MYERS WHR, WHRH, WHRE, WHR-DS, WHR-SD L/D Installation And Servicing Instructions

...
WHR/WHRH and WHRE WASTE HANDLING SUMP PUMPS
Installation and Servicing Instructions for Myers WHR/WHRH and WHRE Submersible Sump Pumps Single & Three Phase Power Single & Double Seal
SINGLE SEAL PUMPS
23833A201 (Rev. 6/09)
DOUBLE SEAL PUMPS
TYPICAL SECTIONAL DRAWINGS
FOR WHR/WHRH AND WHRE
SINGLE AND DOUBLE SEAL WASTE HANDLING PUMPS
SINGLE SEAL
FIG. 1
WHR WHRH WHRE
23833A201 2
DOUBLE SEAL
FIG. 2
WHR-DS WHR-SD L/D WHRH-DS WHRH-DS L/D WHRE-DS WHRE-DS L/D
GENERAL DESCRIPTION AND USES
The WHR and WHRH Series are solids handling pumps that can be used to pump RAW SEWAGE for COMMERCIAL and DOMESTIC use, but are not intended to handle large rags, mop heads, or strings. All pumps can be used for normal sump duty where extra capacity is required. The WHRE Series is for pumping sump water and EFFLUENT from septic tanks only. DO NOT USE FOR RAW SEWAGE.
Plug in cords can be used on all the single phase pumps without seal leak detector. The cord has a GROUND pin that plugs into a grounded receptacle. The grounded receptacle cannot be used in the wet sump or basin due to DANGER of current leakage.
Sealed junction boxes must be used in wet sumps or basins to make connections to motor cord. The AWS-1 control also acts as a sealed junction box for connecting power cord to pump cord.
RECESSED IMPELLERS
All of the pumps are of the recessed impeller type that provides a clear volute passage for solids as no solids pass through the impeller. All of the pumps listed can be used to pump septic tank EFFLUENT or GROUND sewage as used in some pressure sewer systems.
DOUBLE SEAL PUMPS
All double seal models have two seals with an oil chamber between the seals so that seal faces of both lower and upper seals are oil lubricated for longer life and greater protection against water leaking into the motor windings. These double seal units are made with and without a seal leak probe. The leak probe in the oil seal chamber detects any water leakage into the chamber and turns on a red signal light in the control panel. Pumps should be removed from sump and seals replaced after seal light shows in the panel. Control panels must be used for pumps having the seal leak probe.
Double seal pumps without the seal leak probe, should be pulled and seal leak checked in 12 to 18 months.
LEVEL CONTROLS
All pumps must use sealed level control switches for automatic operation. MLC and MFLC controls have sealed mercury* switches that are 1 H.P. rated at 230 volts. ALC and AWS-1 controls have sealed mechanical switches that are rated 2 H.P. at 230 volts. Simplex single phase pumps can be made automatic by attaching MFLC or MLC controls to pump. These switches have a fixed draw off level of 8 to 10” and can be used up to 1 H.P. For higher H.P. ratings two mercury* switch (or SMNO) controls with a magnetic starter can be used.
The ALC and AWS-1 controls can be used for simplex single phase pumps with ratings up to 2 H.P.
SAFETY WARNING
All pumps single or three phase must have a GROUND WIRE that is connected to a screw in the metal pump housing. This wire goes to the control box and is connected to a good outside GROUND such as a metal water pipe or GROUND STAKE driven at least 6 feet into the ground.
MOTOR TYPES
All single phase pump motors are of the permanent split capacitor type that do not require a start switch or start relay.
Automatic reset overload switches are attached directly to the motor windings.
Three phase pump motors require a magnetic starter with 3 leg overload protection.
INSTALLATION
Pumps can be installed inside sealed basin with proper venting for either simplex or duplex systems. SIMPLEX or DUPLEX basin systems are available. See Figs. 3 and 4.
It is not recommended that basins be used for RAW SEWAGE inside the home, but are for use in office buildings and small industrial buildings and factories.
*This product contains mercury and must be disposed of according to local
3 23833A201
and federal codes.
“O” RING SEAL INLET FLANGE FOR 4 PLASTIC PIPE
FIBERGLASS BASIN
WHR – WHRH – WHRE SEWAGE PUMP SINGLE PHASE
1
/2-3/4-1-2 HP
1
/2” O.D.
PUMP CORD PLUGS INTO SERIES SWITCH CORD FOR AUTOMATIC OPERATION
3” VENT PIPE
GATE VALVE
MYERS FREE FLOW CHECK VALVE
MLC or MFLC LEVEL CONTROL WITH SERIES PLUG
SIMPLEX SYSTEM WITH
ALC LEVEL CONTROLS.
