MYDAX 1M9W-S Maintance Manual

advanced temperature control technology
MYDAX, INC.
INSTRUCTION/OPERATIONS MANUAL
1M9W-S WATER COOLED CHILLER
Serial Number 120-07XX
MYDAX, INC.
12260 Shale Ridge Road
Auburn, CA 95602
FAX: (530) 888-0962
March 2001
TABLE OF CONTENTS
I. SPECIFICATIONS ....................................................................................................... 1
II. SYSTEM OVERVIEW ................................................................................................. 2
III. INSTALLATION ......................................................................................................... 4
IV. FRONT PANEL CONTROLS ..................................................................................…… 5
V. ERROR MESSAGES ................................................................................................... 7
VI. DIAGNOSTIC DISPLAYS .......................................................................................... 8
VII. SERVICE & WARRANTY .......................................................................................…. 11
VIII. RESHIPPING & LONG-TERM STORAGE PREPARATION ............................ ..................… 12
IX. APPENDIX A: RS-232C SERIAL INTERFACE OPERATION
X. APPENDIX B: DRAWINGS
Lawrence Berkeley Laboratory
Mydax, Inc. 1M9W-S Water Cooled Chiller
SPECIFICATIONS
SYSTEM CAPACITIES
Cooling Capacity @ +20°C 2500 Watts
Coolant Temperature Setpoint Range +15°C to +25°C
Coolant Output Temperature Stability
Polypropylene Reservoir Volume 10 Gallons
Recirculating Coolant Low Conductivity Water
Coolant Flow/Pressure 10 Gpm @ 100 Psi (Bypass Provided)
Recirculating Supply/Return Fittings 1" Stainless Steel FPT
Condenser Water @ 75°F 1.5 Gpm Required (∆P = 20 Psi)
Condenser Water Connections 1/2" Stainless Steel FPT
Electrical Service 208/230 volt, 60 Hz, 3 phase, 20 amp
Physical Parameters 42"H x 24"W x 33"D, 450 lbs.
STANDARD FEATURES
System is complete with microprocessor-controlled low-stress refrigeration circuit, recirculating pump and fluid reservoir. R-22 refrigeration circuit uses all-brazed construction for extra strength. The heavy-duty frame is constructed of welded steel tubing equipped with locking casters.
±
0.05°C
With 10' line cord and L15-30P plug.
The microprocessor-based control system includes an extensive monitoring capability including comprehensive controls, error messages and diagnostics. System status is indicated via a two-row (40 characters each) alphanumeric LCD (liquid crystal display) and with red light-emitting diodes (LED's). The control keyboard employs membrane switches with a sealed polycarbonate overlay for protection from liquid spills. This chiller is complete with a liquid-filled panel mounted pressure gauge, an internal pressure bypass circuit, a full-flow 10 micron particulate filter and an RS-232C Interface for remote control and monitoring.
SAFETY FEATURES
1. Warning & Error Messages: including coolant over-temperature warning & shutdown, low tank level warning & shutdown and others (see ERROR MESSAGES section).
2. System Diagnostics: including coolant & freon temperatures, valve and heater drives and others (see DIAGNOSTIC DISPLAYS section).
3. Integral compressor refrigerant high pressure protection.
4. Circuit breaker & contactor.
5. Interlock loop, including reset switch.
6. Thermal protection of pump and compressor motors.
7. Manufactured and wired in accordance with IBM Non-Product Safety Design Standards.
Lawrence Berkeley Laboratory 1
Mydax, Inc. 1M9W-S Water Cooled Chiller
SYSTEM OVERVIEW
System Fluid Schematic
Refer to drawing #B2343, the fluid schematic. The heart of the design is the evaporator valve. This is a thermal-electric expansion valve, controlled directly by the system's embedded microprocessor. Hermetically sealed, it consists of a spring-loaded needle valve in contact with a bimetallic plate. The plate is wound by a coil of wire connected to terminals on top of the valve. The curvature of the plate, and therefore the position of the needle valve, varies with its temperature which is controlled by electrical current flow through the coil. So by controlling the duration of electrical pulses applied to the valve terminals, the microprocessor opens the valve to a precisely determined point. This passes a precisely determined flow of freon to the evaporator, allowing for exceptionally stable recirculating temperatures. This system is designed to control the recirculating output temperature to ±0.05°C across the system operating range.
The microprocessor sets the exact position of the valve based upon the system heat load. If the load increases, the evaporator valve is opened slightly, passing more refrigerant. If the load decreases, the valve is closed slightly, passing less refrigerant. During normal operation, the position of this valve stays nearly constant. Only major changes in heat load or system-wide power cycling cause large changes in the valve opening. In the case of a step-wise change in heat load, the microprocessor quickly drives the valve to the new setting and refrigerant flow soon settles at the proper level.
The valve drive setting is based primarily upon data received from RTD's (resistance temperature devices) located about the circuit. The drawing shows RTD's at the evaporator valve, at the discharge line from the pump, at the reservoir and between the condenser and receiver. The microprocessor "reads" these and other sensors constantly and sets the refrigerant valve accordingly.
Thus refrigerant flow is truly proportioned, through a valve which only rarely cycles all the way open or shut. Besides precise temperature control, this allows continuous compressor operation without the normal addition of cycling, and therefore failure-prone, pressure-actuated hot gas bypass valves. All other refrigeration circuit components are used as in conventional systems. All permanent copper joints in the refrigeration circuit are brazed for extra strength. Much of the circuitry is insulated to eliminate cooling capacity loss and unpredictable operation due to drafts or fluctuating ambient air conditions.
This system is designed to recirculate water. It is not designed to recirculate solutions of automotive antifreeze. Approximately 10 gallons are required to fill the polypropylene reservoir. The heating elements are stainless steel cartridge heaters. The freon evaporator is a coaxial heat exchanger, located in the recirculating return line leading to the reservoir.
The reservoir is fitted with two level sensors. One level sensor drives a FILL TANK alarm at the main panel, indicating coolant level has dropped somewhat. The second sensor, the TANK EMPTY sensor, is connected to the safety interlock loop and shuts the system down if tripped. Note that "empty" is a relative term only. The real function of this sensor is to prevent the coolant level from dropping so low as to expose the pump suction line.
Lawrence Berkeley Laboratory 2
Mydax, Inc. 1M9W-S Water Cooled Chiller
System Electrical Diagram
Refer to drawing #B2344, the system electrical diagram. The central component of the electrical system is the M1001 controller. It is microprocessor-based and communicates with and/or controls various other circuit boards and components. Most controller circuitry is laid out on circuit boards mounted in the main control cabinet. The controller is powered as long as the system circuit breaker is set, receiving 24 VAC power from a bulkhead-mounted transformer.
The controller "reads" the RTD's in the system via board M1002. RTD's are included for the recirculating output temperature and the reservoir, as well as for the freon circuit. Also routed through this board are the 100 and 120 • precision RTD calibration resistor circuits. The evaporator valve drive signal is routed through board M1004, as is the phase detector circuit.
The system interlock loop is controlled by the M1002 circuit board. In this application the interlock loop consists of the freon high pressure switch, the tank over-temperature switch, the TANK EMPTY level sensor, the RESET momentary switch, one power relay coil and a relay pole (1R 5-8). The RESET switch serves to feed power to the relay, which energizes the contactor. When energized, the contactor feeds power back to the relay so the RESET switch may open up without cutting off power to the relay. If the freon pressure switch, the over-temperature switch or the level sensor trips, power to the loop is interrupted. The microprocessor senses this via the M1002 board. Provided the system has power, if the loop trips out, the controller drives the PUSH RESET error message. The loop must be reset when the fault condition is resolved.
