MYDAX 1M9W-S Maintance Manual

advanced temperature control technology
MYDAX, INC.
INSTRUCTION/OPERATIONS MANUAL
1M9W-S WATER COOLED CHILLER
Serial Number 120-07XX
MYDAX, INC.
12260 Shale Ridge Road
Auburn, CA 95602
FAX: (530) 888-0962
March 2001
TABLE OF CONTENTS
I. SPECIFICATIONS ....................................................................................................... 1
II. SYSTEM OVERVIEW ................................................................................................. 2
III. INSTALLATION ......................................................................................................... 4
IV. FRONT PANEL CONTROLS ..................................................................................…… 5
V. ERROR MESSAGES ................................................................................................... 7
VI. DIAGNOSTIC DISPLAYS .......................................................................................... 8
VII. SERVICE & WARRANTY .......................................................................................…. 11
VIII. RESHIPPING & LONG-TERM STORAGE PREPARATION ............................ ..................… 12
IX. APPENDIX A: RS-232C SERIAL INTERFACE OPERATION
X. APPENDIX B: DRAWINGS
Lawrence Berkeley Laboratory
Mydax, Inc. 1M9W-S Water Cooled Chiller
SPECIFICATIONS
SYSTEM CAPACITIES
Cooling Capacity @ +20°C 2500 Watts
Coolant Temperature Setpoint Range +15°C to +25°C
Coolant Output Temperature Stability
Polypropylene Reservoir Volume 10 Gallons
Recirculating Coolant Low Conductivity Water
Coolant Flow/Pressure 10 Gpm @ 100 Psi (Bypass Provided)
Recirculating Supply/Return Fittings 1" Stainless Steel FPT
Condenser Water @ 75°F 1.5 Gpm Required (∆P = 20 Psi)
Condenser Water Connections 1/2" Stainless Steel FPT
Electrical Service 208/230 volt, 60 Hz, 3 phase, 20 amp
Physical Parameters 42"H x 24"W x 33"D, 450 lbs.
STANDARD FEATURES
System is complete with microprocessor-controlled low-stress refrigeration circuit, recirculating pump and fluid reservoir. R-22 refrigeration circuit uses all-brazed construction for extra strength. The heavy-duty frame is constructed of welded steel tubing equipped with locking casters.
±
0.05°C
With 10' line cord and L15-30P plug.
The microprocessor-based control system includes an extensive monitoring capability including comprehensive controls, error messages and diagnostics. System status is indicated via a two-row (40 characters each) alphanumeric LCD (liquid crystal display) and with red light-emitting diodes (LED's). The control keyboard employs membrane switches with a sealed polycarbonate overlay for protection from liquid spills. This chiller is complete with a liquid-filled panel mounted pressure gauge, an internal pressure bypass circuit, a full-flow 10 micron particulate filter and an RS-232C Interface for remote control and monitoring.
SAFETY FEATURES
1. Warning & Error Messages: including coolant over-temperature warning & shutdown, low tank level warning & shutdown and others (see ERROR MESSAGES section).
2. System Diagnostics: including coolant & freon temperatures, valve and heater drives and others (see DIAGNOSTIC DISPLAYS section).
3. Integral compressor refrigerant high pressure protection.
4. Circuit breaker & contactor.
5. Interlock loop, including reset switch.
6. Thermal protection of pump and compressor motors.
7. Manufactured and wired in accordance with IBM Non-Product Safety Design Standards.
Lawrence Berkeley Laboratory 1
Mydax, Inc. 1M9W-S Water Cooled Chiller
SYSTEM OVERVIEW
System Fluid Schematic
Refer to drawing #B2343, the fluid schematic. The heart of the design is the evaporator valve. This is a thermal-electric expansion valve, controlled directly by the system's embedded microprocessor. Hermetically sealed, it consists of a spring-loaded needle valve in contact with a bimetallic plate. The plate is wound by a coil of wire connected to terminals on top of the valve. The curvature of the plate, and therefore the position of the needle valve, varies with its temperature which is controlled by electrical current flow through the coil. So by controlling the duration of electrical pulses applied to the valve terminals, the microprocessor opens the valve to a precisely determined point. This passes a precisely determined flow of freon to the evaporator, allowing for exceptionally stable recirculating temperatures. This system is designed to control the recirculating output temperature to ±0.05°C across the system operating range.
The microprocessor sets the exact position of the valve based upon the system heat load. If the load increases, the evaporator valve is opened slightly, passing more refrigerant. If the load decreases, the valve is closed slightly, passing less refrigerant. During normal operation, the position of this valve stays nearly constant. Only major changes in heat load or system-wide power cycling cause large changes in the valve opening. In the case of a step-wise change in heat load, the microprocessor quickly drives the valve to the new setting and refrigerant flow soon settles at the proper level.