DISCHARGE PIPE
FIG. 3
NOT MORE THAN 14”
HEIGHT
TO SUIT
“O” RING SEAL INLET FLANGE FOR 41/2” O.D. PLASTIC PIPE
OPTIONAL ALARM CONTROL
30” DIA. x 36” DEEP FIBERGLASS BASIN
PUMP CORD
LEVEL CONTROL CORD
OPTIONAL ALARM CORD
NEMA 1 DUPLEX CONTROL BOX
2” PUMP PIPING, CAN BE 3” IF REQUIRED
1
1
/2” CONDUIT
BUSHING
1
1
/2” CONDUIT
35”
SPLIT RUBBER SEAL BUSHING
PUMP 1
CAST IRON PUMP COVER SEALS WITH RUBBER GASKET
STEEL BASIN COVER EPOXY COATED. SEALED TO BASIN WITH CAULKING COMPOUND
SEPARATE 2” DISCHARGE PIPE CAN BE RUN FROM EACH PUMP IF DESIRED
PUMP 2
3”– 45º TEE
3” VENT PIPE
2” GATE VALVE
CV-200 CHECK VALVE
OVERRIDE CONTROL
START CONTROL
WASTE HANDLING PUMPS
STOP CONTROL
10”
3” DISCHARGE PIPE
10”
REMOTE CONTROL BOX.
36”
DUPLEX SYSTEM WITH
FLOAT CONTROLS AND
FIG. 4
23833A201 4
Basins can be used inside the home where extra capacity sump pumps are required for water softeners and wash water.
If raw sewage must be pumped in the home use outside basins that connect with pressure sewer mains or gravity sewers, or run to septic tanks.
If an inside basin is used it is usually installed at time of pouring the concrete floor.
Pumps can be installed in a compartment of septic tanks for pumping to pressure sewer mains, gravity sewers, leach fields, or evaporation mounds. See Figs. 5, 6 and 7.
PROPER VENTING FOR BASINS
INSTALLED INSIDE
All inside sealed basins must have a 2” or 3” vent pipe installed in accordance with local codes. Sumps for handling softener water, wash or drainage water do not have to be sealed or vented.
Outside basins are usually of fiberglass and from 4 to 8 feet deep and have a sealed cover. Pump is usually installed with a lift out rail system so that pump can be removed without disturbing the discharge piping. The check valve comes out with pump for servicing. Complete LIFT OUT SYSTEMS mounted in fiberglass basins are available to meet customer’s specifications.
WARNING: Sump basin must be vented in accord­ance with local plumbing codes. These pumps are not designed for and CANNOT be installed in locations classified as hazardous in accordance with the National Electric Code ANSI/NFPA 70.
PIPING
Pumps are fitted with 2” or 3” female threaded pipe flange. Galvanized or PVC plastic pipe can be used. Plastic pipe is preferred for raw sewage or septic tank effluent.
CHECK VALVES AND SHUT-OFF VALVES
All pumps must have check valves and shut-off valves in the discharge line. Check valves must be flapper type with outside spring or ball type. Shut­off valves can be ball or gate type. Plastic construc­tion for both check and shut-off valves is preferred.
STARTING SIMPLEX SYSTEMS
1. For single phase pumps with MLC or MFLC control, plug cords piggy back into receptacle and run water into sump until pump starts. Allow pump to make several on/off cycles. Leave power cord plugged in. If pump runs but does not pump it may be air locked. Unplug cord and crack union in the discharge line then restart pump, this should vent off any trapped air. Re-tighten union.
AIR LOCKING
A sump pump is said to be air locked if water traps in the pump and it cannot get out, thus preventing pump from operating. ALL MYERS SUMP PUMPS HAVE A SMALL AIR VENT HOLE IN THE IMPELLER CHAMBER TO LET OUT TRAPPED AIR. IF THIS HOLE BECOMES PLUGGED, PUMP MAY AIR LOCK. THIS USUALLY HAPPENS ON PUMPS THAT ARE USED MAINLY IN THE SEASONS. IN SUMMER MONTHS, THE PUMP MAY BE TURNED OFF AS SUMP WATER DRIED UP. WHEN PUMP IS TURNED ON AGAIN AND WATER COMES UP IN SUMP, THE AIR WILL TRAP IN PUMP IF NOT VENTED.
AS A SECONDARY PRECAUTION IN INSTALLATIONS OF THIS TYPE – 1/8” HOLE SHOULD BE DRILLED IN THE DISCHARGE PIPE BELOW THE CHECK VALVE. THE CHECK VALVE SHOULD BE 12 TO 18 INCHES ABOVE PUMP DISCHARGE. DO NOT PUT CHECK VALVE DIRECTLY INTO PUMP DISCHARGE OPENING.