The M1002 board also routes signals for the FILL TANK level sensor. If this sensor trips, the microprocessor drives the FILL TANK error message.
Lawrence Berkeley Laboratory 3
Mydax, Inc. 1M9W-S Water Cooled Chiller
INSTALLATION
POWER CONNECTION
This chiller requires a 20 amp or larger circuit, 208/230 volt, 60 Hz, 3 phase and is equipped with a line cord and twist-lock L15-30P electrical plug.
PLUMBING INTERFACE CONNECTIONS
The chiller's 1" female pipe thread (FPT) fitting labeled "TANK OUT" must be plumbed to the inlet of the device to be cooled. The outlet of the device to be cooled must be plumbed to the chiller's 1" FPT fitting labeled "TANK IN". This system is equipped with a ½" FPT fitting labeled "DRAIN". It may be desirable to install a valve at this location prior to the initial filling of the reservoir, for the convenience of future draining procedures.
The condenser cooling water supply must be plumbed to the chiller's ½" FPT fitting labeled "CONDENSER IN". The chiller's ½" FPT fitting labeled "CONDENSER OUT" must be plumbed to either a drain or the return path of the condenser cooling water circuit. Verify that condenser cooling water into and out of the chiller is unobstructed. Obstructions may cause loss of cooling capacity and eventual overheating.
Both the recirculating loop and the condenser cooling water loop are under pressure when the system is operating. Check all fluid interface connections now to ensure against leaks.
CIRCUIT BREAKER
Set the circuit breaker mounted on the front of the system. Upon setting the circuit breaker, a message similar to the following appears on the 2 by 40-character main display:
This display indicates that the system's phase monitor circuit is checking for correct electrical power phase relationship. Should a live and ground line be reversed, the phase detector reads PHASE MISSING. Correct the error and the controller no longer indicates PHASE MISSING. If the display reads PHASE REVERSED, disconnect and switch two of the three phases.
FILL RESERVOIR
To fill the system's reservoir, unscrew the fill plug on the top of the vertical stand-pipe for the tank and pour in the recirculating fluid. If the system is powered before the tank is filled, the "FILL TANK" error message is displayed at the main panel, the alarm LED is lighted and the audible alarm sounds. Filling the tank eliminates the alarms. Replace the plug.
Output --- Warmup Delay --- Local Set
20.02°C 20.0°C
WARNING
The system should be powered for a period of ½ hour before starting, to
allow the crankcase heater to separate the refrigerant from the oil.
PUSH RESET BUTTON
The Reset button, located below the main panel, must be pushed upon powering the system. This resets the power safety interlock loop, which protects the operator and electrical circuitry.
Lawrence Berkeley Laboratory 4
Mydax, Inc. 1M9W-S Water Cooled Chiller
FRONT PANEL CONTROLS
All Mydax chillers are controlled by a microprocessor which is accessed via the system control panel. System controls are simple, yet powerful and in concert with built-in diagnostics and error messages, are exceptionally comprehensive.
POWER LED:
RESET:
START:
STOP:
MUTE ALARM:
SET:
Indicates unit is powered (the circuit breaker is set).
Must be pressed prior to system start-up to energize the interlock loop.
Starts compressor and pump and turns on LED's. Once the start-up routine is complete the display changes to the MAIN DISPLAY:
Output --- MYDAX --- Local Set
20.02°C 20.0°C
Shows the actual Output Temperature and Setpoint Temperature in °C. Also indicates that the local SET TEMPERATURE MODE can be enabled.
Stops both the compressor and pump and blanks the display.
May be used to deactivate audible alarm for 10 minutes, leaving alarm LED on. Pressing the CLEAR key reactivates the alarm, which sounds until the fault condition is eliminated or the MUTE ALARM switch is depressed again. Pressing MUTE ALARM when no alarm is active causes the alarm to sound once and the TEST ALARM display to appear.
Enables SET TEMPERATURE MODE. SET MODE is disabled from panel if an alarm is active or if the unit is in REMOTE. To set, depress:
TEST:
ENTER:
CLEAR:
MODE:
ARROW KEYS:
SET:
ARROWS KEYS:
"." (DECIMAL):
KEYPAD:
CLEAR:
ENTER:
Initiates Test Mode. See description under DIAGNOSTIC DISPLAYS section of this manual.
Enters temperature selections while in the SET mode.
Erases incorrect temperature selections; exits Test Mode; clears Mute Alarm selection.
Toggles between the RS-232C remote control mode and Local Set mode.
Changes temperature setpoint by 0.1° or 1°C increments/decrements; toggles tank
"Set Mode" appears at the right of the display. Cursor flashes at "units" digit of the temperature display.
Changes temperature setting in one degree increments unless "." (decimal) key is depressed.
Moves cursor to the "tenths" digit of the temperature display and causes arrow keys to change setting in tenths of a degree.
Changes temperature setting by entering numbers directly.
Erases an incorrect entry.
Selects temperature setting and deselects SET mode.
Lawrence Berkeley Laboratory 5
Mydax, Inc. 1M9W-S Water Cooled Chiller
temperature, setpoint temperature and evaporator data view modes for multiple channel systems.
"." (DECIMAL):
RUN PUMP:
X & Y:
Z:
EMO SWITCH:
Display shows model number and software revision date and copyright:
1M9W-S 2001.01.18 Copyright 2001 Mydax, Inc.
Inactive in this system.
For future use.
See Test Panel 9 in the Diagnostic Displays Section.
This is a large red emergency off switch mounted on the left of the main panel. It shuts down the entire system, excluding the controller.
Lawrence Berkeley Laboratory 6
Mydax, Inc. 1M9W-S Water Cooled Chiller
ERROR MESSAGES
A unique feature of Mydax systems is the error messages displayed on the 2 by 40-character liquid crystal display (LCD). The microprocessor constantly checks various points and parameters throughout the system and automatically displays messages when error conditions are sensed. Many displays are announced by an audible alarm and LED indicator. The error message persists until the fault condition is resolved, provided that the fault condition was not fatal, resulting in a system shutdown.
Condenser Hot
Fill Tank
Tank Too Hot
Push Reset
Phase Missing
Indicates high discharge pressure condition with temperature over +50°C. This is a warning message only. A separate mechanical overpressure switch, part of the safety interlock loop, shuts the system down in case of an overpressure condition. The purpose of this message is to allow maintenance workers to correct the problem at an early stage. (Caused by a clogged filter, low or warm condenser cooling water flow or condenser scale build-up.)
Indicates low tank liquid level.
Indicates that the reservoir temperature is more than 10°C above the highest allowable set point. Microprocessor shuts down the system.
Indicates that the reset button has not been pushed since the last system power-up or that the system interlock loop has a fault condition.
A series-wired safety interlock loop protects all Mydax systems, disconnecting AC power from nearly all circuitry. The loop consists of the freon pressure switch, tank "hot" sensor and low level switch. If any link in the loop is opened, the "Push Reset" error message is displayed. Once the fault is corrected, the Reset button must be used to re-establish loop integrity. The reset button must also be pushed at system power up.