The valve drive setting is based primarily upon data received from RTD's (resistance temperature devices) located about the circuit. The drawing shows RTD's at the evaporator valve, at the discharge line from the pump, at the reservoir and between the condenser and receiver. The microprocessor "reads" these and other sensors constantly and sets the refrigerant valve accordingly.
Thus refrigerant flow is truly proportioned, through a valve which only rarely cycles all the way open or shut. Besides precise temperature control, this allows continuous compressor operation without the normal addition of cycling, and therefore failure-prone, pressure-actuated hot gas bypass valves. All other refrigeration circuit components are used as in conventional systems. All permanent copper joints in the refrigeration circuit are brazed for extra strength. Much of the circuitry is insulated to eliminate cooling capacity loss and unpredictable operation due to drafts or fluctuating ambient air conditions.
This system is designed to recirculate water. It is not designed to recirculate solutions of automotive antifreeze. Approximately 10 gallons are required to fill the polypropylene reservoir. The heating elements are stainless steel cartridge heaters. The freon evaporator is a coaxial heat exchanger, located in the recirculating return line leading to the reservoir.
The reservoir is fitted with two level sensors. One level sensor drives a FILL TANK alarm at the main panel, indicating coolant level has dropped somewhat. The second sensor, the TANK EMPTY sensor, is connected to the safety interlock loop and shuts the system down if tripped. Note that "empty" is a relative term only. The real function of this sensor is to prevent the coolant level from dropping so low as to expose the pump suction line.
Lawrence Berkeley Laboratory 2
Mydax, Inc. 1M9W-S Water Cooled Chiller
System Electrical Diagram
Refer to drawing #B2344, the system electrical diagram. The central component of the electrical system is the M1001 controller. It is microprocessor-based and communicates with and/or controls various other circuit boards and components. Most controller circuitry is laid out on circuit boards mounted in the main control cabinet. The controller is powered as long as the system circuit breaker is set, receiving 24 VAC power from a bulkhead-mounted transformer.
The controller "reads" the RTD's in the system via board M1002. RTD's are included for the recirculating output temperature and the reservoir, as well as for the freon circuit. Also routed through this board are the 100 and 120 • precision RTD calibration resistor circuits. The evaporator valve drive signal is routed through board M1004, as is the phase detector circuit.
The system interlock loop is controlled by the M1002 circuit board. In this application the interlock loop consists of the freon high pressure switch, the tank over-temperature switch, the TANK EMPTY level sensor, the RESET momentary switch, one power relay coil and a relay pole (1R 5-8). The RESET switch serves to feed power to the relay, which energizes the contactor. When energized, the contactor feeds power back to the relay so the RESET switch may open up without cutting off power to the relay. If the freon pressure switch, the over-temperature switch or the level sensor trips, power to the loop is interrupted. The microprocessor senses this via the M1002 board. Provided the system has power, if the loop trips out, the controller drives the PUSH RESET error message. The loop must be reset when the fault condition is resolved.
The M1002 board also routes signals for the FILL TANK level sensor. If this sensor trips, the microprocessor drives the FILL TANK error message.
Lawrence Berkeley Laboratory 3
Mydax, Inc. 1M9W-S Water Cooled Chiller
INSTALLATION
POWER CONNECTION
This chiller requires a 20 amp or larger circuit, 208/230 volt, 60 Hz, 3 phase and is equipped with a line cord and twist-lock L15-30P electrical plug.
PLUMBING INTERFACE CONNECTIONS
The chiller's 1" female pipe thread (FPT) fitting labeled "TANK OUT" must be plumbed to the inlet of the device to be cooled. The outlet of the device to be cooled must be plumbed to the chiller's 1" FPT fitting labeled "TANK IN". This system is equipped with a ½" FPT fitting labeled "DRAIN". It may be desirable to install a valve at this location prior to the initial filling of the reservoir, for the convenience of future draining procedures.
The condenser cooling water supply must be plumbed to the chiller's ½" FPT fitting labeled "CONDENSER IN". The chiller's ½" FPT fitting labeled "CONDENSER OUT" must be plumbed to either a drain or the return path of the condenser cooling water circuit. Verify that condenser cooling water into and out of the chiller is unobstructed. Obstructions may cause loss of cooling capacity and eventual overheating.
Both the recirculating loop and the condenser cooling water loop are under pressure when the system is operating. Check all fluid interface connections now to ensure against leaks.