In normal sumps where the pump is operating daily, air locking rarely occurs.
2. With 2 float controls turn on power at the control box and run water into sump. When level gets above top control pump should start and continue to pump until level drops to lower control stopping pump. Run pump through several cycles. If pump runs but does not pump, check air lock as in 1. Leave power on for automatic operation.
3. Where ALCL or AWS-1 controls are used plug in cord or turn on power and run water into sump, when level is about half way up on upper weight pump should start and run until level drops until about half the lower weight is above water, stopping pump. Check 1, if pump does not operate properly. For all cases if motor does not start when water level is up check for proper plug in or that start switch is on, or if fuse is blown. ALWAYS HAVE ELECTRICTIAN MAKE ELECTRICAL CHECKS.
STARTING PUMP “WHE-P” (AUTOMATIC)
USING MECHANICAL SWITCH WITH
SERIES PLUG-SIMPLEX SYSTEM
1. These pumps have a mechanical (mercury-free) float switch with a 20 ft. cord and 115 volt or 230 volt series piggy-back plug on ½ H.P. with switch mounted to the pump. On ¾ H.P. and 1 H.P., it requires 20 ft. cord and 230 volt only.
2. Plug the switch cord plug into a proper voltage properly grounded outlet.
3. Plug the pump power cord into the back of the switch cord series plug.
4. Tape the cords to the discharge pipe every 12”.
5. Run water into sump until pump starts. Be sure discharge line valve is open.
6. Allow pump to operate through several on/off cycles.
7. If pump does not operate properly, see trouble shooting service chart for remedy.
5 23833A201
HOW TO SET CONTROLS AND START
DUPLEX SYSTEMS
CONTROL BOX MUST BE USED ON ALL DUPLEX SYSTEMS
1. 4 float controls are used for duplex systems. Set turn-on control 6” to 8” above pumps. Set turn-off control 8” to 10” above bottom of sump. Set override control 6” to 8” above turn­ on control. Set high level alarm control about 6” to 8” above override control. Mark all control cords so that they can be
connected correctly in
the control box. See Fig. 4.
2. Turn Hand-Off-Auto switches to OFF position and close circuit breaker.
3. Turn H-O-A switches to the AUTO position and run water into sump. When level floats up and activates the turn-on switch one pump should start and run, pump will continue to run until lower control is exposed stopping pump.
4. Run water into sump again and when level floats up turn-on control, opposite pump will start and run until level drops exposing lower control, stopping pump.
5. Run this test several times to be sure pumps are alternating properly.
LEVEL CONTROL SYSTEMS AVAILABLE
1. Simplex single phase packaged automatic system. This system has the MLC or MFLC
float switch attached directly to the pump. This system has a fixed pump-off level of 8” to 10” and is usually used for drainage water and is good up to and including 1 H.P.
2. Simplex single phase pumps can use the ALC or AWS-1 controls which are mounted separate from the pump. These controls can be used up to 2 H.P. motors. See Fig. 3
3. Simplex pumps can use two float controls mounted separate from the pump. These controls must be used with a control box and magnetic contactor. These controls can be spaced apart for any draw off level required and can be used for 2 H.P. or larger motors.
4. Duplex pump systems must use only the float controls with electrical control box. These control boxes mounted remote from the sump tank are generally of plastic construction for best corrosion resistance. See Fig. 4.
MOTOR OVERLOAD PROTECTION
All single phase motors have built-in automatic reset overload switches fastened directly to the motor windings.
All 3 phase motors must be installed with magnetic starters having 3 leg overload protection.
HOW TO SET CONTROLS AND START
SIMPLEX SYSTEMS
1. Automatic systems – These systems have the MLC, MFLC, or ALC switches mounted on the
pump, so pump is installed in the sump and motor cord is plugged into GROUNDED receptacle. For sealed sump cover, power cord is brought through a split rubber plug in the sump cover.
2. Where 2 float controls are used the turn on control is set 3” to 6” above top of motor, and the turn-off control is set about 6” to *’ above bottom of sump. If a high level alarm control is used it is set about 6” above upper control. If sump depth will not allow these settings closer spacing can be used.
3. Where ALLC or AWS-1 controls are used the DISPLACEMENT WEIGHTS are set so that turn­ on weight is 4” to 6” above top of motor and lower weight is set about 6” above sump bottom.
4. Repeat this operation with one pump off which will duplicate a failed pump condition. When the level reaches the override control the pump that is turned on should start and run and pump down sump level.