Indicates that one or more electrical phases are missing.
Phase Reversed
Low AC Line
Open RTD
Lawrence Berkeley Laboratory 7
Indicates that electrical phases are incorrectly connected. Reverse any two legs.
Indicates a low voltage condition exists on the input AC line.
Indicates that an RTD connected to the M1002 Input Board has failed and that the system has shut down to prevent damage due to lack of data. The RTD at fault may be located by accessing Test Panel #8. The RTD must be replaced for the system to operate again.
Mydax, Inc. 1M9W-S Water Cooled Chiller
DIAGNOSTIC DISPLAYS
Mydax chillers are provided with a computerized self-diagnostic capability. This system is equipped with 9 different test panels, which are accessed by pressing the TEST key, followed by the test panel number. Diagnostic mode is terminated by pressing the CLEAR key, and results in a display similar to that below:
MAIN DISPLAY
Output --- MYDAX --- Local Set
20.02°C 20.0°C
Diagnostic messages are displayed on the main 2 by 40-character LCD. Display #5 automatically appears when the TEST key is first depressed. Once in diagnostic mode, other displays can be selected by depressing number keys 1 through 9. The following describes each of the test displays:
TEST PANEL #1:
Valve 7 Htr 8 Avg Valve 5 Htr 6
Numbers represent the drive signals for the evaporator valve and tank heater. The range is 0 (minimum) to 20 (maximum drive). Each digit represents 5% of the available 24VDC drive voltage. Avg Valve shows a 32 second running average of the valve's drive, displayed above it.
TEST PANEL #2:
This display shows the refrigerant circuit RTD temperatures in °C. The display reads:
Limit = Max Evaporator Temp Suct = Suction Temp Psig = Suction Pressure Sup.Ht = Superheat Temp SHavg = Avg Super Ht Temp Cond = Condenser Temp
The condenser reading is a direct indicator of condenser temperature and pressure. The microprocessor sends the CONDENSER HOT error message if the condenser temperature exceeds +54°C.
TEST PANEL #3:
The first 3 sets of 4-digit numbers are hexadecimal. They represent correction values for the slow gain servos for up to 3 reservoirs. The function of this servo is to dynamically adjust the main temperature control servo to near zero error and thereby maintain temperature stability.
The first 2 digits in each set of 4 show the gain offset. Each increment equals 0.05°C, so 14 Hex = 20 decimal = 1.0°C. This value is internally subtracted from the operator-entered temperature setpoint if the actual temperature is above the setpoint, thus reducing the coolant temperature. When the actual coolant temperature is below setpoint, the main servo is driving a heater and no adjustment is made to the setpoint. The setpoint offset is continuously monitored by the controller and adjusted according to current conditions.
4.0 -4.8 48.2 35.0 Limit Suct Psig Sup.Ht SHavg Condr
302B 0000 091F Z 0.00 G 51.95 14.4 SS-1 SS-2 SS-3 RTD Reference SH Avg
The second 2 digits in each set of 4 show the time prescaler. This is a counter which increments or decrements once a second and times the next update of the setpoint offset. A typical value is 20 seconds per offset change. When the count reaches "00", the offset may or may not be changed and the count resets to "0A" Hex (10 decimal). Together these numbers show that the controller is internally changing the control setpoint to maintain temperature stability, and give the magnitude and timing of the change.
Lawrence Berkeley Laboratory 8
Mydax, Inc. 1M9W-S Water Cooled Chiller
The center of the display shows readings for the RTD "Zero" and "Gain" calibration resistors. Precision resistors 100Ω and 120Ω (0.1% tolerance or better, representing ideal nominal RTD's) are used as a reference. Typical readings are shown.
TEST PANEL #4:
This display shows auxiliary voltmeter readings of Ext 1, Ext 2 and Ext 3. These are not used in this system. VAC is the 24 VAC internal control voltage; a typical value is in the range of 22 to 28. To the right of this value is a 0. At the far right of this display is a time indicator in seconds. The timer stops at 255 seconds and is used internally for turn on routine procedures.
TEST PANEL #5:
This diagnostic shows the Output temperature slope. Slope is a measure of the direction and amount of the output temperature change per 60 seconds.
TEST PANEL #6:
This diagnostic shows the Tank temperature with resolutions of 0.05°C and 0.01°C, and the Output temperature with resolutions of 0.05°C and 0.01°C.
-5.294 -1.292 -1.308 +26.46 0 255 Ext 1 Ext 2 Ext 3 VAC Secs
20.00 20.0 0.0
Tank Set DgMin
Output
RTD (coolant) temperature in °C, the Output Setpoint temperature and
19.80 19.79 20.00 20.02
TEST PANEL #7:
This display shows voltmeter readings for up to 3 optional water resistivity monitor interface raw data outputs. Each resistance monitor channel has a positive and a negative voltage reading. These readings are approximately equal, but are of opposite polarity.
The refrigerant type that the control system is calibrated for is shown. For example:
The two numbers at the top, far right-hand side of this display represent the internally computed maximum evaporator temperature and a counter ranging from 0 to 99, which are used to adjust the valve drives and regulate the superheat temperature.
The second line of the right side of this display indicates the status of the lithium battery, mounted on the M1001 circuit board, used to run the system's elapsed run-time clock depicted in Test Panel 8 and the run/event recorder depicted in Test Panel 9. A "Bat. OK" message indicates that the battery is operational, while a "No Bat." message indicates that the battery is dead and should be replaced.
TEST PANEL #8:
The top left side of this display shows the alarm (error message) history. If there have been no alarms since the
+ 0.000 + 0.000 + 0.000 R22 6.00 0
- 0.000 - 0.000 - 0.000 Bat. OK
R22
Alarms: Fill Tank ! KEY Run 356d 11:31:25
Lawrence Berkeley Laboratory 9
Mydax, Inc. 1M9W-S Water Cooled Chiller
last history reset, the display reads "No Alarms". If alarms have occurred, the display shows them in sequence, like the main display. The history can be cleared 3 ways:
1. Power Off/On
2. Press START Key when unit is stopped
3. Press 0 Key when viewing Test Panel 8
The second line of the display can be read when the chiller is stopped. It indicates the reason that the chiller was last stopped: KEY, FATAL, RS232 or EXT. The right side of the second line indicates the elapsed run time on the system in days (from 0 to 9999), hours, minutes and seconds. This system is equipped with a battery which, if operational, saves the elapsed run time value when the system is stopped and restarted. The elapsed run time is reset each time the system is restarted.
TEST PANEL #9:
This display provides run/event recorder data. The run/event recorder continuously records important information into a non-volatile memory while the system is operating. Data is stored at one-second intervals for the last 120 seconds of run time and it is also stored at two-minute intervals for the last 240 minutes of run time.
The first line of this display indicates the run time in hours, minutes and seconds prior to the last system shutdown, the output and setpoint temperatures of whichever recirculating channel was last selected at the Main Display and the system-wide alarm history. The second line indicates which recirculating channel was last selected at the Main Display, the evaporator, bypass, condenser and superheat RTD temperatures in °C, the average superheat temperature from Test Panel 3 and the flow rate. Both the evaporator temperature and the flow rate are specific to the recirculating channel being viewed. All freon circuit RTD temperatures are truncated to the nearest 1°C for this display.
