circuit 1 CT input for Circuit 2
L32 L31 L22 L21 L12 L11 L32 L31 L22 L21 L12 L11
Voltage Input Pulse 1Pulse 2 RS485
N L3 L2 L1 - + - + B A
Loading...