5. To check high level alarm, again turn both switches to OFF and fill sump until level is above the alarm control. Turn switches to Auto position and ALARM BUZZER should sound and alarm light should come on. When level drops below the alarm control buzzer should stop.
6. If pumps operate as described then set both H-O-A to Auto and pumps are ready to operate automatically.
7. If pumps do not operate properly then check as described for simplex systems. See page. 13. CAUTION – NEVER WORK ON PUMPS OR CONTROL BOXES UNTIL CIRCUIT BREAKERS ARE TURNED OFF.
Always have a qualified ELECTRICIAN make electrical connections and service checks.
23833A201 6
SPECIAL INSTRUCTIONS FOR
THREE PHASE PUMPS
1. WARNING! Only qualified persons shall conduct services and installations of this pump. The pump must be wired by a qualified electrician, using an approved starter box and switching device. CAUTION! Risk of electric shock. Do not
connect conduit to pump
2. Three phase pumps are always installed with control boxes having magnetic starters with 3 leg overload protection. DO NOT
TRY TO RUN THREE PHASE PUMPS DIRECTLY ACROSS THE LINE.
3. To Connect Pump: Run wire from pump to the bottom of control box or appropriate junction box suitable for enclosing splice connections. A hole must be cut into the control box for the wires. With power to control box off, connect green (ground) line to ground lug. Connect black (power) wires to power lead terminals. Make sure that all wires are inside control box and not in a position to be pinched or shorted when the door is closed. See wiring diagrams, page 8.
4. All three phase motors can run either direction, ROTATION can be changed by interchanging any two line leads at magnetic starter. BE
SURE CIRCUIT BREAKER IS OFF BEFORE MAKING THIS CHANGE.
To find if rotation is correct operate pumps and check delivery operation. If flow and head is low (refer to pump curves shown in this manual) the rotation is wrong. With duplex pumps check operation of both pumps. All pump impellers either single or three phase must turn counterclockwise when looking into pump inlet. If uncertain of rotation, TURN OFF POWER and lift pump from basin with cord connected and lay pump on side so impeller can be seen. Turn on power and start pump using hand position of H-O-A switch. Turn on and off fast so that coast of impeller can be seen.
ON THE IMPELLER.
leads at the magnetic starter to change rotation.
NEVER PUT HAND OR FINGERS
Interchange any two line
WIRING DIAGRAMS SINGLE PHASE MOTORS
SINGLE PHASE PUMPS
WARNING – Risk of electric shock. This pump
is supplied with a grounding conductor and grounding-type attachment plug. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, grounding-type receptacle.
POWER CORD
POTTING RESIN
CAPACITOR
GRN.
BLACK
WHT. OR YELL
WHITE
BLACK
STATOR
115 VOLT OR 200 or 230 VOLT - 1 PHASE SINGLE VOLTAGE P.S.C. MOTOR
BROWN
BROWN
SINGLE SEAL PUMPS AND DOUBLE SEAL
PUMPS WITHOUT SEAL LEAK PROBE
POWER CORD
POTTING RESIN
GRN.
RED
BLACK
WHT. OR YELL
SEAL LEAK
RED
BLACK
WHITE
ELECTRODE
STATOR
115 VOLT OR 200 or 230 VOLT - 1 PHASE SINGLE VOLTAGE P.S.C. MOTOR
CAPACITOR
BROWN
BROWN
7 23833A201
DOUBLE SEAL PUMPS WITH
SEAL LEAK PROBE
(RED CONDUCTOR IN POWER CORD
IS FOR SEAL LEAK PROBE)
WIRING DIAGRAMS FOR 3 PHASE MOTORS
POWER CORD
POTTING RESIN
SPLICES
B
B
B
CONNECTORS
B
B
B
MOTOR STATOR
200 or 575 VOLT - 3 PHASE
FOR SINGLE SEAL PUMPS AND DOUBLE SEAL PUMPS
GREEN
GROUND
SCREW
POWER CORD
POTTING RESIN
SPLICES
CONNECTORS
T9
B
B
T8
T3
GROUND
B
SCREW
GREEN
T7
T6
T5
T1
T2
T4
MOTOR STATOR
230 VOLT - 3 PHASE
WITHOUT SEAL LEAK PROBE
POWER CORD
POTTING RESIN
SPLICES
CONNECTORS
MOTOR STATOR
460 VOLT - 3 PHASE
B
B
B
T1
T2
T3
T9
GREEN
T6
GROUND
SCREW
T5
T8
T7
T4
23833A201 8
Loading...
+ 16 hidden pages