After the system is stopped and Test Panel 9 is selected, the memory is displayed at the last or most recent second (T- 0: 0: 0). The downward arrow key can be used to decrement time into the past. There are 120 "1­second slots" and 120 "2-minute slots". If the downward arrow key is held down, the time slots decrement at the rate of two slots per second. The upward arrow key increments to more recent time slots. If the "Z" key is depressed, the display goes to the oldest 1-second slot (T- 0: 1:59 if the actual run time was of at least that duration). If the "9" key is depressed while viewing Test Panel 9, the display reverts back to "T- 0: 0: 0", the stop time.
T- 0: 0: 0 20.02 20.0 No Alarms.....
Tank 1 4Ev 0By 37Cd 13Sh 14SA Gpm
The alarm messages are accurate for the slot that is current. If the display is on the minutes slot, then the alarms indicated are any which have occurred during that 2-minute interval. Alarm messages cycle or flash in an identical fashion to those appearing in either the Main Display or in Test Panel
Lawrence Berkeley Laboratory 10
Mydax, Inc. 1M9W-S Water Cooled Chiller
SERVICE & WARRANTY
If a unit malfunctions, please contact the Mydax Service Department as soon as possible. Many small problems can lead to large problems if not dealt with immediately. Please have the serial number and model number on hand when calling.
Mydax Service Department: (530) 888-6662
FAX: (530) 888-0962
RETURN OF UNIT FOR SERVICE
Many problems may be repaired by field exchanges of a module, pump, controller, etc. If return is required, please obtain a return authorization number from the Mydax Service Department or the unit may not be accepted at our receiving dock.
Please refer to the shipping instructions which follow.
SERVICE OF REFRIGERATION UNIT
Nearly all repairs to the refrigeration unit involve brazing or silver soldering. This should only be done by a person trained in refrigeration service and familiar with the Mydax system.
NOTE: Before servicing any refrigeration unit involving brazing, remove all freon from the system. Evacuate
to a 400 micron vacuum to remove freon residues, then open all service valves to dry air or dry nitrogen before use of a torch.
In particular, service of Mydax refrigeration circuits requires attention to the following:
1) Use caution to protect components from heat damage.
2) Prevent any moisture from entering the circuit, as Mydax proportional valves do not function with moisture present. Once moisture has entered the system it cannot be removed.
3) Remove insulation and instrumentation wiring or use heat shields to protect them from torch heat during work.
4) Before recharging the circuit, evacuate it to 200 microns at a minimum room temperature of 75°F for three hours.
ONE YEAR WARRANTY
Mydax, Inc. warrants that its temperature control system, and the component parts thereof, will be free from defects in workmanship and materials for a period of one year from the date of delivery. In the event that warranty service is required, the customer is requested to send the equipment freight prepaid to the factory for service. Mydax will then perform the appropriate service and will return the equipment freight prepaid.
If field service is required during the warranty period, the customer will be responsible for all travel expenses including mileage. The customer will not be invoiced for any warranty service performed, with regard to either labor or materials, during a field service visit.
Lawrence Berkeley Laboratory 11
Mydax, Inc. 1M9W-S Water Cooled Chiller
RESHIPPING & LONG-TERM STORAGE PREPARATION
Reshipped systems should be protected from freezing temperatures in shipment or serious damage may occur. Freezing temperatures can be encountered in air and over-mountain surface shipments in any month of the year. In-transit freeze­up can occur in the recirculating coolant loop and in a water-cooled condenser's cooling loop. To protect against freezing, all water must be removed from these circuits, or ethylene glycol must be added.
This system has a preparation:
1. Feed in a charge of water-glycol mix into the condenser through the "Condenser In" connection. This can be done by pump or gravity flow.
2. Feed water-glycol until mixture is visibly flowing out of the "Condenser Out" connection.
3. Plug the "Condenser In" and "Condenser Out" fittings to avoid leakage in shipment.
4. Since the system has been run with water, remove it from the reservoir via the "Drain" fitting. As much water as possible should be drained from the system before shipment. Water adds significant shipping weight and may damage electrical parts if it sloshes out of the tank.
5. Continue to remove as much water as possible with a wet/dry vacuum to prevent ice-up in the small "nooks & crannies" of the plumbing.
6. Plug the "Tank In", "Tank Out" and "Drain fittings.
water-cooled
refrigeration condenser. The following instructions apply to shipment or storage
Call Mydax for any help
needed at (530) 888-6662
Lawrence Berkeley Laboratory 12
Mydax, Inc.
-Appendix A -
RS-232 Serial Interface Operati o n
RS-232C INTERFACING
The use of an embedded microproc essor allows Mydax to offer an RS-232C (remote) interfacing capability. Mydax systems c an be controlled from a computer with either the MYDAX REMOTE Window's ™ software package or any control software of the user's choice. Full control and monitoring is possible, allowing complete s ystem operation from any convenient location.
Cable connection is via a rear panel DB-25S connector. Connector pin-out is as follows:
Pin 1 Shield Pin 2 Transmit Data Pin 3 Receive Data Pin 7 Common
A typical interconnect cable for an IBM-PC COM port s hould be wired as follows:
IBM-PC MYDAX
DB-25S Female Connector DB-25P Male Connector
1 1 2 2 3 3 4 4 5 5 6 6 7 7
20 20
Appendix A RS-232 Page A-1
Mydax, Inc.
RS-232C COMMANDS
The following ASCII commands can be transmitted to the system MPU via the RS-232C link:
RO Enables RS-232C control. RF Disables RS-232C control. With remote disabled, system only
responds to RO.
GO Starts the compressor and pump. HA Stops the compressor and pump.
RP Run Pump only, active only on selected systems. S?xy.z Sets fluid temperature (x, y and z are any numbers) of tank A,
B or C. Settings outside the range default to the nearest limit. Entering a decimal point is optional, as the last digit is assumed to be the tenths digit. For example: "SA180" selects +18.0°C for tank A, "SA245", "SA24.5" & "SA+24.5" all select +24.5°C for tank A, "SA93.2" selects +30.0°C for tank A.
TE1 Sends a transmission of abbreviated status including system on/off
status, actual tank temperature and the set point temperature.
TE2 Causes transmission of flow and resistance, if the options exist. For
example:
TE3 Transmits the contents of the 2 by 40-character main display over the
RS-232 line.
TE4 Same output as TE1 plus RTD temperatur es and valve & heater drive
signals.
TR or TR0 Turns off repeat transmission mode.
TRx Enables auto matic periodic repeat transmission (x= 1-60 and
represents the number of seconds between transmissions). The instructions which follow the TRx command are repeated at the transmission rate that was set by the TRx command. TE1, TE2, TE3 and TE4 are commands that can be repeated in all or any combination.
TPx Changes the 2 by 40-character display at the main contro l panel to
Test Panel "x" "0" = normal main display; "1" - "8" = diagnostic displays. See section on DIAGNOSTIC DISPLAYS. Does NOT cause transmission of the display over the RS-232C line (see command TE3)
ID Causes transmission of the model number and software revision date.
For example:
Appendix A RS-232 Page A-2
"ID: 1VLH14W 1-24-2000"
Mydax, Inc.
AL Causes transmission of the alarm status. For example:
AH Causes transmission of the alarm history status. For example:
This history is the same as the Test 8 display. The history represents all alarms that have occurred since the last "Start" command.
CH Clears alarm history. This can also be cleared with the "Start" key or
with the "0" key when viewing Test Panel 8.