CIRCUIT BREAKER
Set the circuit breaker mounted on the front of the system. Upon setting the circuit breaker, a message similar to the following appears on the 2 by 40-character main display:
This display indicates that the system's phase monitor circuit is checking for correct electrical power phase relationship. Should a live and ground line be reversed, the phase detector reads PHASE MISSING. Correct the error and the controller no longer indicates PHASE MISSING. If the display reads PHASE REVERSED, disconnect and switch two of the three phases.
FILL RESERVOIR
To fill the system's reservoir, unscrew the fill plug on the top of the vertical stand-pipe for the tank and pour in the recirculating fluid. If the system is powered before the tank is filled, the "FILL TANK" error message is displayed at the main panel, the alarm LED is lighted and the audible alarm sounds. Filling the tank eliminates the alarms. Replace the plug.
Output --- Warmup Delay --- Local Set
20.02°C 20.0°C
WARNING
The system should be powered for a period of ½ hour before starting, to
allow the crankcase heater to separate the refrigerant from the oil.
PUSH RESET BUTTON
The Reset button, located below the main panel, must be pushed upon powering the system. This resets the power safety interlock loop, which protects the operator and electrical circuitry.
Lawrence Berkeley Laboratory 4
Mydax, Inc. 1M9W-S Water Cooled Chiller
FRONT PANEL CONTROLS
All Mydax chillers are controlled by a microprocessor which is accessed via the system control panel. System controls are simple, yet powerful and in concert with built-in diagnostics and error messages, are exceptionally comprehensive.
POWER LED:
RESET:
START:
STOP:
MUTE ALARM:
SET:
Indicates unit is powered (the circuit breaker is set).
Must be pressed prior to system start-up to energize the interlock loop.
Starts compressor and pump and turns on LED's. Once the start-up routine is complete the display changes to the MAIN DISPLAY:
Output --- MYDAX --- Local Set
20.02°C 20.0°C
Shows the actual Output Temperature and Setpoint Temperature in °C. Also indicates that the local SET TEMPERATURE MODE can be enabled.
Stops both the compressor and pump and blanks the display.
May be used to deactivate audible alarm for 10 minutes, leaving alarm LED on. Pressing the CLEAR key reactivates the alarm, which sounds until the fault condition is eliminated or the MUTE ALARM switch is depressed again. Pressing MUTE ALARM when no alarm is active causes the alarm to sound once and the TEST ALARM display to appear.
Enables SET TEMPERATURE MODE. SET MODE is disabled from panel if an alarm is active or if the unit is in REMOTE. To set, depress:
TEST:
ENTER:
CLEAR:
MODE:
ARROW KEYS:
SET:
ARROWS KEYS:
"." (DECIMAL):
KEYPAD:
CLEAR:
ENTER:
Initiates Test Mode. See description under DIAGNOSTIC DISPLAYS section of this manual.
Enters temperature selections while in the SET mode.
Erases incorrect temperature selections; exits Test Mode; clears Mute Alarm selection.
Toggles between the RS-232C remote control mode and Local Set mode.
Changes temperature setpoint by 0.1° or 1°C increments/decrements; toggles tank
"Set Mode" appears at the right of the display. Cursor flashes at "units" digit of the temperature display.
Changes temperature setting in one degree increments unless "." (decimal) key is depressed.
Moves cursor to the "tenths" digit of the temperature display and causes arrow keys to change setting in tenths of a degree.
Changes temperature setting by entering numbers directly.
Erases an incorrect entry.
Selects temperature setting and deselects SET mode.
Lawrence Berkeley Laboratory 5
Mydax, Inc. 1M9W-S Water Cooled Chiller
temperature, setpoint temperature and evaporator data view modes for multiple channel systems.
"." (DECIMAL):
RUN PUMP:
X & Y:
Z:
EMO SWITCH:
Display shows model number and software revision date and copyright:
1M9W-S 2001.01.18 Copyright 2001 Mydax, Inc.
Inactive in this system.
For future use.
See Test Panel 9 in the Diagnostic Displays Section.
This is a large red emergency off switch mounted on the left of the main panel. It shuts down the entire system, excluding the controller.
Lawrence Berkeley Laboratory 6
Mydax, Inc. 1M9W-S Water Cooled Chiller
ERROR MESSAGES
A unique feature of Mydax systems is the error messages displayed on the 2 by 40-character liquid crystal display (LCD). The microprocessor constantly checks various points and parameters throughout the system and automatically displays messages when error conditions are sensed. Many displays are announced by an audible alarm and LED indicator. The error message persists until the fault condition is resolved, provided that the fault condition was not fatal, resulting in a system shutdown.