A delimiter between command strings can be a carriage return (CR), a semi­colon (;) or a comma (,). I f a command is understood, a (>) is returned for acknowledgment. If a command is not understood or ignored then a (?) is returned.
RS-232C STATUS MESSAGES
"ALARM: 0" denotes no alarm condition.
"ALHIS: 13" denotes one alarm.
TE1 status messages include the following:
ON 19.95 20.0 (CR)(LF) A B C
Key: A) System is ON or OFF
B) Actual Tank Temperature in °C C) Set point Temperature in °C
A TE4 status message consists of TE1/TE3 data plus RTD temperatures and valve & heater drives:
ON 19.9 20 -63 -8 41.5 34.5 102 0 2 2 0 4 10 8 2 11 (CR)(LF)
A B C D E F G H I J K L M N O P Q
An alarm status message is transmitted whenever there is an alarm that occurs for the first time and whenever the alarm status changes:
ALARM: 4 13 (CR)(LF)
R S T
A halt indication is transmitted when the system is stopped for any reason:
STOP: KEY (CR)(LF)
U V
Key: A) System is ON or OFF
B) Actual Tank Temperature in °C, as sensed by the Output RTD
Appendix A RS-232 Page A-3
Mydax, Inc.
C) Set point Temperature in °C D) Calculated temperature in °C of the refrigerant line at the suction pressure
transducer E) Pressure in PSIg of the refrigerant line at the suction pressure transducer F & G) Temperature in °C in the refrigerant line at the Superheat and Condenser
RTDs H) Temperature in °C in the refriger ant line at the Discharge RTD (2-stage design
only) I ) Temperature in °C in the refrigerant line at the Subcooler RTD (inactive) J & K) Valve dr ives of evap orator valves 1 and 2; valve 2 is inactive in single
channel systems (See "DIAGNOSTIC DISPLAYS, Test Panel 1" for explanation of drive signals.)
L, M & N) Bypass, Superheat, and De superheat valve drives. Desuperheat is no t available in all designs.
O & P) Heater drive signals; Heater 2 is inactive in single channel systems (See "DIA GNOSTIC DISPLAYS, Test Panel 1" fo r explanation of driv e signals.)
Q) Flow rate in gallons-per-minute(GPM) of r ecirculation fluid. On systems without a flow meter, this number has no meaning.
R) Any active alarms, by code # (See the next section for a description of alarm codes.)
S & T) Actual code # for the alarm U) Stop is displayed whenever the system is halted V) Indicates the origin of the Stop Command (status message "S") whether it is
from the system front panel (KEY), the external stop line (EXT.), an RS-232C command (RS232) or it originated from a fatal alarm (FATAL).
Appendix A RS-232 Page A-4
Mydax, Inc.
RS-232C ALARM CODES
The following alarm codes may be transmitted in an AL or AH status message. Not all of these codes are possible in every system:
1CONDENSER HOT: The reading from the condenser RTD indicates a
temperature in excess of +50°C. The system microprocessor incrementally reduces the evaporator valve drive to reduc e the flow of refriger ant into the evaporator. This effectively reduces the heat-rejecting capacity of the system, which keeps the temperature in the condenser at acceptable levels.
2 LOW FREON: Indicates pressure of refrigerant is low. Have unit serv iced by
Mydax or a qu alified service center.
3RTD OPEN: Indicates that one of the syste m RTD's has failed and the
system has shut down to protect itself. The main display shows which RTD is faulty by giving its pin number location on the M1002 or M1005 circuit board.
4PUSH RESET: The interlock loop has been broken and the reset switch must
be depressed to re-establish it.
5 FILL TANK #1: The tank 1 low level sensor has tripped. If coolant is not
added "soon", the "empty" sensor trips and the system shuts down. 6 Inactive in this system. 7 FILL TANK #2: The tank 2 low level sensor has tripped. If coolant is not
added "soon", the "empty" sensor trips and the system shuts down. 8 LOW FLOW: Indicates that a low flow condition exists in one of the
recirculating channels.
9 Inactive. 10 PHASE MISSING: Indicates one or two of the three electrical power phases
is missing. Inactive on single-phase units. 11 PHASE REVERSED: Indicates incorrect electrical power phase relationship.
May be corrected by re versing any 2 phases. Inactive on single-phase units.
12 Inactive in this system. 13 LOW AC LINE: Indicates a low voltage conditio n exists on the input AC line. 14 RESISTANCE LOW: Indicates that the deionized water resistivity has
dropped below the programmed limit. 15 TAN K x TOO HOT / EXTREME TEMP: Indicates that the tank temper ature is
either more than +10.0°C above its upper maximum set point, or too close to
freezing and that the system has shut down.
Appendix A RS-232 Page A-5
This page is intentionally left blank.
sheet 1 of 1 DWG. B2343, Rev 3
Mydax, Inc.
Auburn, CA
1M9W-S Chiller Fluid Schematic
January 25, 2001
Water Cooled
High
Pressure
Switch
Filter Drier
Condenser
Water Flow Control Valve
Capillary Tubes
Drain
Condenser RTD
Condenser
Cooling Water
1.5 Gpm @ 75°F, P = 20 Psi
Evaporator
R-22
Compressor
With Suction
Accumulator
Pressure
Relief Valve Set at
110 Psi
10 Micron
Particulate
Filter
Pressure Gauge
Coolant Supply +15°C to +25°C 10 Gpm @ 100 Psi
Coolant Return
Heat Exchanger
Evaporator Valve
Sight Glass
Refrigerant Liquid
Tank RTD (Installed Through Side)
Tank Heaters
Level Switches
Tank Baffle
10 Gallon Polypropylene Reservoir
1 Hp Multi-Stage
Centrifugal Pump
Output RTD
* Refrigerant control valves are set continuously by the system microprocessor.
* All RTD's are read continuously by the system microprocessor.
#4,742,689 #4,918,931 #4,934,155
This circuit is covered by one or more of the following U.S. Patents:
Receiver
Linear
Pressure
Sensor
HP160
PSIG
3/4"
Copper 90's
1/4" Ball
Valve
1/2"
1"
1"
Power
20A #12 AWG
24VAC / Interlock Loop is Red #18AWG Refrig valves are wired in Yellow
High Voltage Wiring Chart: (All HV wire is Black)
Low-Voltage Wiring Chart:
DC / Logic wiring is Blue #18 AWG
Power
Evaporator
Reset
69
RL1,C
RL1
A
B
Wh
Red
High
Pressure Switch
Red
CON1
T1
T2
T3
Keyboard
J1
56
56
50
50
23 Reset
M1004 Power Supply, Phase Detector & Output Drivers
50 +5V 20 Comp
EV1
3+42
1
SSR1
L3L2L1
Red
M1002 Inputs & RTD's
LCD Display
8
5
RL1,B
J2
J1
J3
RS-232 Connector
J2
M1001 Controller
Power
24 VAC
Out
Gnd In
Gnd
24 VAC
40 VA
CON1
20 Amp
D2402
4
7
RL1,A
L3
L2
L1
Compressor
Crankcase Heater
Grn
Pump
53
Tank
Empty
Fill
Tank
22 Tank1 Lo
+5V 49
HTR1 23
sheet 1 of 1DWG. B2344, Rev 3
Mydax, Inc.
Auburn, CA
1M9W-S Chiller Electrical Diagram
Water Cooled
January 25, 2001
D2440
23+
1000W
SSR4
14
23+
1000W
D2440
D2440
SSR2
SSR3
1
1
2
4
3+
4
Tank Heaters
1000W
208/230 VAC, 3 phase
Grn
Tank
RT10
Cond. Output
RT3
RT4
RT7
Trim_01
RTD's
1
2
M1007
LED PS
M1010 Interface
Linear
Pressure
Sensor
4 5 6
7
J4
J4
Blue
Gnd
13' of 12/4 Cable with L-15-30 Plug
54
55
EMO
Over Temp
13' of 12/4 Cable with L-15-30 Plug
sheet 1 of 6 DWG. B2240
Mydax Inc.
Auburn, CA.
Mydax Controller M1001
'CPU'
D0
D1
D3 D2
D6
D7
D5 D4
A14
A13
+5V
26
27 28 1 28 26
A0
A1
A8
A4
A11
A12
A10 A9
A7 A6 A5
A3 A2
CE OE
A15 WRN
U22 U16
27C256
EPROM
6264
Read/Write Memory
20 22 14
20 22 27 14
11
12
13
15
16
17
18
19
10
9
8
7
6
5
4
3
25
24
21
23
2
D4
D5
D7 D6
D2
D3
D1 D0
A0 A1
+5v
1 2 3 4 5 6 7 8
11 9 14 15 16 18
20 19 24
22 23 21 14
RDN
WRN
8254AN
U17
82C54 Counter
Timer
100 Hz
200 KHz
Baud Clock
10
13
17
A12
A13
A14
MREQN
A15
U14
8251N
KEYN
Nov 10, 1997
0.1uf
+5V
ResetN
In4
ResetN
+5V
U21
Max 690
8 7 6 54
3
2
1
2
3
41
1kWaitN
J7
R1
10k
0.1uf8.0MHz
D0
D1
D3 D2
D6
D7
D5 D4
26
27
20
19
22
21
14
15
12
8
7
9
10
29
17
16
13
30
31
32
33
34
35
36
37
38
39
40
1
2
3
4
5
1125
6
24 "CPU"
Z84C0008
U9
M1N
IOREQN
MREQN
WRN
RDN
A0
A1
A3 A2
A6
A7
A5 A4
A8
A9
A11 A10
A14
A15
A13 A12
+5V
8.0 Mhz Osc. U15
+5V
NMI J7
Int J7
10K
10K
1K
1K
U7 U12
1
2
13
12
3
4
8255N
8254BN
CPrQ
11
10
12
13
Qn8ClD
U8
9
+5V
RTC
In3
CPrQ
3
4
2
1
QnClD
U8
5
U7
7
4 5
3
RxRdy
TxRdy
from sheet 2
4 MHz to sheet 2
Bat.
Lithium Battery
U44
9
10
8
74HC138
A
B
C
1
2
3
4
5
6
15
14
13
12
11
10
9
7
sheet 2 of 6
DWG. B2240-2
Mydax Inc.
Auburn, CA.
Mydax Controller M1001
IOREQN
A7
RDN
WRN
U13
U12
A0
A1
A2
A2
A3
A4
IN 1 IN 0
IN 2
IN 3
IN 7 IN 6
IN 4
IN 5
OUT 8 OUT 4 OUT 0
OUT 12
OUT 16
OUT 20
13
12
D1 D0
D2
D3
D7 D6
D4
D5
+5V
Seiko L4042
LCD DISPLAY MODULE
12
4 5 6
14 13 12 11 10
9
8 7
10K 10K10K10K10K 10K
A0
A1
A2
+5V
KEYN
U42
5 ea. 1N914
10K
10K10K10K 10K 10K
KEYN
SIP
D7D6D0 D5D1D0 D2 D3
74HC240
U41
KEY MATRIX (26 Keys)
11 8 13 6 15 4 17 2
1
19
912714516318
D2 D3 D4 D5 D6
U10
82C51A
A0
PCLR
RDN
WRN
BAUD CLOCK
8251N
4.0MHz
+5V
26 4 12 21 13 10
8 7 6 5 2 1 28 27
9 25
11 20
Rd
CTS
Td
RTS
U4 MAX232
15 14
3
17
19
23
12
9
11
10 7
14
8
13
RS-232 Interface
0.1uf
0.1uf
Jan. 15, 1996
U31
Out 24
Out 28
RTC
SIP
+5V
VLC
3
10K
LCD R/W
LCD RS
LCD EN
37 38 39 40
1 2 3 4
U11 8255
"A" Section
D7 27
28
D6 D5
29 30
D4 D3
31 32
D2 D1
33 34
D0
536
RDN
WRN
8255N
67
35 26
ResetN
TxRdy RxRdy
+5V
+
+
+
+
+
10
10
10
10
10
6
2
16
1
3
4
5
15
J3
11 12 13 14 15
6 5
4
3 2 1
C B
A
74HC138
to sheet 1
74HC138
A
B
C
1
2
3
4
5
6
15
14
13
12
11
10
9
7
74HC138
A
B
C
1
2
3
4
5
6
15
14
13
12
11
10
9
7
sheet 3 of 6 DWG. B2240-3
Mydax Inc.
Auburn, CA.
Mydax Controller M1001
Input-Output
11 12
13 17
16 15 14
D0
D1
D2
D3
D4
D5
D6
D7
IN 5
U3
74HC244
18
3
16
5
14
7
12
9
19
1
11
8
13
6
15
4
17
2
T2 Low
Interlock
T1 Low
Reset Rly
Freon Lo Ext Stop
Ext Start
J1-17
J1-18 J1-15
J1-13 J1-14 J1-11 J1-14
J1-16
J1-6
J1-5
J2-4
J2-3
J1-8
J1-7
J1-10
J1-9
T3 Low
Miss Ph.
Rev Ph.
Key Sw.
Remote Dig/Ana
24 23
22 21
20 19 18
2
17 4
15 6
13 8 11
1
19
9
12
7
14
5
16
3
18
74HC244
U1
10k
+5V
IN 7
D7
D6 D5 D4 D3 D2 D1 D0
2
17 4
15 6
13 8 11
1
19
9
12
7
14
5
16
3
18
74HC244
U2
10k
+5V
IN 6
D7
D6 D5 D4 D3 D2 D1 D0
Res On/Off
On=Remote
On=ext
virtual On=Volt Set En.
On=no Fudge
Baud
Dip Switch
PCLRN
74HC273
U18
9
6 5 2
1
11
3
4
7
8D3 D2 D1 D0
Out 28
April 24, 1996
Switch 2
Switch 3
+5V
10k
100K
+5V 10k
100k
25 10
100k
10k
+5V
U11 82C55 "B
U11 82C55 "C
D4
D5
13
14
15 12
16
19
18
17
D7 D6
LCD R/W LCD EN LCD RS
EV1 J2-20
EV2 J2-19
EV3 J2-18
EV4 J2-17
EV5 J2-15
U24 ULN2003A
+5V
9
8
1
2
3
4
5
6
710
11
12
13
14
sheet 4 of 6 DWG. B2240-4
Mydax Inc.
Auburn, CA.