Condenser Hot
Fill Tank
Tank Too Hot
Push Reset
Phase Missing
Indicates high discharge pressure condition with temperature over +50°C. This is a warning message only. A separate mechanical overpressure switch, part of the safety interlock loop, shuts the system down in case of an overpressure condition. The purpose of this message is to allow maintenance workers to correct the problem at an early stage. (Caused by a clogged filter, low or warm condenser cooling water flow or condenser scale build-up.)
Indicates low tank liquid level.
Indicates that the reservoir temperature is more than 10°C above the highest allowable set point. Microprocessor shuts down the system.
Indicates that the reset button has not been pushed since the last system power-up or that the system interlock loop has a fault condition.
A series-wired safety interlock loop protects all Mydax systems, disconnecting AC power from nearly all circuitry. The loop consists of the freon pressure switch, tank "hot" sensor and low level switch. If any link in the loop is opened, the "Push Reset" error message is displayed. Once the fault is corrected, the Reset button must be used to re-establish loop integrity. The reset button must also be pushed at system power up.
Indicates that one or more electrical phases are missing.
Phase Reversed
Low AC Line
Open RTD
Lawrence Berkeley Laboratory 7
Indicates that electrical phases are incorrectly connected. Reverse any two legs.
Indicates a low voltage condition exists on the input AC line.
Indicates that an RTD connected to the M1002 Input Board has failed and that the system has shut down to prevent damage due to lack of data. The RTD at fault may be located by accessing Test Panel #8. The RTD must be replaced for the system to operate again.
Mydax, Inc. 1M9W-S Water Cooled Chiller
DIAGNOSTIC DISPLAYS
Mydax chillers are provided with a computerized self-diagnostic capability. This system is equipped with 9 different test panels, which are accessed by pressing the TEST key, followed by the test panel number. Diagnostic mode is terminated by pressing the CLEAR key, and results in a display similar to that below:
MAIN DISPLAY
Output --- MYDAX --- Local Set
20.02°C 20.0°C
Diagnostic messages are displayed on the main 2 by 40-character LCD. Display #5 automatically appears when the TEST key is first depressed. Once in diagnostic mode, other displays can be selected by depressing number keys 1 through 9. The following describes each of the test displays:
TEST PANEL #1:
Valve 7 Htr 8 Avg Valve 5 Htr 6
Numbers represent the drive signals for the evaporator valve and tank heater. The range is 0 (minimum) to 20 (maximum drive). Each digit represents 5% of the available 24VDC drive voltage. Avg Valve shows a 32 second running average of the valve's drive, displayed above it.
TEST PANEL #2:
This display shows the refrigerant circuit RTD temperatures in °C. The display reads:
Limit = Max Evaporator Temp Suct = Suction Temp Psig = Suction Pressure Sup.Ht = Superheat Temp SHavg = Avg Super Ht Temp Cond = Condenser Temp
The condenser reading is a direct indicator of condenser temperature and pressure. The microprocessor sends the CONDENSER HOT error message if the condenser temperature exceeds +54°C.
TEST PANEL #3:
The first 3 sets of 4-digit numbers are hexadecimal. They represent correction values for the slow gain servos for up to 3 reservoirs. The function of this servo is to dynamically adjust the main temperature control servo to near zero error and thereby maintain temperature stability.
The first 2 digits in each set of 4 show the gain offset. Each increment equals 0.05°C, so 14 Hex = 20 decimal = 1.0°C. This value is internally subtracted from the operator-entered temperature setpoint if the actual temperature is above the setpoint, thus reducing the coolant temperature. When the actual coolant temperature is below setpoint, the main servo is driving a heater and no adjustment is made to the setpoint. The setpoint offset is continuously monitored by the controller and adjusted according to current conditions.
4.0 -4.8 48.2 35.0 Limit Suct Psig Sup.Ht SHavg Condr
302B 0000 091F Z 0.00 G 51.95 14.4 SS-1 SS-2 SS-3 RTD Reference SH Avg
The second 2 digits in each set of 4 show the time prescaler. This is a counter which increments or decrements once a second and times the next update of the setpoint offset. A typical value is 20 seconds per offset change. When the count reaches "00", the offset may or may not be changed and the count resets to "0A" Hex (10 decimal). Together these numbers show that the controller is internally changing the control setpoint to maintain temperature stability, and give the magnitude and timing of the change.
Lawrence Berkeley Laboratory 8
Loading...
+ 23 hidden pages