Mydax Controller M1001
Output Dec 20, 1995
U19
74HC273
19 16 15 12
9 6 5 2
111
3
4
7
8
13
14
17
18
PCLRN
Out 8
D0
D1
D2
D3
D4
D5
D6
D7
ULN2003A
9
16
15
14
13
12
11
8
10
7
6
5
4
3
2
1
U16
+5V
Beep
220
220
220
220
+5V
Compr. J2-13
Pump J2-16
"Alarm" J2-14
LED
LED
LED
J8-1
J8-2
J8-6
"Power"
D7 D6 D5 D4 D3 D2 D1 D0
U32
74HC273
19 16 15 12
9 6 5 2
111
3
4
7
8
13
14
17
18
U28
74HC273
19 16 15 12
9 6 5 2
111
3
4
7
8
13
14
17
18
Out 4
+5V +5V
DVB DVA
High R J4-4 POS R J4-3 DIB J4-6 DIA J4-5
LED
+5V
+15V
Run DVM
DVC
1K 1K 1K 1K
DVM RDY
+5V+5V
Out 0
14 13 11 6 4 3
9 1
2
5
7
10
12
15
74HC174
U5
14 13 11 6 4 3
9 1
2
5
7
10
12
15
74HC174
U6
D5 D4 D3 D2 D1 D0
1K 1K 1K 1K
RA J1-3
RB J1-4
RC J1-1
RD J1-2
18 17 14 13 8 7 4 3
11
1
2
5
6
9
12
15
16
19
74HC273
U20
PCLRN
Out 12
D0
D1
D2
D3
D4
D5
D6
D7
Spare J2-6
FAN 3 J2-5
FAN 2 J2-8
FAN 1 J2-7
HTR 3 J2-10
HTR 2 J2-9
HTR 1 J2-12
U26
ULN2003A
9
16
15
14
13
12
11
8
10
7
6
5
4
3
2
1
+5V
sheet 5 of 6
DWG. B2240-5B
Mydax Inc.
Auburn, CA.
Mydax Controller M1001
Analog March 20, 2000
U38
4
5
6
7
12
11
10
9
8
14 13 3
1 16 15
2
10.0K*
10.0K*
RTD Out J1-24
Set 1 J4-16
Set 2 J4-15
AC Det. J2-1
T1 Ext. J4-14
T2 Ext. J4-12
T3 Ext. J4-13
U35
DG508CJ
-15V
DVA DVB DVC +5V
D0
D5
D4
D3
D2
D1
D0
D7
D6
D5
D4
D3
D2
D1
+5V
IN 0
IN1
1
20 19 18 17 16 15 14 13 12 11 10 9
40
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
8 7 6 5 4 3 2
+5V
Run DVM
-15V
U43 79L05
-5V
1 uf+
0.1 uf
200K*
0.1uf .056uf
200kHz
+1uf
200K*
.0047uf
47
+5V
1uf
+
DVM RDY
U27
12
U36
ICL7109
74HC14
+15V
3
2
8
1
7
6
5
U38
TL032CP
+10.24V
-10.24V
10.0k
0.1%
10.0K
0.1%
20.0K*
10.0K*
D01413D1
D2
12
11
D3
D4
10
9
D5
D6
8
7
D7
U40
U39
AD7528KN
U40
+5V
A0
Out 16
17 6
16 15 5
418
Ref A
Ref B
1
2
3
7
6
5
3
2
19
20 1
TL032CP
Gain Dac J1-23 0 to -5.1V
VFan J2-2 0 to +10.0V
DI Amp J4-11
40.2K 0.1%
10.0K 0.1%
10.0K 0.1%
40.2K 0.1%
10.0K 0.1%
30.1K 0.1%
10.0K 0.1%
10.0K 0.1%
10K*
10.0K 0.1%
10.0K 0.1%
10.0K 0.1%
30.1K 0.1%
30.1K 0.1%
+15V
+5.12V J4-8
Test Point A adjust to +1.024V
Note:
1. Resistors with * are 1/4W 1% metal film
2
Ref-02CP U37
6
5
4
"Adj"
20.0K
0.1%
10.0K 0.1%
10.0K 0.1%
10K
10.0K 0.1%
10.0K 0.1%
10.0K 0.1%
20.0K 0.1%20.0K 0.1%10.0K 0.1%
RTD X5
sheet 6 of 6 DWG. B2240-6
Mydax Inc.
Auburn, CA.
Mydax Controller M1001
Optional Jan. 15, 1996
10K
10K
10K
10K
10K
+5V
2K
2K
2K
2K
2K
1K
1K
Ctr1 J5
Ctr0 J5
+5V
0.1uf
13
10
Counter Timer
82C54
U23
8254BN
WRN
RDN
14212322
241920
18
16
15
14
9
11
8
7
6
5
4
3
2
1
A1
A0
D4
D5
D7 D6
D2
D3
D1 D0
FlwSw3 J5
FlwSw2 J5
FlwSw1 J5
200KHz
U30U30
(optional)
Tank1 J4-9
TL032CP
10.0K 0.1%
20.0K 0.1%
20.0K
0.1%
0.1uf0.1uf +15V-15V
84
5
6
7
3
2
1
16
1
2
345671110128
9
13
14
15
A1
+5V
++
+10.24V +5.12V
Pin Jumpers
EDCBA
Out20
AD7542KN
U29
D3
D2
D1
D0
A0
A0
D0D1D2
D3
U33
AD7542KN
Out24
ABCDE
Pin Jumpers
+5.12V
+10.24V
++
+5V
A1
15
14 13
9
812101176543
2
1
16
1
2
3
7
6
5
48
-15V +15V
0.1uf 0.1uf
20.0K
0.1%
20.0K 0.1%
10.0K 0.1%
TL032CP
Tank2 J4-7
(optional)
U34 U34
Range A B C D E +5.12V on - - on ­+10.24V - on - on ­+-5.12V on - on - on +-10.24V - on on - on
Pin Jumpers
sheet 1 of 1 DWG. B2242
Mydax Inc.
Auburn, CA.
RTD and Inputs M1002
Dec 28, 1995
100
100
100
100
100
100
100
RT12
RT11
RT10
T3 Evap
T3 Out
T2 Evap
T2 Out
T1 Evap
T1 Out
Condr.
Sup Ht.
Bypass
100
100
Gain DAC J1-23
5VRTD
120 0.1%
100 0.1%
100K*
1.27K 0.1%
100
+
10K
0.01uf 6
2
U1
-15V +15V
4
3
7
19
S1
S2
20
21
S3
S4
22
23
S5
S6
24
25
S7
S8
26
11
S9
S10
10
9
S11
S12
8
7
S13
S14
6
5
S15
S16
4
A0 A1 A2
A3
17 16 15
14
14
151617
A3
A2A1A0
4
S16 S15
5 6
S14 S13
7 8
S12 S11
9 10
S10 S9
11 26
S8 S7
25 24
S6 S5
23 22
S4 S3
21 20
S2 S1
19
U5 DG506A
U6 DG506A
18 1 27
+15V
+5V
-15V
28
28
-15V
+5V +15V
27
1
18
100K
100K
100K
100K
100K
100K 100K
100K
RA J1-3 RB J1-4 RC J1-1 RD J1-2
U3
+
+
U2
10K
0.001 uf
1.00K
0.1%
9.09K 0.1%
7
6
5
4
6
7
2
3
4
LT1001
TL032
-15V
-15V
+15V
5.12V J1-8
+
U2
+15V
5VRTD
10K
10K
1
2
3
8
LT1001
RTD's
0.1uf
+
Bridge
24VAC
24VAC
Ext 4
Stop
Start
Com.
+
U8
U8
U7
PS2501-2
PS2501-2
to Ana. En.
-28-
to Stop
-26-
to Start
-27-
2K
2K
2K
10K
47uf
1N914
6
5
4
3
8
7
1
2
1
2
4
3
7
5
8
6
LT1001
RTD Out J1-24
0.001 uf
2
3
4
7
6
+15V
U4
+
-15V
12.1K 0.1%
10.0K 0.1%
A B C
1. Resistor with * are 1/4W 1% metal film
PS2501-2
40.2K 0.1%
50.0k 0.1%
100k 0.1%
"Gain"
"Zero"
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
U3
+
sheet 1 of 2 DWG. B2244
Mydax Inc.
Auburn, CA.
Power Supply M1004
24 VAC
GND
47 volt
Varister
V
1N4002
4700uf 50V
June 19, 1996
Fuse
In
Out
Out
Out
Out
Out
511*47
6 5
30.1K 0.1%
10.0K 0.1%
1.0K*
750*
U4
+
0.1 10uf
+
+15V 100mA
U2 LM317T
+
U4
9.76K*
1.0K*
1.0K*
10.0K 0.1%
10.0K 0.1%
3
2
1
511*
1
0.1
U3 LM317T
+
15.1 2W
2.0K*
+
+5V 200mA
10uf
10uf
-15V 100mA
+
20 1W 1
+
U1 LM337T
0.11000uf
50V
500
2.49K*
249*
Q2004L3
220
6
4
2
1
47
1K 1EV1
Q1
MOC 3032
U6
EV1 J2-20
EV2 J2-19
U7 MOC 3032
Q2
EV2 11K
47
1 2
4
6
220
Q2004L3Q2004L3
220
6
4
2
1
47
1K 1EV3
Q3
MOC 3032
U8
EV3 J2-18
EV4 J2-17
U9 MOC 3032
Q4
EV4 11K
47
1 2
4
6
220
Q2004L3Q2004L3
220
6
4
2
1
47
1K 1EV5
Q5
MOC 3032
U10
EV5 J2-15
Freon Control Valves
1N4002
ACDet J2-1
+
+
U5
U5
1
2
3
7
6
5
1uf
1N914
200K*
200K*
4.02K*
511*
10M
LM358A
Power Connectors
TL032
8
4
+15V
-15V U18
AL
Run
43 +
45 +
42 -
44 -
1K
1K
PS2501-2
6
5
8
7
1
2
3
4
10K
Q8
2N2222
10K
10K
2N2222
Q7
10K
+5V
20 Comp.
21 Pump
22 Alarm
23 Htr1
24 Htr2
25 Htr3
26 Fan1
27 Fan2
28 Fan3
29 Beep
J2-11
10K
10K
J2-5
J2-8
10K
10K
J2-7
J2-10
10K
10K
J2-9
J2-12
10K
10K
J2-14
J2-16
10K
10K
J2-13
+5V
50 +5V
49 +5V
48 +5V
47 +5V
46 +5V
41 VFAN
+5V
J2-2
0.1uf
sheet 2 of 2 DWG. B2244-2
Mydax Inc.
Auburn, CA.
Phase Detector M1004
April2 4, 1996
Note:
1. Resistors marked with  are 1% 1/4W, all other resistors are 5% 1/4W.
4
4
8
-15V
+15V
4
8
8
4
+15V
Loop 40
Gnd 39
0.1uf
1M
2
Jumpers
"VAC"220210200190180
1N914 0.1uf
1.58K*
1.50K*
1.43K*
1.33K*
1.27K*
0.1uf
U11
+
6
5
7
7
5
6
+
U14
0.001uf
+5V
1.00M
1.00M 1.00M
0.001uf
1.00M
1.00M
0.001uf0.001uf
1.00M1.00M
1.00M
1.00M
1.00M 1.00M
0.001uf 0.001uf
1.00M
470K
470K
74HC14
+5V
8
Interlock Loop
Relay
Q1 BS170
1N4002
1K
+5V
"OK"
Green LED
12
1
13
U16
Miss Ph. J2-4
Rev Ph. J2-3
1.0uf
10M 8
96
5
4
3
U17U16
74HC27
11
10
9
8
U16
1K Red
LED
"REV."
+5V
Red LED
+5V
+5V
"UNBAL"
Red LED
1K
U17U17
LM358A
LM358A
U17
1.0M
1213
1N914
0.1uf
2
1.0M
0.1uf
1
1N914
LM393A
LM393A
5
4.7K
4.7K
4.7K
10K
470K
1
10K
2
3
+
U14
U12
+
5
6
10K
+5V
7
1
470K
+5V
10K
2
3
+
U12
65
4.7K
3
2
U11
+
1
U13
+
10K*
10K*
7
6
5
3
2
1
10K*
10K*
+
U13
10K*
10K*
74HC74
26
4
3
1
U15
ClPr Qn
Q
D
C
12
11
CDQ
QnPrCl
U15
10
13
1K
"LOWAC"
11 10
U17
"Scale" Jumpers
X2X1
8.66K*
18.7K*
-15V
L1
L2
L3
Input Range 190-480VAC
0.1uf
0.1uf
sheet 1 of 1 DWG. D2729
Mydax Inc.
Auburn, CA.
M1007 LED Power Supply
Sept 24, 1997
0.1
5.1
1 watt
1000uf
50V
24 VAC
Common
Polyswitch
LM317T
1.0 Positive
Negative
250 mA @4.1 volt
to Display LED backlight
Heat Sinked In
Out
Ref
1N4002
sheet 1 of 1 DWG. D2616
Mydax Inc.
Auburn, CA.
Interface M1010
Jan 25, 2000
15.0K 0.1%
10.0K 0.1%
+
U3
1
2
3
TL032
4
3
2
1
0.1
10K
Rt
Ct
10uf
U1
LM2907-8
Note:
1. Resistors with * are 1/4W 1% metal film.
2. For Proteus 500C-high Ct=0.0047uf, Rt=69.8K* Rp=50K, 100Hz=0.714V
3. For Proteus 550C Ct=0.01uf, Rt=49.9K* Rp=50K, 100Hz=0.97V
4. For Gems 1/2" Lo range, Rp= 20k, Rt=30.1k, Ct= 0.01uf 100 Hz=0.595 V
Rp
8 7
6 5
1
2
3
Flow In
Common
Shield
+15V
To J4-14 T1 Ext
To J4-12 T2 Ext
8
9
10
Flow Gnd Press.
U2
+10 Ref.
+ Pres.
- Pres.
Common
1.02K *
2
1 8
3
4
5
6
7
-15 V
+15 V
7
4
5
6
INA114
Optional
0.1
0.1
-15 V
1M
10K
Pressure Zero
10.0K 0.1%
J4-11 DI Amp
J6
10.0K 0.1%15.0K 0.1%
+
U3
6
5
TL032
Optional
7
4
8
Alarm
Common
Alarm NC
Alarm NO
Relay
11
12
13
14
200K 0.1%
Optional for
Gems Flowmeters
0.0047 100k
2k
J4-16 Set1
Using Sensym STImV300G1A sensor: 0 psig= 1.125 volt, 300 psig= 8.625 volt
Using Sensym STImV300A1A sensor: 0 psia= 1.125 volt, 300 psia= 8.625 volt Sea level mean pressure= 14.7 psia = 1.4925 volt
+5V
Loading...